10-0760 (CONR) Title 24BUILDING.ENERGY ANALYSIS REPORT •.:. a y. . I I " PROJECT: Fitness Building -Tradition Club Assoc. 78505 Old Ave 52 La Quinta,, Ca 92253 Project Designer: MAI Design Group 383 Inverness Parkway, Suite 190 Englewood, CO 80112-5862 (720) 266-2582 Report Prepared by: Tim Scott Scott Design and Title 24, 1 77-085 Michigan Drive Palm Desert, Ca 92211 (760) 200-4780 •r IC! -n- �c �' �OF LA QUINT UILDING & SAFETY DEpt A APPS ®VEE FOR CONSTRUCTION i.. DA rE 2 y ZoII By - a 1IECEIVMD Job Number: , JAN: 13 2011 Date: : TABLE OF CONTENTS Cover Page Table of Contents Nonresidential Performance Title 24 Forms Form ENV -MM Envelope Mandatory Measures Form LTG -4-C Tailored Method Worksheet Form LTG -MM Lighting Mandatory Measures Form OLTG-1-C Certificate of Compliance Form OLTG-2-C Lighting Compliance -Summary Form MECH-MM Mechanical Mandatory Measures HVAC System Heating and Cooling Loads Summary Zone Load Summary Room Load Summary Room Heating Peak Loads Room Cooling Peak Loads • Room Cooling Coil Loads` EnergyPro 5.1 by EnergySoft Job Number. ID: User Number. 6712 1 2 3 34 35 37 38 42 45 46 .51 , 56 61 70 80 L 4 PERFORMANCE CERTIFICATE OF COMPLIANCE (Part 1 of 3) PERF -1 C Project Name Date itness Building -Tradition Club Assoc. 12/16/2010 Project Address Climate Zone Total Cond. Floor Area Addition Floor Area 78505 Old Ave 52 La Quinta CA Climate Zone 15 5,096 n/a GENERAL INFORMATION Building Type: m Nonresidential ❑ High -Rise Residential ❑ Hotel/Motel Guest Room ❑ Relocatable - indicate ❑ specific climate zone ❑ all climates Phase of Construction: m New Construction ❑ Addition ❑ Alteration STATEMENT OF COMPLIANCE This certificate of compliance lists the building features and specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of Regulations. This certificate applies only to a Building using the performance compliance approach. The documentation author hereby certifies that the documentation is accurate and corn tete. Documentation Author d Name Tim Scott Signature Company Scott Design and Title 24, Inc, Date 12116/2010 Address 77-085 Michigan Drive Phone (760) 200-4780 City/State/Zip palm Desert Ca 92211 The Principal Designer hereby certifies that the proposed building design represented in this set of construction documents is consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with this permit application. The proposed building has been designed to meet the energy efficiency requirements contained in sections 110, 116 through 118, and 140 through 149 of Title 24, Part 6. Please check one: ENV. LTG. MECH. I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to ❑ ❑ ❑ sign this document as the person responsible for its preparation; and that I am licensed in the State of California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect. I affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by section ❑ ❑ ❑ 5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed contractor performing this work. I affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document ❑ ❑ ❑ because it pertains to a structure or type of work described as exempt pursuant to Business and Professions Code Sections 5537, 5538 and 6737.1. Principal Envelope Designer Name Bill Wenche/l Signature Company MAI Design Group Date Address 383 Inverness Parkway, Suite 190 License # City/State/Zip Englewood, CO 80112-5862 Phone (720) 266-2582 Principal Mechanical Designer Name Tim Scott Signature Company Scott Design and Title 24, Inc. Date If z � 10 Address 77-085 Michigan Drive License # City/State/Zip Palm Desert, Ca 92211 Phone (760) 200-4780 Principal Lighting Designer Name Bill Wenchell Signature Company MAI Design Group Date Address 383 Inverness Parkway, Suite 190 License # City/State/Zip Englewood, CO 80112-5862 Phone (720) 266-2582 INSTRUCTIONS TO APPLICANT COMPLIANCE & WORKSHEETS (check box if worksheets are included) m ENV -1C Certificate of Compliance. Required on plans. m MECH-1C Certificate of Compliance. Required on plans. m LTG -1 C Certificate of Compliance. Required on plans. m MECH-2C Air/Water Side/Service Hot Water & Pool Requirements. m LTG -2C Lighting Controls Credit Worksheet. m MECH-3C Mechanical Ventilation and Reheat. 0 LTG -3C Indoor Lighting Power Allowance. m MECH-5C Mechanical Equipment Details. Energ Pro 5.1 by Energ Soft User Number: 6712 Run Code: 2010-12-16709:50:29 ID: Page 3 of 89 goilfitnessBuildihg-Tr,iditionblubAssoc.' ,. "' y �` - -12/1612010 ' ANN UAL-TDV ENERGY USES MMARYkBtu/s ft- r _ ' i Standard . ProposedComplianceRM- „ Space Heating Space Cooling Indoor Fans.- 'Heat ans'Heat Rejection ; Pumps & Misc.- Domestic Hot Water Lighting , Receptacle Process Processlighting : TOTALS - 3.21 163 1.58 210.99 154.16 56.82 54.14 85.5 0 ;' 31.36 0:00 y w o.o0 0.00 ` 0.00 `_ -0.00 OM 17.63 14.29 - 3.33 86.35 '` 41;12.27 ; `-25.92 z 4 •.• 132.05 32.05 0.00 0.00 4 0.00 ' -0.00 " 0.00 0.00 0.00 404.36 ; 399.90 4.46 Heating Cooling Fans.. Heat Rei Pumps «. "• ..DHW Lighting Receptacle Process Process Lt 1. g Percent better than Standard ` 1.1 ' i1 % excluding rocess ''BUILDING COMPLIES GENERAL INFORMATION. Building;Orientation (s)160deg Conditioned•Floor'Area` x5,096 sqf.. . Number of Stories ;.sgft. sqk l'p = �`�'-'.225 sgft, , Number of Systems..: _. < E6 .y ` 9 - f6•� �•` `' p.- 11 Natural Gas Available On Site; ' : Yes ' sgft. sgft. `. Right Elevation .sgft.' sgft: (e) ; 741 23 14,894 576sgft. � s Total Roof, t . sgft: k -sgft. Y.P soft• 5,096 . Percent better than Standard ` 1.1 ' i1 % excluding rocess ''BUILDING COMPLIES GENERAL INFORMATION. Building;Orientation (s)160deg Conditioned•Floor'Area` x5,096 sqf.. . Number of Stories ;.sgft. Unconditioned Floor Area = �`�'-'.225 sgft, , Number of Systems..: _. < E6 Conditioned Footprint Area ' ^ 'v.5,096 sgft.. ` Number of Zones `' p.- 11 Natural Gas Available On Site; ' : Yes ' -Orient ation:''� Gross Area Glazin 'Area ' ' ' Glazin Ratio ' 23.6''% 0.6 13.0% c 3.2 11:8.�Y o.o % Front Elevation (s) 't, . ..., 1,545 -sgft: 365 ;.sgft. Left. Elevation # : sgft. sgft.. ` (w1: 1,201 7 , . (N)' :° .'1,407 183 Re'ar�Elevation sgft. sgft. `. Right Elevation .sgft.' sgft: (e) ; 741 23 14,894 576sgft. � s Total Roof, t . sgft: k -sgft. Y.P soft• 5,096 ' ` 0 23.6''% 0.6 13.0% c 3.2 11:8.�Y o.o % r I� PERFORMANCE CERTIFICATE OF COMPLIANCE (Part 3 of 3) PERF -1 C Project Name fitness Building -Tradition Club Assoc. Date 11211612010 ZONE INFORMATION System Name Zone Name Floor Inst. Ctrl. Allowed LPD Proc. Area LPD Credits Area Tailored Loads Occupancy Type s ft. W/sf' W/sf 2 W/sf 3 W/sf ° W/sf HP 1 Yoga Exercise, Gymnasium 673 1.004 0.201 1.300 HP 2 & 3 Cardio/Circuit Exercise, Gymnasium 1,740 1.609 0.175 1.400 Free Weights Exercise, Gymnasium 281 2.491 0.498 1.400 HP 4 Relaxation Room Exercise, Gymnasium 300 3.267 0.773 1.400 Therapy 1 Exercise, Gymnasium 124 1.258 0.252 1.400 Therapy 2 Exercise, Gymnasium 112 1.393 0.279 1.400 Foyer/Reception Lobby, Main Entry 643 3.994 0.7401 1.100 HP 5 Men's Locker Room Locker/Dressing Room 563 1.837 0.325 1.100 HP 6 Women' Locker Room Locker/Dressing Room 660 1.167 0.197 1.100 Mech Room Electrical, Mechanical Room 78 0.333 0.067 Mech/Elec Room Electrical, Mechanical Room 147 0.531 0.106 Notes: 1. See LTG -1C 2. See LTG -2C 3. See LTG -3C 4. See LTG -4C Items above require special documentation items marked with asterisk, see LTG -1 -C by others) (by others EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST The local enforcement agency should pay special attention to the items specified in this checklist. These items require special written justification and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of the justifications, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation submitted. The DHW System Bradford -White Corp. EF-60T-125E-3NA is a non-NAECA large storage gas water heater. Verify DHW details. The HVAC System HP 1 incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the MECH-4-A. The HVAC System HP 2 & 3 incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the MECH-4-A. The HVAC System HP 4 incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the MECH-4-A. The HVAC System HP 5 incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the MECH-4-A. The HVAC System HP 6 incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the MECH-4-A. The HVAC System Lennox XP17-048-230' A Premium Efficiency 0.50 BHP Supply Fan Motor has been specified. The HVAC System Lennox XP17-060-230" A Premium Efficiency 0.70 BHP Supply Fan Motor has been specified. The exceptional features listed In this performance approach application have specifically been reviewed. Adequate written justification and documentation for their use have been provided by the applicant. Authorized Signature or Stamp Energ Pro 5.1 by EnergySoft User Number- 6712 RunCode: 2010-12-16709:50:29 ID: Page 5 of 89 C� J • r-1 L -a CERTIFICATE OF COMPLIANCE (Part 1 of 3) ENV -1 C AND FIELD INSPECTION ENERGY CHECKLIST Project Name Fitness Building -Tradition Club Assoc. Date 1 12/16/2010 Project Address 78505 Old Ave 52 La Quinta Climate Zone 15 Total Cond. Floor Area 5, 096 Addition Floor Area n/a GENERAL INFORMATION Building Type: m Nonresidential ❑ High -Rise Residential ❑ Hotel/Motel Guest Room ❑ Schools (Public School) ❑ Bledlocatable g. Public School m Conditioned Spaces [3 Unconditioned Spaces ❑ Skylight Area for Large Enclosed Space >_ 8000 ft2 (If checked include the ENV -4C with submittal) Phase of Construction: m New Construction ❑ Addition ❑ Alteration Approach of Compliance: ❑ Component m Overall Envelope ❑ Unconditioned (file affidavit) Front Orientation: N, E, S, W or in Degrees: 160 deg FIELD INSPECTION ENERGY CHECKLIST OPAQUE SURFACE DETAILS INSULATION [Ta/ID' AssemblyType 2 •C y Q 0 3 N d W O z 0 D �. � R V M ac � d % To V w> Cm O� V w U. m � d 7 eo > 0 E - d v 0 c. x E-O o a -3 a c C o .. 0 rn N m a is a 1 Roof 673 (N) 1 0.026 R-38 4.2.1-A9 New ❑ ❑ 2 Wall 232 (E) 0.069 R-21 4.3.1-A6 New ❑ ❑ 3 Wall 62 (S) 0.069 R-21 4.3.1-A6 New ❑ ❑ 4 Wall 248 (W) 0.069 R-21 4.3.1-A6 New ❑ ❑ 5 Wall 200 (N) 0.069 R-21 4.3.1-A6 New ❑ ❑ 6 Slab 673 (N) 1 0.730 None 4.4.7-A1 New ❑ ❑ 7 Roof 1,740 (N) 0.026 R-38 4.2.1-A9 New ❑ ❑ 8 Wall 38 (E) 0.069 R-21 4.3.1-A6 New ❑ ❑ 1. See Instructions in the Nonresidential Compliance Manual, page 3-96. 2. If Fail, then describe on Page 2 of the Inspection Checklist Form and take appropriate action to correct. A fail does not meet compliance. FENESTRATION SURFACE DETAILS Tag/ID' Fenestration Type ' d Q 03 ~O cN W O Z v LL > 0 v 4 O > CO 2 Cn °G U v Z O N N C C L > O c C O 0 U ur H a a 1 Window 23 (E) 0.250 NFRC 0.3901 NFRC ❑ New ❑ ❑ 2 Window 45 (S) 0.250 NFRC 0.390 NFRC ❑ New ❑ ❑ 3 Window 58 (S) 0.250 NFRC 0.390 NFRC ® New ❑ ❑ 4 Window 58 (S) 0.250 NFRC 0.390 NFRC ® New ❑ ❑ 5 Window 58 (S) 0.250 NFRC 0.390 NFRC ® New ❑ ❑ 6 Window 58 (S) 0.250 NFRC 0.390 NFRC ® New ❑ ❑ 7 Window 98 (N) 0.250 NFRC 0.390 NFRCJ ® New ❑ ❑ 8 Window 42 (N) 0.250 NFRC 0.390 NFRC ® New ❑ ❑ 0 13+13 13 13 13 1. See Instructions in the Nonresidential Compliance Manual, page 3-96. 2. If Fail then describe on Page 2 of the Inspection Checklist Form and take appropriate action to correct. Verify building plans if necessary. EnergyPro 5.1 by EnergySoft User Number: 6712 Run Code: 2010-12-16709:50:29 ID: Page 6 of 89 n AL C� CERTIFICATE OF COMPLIANCE (Part 1 of 3) ENV -1 C AND FIELD INSPECTION ENERGY CHECKLIST Project Name Fitness Building -Tradition Club Assoc. Date 1 12/16/2010 Project Address 78505 Old Ave 52 La Quinta Climate Zone 15 Total Cond. Floor Area 5,096 Addition Floor Area n/a GENERAL INFORMATION Buildin Type: m Nonresidential ❑ High -Rise Residential ❑ Hotel/Motel Guest Room ❑ Schools (Public School) ❑ RRledlocatable g. Public School m Conditioned Spaces ❑ Unconditioned Spaces ❑ Skylight Area for Large Enclosed Space z 8000 ft2 (If checked include the ENV -4C with submittal) Phase of Construction: m New Construction ❑ Addition ❑ Alteration Approach of Compliance: ❑ Component m Overall Envelope ❑ Unconditioned (file affidavit) Front Orientation: N, E, S, W or in Degrees: 160 deg FIELD INSPECTION ENERGY CHECKLIST OPAQUE SURFACE DETAILS INSULATION Ta /ID z AssemblyType Q C o C N OZ cd V M .�'. 0M oC¢ 01 W> �� C WU. C 0) 5> C 51L v K 'a 0C! CL �< c oe 7 C VN a ti 9 Wall 460 (S) 0.069 R-21 4.3.1-A6 New ❑ ❑ 10 Wall 174 (IM 0.069 R-21 4.3.1-A6 New ❑ ❑ 11 Wall 230 (N) 0.069 R-21 4.3.1-A6 New ❑ ❑ 12 Slab 1,740 (N) 0.730 None 4.4.7-A1 New ❑ ❑ 13 Roof 281 (N) 1 0.026 R-38 4.2.1-A9 New ❑ ❑ 14 Wall 78 (E) 0.069 R-21 4.3.1-A6 New ❑ ❑ 15 Wall 219 (N) 0.069 R-21 4.3.1-A6 New ❑ ❑ 16 Wall 174 (IM 0.069 R-21 4.3.1-A6 New ❑ ❑ ❑ ❑ ❑ ❑ 1. See Instructions in the Nonresidential Compliance Manual, page 3-96. 2. If Fail, then describe on Page 2 of the Inspection Checklist Form and take appropriate action to correct. A fail does not meet compliance. FENESTRATION SURFACE DETAILS Tag/ID' Fenestration Type z i a •C°- 3 A cN d W O Z .0.. s . 4 M> .0 � t 4 .O > N � x y 2¢ " U x 0 N V) rn C t > O c ya v o r U to N tyo a iv a 9 Window 42 (N) 0.250 NFRC 0.390 NFRC ® New ❑ ❑ 10 Window 86 (S) 0.250 NFRC 0.390 NFRC ® New ❑ ❑ 11 Window 7 (IM 0.250 NFRC 0.390 NFRC ❑ New ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ Cl ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ 1. See Instructions in the Nonresidential Compliance Manual, page 3-96. 2. If Fail then describe on Page 2 of the Inspection Checklist Form and take appropriate action to correct. Verify building plans if necessary. EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2010-12-16709:50:29 ID: Pae 7 of 89 0 • CERTIFICATE OF COMPLIANCE (Part 1 of 3) ENV -1 C AND FIELD INSPECTION ENERGY CHECKLIST Project Name Fitness Building -Tradition Club Assoc. Date 1 12/16/2010 Project Address 78505 Old Ave 52 La Quinta Climate Zone 15 Total Cond. Floor Area 5,096 Addition Floor Area n/a GENERAL INFORMATION Building Type: m Nonresidential ❑ High -Rise Residential ❑ Hotel/Motel Guest Room ❑ Schools (Public School) ❑ RRledlocatable g. Public School m Conditioned Spaces ❑ Unconditioned Spaces ❑ Skylight Area for Large Enclosed Space z 8000 ft2 (If checked include the ENV -4C with submittal) Phase of Construction: m New Construction ❑ Addition ❑ Alteration Approach of Compliance: ❑ Component m Overall Envelope ❑ Unconditioned (file affidavit) Front Orientation: N, E, S, W or in Degrees: 160 deg FIELD INSPECTION ENERGY CHECKLIST OPAQUE SURFACE. DETAILS INSULATION Ta /ID 2 AssemblyType Q c 0Z M V¢ W> uJ{L C> CLL v -°7Q i°iN d LL 17 Slab 281 (N) 0.7301 None 4.4.7-A1 New ❑ ❑ 18 Roof 300 (N) 0.026 R-38 4.2.1-A9 New ❑ ❑ 19 Wall 60 (E) 0.069 R-21 4.3.1-A6 New ❑ ❑ 20 Wall 33 (IM 0.069 R-21 4.3.1-A6 New ❑ ❑ 21 Wall 265 (N) 0.069 R-21 4.3.1-A6 New ❑ ❑ 22 Slab 300 (N) 0.730 None 4.4.7-A1 New ❑ ❑ 23 Roof 124 (N) 0.026 R-38 4.2.1-A9 New ❑ ❑ 24 Wall 85 (E) 0.069 R-21 4.3.1-A6 New ❑ ❑ ❑ ❑ ❑ ❑ 1. See Instructions in the Nonresidential Compliance Manual, page 3-96. 2. If Fail, then describe on Page 2 of the Inspection Checklist Form and take appropriate action to correct. A fail does not meet compliance. FENESTRATION SURFACE DETAILS Tag/ID' Type 2 � a 0 3 w "d N O Z ` S v 2 L S LLv v > n U m�NFenestration E. 2 zU v' N rn c, ` t> O c 0 o U w m a A a ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ 1. See Instructions in the Nonresidential Compliance Manual, page 3-96. 2. If Fail then describe on Page 2 of the Inspection Checklist Form and take appropriate action to correct. Verify building plans if necessary. EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2010-12-16T09:50:29 ID: Page 8 of 89 C� J C CERTIFICATE OF COMPLIANCE (Part 1 of 3) ENV -1 C AND FIELD INSPECTION ENERGY CHECKLIST' Project Name Fitness Building -Tradition Club Assoc. Date 1 12/16/2010 Project Address 78505 Old Ave 52 La Quinta Climate Zone 15 Total Cond. Floor Area 5,096 Addition Floor Area n/a GENERAL INFORMATION Building Type: m Nonresidential ❑ High -Rise Residential ❑ Hotel/Motel Guest Room ❑ Schools (Public School) ❑ Bledlocatable g. Public School 0 Conditioned Spaces ❑ Unconditioned Spaces ❑ Skylight Area for Large Enclosed Space z 8000 ft2 (If checked include the ENV -4C with submittal) Phase of Construction: m New Construction ❑ Addition ❑ Alteration Approach of Compliance: ❑ Component m Overall Envelope ❑ Unconditioned (file affidavit) Front Orientation: N, E, S, W or in Degrees: 160 deg FIELD INSPECTION ENERGY CHECKLIST OPAQUE SURFACE DETAILS INSULATION t Ta /ID 2 Assembly Ty e Q 0 3 cN OZ L t;00 0M oC ` W� ` „, c WU. � °m E> ° U. x «aci -54 c .0 v tiw gn a LL 25 Wall 88 (tM 0.069 R-21 4.3.1-A6 New ❑ ❑ 26 Wall 64 (N) 0.069 R-21 4.3.1-A6 New ❑ ❑ 27 Slab 124 (N) 0.730 None 4.4.7-A1 New ❑ ❑ 28 Roof 112 (N) 0.026 R-38 4.2.1-A9 New ❑ ❑ 29 Wall 40 (E) 0.069 R-21 4.3.1-A6 New ❑ ❑ 30 Wall 64 (N) 0.069 R-21 4.3.1-A6 New ❑ ❑ 31 Slab 112 (N) 0.730 None 4.4.7-A1 New ❑ ❑ 32 Roof 643 (N) 0.026 R-38 4.2.1-A9 New ❑ ❑ ❑ ❑E ❑ ❑ 1. See Instructions in the Nonresidential Compliance Manual, page 3-96. 2. If Fail, then describe on Page 2 of the Inspection Checklist Form and take appropriate action to correct. A fail does not meet compliance. FENESTRATION SURFACE DETAILS Tag/ID' Type 2 c3 A "' N y WV O Z V 'a o , V V o > in V O _ ^ V zo> N N -E O H .c°-- N o: O - mFenestration a iv ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ Cl ❑ ❑ ❑ ❑ 1. See Instructions in the Nonresidential Compliance Manual, page 3-96. 2. If Fail then describe on Page 2 of the Inspection Checklist Form and take appropriate action to correct. Verify building plans if necessary. EnergyPro 5. 1 by EnergySoft User Number. 6712 RunCode: 2010.12-16709:50:29 ID: Page 9 of 89 0 C C CERTIFICATE OF COMPLIANCE (Part 1 of 3) ENV -1 C AND FIELD INSPECTION ENERGY CHECKLIST Project Name Fitness Building -Tradition Club Assoc. Date 1 12/16/2010 Project Address 78505 Old Ave 52 La Quinta Climate Zone 15 Total Cond. Floor Area 5,096 Addition Floor Area n/a GENERAL INFORMATION Building Type: m Nonresidential ❑ High -Rise Residential ❑ Hotel/Motel Guest Room ❑ Schools (Public School) ❑ Blldlocatable Public Schoolg. m Conditioned Spaces ❑ Unconditioned Spaces ❑ Skylight Area for Large Enclosed Space z 8000 ft2 (If checked include the ENV -4C with submittal) Phase of Construction: m New Construction ❑ Addition ❑ Alteration Approach of Compliance: ❑ Component m Overall Envelope ❑ Unconditioned (file affidavit) Front Orientation: N, E, S, W or in Degrees: I 160 deg FIELD INSPECTION ENERGY CHECKLIST OPAQUE SURFACE DETAILS INSULATION 1 Ta /ID Assembly Te 2 y Q c O 3 ,.0.. C N d! W 02 ` r V ti M 7 >> UM ¢ O d N 7 W > O 'C. C N W {L O .` d N O Ci .O C N ALL v x .� d C O -24 c 'O 7 C 02 U( 0 • 0 CERTIFICATE OF COMPLIANCE (Part 1 of 3) ENV -1 C AND FIELD INSPECTION ENERGY CHECKLIST Project Name Fitness Building -Tradition Club Assoc. Date 12/1612010 Project Address 78505 Old Ave 52 La Quinta Climate Zone 15 Total Cond. Floor Area 5,096 Addition Floor Area n/a GENERAL INFORMATION Building Type: m Nonresidential ❑ High -Rise Residential ❑ Hotel/Motel Guest Room ❑ Schools (Public School) ❑ Bedlocatable g. Public School m Conditioned Spaces ❑ Unconditioned Spaces ❑ Skylight Area for Large Enclosed Space z 8000 ft2 (If checked include the ENV -4C with submittal) Phase of Construction: m New Construction ❑ Addition ❑ Alteration Approach of Compliance: ❑ Component m Overall Envelope ❑ Unconditioned (file affidavit) Front Orientation: N, E, S, W or in Degrees: 160 deg FIELD INSPECTION ENERGY CHECKLIST OPAQUE SURFACE DETAILS INSULATION t Ta /ID 2 Assembly T e A a 23 .0 N y UJ OZ L O l0 W Y? •> l0 ti oi: o'c L O d 7 W> L� O C d Lu LL tr L O 41 d C] O co d �LL x •C .+ C a -.54C1N c 0 O7 'O C -4 y y d IL 41 Wall 185 (E) 0.069 R-21 4.3.1-A6 New ❑ ❑ 42 Wall 280 (►M 0.069 R-21 4.3.1-A6 New ❑ ❑ 43 Slab 660 (N) 0.730 None 4.4.7-A1 New ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ 1. See Instructions in the Nonresidential Compliance Manual, page 3-96. 2. If Fail, then describe on Page 2 of the Inspection Checklist Form and take appropriate action to correct. A fail does not meet compliance. FENESTRATION SURFACE DETAILS Tag/ID' Fenestration Type 2 a c3 O d W Z O G RLL 2> r LL oo > N V '� r^ ¢ _ 'o N N C O Cc r< 0- U w m a cc LL ❑ ❑ ❑ ❑j ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ a ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ 1. See Instructions in the Nonresidential Compliance Manual, page 3-96. 2. If Fail then describe on Page 2 of the Inspection Checklist Form and take appropriate action to correct. Verify building plans if necessary. EnergyPro 5. 1 by EnergySoft User Number. 6712 RunCode: 2010-12-16709:50:29 ID: Pae 11 of 89 a a CERTIFICATE OF COMPLIANCE (Part 2 of 3) AND FIELD INSPECTION ENERGY CHECKLIST ENV -1 C Project Name Fitness Building -Tradition Club Assoc. Date 12/16/2010 ROOFING PRODUCT COOL ROOFS (Note if the roofing product is not CRRC certified, this compliance approach cannot be used). Go to Overall Envelope Approach or Performance Approach. CHECK APPLICABLE BOX BELOW IF EXEMPT FROM THE ROOFING PRODUCT "COOL ROOF" REQUIREMENTS: Pass Fail' N/A ❑ Roofing compliance not required in Climate Zones 1 andl6 with a Low -Sloped. 2:12 pitch or less. ❑ ❑ ❑ ❑ Roofing compliance not required in Climate Zone 1 with a Steep -Sloped with less than 5 Ib/ft2. Greater than 2:12 pitch. ❑ ❑ ❑ Low -sloped Wood framed roofs in Climate Zones 3 and 5 are exempted, solar reflectance and thermal emittance or 13 SRI that have a U -factor of 0.039 or lower. See Opaque Surface Details roof assembly, Column H of ENV -2C. 13 13 13 ❑ Low -sloped Metal building roofs in Climate Zone 3 and 5 are exempted, solar relectance and thermal emittance or SRI that have a U -factor of 0.048 or lower. See Opaque Surface Details roof assembly below, Column H of ENV -2C. ❑ ❑ ❑ ❑ The roof area covered by building integrated photovoltaic panels and building integrated solar thermal panels are exempted. Solar reflectance and thermal emittance or SRI, seespreadsheet calculator at www.ener .ca. ov/title24/ ❑ ❑ ❑ 13 Roof constructions that have thermal mass over the roof membrane with a weight of at least 25 Ib/ft are exempt from the Cool Roof criteria below. ❑ ❑ ❑ ❑ High-rise residential buildings and hotels and motels with low -sloped roofs in Climate Zones 1 through 9, 12 and 16 are exempted from the low -sloped roofing criteria. ❑ ❑ ❑ 1. If Fail then describe on this page of the Inspection Checklist Form and take appropriate action to correct. Verify building plans if necessary. CRRC Product ID Number' Roof Slope Product Weight s 2:12 > 2:12 < 51b/ftp t 51b/ft2 Product Type 2 Aged Solar Reflectance Thermal Emmitance SR 15 Pass Fail6 ❑ ❑ ❑ ❑ ❑ 4 ❑ ❑ ❑ ❑ ❑ ❑ ❑ 4 ❑ ❑ ❑ ❑ ❑ ❑ ❑4 ❑ 1 ❑ ❑ ❑ ❑ ❑ ❑ 4 ❑ ❑ ❑ ❑ ❑ ❑ ❑4 ❑ ❑ ❑ ❑ ❑ 1 ❑ ❑ 4 ❑ ❑ 1. The CRRC Product ID Number can be obtained from the Cool Roof Rating Council's Rated Product Directory at www.coolroofs.or-q/r)roducts/search.php 2. Indicate the type of product is being used for the roof top, i.e. single -ply roof, asphalt roof, metal roof, etc. 3. If the Aged Reflectance is not available in the Cool Roof Rating Council's Rated Product Directory then use the Initial Reflectance value from the same directory and use the equation (0.24.7(p;n;,,a, — 0.2) to obtain a calculated aged value. Where p is the Initial Solar Reflectance from the Cool Roof Rating Council's Rated Product Directory. 4. Check box if the Aged Reflectance is a calculated value using the equation above. 5. The SRI value needs to be calculated from a spreadsheet calculator at http://www.enerciv.ca.gov/title24/ 6. If Fail then describe on this page of the Inspection Checklist Form and take appropriate action to correct. Verify building plans if necessary. To apply Liquid Field Applied Coatings, the coating must be applied across the entire roof surface and meet the dry mil thickness or coverage recommended by the coatings manufacturer and meet minimum performance requirements listed in §118(i)4. Select the applicable coating: ❑ Aluminum -Pigmented Asphalt Roof Coating ❑ Cement -Based Roof Coating ❑ Other Discrepancies: EnemyPro 5.1 by EnemySoft User Number: 6712 RunCode: 2010-12-16709:50:29 ID: Pae 12 of 89 CJ • CERTIFICATE OF COMPLIANCE (Part 3 of 3) ENV -1 C AND FIELD INSPECTION ENERGY CHECKLIST Project Name Fitness Building -Tradition Club Assoc. Date 11211612010 Required Acceptance Tests Designer: This form is to be used by the designer and attached to the plans. Listed below is the acceptance test for Envelope Fenestrations system. The designer is required to check the acceptance tests and list all the fenestration products that require an acceptance test. If all the site -built fenestration of a certain type requires a test, list the different fenestration products and the number of systems. The NA7 Section in the Appendix of the Nonresidential Reference Appendices Manual describes the test. Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work appropriately. Enforcement Agency: Systems Acceptance. Before Occupancy Permit is granted for a newly constructed building or space or whenever new fenestration is installed in the building or space shall be certified as meeting the Acceptance Requirements. The ENV -2A form is not considered a complete form and is not to be accepted by the enforcement agency unless the boxes are checked and/or filled and signed. In addition, a Certificate of Acceptance forms shall be submitted to the enforcement agency that certifies plans, specifications, installation certificates, and operating and maintenance information meet the requirements of §10-103(b) of Title 24 Part 6. The field inspector must receive the properly filled out and signed forms before the building can receive final occupancy. A copy of the ENV -2A for each different fenestration product line must be provided to the owner of the building for their records. Test Description ENV -2A Test Performed By: Fenestration Products Name or ID Area of like Building Envelope Requiring Testing or Verification Products Acceptance Test Double Non Metal Tinted 578 m 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 �89 EnergyPro 5.1 by EnergySoft User Number: 6712 Run Code: 2010-12-16709:50:29 ID: Pae 13 of CERTIFICATE OF COMPLIANCE (Part 1-of_3)LTG-1C Project Name '° . - itness`Bu►Iding-Tradition Club Assoc Date . 12/16/2010 INDOOR LIGHTING SCHEDULE and FIELD.INSPECTION.ENERGY CHECKLIST,, .Installation Certificate, LTG -1- INST (Retain a.co and verif form is completed and signed.) Field Inspector ❑ Certificate of Acceptance, LTG -2A (Retain a copy and verify form is completed and signed. Field'Ins ector ❑ A separate Lighting Schedule Must Be Filled Out for Conditioned and Unconditioned Spaces Installed Lighting Power listed on . this Lighting Schedule is onlyfor: m -CONDITIONED SPACE ❑ ,'UNCONDITIONED SPACE . m• The actual indoor lighting power listed below includes all installed permanent and portable lighting systems in accordance with §146(a).:- Only for offices: Up to the first 0.2 watts per square foot of portable lighting shall not be required to be included in the m calculation of actual: indoor lighting power density in accordance with the Exception to §146(a): All portable lighting in..excessof 0.2 watts per square foot is 4otaled below. s ° Luminaire T e lam s, Ballasts Installed Watts A B C D E. F G H. None or Item'(i.e,;3lamp`fluorescent Ta - . w "- . Complete Luminaire Description - troffer, 'i F32T8;bne dimmable electronic ballasts �. a a°� >ed How wattage Was determined E E_. > > U' mca 'N F Ins eId_ �u `, eetoi� . „a -.'CEC Default From NA8k<„ o.w, �' o A2 (1) 4 It Fluorescent T8 Energy Savings Elec' ❑ 26.0 ® ❑ 3 78 81 (1) 41t;Fluorescent T8 Energy Savings Elec ❑ 26.0 ®: { ❑ "� . 27 7011 ® „ B2 (1).4 R FluorescenfTB Energy Savings E/ec `. ❑ 26.0. ® ❑ 53 1,378, ❑� JDC1�.: 18-60w Recessed Incandescent, ❑ 1,080.0 - ® ❑ 1 1,080 ® k IDC2 3-60w Incandescent . ' ❑ � 180.0. ®" �, • ; • . - 2 360 fy'❑ IDC3 12-60w Incandescent , . ' ❑ 720.'0. -,0 ❑ '1 720 "d IDC5 3-60w Incandescent I> '180.0 _ ® ❑ 4 -720 ® 0 IDW# 60w Surface Mount Incandescent , D 60.0; ® ❑ " 2 120❑ �n ❑ IDW3 ' 60w Surface Mount Incandescent. • ❑. 60.0 ®. _❑ 2 120 0 IDW4 2-60w Wall Mount Incandescent ❑ 120. ® ❑ 6 720 u 0 Q3 35w Low Voltage Halogen ❑ 35.0 ® ❑ 16 560® R 50w Low Voltage Halogen ❑ ' 50.0 21 ❑ • 41 2,050 kr R2 50w Low Voltage Halogen ❑ 50:0 ® ❑ 10. 500 RF ' (1) 26wCompact Fluorcent Triple 4 Pin ❑;` 28.0 = ® ❑ 24 672 WP1F (1) 13w Compact Fluorescent Triple 4 Pin El 15.0 ® �'' 4 60 t] ❑ ❑' o _ moo. • o ❑ :° ❑ ❑ a• a 1®1 Installed Watts Pa eJotal; 9,840 Building total number of pages: Installed Watts Building Total Sum of all pages) ..: 9.840 Enter into LTGA C Page 4 of 4 1. Wattage shall be determined according Section'130 (d and:e). Wattage shall berating of light fixture, not rating of bulb. 2. If Fail then describe on Page 2 of theinspection Checklist Form and take appropriate action to correct. Verifybuilding plans,if necessary. Energypro 5.1 by Erie Soft User Number. 6712; Run Code: 2010-12-1670930:29 ID: Pae 14 of 89 CERTIFICATE OF COMPLIANCE (Part 1 of,3) ' LTG-1C r Pr61ect NameDate is itness Building-Tradition 06b Assoc: ` ,� 12116/2010 . INDOOR LIGHTING SCHEDULE and -FIELD INSPECTION-ENERGY CHECKLIST 11 Installation Certificate, LTGA- INST Retain a copy and verify form is completed and signed.) ; Field Inspector Certificate of Acceptance; LTG-2A (Retain a copy and verify form is completed and signed.) Field Ins ector . ❑ 1 A separate Lighting Schedule Must Be Filled Out for Conditioned and Unconditioned Spaces lristalied Lighting, Power listed,on this Lighting Schedule is only for: . ❑ CONDITIONED SPACE 0 UNCONDITIONED SPACE m The actual indoor lighting power listed below includes all, installed permanent and portable lighting systems in accordance- with §146(a). Only for offices;-Up to'the first 0.2 watts per square foot,of.portable lighting shall not be required to be included in the,.. m " calculation of actual indoor lighting power density in accordancewith the Exception to §146(a). All portable lighting in excess of 0.2.watts per square footis totaled below: Luminaire (Type, Lamps, Ballasts Installed Watts A $_ .. :, C D E F. G .• H. • How.wattage Fields Was determinedLL Ins "ecio None . LL a•� U CEC v c,),� v W or Complete Luminaire Description 4, 0 m 'E. Default 0 aa, " From 8 ` E '>_ = m N = c0 Item Ta (Le, 3 lamp fluorescent troffer, . F32T8, one dimmable electronic ballasts a J 0 NAf3 Q 1-- > Z "u A4 (1) 4 ft Fluorescent T8 Energy Savings Elec ' ❑ 26.0 ,: ® ❑ 4 ;' 104 ®� ❑ o��o 0 ❑.❑. = o' �p - ❑. = ❑ ®� god o °:® f ❑ ❑ ❑ ®F❑ o ❑ ❑ ❑ ` ❑ ❑ ❑: o •, . o ❑�: o ❑�a a;a - - - ❑. r❑ ❑.r�m. Wir A Roy, a ❑ ❑ _ - ' ❑ ❑ T o = •❑ ❑®o 'Installed-WattsPag6 Total: - 104 �.- - Installed Watts Building',Total Building total number of.pages: Sum of all pages Enter, into, LTG-1 C Page 4 of 4 . 10.4 { 1. Wattage shall be determined according to Section 130 (d and e): Wattage shall be rating of light fixture, not rating.of bulb 2 _ If Fail then describe on Page 2 of the Inspection Checklist Form and take appropriate action to correct.-Verify building plans if necessary._,' Ene Pro 5 1 b Ene Soft User Number.- 6712 RunCode: 2010-12-16709:50:29 ID: - Page 15 of 89 r .CERTIFICATE OF COMPLIANCE": (Part 2. of 3) _ LTG -1 C Project Name Fitness Building -Tradition Club Assoc. ,. '� Date 12/16/20,10 INDOOR LIGHTING SCHEDULE and FIELD INSPECTION ENERGY -CHECKLIST Fill in'controls for all spaces: a) area controls, b) multi-level controls, c) manual daylighting controls for daylit areas > 250.ft?; automatic daylighting controls for daylit` areas > 2,500 ft2, d) shut=off controls, e) display lightirig:controls, f); tailored lighting controls general lighting.controlled separately from display, ornamental and display case,lighting'and g) demand responsive automatic controls for retail stores ,> 50;000 ft2, in accordance with Section 131., - MANDATORY LIGHTING CONTROLS — FIELD INSPECTION ENERGY CHECKLIST , i ^- sp t Iris ector . Number Speciale z , T e/•Descri tion of Units Location in Buildin Features Pass , , Faila ,< ❑�IN®r T ,g,� 2`i%I��px} BE gn .. - ❑ f®BM ,❑ l vy ave. b ��1E. 10 a Iff am 13 113 13 d Ern Y 13 INN W _ oo. a o , _ , ❑ . E4 , �� - `o- foo ❑A it SPECIAL FEATURES INSPECTION CHECKLIST See Pa4e 2 of 4 of LTG -1C ' The local enforcement agency should pay special -attention to the items specified in this checklist. These items require special written justification and documentation, and special verification. The local enforcement agency determines the adequacy of the justification, and.may reject a building or design that otherwise complies based on the adequacy of the`special justification and documentation _. submitted. r Field Inspector's Notes or Discrepancies: . EnergyPro 5.1 by EnergySoft User Number. 6712 RunCode: 2010-12-16709:50:29 ID. .. > Pae 16 of 89 r� U CERTIFICATE OF COMPLIANCE Part 3 of 3 LTG -1 C Project Name 1 Date Fitness Building -Tradition Club Assoc. 12/16/2010 CONDITIONED AND UNCONDITIONED SPACE LIGHTING MUST NOT BE COMBINED FOR COMPLIANCE Indoor Li htin 'Power for Conditioned S aces Indoor Lighting Power for Unconditioned Spaces Watts Watts Installed Lighting 9,840 Installed Lighting 104 from Conditioned LTG -1 C, Page 2 from Unconditioned LTG -1C, Page 2 Lighting Control Credit - 1662 Lighting Control Credit 21 Conditioned Spaces from LTG -2C Unconditioned Spaces from LTG -2C Adjusted Installed — 8,178 Adjusted Installed = 83 Lighting Power Liahtina Power Complies if Installed 5 Allowed Complies if Installed:5 Allowed Allowed Lighting Power Allowed Lighting Power Conditioned Spaces from LTG -3C or PERF -1 8,178 Unconditioned Spaces from LTG -3C)158 Required Acceptance Tests Designer: This form is to be used by the designer and attached to the plans. Listed below is the acceptance test for the Lighting system, LT6-2A. The designer is required to check the acceptance tests and list all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for Code Compliance. If all the lighting system or control of a certain type requires a test, list the different lighting and the number of systems. The NA7 Section in the Appendix of the Nonresidential Reference Appendices Manual describes the test. Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work appropriately. Forms can be grouped by type of Luminaire controlled. Enforcement Agency: Systems Acceptance. Before Occupancy Permit is granted for a newly constructed building or space or when ever new lighting system with controls is installed in the building or space shall be certified as meeting the Acceptance Requirements. The LTG -2A form is not considered a complete form and is not to be accepted by the enforcement agency unless the boxes are checked and/or filled and signed. In addition, a Certificate of Acceptance forms shall be submitted to the enforcement agency that certifies plans, specifications, installation certificates, and operating and maintenance information meet the requirements of §10-103(b) of Title 24 Part 6. The field inspector must receive the properly filled out and signed forms before the building can receive final occupancy. A copy of the LTG -2A for each different lighting luminaire control(s) must be provided to the owner of the building for their records. Controls for Credits LTG -2A Controls and Sensors and Automatic Number of Daylighting Luminaire Controls Equipment Re uirin Testing Description controls Location Acceptance Occ Sensor- Multi -Level (1) 4 ft Fluorescent T8 Energy Saving: 241 Yoga Occ Sensor- Multi -Level (1) 4 If Fluorescent T8 Energy Saving: 2 Yoga Occ Sensor - Multi -Level 50w Low Voltage Halogen 16 Cardio/Circuit 91 Dimming - Manual 2-60w Wall Mount Incandescent 6 Cardio/Circuit Dimming - Manual 3-60w Incandescent 4 Cardio/Circuit Occ Sensor - Multi -Level 50w Low Voltage Halogen 14 Free Weights ❑ Dimming w/Occ Sensor 12-60w Incandescent 1 Relaxation Room ❑ Occ Sensor- Multi -Level (1) 4 It Fluorescent T8 Energy Saving: 10 Relaxation Room IZI Occ Sensor- Multi -Level (1) 4 ft Fluorescent T8 Energy Saving: 6 Therapy 1 m Occ Sensor - Multi -Level (1) 4 It Fluorescent T8 Energy Saving: 6 Therapy 2 Occ Sensor- Multi -Level (1) 4 ft Fluorescent T8 Energy Saving., 2 FoyerlReception m Dimming w/Occ Sensor 3-60w Incandescent 2 FoyerlReception ❑ Dimming w/Occ Sensor 18-60w Recessed Incandescent 1 FoyerlReception Occ Sensor - Mufti -Level 50w Low Voltage Halogen 10 Foyer/Reception Occ Sensor- Multi -Level (1) 4 ft Fluorescent T8 Energy Saving: 1 Foyer/Reception m EnemvPro 5.1 by EnemySoh User Number: 6712 Run Code: 2010-12-16709:50:29 ID: Pae 17 of 89 n LJ • • CERTIFICATE OF COMPLIANCE Part 3 of .3 LTG -1 C Project Name Date Fitness Building -Tradition Club Assoc. 12/16/2010 CONDITIONED AND UNCONDITIONED SPACE LIGHTING MUST NOT BE COMBINED FOR COMPLIANCE Indoor Lighting Power for Conditioned S aces Indoor Lighting Power for Unconditioned Spaces Watts Watts Installed Lighting 9,840 Installed Lighting 104 from Conditioned LTG -1 C, Page 2 from Unconditioned LTG -1 C, Page 2 Lighting Control Credit - 1662 Lighting Control Credit _ 21 Conditioned Spaces from LTG -2C Unconditioned Spaces from LTG -2C Adjusted Installed - 8178 Adjusted Installed = 83 Lighting Power Lighting Power Complies if Installed:5 Allowed Complies if Installed 5 Allowed Allowed Lighting Power Allowed Lighting Power Conditioned Spaces from LTG -3C or PERF -1 8'178 Unconditioned Spaces from LTG -3C)158 Required Acceptance Tests Designer: This form is to be used by the designer and attached to the plans. Listed below is the acceptance test for the Lighting system, LTG -2A. The designer is required to check the acceptance tests and list all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for Code Compliance. If all the lighting system or control of a certain type requires a test, list the different lighting and the number of systems. The NA7 Section in the Appendix of the Nonresidential Reference Appendices Manual describes the test. Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work appropriately. Forms can be grouped by type of Luminalre controlled. Enforcement Agency: Systems Acceptance. Before Occupancy Permit is granted for a newly constructed building or space or when ever new lighting system with controls is installed in the building or space shall be certified as meeting the Acceptance Requirements. The LTG -2A form is not considered a complete form and is not to be accepted by the enforcement agency unless the boxes are checked and/or filled and signed. In addition, a Certificate of Acceptance forms shall be submitted to the enforcement agency that certifies plans, specifications, installation certificates, and operating and maintenance information meet the requirements of §10-103(b) of Title 24 Part 6. The field inspector must receive the properly filled out and signed forms before the building can receive final occupancy. A copy of the LTG -2A for each different lighting luminaire control(s) must be provided to the owner of the building for their records. Controls for Credits LTG -2A Controls and Sensors and Automatic Number of Daylighting Luminaire Controls Equipment Re uirin Testing Descriptio controls Location Acceptance Occ Sensor- Multi -Level (1) 4 ft Fluorescent T8 Energy Saving: 201 Men's Locker Room Occ Sensor - Multi -Level (1) 26w Compact Fluorescent Triple 4 13 Men's Locker Room Occ Sensor - Multi -Level (1) 13w Compact Fluorescent Triple 4 2 Men's Locker Room Occ Sensor - Multi -Level (1) 4 ft Fluorescent T8 Energy Saving: 1 Women's Locker Room Occ Sensor - Multi -Level (1) 4 It Fluorescent T8 Energy Saving: 11 Women's Locker Room Occ Sensor- Multi -Level (1) 13w Compact Fluorescent Triple 4 2 Women's Locker Room ❑ Occ Sensor - Multi -Level (1) 26w Compact Fluorescent Triple 4 11 Women's Locker Room ❑ Occ Sensor- Multi -Level (1) 4 ft Fluorescent T8 Energy Saving: 1 Mech Room El Occ Sensor- Multi -Level (1) 4 It Fluorescent T8 Energy Saving: 3 Mech Room m 13 11 EnemyPro 5.1 by EnemySoh User Number: 6712 Run Code: 2010-12-16709:50:29 ID: Pae 18 of 89 0 • • CERTIFICATE OF COMPLIANCE and (Part 1 of 4) MECH-1 C FIELD INSPECTION ENERGY CHECKLIST Project Name Fitness Building -Tradition Club Assoc. Date 12/16/2010 Project Address 78505 Old Ave 52 La Quinta Climate Zone 15 Total Cond. Floor Area 5,096 Addition Floor Area n/a GENERAL INFORMATION Building Type: ® Nonresidential ❑ High -Rise Residential ❑ Hotel/Motel Guest Room ❑ Schools (Public School) ❑ Relocatable Public School Bldg. m Conditioned Spaces ❑ Unconditioned Spaces affidavit Phase of Construction: ® New Construction ❑ Addition ❑ Alteration Approach of Compliance: ❑ Component ❑ Overall Envelope TDV ❑ Unconditioned (file affidavit) Energy Front Orientation: N, E, S, W or in Degrees: 160 deg HVAC SYSTEM DETAILS FIELD INSPECTION ENERGY CHECKLIST E ui ment2 Inspection Criteria Meets Criteria or Requirements Pass Fail — Describe Reason Item or System Tags AC -1 RTU -1 HP -1 DHWHeater, 13 13i.e. Equipment T e3: Gas Fired DHW Boiler ❑ ❑ Number of Systems 1 ❑ ❑ Max Allowed Heating Capacity' 125,000 Btu/hr ❑ ❑ Minimum Heating Efficiency' 96% ❑ ❑ Max Allowed Cooling Capacity' n/a ❑ ❑ Cooling Efficiency' n/a ❑ ❑ Duct Location/ R -Value n/a ❑ ❑ When duct testing is required, submit MECH-4A & MECH-4-HERS n/a ❑ ❑ Economizer n/a ❑ ❑ Thermostat n/a ❑ ❑ Fan Control n/a ❑ ❑ E ui ment2 Inspection Criteria FIELD INSPECTION ENERGY CHECKLIST Pass Fail — Describe Reason Item or System Tags i.e. AC -1, RTU -1, HP -1 HP 1 ❑ ❑ Equipment T e3: Packaged DX ❑ ❑ Number of Systems 1 ❑ ❑ Max Allowed Heating Capacity' 47,000 Btu/hr ❑ ❑ Minimum Heating Efficiency' 9.20 HSPF ❑ ❑ Max Allowed Cooling Capacity' 4 8, 000 Btu/hr ❑ ❑ Cooling Efficiency' 15.0 SEER / 12.5 EER ❑ ❑ Duct Location/ R -Value R-4.2 ❑ ❑ When duct testing is required, submit MECH-4A & MECH-4-HERS Yes ❑ ❑ Economizer No Economizer ❑ ❑ Thermostat Setback Required ❑ ❑ Fan Control Constant Volume ❑ ❑ 1. If the Actual installed equipment performance efficiency and capacity is less than the Proposed (from the energy compliance submittal or from the building plans) the responsible party shall resubmit energy compliance to include the new changes. 2. For additional detailed discrepancy use Page 2 of the Inspection Checklist Form. Compliance fails if a Fail box is checked. 3. Indicate Equipment Type: Gas (Pkg or, Split), VAV, HP (Pkg or split), Hydronic, PTAC, or other. EnergyPro 5.1 by EnergySoft User Number: 6712 Run Code: 2010-12-16709:50:29 ID: Pae 19 of 89 0 • • CERTIFICATE OF COMPLIANCE and (Part 1 of 4) MECH-1 C FIELD INSPECTION ENERGY CHECKLIST Project Name Fitness Building -Tradition Club Assoc. Date 12/16/2010 Project Address 78505 Old Ave 52 La Quinta Climate Zone 15 Total Cond. Floor Area 5,096 Addition Floor Area n/a GENERAL INFORMATION Building Type: ® Nonresidential ❑ High -Rise Residential ❑ Hotel/Motel Guest Room ❑ Schools (Public School) ❑ Relocatable Public School Bldg. m Conditioned Spaces ❑ Unconditioned Spaces affidavit Phase of Construction: ® New Construction ❑ Addition ❑ Alteration Approach of Compliance: ❑ Component ❑ Overall Envelope TDV ❑ Unconditioned (file affidavit) Energy Front Orientation: N, E, S, W or in Degrees: I 160 deg HVAC SYSTEM DETAILS FIELD INSPECTION ENERGY CHECKLIST E ui menu Inspection Criteria Meets Criteria or Requirements Pass Fall — Describe Reason Item or System Tags AC -1, RTU -1 HP -1 HP 2 & 3 ❑ [3 E ui ment T e3: Equipment Packaged DX ❑ ❑ Number of Systems 2 ❑ ❑ Max Allowed Heating Capacity' 53,000 Btu/hr ❑ ❑ Minimum Heating Efficiency' 9.00 HSPF ❑ ❑ Max Allowed Cooling Capacity' 55,500 Btu/hr ❑ ❑ Cooling Efficiency' 14.5 SEER / 12.0 EER ❑ ❑ Duct Location/ R -Value R-4.2 ❑ ❑ When duct testing is required, submit MECH-4A & MECH-4-HERS Yes ❑ ❑ Economizer No Economizer ❑ ❑ Thermostat Setback Required ❑ ❑ Fan Control Constant Volume ❑ ❑ E ui ment2 Inspection Criteria FIELD INSPECTION ENERGY CHECKLIST Pass Fail — Describe Reason Item or System Tags i.e. AC -1, RTU -1, HP -1 HP ❑ ❑ Equipment T e3: Packaged DX ❑ ❑ Number of Systems 1 ❑ ❑ Max Allowed Heating Capacity' 53,000 Btu/hr ❑ ❑ Minimum Heating Efficiency' 9.00 HSPF ❑ ❑ Max Allowed Cooling Capacity' 55,500 Btu/hr ❑ ❑ Cooling Efficiency' 14.5 SEER / 12.0 EER ❑ ❑ Duct Location/ R -Value R-4.2 ❑ ❑ When duct testing is required, submit MECH-4A & MECH-4-HERS Yes ❑ ❑ Economizer No Economizer ❑ ❑ Thermostat Setback Required ❑ ❑ Fan Control Constant Volume ❑ ❑ 1. If the Actual installed equipment performance efficiency and capacity is less than the Proposed (from the energy compliance submittal or from the building plans) the responsible party shall resubmit energy compliance to include the new changes. 2. For additional detailed discrepancy use Page 2 of the Inspection Checklist Form. Compliance fails if a Fail box is checked. 3. Indicate Equipment Type: Gas (Pkg or, Split), VAV, HP (Pkg or split), Hydronic, PTAC, or other. JEnergyPro5.1byEnergySoft User Number.- 6712 RunCode: 2010-12-16T09:50:29 ID: Pa a 20of 69 C • CERTIFICATE OF COMPLIANCE and (Part 1 of 4) MECH-1 C FIELD INSPECTION ENERGY CHECKLIST Project Name Fitness Building -Tradition Club Assoc. Date 12/16/2010 Project Address 78505 Old Ave 52 La Quinta Climate Zone 15 Total Cond. Floor Area 5,096 Addition Floor Area n/a GENERAL INFORMATION Building Type: ® Nonresidential ❑ High -Rise Residential ❑ Hotel/Motel Guest Room ❑ Schools (Public School) ❑ Relocatable Public School Bldg. m Conditioned Spaces ❑ Unconditioned Spaces affidavit Phase of Construction: ® New Construction ❑ Addition ❑ Alteration Approach of Compliance: ❑ Component ❑ Overall Envelope TDV ❑ Unconditioned (file affidavit) Energy Front Orientation: N, E, S, W or in Degrees: I 160 deg HVAC SYSTEM DETAILS FIELD INSPECTION ENERGY CHECKLIST E ui ment2 Inspection Criteria Meets Criteria or Requirements Pass Fail — Describe Reason Item or System Tags AC -1, RTU -1, HP -1 HP 5 13 13i.e. Equipment T e3: Packaged DX ❑ ❑ Number of Systems 1 ❑ ❑ Max Allowed Heating Capacity' 4 7, 000 Btu/hr ❑ ❑ Minimum Heatinq Efficiency' 9.20 HSPF ❑ ❑ Max Allowed Cooling Capacity' 4 8, 000 Btu/hr ❑ ❑ Cooling Efficiency' 15.0 SEER / 12.5 EER ❑ ❑ Duct Location/ R -Value R-4.2 ❑ ❑ When duct testing is required, submit MECH-4A & MECH-4-HERS Yes ❑ ❑ Economizer No Economizer ❑ ❑ Thermostat Setback Required ❑ ❑ Fan Control Constant Volume ❑ ❑ E ui ment2 Inspection Criteria FIELD INSPECTION ENERGY CHECKLIST Pass Fail — Describe Reason Item or System Tags i.e. AC -1, RTU -1, HP -1 HP 6 ❑ ❑ Equipment T e3: Packaged DX ❑ ❑ Number of Systems 1 ❑ ❑ Max Allowed Heating Capacity' 4 7, 000 Btu/hr ❑ ❑ Minimum Heating Efficiency' 9.20 HSPF ❑ ❑ Max Allowed Cooling Capacity' 4 8, 000 Btu/hr ❑ ❑ Cooling Efficiency' 15.0 SEER / 12.5 EER ❑ ❑ Duct Location/ R -Value R-4.2 ❑ ❑ When duct testing is required, submit MECH-4A & MECH-4-HERS Yes ❑ ❑ Economizer No Economizer ❑ ❑ Thermostat Setback Required ❑ ❑ Fan Control Constant Volume ❑ ❑ 1. If the Actual installed equipment performance efficiency and capacity is less than the Proposed (from the energy compliance submittal or from the building plans) the responsible party shall resubmit energy compliance to include the new changes. 2. For additional detailed discrepancy use Page 2 of the Inspection Checklist Form. Compliance fails if a Fail box is checked. 3. Indicate Equipment Type: Gas (Pkg or, Split), VAV, HP (Pkg or split), Hydronic, PTAC, or other. EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2010-12-16709:50:29 /D: Page 21 of 89 CERTIFICATE OF COMPLIANCE and (Part 2 of 4) MECH-1 C FIELD INSPECTION ENERGY CHECKLIST • Project Name Fitness Building -Tradition Club Assoc. Date 12/16/2010 Discrepancies: • • EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2010-12-16709:50:29 ID: Page 22 of 89 • • • CERTIFICATE OF COMPLIANCE and FIELD INSPECTION ENERGY CHECKLIST (Part 3 of 4) MECH-1 C Project Name Date Fitness Building -Tradition Club Assoc. 12/16/2010 Required Acceptance Tests Designer: This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for mechanical systems. The designer is required to check the applicable boxes by all acceptance tests that apply and listed all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the equipment description and the number of systems. The NA number designates the Section in the Appendix of the Nonresidential Reference Appendices Manual that describes the test. Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work appropriately. Building Departments: Systems Acceptance: Before occupancy permit is granted for a newly constructed building or space, or a new space -conditioning system serving a building or space is operated for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for Code Compliance. Systems Acceptance: Before occupancy permit is granted. All newly installed HVAC equipment must be tested using the Acceptance Requirements. The MECH-1 C form is not considered a completed form and is not to be accepted by the building department unless the correct boxes are checked. The equipment requiring testing, person performing the test (Example: HVAC installer, TAB contractor, controls contractor, PE in charge of project) and what Acceptance test must be conducted. The following checked -off forms are required for ALL newly installed equipment. in addition a Certificate of Acceptance forms shall be submitted to the building department that certifies plans, specifications, installation, certificates, and operating and maintenance information meet the requirements of §10-103(b) and Title -24 Part 6. The building inspector must receive the properly filled out and signed forms before the building can receive final occupancy. TEST DESCRIPTION MECH-2A MECH-3A MECH-4A MECH-5A MECH-6A MECH-7A MECH-8A MECH-9A MECH-10A MECH-11A Hydronic Outdoor Constant Demand Supply System Automatic Ventilation Volume & Air Control Supply Valve Water Variable Demand For Single -Zone Distribution Economizer Ventilation Fan Leakage Temp. Flow Shed Equipment Re uirin Testing or Verification Qty. VAV & CAV Unitary Ducts Controls DCV VAV Test Reset Control Control Lennox XP17-048-230' 3 ❑ El m ❑ ❑ ❑ ❑ ❑ ❑ m Lennox XP17-060-230' 3 ❑ ® m ❑ ❑ ❑ ❑ ❑ ❑ m ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ EnergyPro 5.1 by EnemySoft User Number: 6712 Runcode: 2010-12-16709:50:29 ID: Page 23 of 89 • CERTIFICATE OF COMPLIANCE and FIELD INSPECTION ENERGY CHECKLIST (Part 4 of 4) MECH-1C Project Name Fitness Building -Tradition Club Assoc. Date 12/16/2010 TEST DESCRIPTION MECH-12A MECH-13A MECH-14A MECH-15A Fault Detection & Diagnostics Equipment Re uirin Testing Qty. for DX Units Automatic Fault Detection & Diagnostics for Air & Zone Distributed Energy Storage DX AC Systems Thermal Energy Storage (TES) Systems' Test Performed By: LennoxXP17-048-230* 3 ❑ ❑ ❑ ❑ Lennox XP17-060-230* 3 ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ - ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑. ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ EnergyPro 5. 1 by EnergySoft User Number. 6712 RunCode: 2010-12-16T09:50:29 ID: Page 24 of 89 • LIGHTING CONTROLS CREDIT WORKSHEET (Part 1 of 2) LTG -2C Project Name Fitness Building -Tradition Club Assoc. Date 1 12/16/2010 POWER ADJUSTMENT FACTORS PAF FOR NON -DAYLIGHT CONTROLS A Separate PAF Worksheet Must Be Filled Out for Conditioned and Unconditioned Spaces. Control Credits listed on this schedule are only for: m CONDITIONED SPACES ❑ UNCONDITIONED SPACES A B C D E F G Room # Zone ID Areas Lighting Control Description' Plan Room Area Reference(ft) Watts of Control Lighting Power Adjustments Factor' Control Credit Watts E x F Yoga Occ Sensor- Mufti -Level B1 673 624 0.20 125 Yoga Occ Sensor- Multi -Level B1 673 52 0.20 10 Cardio/Circuit Occ Sensor- Multi -Level R 1,740 800 0.20 160 Cardio/Circuit Dimming - Manual IDW4 1,740 720 0.10 72 Cardio/Circuit Dimming - Manual IDC5 1,740 720 0.10 72 Free Weights Occ Sensor- Multi -Level R 281 700 0.20 140 Relaxation Room Dimming w/Occ Sensor IDC3 300 720 0.25 180 Relaxation Room Occ Sensor - Multi -Level B2 300 260 0.20 52 Therapy 1 Occ Sensor - Multi -Level B2 124 156 0.20 31 Therapy 2 Occ Sensor- Multi -Level B2 112 156 0.20 31 Foyer/Reception Occ Sensor- Multi -Level A2 643 52 0.20 10 Foyer/Reception Dimming w/Occ Sensor IDC2 643 360 0.25 90 FoyeNReception Dimming w/Occ Sensor IDC1 643 1,080 0.25 270 FoyeNReception Occ Sensor- Multi -Level R2 643 500 0.20 100 FoyeNReception Occ Sensor- Multi -Level B1 643 26 0.20 5 Men's Locker Roory Occ Sensor - Multi -Level B2 563 520 0.20 104 Men's Locker Roory Occ Sensor- Multi -Level RF 563 364 0.20 73 Men's Locker Roory Occ Sensor- Multi -Level WP1F 563 30 0.20 6 Women's Locker R Occ Sensor- Multi -Level A2 660 26 0.20 5 Women's Locker R Occ Sensor- Multi -Level B2 660 286 0.20 57 Women's Locker R Occ Sensor- Multi -Level WP1F 660 30 0.20 6 Women's Locker Ri Occ Sensor- Multi -Level RF 660 308 0.20 62 PAGE TOTAL 1,662 Note: Conditioned and Unconditioned Building total of non -daylight control credit watts for all pages of LTG -2C Pae 1 of 2 Enter building total of all daylight controls credit watts from LTG -2C Page 2 of 2 0 Space shall be separately totaled BUILDING TOTAL OF ALL CONTROL CREDIT WATTS (FOR BOTH NON -DAYLIGHT AND DAYLIGHT CONTROL CREDITS) Enter in LTG -1 C; Page 4: Lighting Control Credit as appropriate for CONDITIONED or UNCONDITIONED Spaces 1,662 1. Description shall be consistent with Type of Control defined in Table 146-C 2. Power Adjustment Factor taken from Table 146-C EnergyPro5.1byEnergySoft User Number: 6712 RunCode: 2010.12-16T09:50:29 ID: Page 25 of 89 1-7, 0 LIGHTING CONTROLS CREDIT NORKSHEET Part 1 of 2 LTG -2C Project Name Fitness Building -Tradition Club Assoc. Date 12/16/2010 POWER ADJUSTMENT FACTORS PAF FOR NON -DAYLIGHT CONTROLS A Separate PAF Worksheet Must Be Filled Out for Conditioned and Unconditioned Spaces. Control Credits listed on this schedule are only for: ❑ CONDITIONED SPACES m UNCONDITIONED SPACES A B C D E F G Watts of Power Room # Zone ID Plan Room Area Control Adjustments Areas Lighting Control Description' Reference (ft) Lighting Factor' Control Credit Watts E x F Mech Room Occ Sensor- Multi -Level A4 78 26 0.20 5 Mech Room Occ Sensor- Multi -Level A4 147 78 0.20 16 PAGE TOTAL 21 Note: Conditioned and Building total of non -daylight control credit watts for all pages of LTG -2C Page 1 of 2 Enter building total of all daylight controls credit watts from LTG -2C Page 2 of 2 0 Unconditioned Space shall be separately totaled � BUILDING TOTAL OF ALL CONTROL CREDIT WATTS (FOR BOTH NON -DAYLIGHT AND DAYLIGHT CONTROL CREDITS) Enter in LTG -1 C; Page 4: Lighting Control Credit as appropriate for CONDITIONED or UNCONDITIONED Spaces 21 1. Description shall be consistent with Type of Control defined in Table 146-C 2. Power Adjustment Factor taken from Table 146-C EnergyPro5.1byEnergySoft User Number. 6712 RunCode: 2010-12-16T09:50:29 ID: Page 26 of 89 INDOOR LIGHTING -POWER ALLOWANCE LTG -3C INDOOR Projept Name ifness Building -Tradition Club Assoc. - 7 Date 12/16/2010 ALLOWED LIGHTING POWER Chose One Method A Separate LTG -3C must be filled out for Conditioned and Unconditioned Spaces. Indoor Lighting Power Allowances listed on this page are only for: ❑ CONDITIONED SPACES m UNCONDITIONED SPACES COMPLETE BUILDING METHOD WATTS BUILDING CATEGORY From §146 Table 146-E PER(ft') X COMPLETE BLDG. AREA = ALLOWED WATTS Comp Bldg Office 0.85 225 191 TOTALS AREA WATTS AREA CATEGORY METHOD WATTS BUILDING CATEGORY From §146 Table 146-F PER(ft) X Area ft2 = ALLOWED WATTS TOTALS AREA WATTS TAILORED METHOD Total Allowed Watts using the Tailored Method taken from LTG -4C Pae 1 of 4 Row 3 The indoor lighting power allowance using the Tailored Method of compliance shall be determined using the LTG -4C set of forms. A separate set of LTG - 4C forms shall be filled out for CONDITIONED and UNCONDITIONED spaces EnemyPro 5.1 by EnemySoft User Number: 6712 RunCode: 2010-12-16T09:50:29 ID: Page 27 of 89 AIR SYSTEM REQUIREMENTS (Part 1 of 2 Project Name =itness Building -Tradition Club Assoc. Indicate Air Systems Type Central, Single Zone, Package Item or System Tags i.e. AC -1, RTU -1, HP -1 ., _,, HP 1 HP 2 & 3 Number of Svstems ;? 1 2 MANDATORY MEASURES Heating Equipment Efficiency Cooling Equipment Efficiency HVAC Heat Pump Thermostat Furnace Controls/Thermostat Natural Ventilation Mechanical Ventilation VAV Minimum Position Control Demand Control Ventilation Time Control Setback and Setup Control Outdoor Damper Control Isolation Zones Pipe Insulation Duct Insulation PRESCRIPTIVE MEASURES Calculated Design Heating Load Proposed Heating Capacity Calculated Design Cooling Load Proposed Cooling Capacity Fan Control DP Sensor Location Supply Pressure Reset (DDC only) Simultaneous Heat/Cool Economizer Heat Air Supply Reset Cool Air Supply Reset Electric Resistance Heating' Air Cooled Chiller Limitation Duct Leakage Sealing. If Yes, a MECH-4-A must be submitted Indicate Pal T-24 Sections 112(a) 112(a) 112(b), 112(c) 112(c), 115(a) 121(b) 121(b) 121 122' 122' 122' 1222 12,: 144 144 144 144 144 144 Reference on Plans or Schedule and indicate the 9.20 HSPF 15.0 SEER/ 12.5 EER Yes n/a Yes 481 cfm No No Programmable Switch Setback Required Auto n/a Yes No No Economizer Constant Temp Constant Temp Yes 9.00 HSPF 14.5 SEER/ 12.0 'EER Yes n/a Yes 1,071 cfm No No Programmable Switch Setback Required Auto n/a R-4.2 n/a 62, 613 Btu/hr n/a 83,008 Btu/hr Constant Volume Yes No No Economizer Constant Temp Constant Temp Yes MECH-2C Date 12116/2010 VAV, or etc...) HP 4 1 icable 9.00 HSPF 14.5 SEER / 12.0 EER Yes n/a Yes 296 cfm No No Programmable Switch Setback Required Auto n/a R-4.2 n/a 31,306 Btu/hr n/a 36,921 Btu/hr Constant Volume Yes No No Economizer Constant Temp Constant Temp Yes 01, Total installed capacity (MBtu/hr) of all electric heat on this project exclusive of electric auxiliary heat for heat pumps. if electric heat is used explain which exception(s) to §144(g) apply. EnemvPro 5.1 by EnemySoR User Number: 6712 Run Code: 2010-12-16709:50:29 ID: Page 28 of 89 R-4.2 & b n/a & b 27,762 Btu/hr & b n/a & b 38,682 Btu/hr Constant Volume Yes No No Economizer Constant Temp Constant Temp Yes 9.00 HSPF 14.5 SEER/ 12.0 'EER Yes n/a Yes 1,071 cfm No No Programmable Switch Setback Required Auto n/a R-4.2 n/a 62, 613 Btu/hr n/a 83,008 Btu/hr Constant Volume Yes No No Economizer Constant Temp Constant Temp Yes MECH-2C Date 12116/2010 VAV, or etc...) HP 4 1 icable 9.00 HSPF 14.5 SEER / 12.0 EER Yes n/a Yes 296 cfm No No Programmable Switch Setback Required Auto n/a R-4.2 n/a 31,306 Btu/hr n/a 36,921 Btu/hr Constant Volume Yes No No Economizer Constant Temp Constant Temp Yes 01, Total installed capacity (MBtu/hr) of all electric heat on this project exclusive of electric auxiliary heat for heat pumps. if electric heat is used explain which exception(s) to §144(g) apply. EnemvPro 5.1 by EnemySoR User Number: 6712 Run Code: 2010-12-16709:50:29 ID: Page 28 of 89 C • AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2C Project Name Date Fitness Building -Tradition Club Assoc. .: i - � = ::._ 4.:- 12/16/2010 Indicate Air Systems Type Central, Single Zone, Package, VAV, or etc... Item or System Tags � ,;, i.e. AC -1, RTU -1, HP -1 HP 5 HP 6 Number of Systems Indicate Page Reference on Plans or Schedule and Indicate the applicable exception(s) MANDATORY MEASURES T-24 Sections Heating Equipment Efficiency 112(a) 9.20 HSPF 9.20 HSPF Cooling Equipment Efficiency 112(a) 15.0 SEER/ 12.5 EER 15.0 SEER/ 12.5 EER HVAC Heat Pump Thermostat 112(b), 112(c) Yes Yes Furnace Controlslfhermostat 112(c), 115(a) n/a n/a Natural Ventilation 121 b Yes Yes Mechanical Ventilation 121 b 402 cim 471 cim VAV Minimum Position Control 121 c No No Demand Control Ventilation 121 c No No Time Control 122(e) Programmable Switch . Programmable Switch Setback and Setup Control 122(e) Setback Required Setback Required Outdoor Damper Control 122(f) Auto Auto Isolation Zones 122 n/a n/a Pipe Insulation 123 Duct Insulation 124 R-4.2 R-4.2 PRESCRIPTIVE MEASURES Calculated Design Heating Load 144(a & b n/a n/a Proposed Heating Capacity 144(a & b 27,762 Btu/hr 27,762 Btu/hr Calculated Design Cooling Load 144(a & b n/a n/a Proposed Cooling Capacity 144(a & b 37,687 Btulhr 38,547 Btulhr Fan Control 144(c) Constant Volume Constant Volume DP Sensor Location 144(c) Supply Pressure Reset (DDC only) 144(c) Yes Yes Simultaneous Heat/Cool 144(d) No No Economizer 144(e) No Economizer No Economizer Heat Air Supply Reset 144(f) Constant Temp Constant Temp Cool Air Supply Reset 144(f) Constant Temp Constant Temp Electric Resistance Heating' 144 - Air Cooled Chiller Limitation 144(i) Duct Leakage Sealing. If Yes, a Yes Yes MECH-4-A must be submitted 144(k) 1. Total installed capacity (MBtu/hr) of all electric heat on this project exclusive of electric auxiliary heat for heat pumps. If electric heat is used explain which exception(s) to §144(g) apply. EnergyPro 5.1 by EnergySoR User Number: 6712 Run Code: 2010-12-16709:50:29 ID: Page 29 of 89 C, • WATER SIDE SYSTEM REQUIREMENTS Part 2 of 2 MECH-2C Project Name Date Fitness Building -Tradition Club Assoc. 1 12/16/2010 WATER' SIDE SYSTEMS: Chillers, Towers, Boilers, H dronic Loops Item or System Tags (i.e. AC -1, RTU -1, HP -1)'. Number of Systems Indicate Page Reference on Plans or Specification 2 MANDATORY MEASURES T-24 Sections Equipment Efficiency 112(a) Pipe Insulation 123 PRESCRIPTIVE MEASURES Cooling Tower Fan Controls 144(a & b Cooling Tower Flow Controls 144(h) Variable Flow System Design 144(h) Chiller and Boiler Isolation 144 CHW and HHW Reset Controls 144 WLHP Isolation Valves 144 VSD on CHW, CW & WLHP Pumps>5HP 144 DP Sensor Location 144 1. The proposed equipment need to match the building plans schedule or specifications. If a requirement is not applicable, put "N/A" in the column next to applicable section. 2. For each chiller, cooling tower, boiler, and hydronic loop (or groups of similar equipment) fill in the reference to sheet number and/or specification section and paragraph number where the required features are documented. If a requirement is not applicable, put "N/A" in the column next to applicable section. Service Hot Water, Pool Heating Item or System Tags DHWHeater (i.e. WH -1, WHP, DHW, etc...)' Number of Systems 1 Indicate Page Reference on Plans or Schedule MANDATORY MEASURES T-24 Sections SERVICE HOT WATER Certified Water Heater 111, 113(a) rd -White Corp. EF -60T-125 Water Heater Efficiency 113(b) 96 Service Water Heating Installation 113(c) Controls Req. Pipe Insulation 123 n/a POOL AND SPA Pool and Spa Efficiency and Control 114(a) Me Pool and Spa Installation 114(b) n/a Pool Heater — No Pilot Light 115(c) n/a Spa Heater — No Pilot Light 1 115 d n/a Pipe Insulation 1 123 Required 1. The Proposed equipment needs to match the building plans schedule or specifications. If a requirement is not applicable, put "N/A" in the column next to applicable section. 2. For each water heater, pool heater and domestic water loop (or groups of similar equipment) fill in the reference to sheet number and/or specification section and paragraph number where the required features are documented. If a requirement is not applicable, put "N/A" in the column. EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2010-12-16T09:50:29 ID: Page 30 of 89 0 MECHANICAL VENTILATION AND REHEAT MECH-3C Project Name Fitness Building -Tradition Club Assoc. Date 12/16/2010 MECHANICAL VENTILATION 121 b 2 REHEAT LIMITATION (§144-(d)) AREA BASIS OCCUPANCY BASIS - VAV MINIMUM A B C D E F G H I J K L M N Zone/System Condition Area (ft2) CFM per ftz Min CFM By Area B X C Number Of People CFM per Person Min CFM by Occupant E X F REQ'D V.A. Max of D or G Design Ventilation Air CFM 50% of Design Zone Supply I CFM B X 0.4 CFM / ftz Max. of Columns H, J, K, 300 CFM Design Minimum Air Setpoint Transfer 1 Air Yoga 673 0.15 101 101 481 HP 1 Total 101 481 Cardio/Circuit 1,740 0.15 261 261 870 Free Weights 281 0.15 42 42 201 HP 2 & 3 Total 303 1,071 Relaxation Room 300 0.15 45 45 129 :Therapy 1 124 0.15 19 19 37 Therapy 2 112 0.15 17 17 34 FoyeNReception 643 0.15 96 96 96 HP 4 Total 177 296 Men's Locker Room 563 0.15 84 84 402 HP 5 Total 84 402 Women' Locker Room 660 0.15 99 99 471 HP 6 Total 99 471 Totals Column I Total Design Ventilation Air C Minimum ventilation rate per Section 121, Table 121-A. E Based on fixed seat or the greater of the expected number of occupants and 50% of the CBC occupant load foregress purposes fors aces without fixed setting. H Required Ventilation Air REQ'D V.A. is the larger of the ventilation rates calculated on an AREA BASIS or OCCUPANCY BASIS Column D or G). I Must be greater than orequal to H, or use Transfer Air column N to make up the difference. J Design fan supply CFM Fan CFM x 50%; or the design zone outdoor airflow rate per 121. K Condition area(ft) x 0.4 CFM / ft2; or L Maximum of Columns H, J, K, or 300 CFM M This must be less than orequal to Column L and greater than orequal to the sum of Columns H plus N. N Transfer Air must be provided where the Required Ventilation Air (Column H) is greater than the Design Minimum Air (Column M). Where required, transfer air must be greater than or equal to the difference between the Required Ventilation Air Column H and the Design Minimum Air Column M), Column H minus M. _EergyPro 5.1 by EnergySoft User Number: 6712 Run Code: 2010-12-16709:50:29 ID: Page 31 of 89 • • • MECHANICAL EQUIPMENT DETAILS Part 1 of 2 MECH-5C Project Name Fitness Building -Tradition Club Assoc. Date 12/16/2010 , CHILLER AND TOWER SUMMARY PUMPS Equipment Name Type Ot . Efficiency Premium Tons Oty. GPM BHP Eff. Motor Pump Control DHW / BOILER SUMMARY System Name Type Distribution Ot . Vol. Energy Factor Rated Input (Gals). or RE Standby Loss Tank Ext. or Pilot R -Value Status Bradford -White Corp. EF -60T-1251 Large Gas All Pipes Ins 1 125,000 60 0.96 0.00% 0.0 New MULTI -FAMILY CENTRAL WATER HEATING DETAILS Hot Water Pump Hot Water Piping Length ft Control Ot . HP Type In Plenum Outside Buried I Add M.' Insulation CENTRAL SYSTEM RATINGS HEATING COOLING System Name Type Ot . Output Aux. kW Efficiency Output Eff iciency Status Lennox XP17-048-230' Packaged DX 3 47,000 0.0 9.20 HSPF 48,000 15.0 SEER / 12.5 EER New Lennox XP17-060-230' Packaged DX 3 53,000 0.0 9.00 HSPF 55,500 14.5 SEER/ 12.0 EER New CENTRAL SYSTEM FAN SUMMARY SUPPLY FAN RETURN FAN System Name Fan Type Economizer Type Premium CFM BHP Eff. Motor CFM BHP Premium Eff. Motor Lennox XP17-048-230` Constant Volume No Economizer 1,600 0.50 m none ❑ LennoxXP17-060-230" Constant Volume No Economizer 2,000 0.70 D none ❑ ❑ ❑ ❑ 1 ❑ EnergyPro 5.1 by EnergySoft User Number. 6712 RunCode: 2010-12-16T09:50:29 ID: Page 32 of 89 m � � rn N = y ZCD(m ~n y a, N N w �0 o m koo3 (p m D �gz y d m'a Z °0 9 0Z n C0 3 m x Cl) Cl) y n _a �� r �E m �n vo N 0o H Q Cl)A z m a 4. -C, d y Z cr CD vv V oo= N Premium 000 ❑ Eff. Motor r N A m Z m d � G X_ A.. c n c � a fD � N o D D z oP N r � os O N o T x T C 000 ❑ Premium s Eff. Motor d A O o o 3 n d d W v m x ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ 110 ❑ Premium Nx Eff. Motor p ❑❑❑o❑❑❑❑❑❑❑❑❑❑❑❑❑❑❑❑ Ian N D Cycles 11 11 ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ECM Motor A m m D m i ny N 0 m C O w Premium OO I (COEff. ❑ ❑ ❑ ❑ Motor 0 • 40 • • • M 'ENVELOPE MANDATORY MEASURES: NONRESIDENTIAL ENV -MM Project Name Date Fitness Building -Tradition Club Assoc. 12/16/2010 DESCRIPTION Building Envelope Measures: §118(a): Installed insulating material shall have been certified by the manufacturer to comply with the California Quality Standards for insulating material, Title 20 Chapter 4, Article 3. §118(c): All Insulating Materials shall be installed in compliance with the flame spread rating and smoke density requirements of Sections 2602 and 707 of Title 24, Part 2. §118(f): The opaque portions of framed demising walls in nonresidential buildings shall have insulation with an installed R -value of no less than R-13 between framing members. §117(a): All Exterior Joints and openings in the building that are observable sources of air leakage shall be caulked, gasketed, weatherstripped or otherwise sealed. Manufactured fenestration products and exterior doors shall have air infiltration rates not exceeding 0.3 cfm/ft.2 of §116(a) 1: window area, 0.3 cfm/ft.2 of door area for residential doors, 0.3 cfm/ft.2 of door area for nonresidential single doors . (swingingand sliding), and 1.0 cfm/ft.2 for nonresidential double doors (swinging). §116(a) 2: Fenestration U -factor shall be rated in accordance with NFRC 100, or the applicable default U -factor. §116(a) 3: Fenestration SHGC shall be rated in accordance with NFRC 200, or NFRC 100 for site -built fenestration, or the applicable default SHGC. 16 b Site Constructed Doors, Windows and Skylights shall be caulked between the unit and the building, and shall be §1 O' weatherstripped (except for unframed glass doors and fire doors). EnemvPro 5.1 by EnemySoft User Number. 6712 Run Code: 2010-12-16T09:50:29 ID: Page 34 of 89 • • • TAILORED METHOD WORKSHEET Part 1 of 4 LTG -4-C Project Name Date Fitness Building -Tradition Club Assoc. 12/16/2010 TAILORED METHOD SUMMARY — Separate Tailored Method Worksheets shall be filled out for Conditioned and Unconditioned Spaces: m CONDITIONED SPACES ❑ UNCONDITIONED SPACES 1. Allowed Watts for Illuminance Categories (Building Total from Column G from Tailored General Lighting 6,507 Power Table below) Watts 2. Watts for Display Lighting 01 10 0 1 0 Wall Display from Floor Display Ornamental/Special Very Valuable LTG -4C + From LTG -4C + Effects Display from + Merchandise = Total Watts Pacie 2 of 4 Page 2 of 4 LTG -4C Page 3 of 4 LTG -4C Page 3 of 4 3. Total Allowed Watts (add lines 1 and 2) 6,507 Watts TAILORED ALLOWED GENERAL LIGHTING POWER A B C D E F G RCR from LTG -4C Floor Room Page 4 of Area for Allowed Room Illuminance Cavity � 4' Primary Allowed Watts Number Prima Function Type' Cate o 2 Ratio Y N Function° LPDS E X F Assembly_ Moderately Difficult E 0.00 ❑ ® 673 1.30 875 Assembly_ Simple D 00,000,000.00 m ❑ 1,740 1.40 2,436 Assembly_ Simple D 00,000,000.00 m ❑ 281 1.40 393 Reading Printed Tasks - 8 & 10 Point D 00,000,000.00 m ❑ 300 1.40 420 Assembly_ Simple D 00,000,000.00 ® ❑ 124 1.40 174 Assembly_ Simple D 00,000,000.00 m ❑ 112 1.40 157 Lobby, Main Entry C 00,000,000.00 m ❑ 643 1.10 707 Locker Rooms General C 00,000,000.00 m ❑ 563 1.10 619 Locker Rooms General C 00,000,000.00 m ❑ 660 1.10 726 ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ te Watts PAGE TOTAL 5,096 6,507 BUILDING TOAL 5,096 6,507 1. From Table 146-G, Column 1 2. From Table 146-G, Column 2 or IESNA Handbook 3. If Column D checked 'N' then enter <3.5 in this column 4. Floor area must be for Primary Function type listed in Table 146-G Column 1. Floor area using the Area Category Method shall not be included 5. In accordance with Table 146-1 -EnerqyPro5.1byEnerqySof User Number: 6712 Run Code: 2010.12-16709:50:29 ID: Page 35 of 89 • C • TAILORED METHOD WORKSHEET Part 4 of 4 LTG -4C Proiect Name Fitness Building -Tradition Club Assoc. Date 1 12/16/2010 (0 CONDITIONED SPACES ❑ UNCONDITIONED SPACES ROOM CAVITY RATIO RCR WORKSHEET m RCR<3.5 Is assumed instead of using one of the calculation methods listed below. Note: Table 146-1 provides the lowest lighting ower density values for RCRs which are less than 3.5 RECTANGULAR SPACES A B C D E F Room Task/Activity Room Room Number Description Length L ft Width W ft RCR Room Cavity 5 X H X (L+W) / Height H ft L X W Cardio/Circuit Assembly_ Simple 0.0 0.0 5.5 0,000,000,000,000,000.00 Free Weights Assembly_ Simple 0.0 0.0 5.5 0,000,000,000,000,000.00 Relaxation Room Reading Printed Tasks - 8 & 10 0.0 0.0 5.5 0,000,000,000,000,000.00 Therapy 1 Assembly_ Simple 0.0 0.0 5.5 0,000,000,000,000,000.00 Therapy 2 Assembly_ Simple 0.0 0.0 5.5 0,000,000,000,000,000.00 Foyer/Reception Assembly_ Simple 0.0 0.0 5.5 0,000,000,000,000,000.00 Wen's Locker Room Locker Rooms General 0.0 0.0 5.5 0,000,000,000,000,000.00 omen's Locker Roo Locker Rooms General 0.0 0.0 5.5 0,000,000,000,000,000.00 NON -RECTANGULAR SPACES A B C D E F Room Task/Activity Room Room Number Description Length A(ft) Perimeter P ft Room Cavity RCR Height H ft 2.5 X H X P / A Use calculation from Column F of this RCR Worksheet to enter into Column C of LTG -4C, Page 1 of 4 EnergyPro&l6 Ene Sc User Number: 6712 RunCode: 2010-12-16T09:50:29 ID: Page 36 of 89 • 10 • LIGHTING MANDATORY MEASURES: NONRESIDENTIAL LTG -MM Project Name Date Fitness Building -Tradition Club Assoc. - 12/16/2010 Indoor Lighting Measures: §131(d): Shut-off Controls For every floor, all interior lighting systems shall be equipped with a separate automatic control to shut off the lighting. 1. This automatic control shall meet the requirements of Section 119 and may be an occupancy sensor, automatic time switch, or other device capable of automatically shutting off the lighting. 2 Override for Building Lighting Shut-off: The automatic building shut-off system is provided with a manual, accessible override switch in sight of the lights. The area of override is not to exceed 5,000 square feet. 19 h §1 ()' Automatic Control Devices Certified: All automatic control devices specified are certified, all alternate equipment shall be certified and installed as directed by the manufacturer. §111: Fluorescent Ballast and Luminaires Certified: All fluorescent fixtures specified for the project are certified and listed in the Directory. All installed fixtures shall be certified. §131(a): Individual Room/Area Controls: Each room and area in this building is equipped with a separate switch or occupancy sensor device for each area with floor -to -ceiling walls. Uniform Reduction for Individual Rooms: All rooms and areas greater than 100 square feet and more than 0.8 watts §131(b): per square foot of lighting load shall be controlled with bi-level switching for uniform reduction of lighting within the room. Daylight Area Control: All rooms with windows and skylights that are greater than 250 square feet and that allow for §131(c): the effective use of daylight in the area shall have 50% of the lamps in each daylit area controlled by a separate switch; or the effective use of daylight cannot be accomplished because the windows are continuously shaded by a building on the adjacent lot. Diagram of shading during different times of the year is included on plans. §131(c): Display Lighting. Display lighting shall be separately switched on circuits that are 20 amps or less.6. Outdoor Lighting Measures: §130(c)1: Mandatory lighting power determination for medium base sockets without permanently installed ballasts §132(a): All permanently installed luminaires with lamps rated over 100 Watts either have a lamp efficacy of at least 60 lumens per Watt or are controlled by a motion sensor. §132(b): All Luminaires with lamps rated greater than 175 Watts in hardscape area, including parking lots, building entrances, canopies, and all outdoor sales areas meet the Cutoff Requirements. §132(c)1: All permanently installed outdoor lighting meets the control requirements listed. §132(c): Building facades, parking lots, garages, canopies, and outdoor sales areas meet the Multi -Level Lighting Requirements listed. EnergyPro 5.1 by EnergySoft User Number: 6712 Run Code: 2010-12-16T09:50:29 ID: Page 37 of 89 • C� J • CERTIFICATE OF COMPLIANCE Part 1 of 4 OLTG-1 C Project Name Date Fitness Building -Tradition Club Assoc. " J -Y= ' - 12/16/2010 Project Address Total Illuminated Area 78505 Old Ave 52 La Quinta, Ca 92253 1,584 GENERAL INFORMATION Phase of Construction: m New Construction ❑ Addition ❑ Alteration Documentation Author's Declaration Statement I certify that this Certificate of Compliance documentation is accurate and complete. Signatur Name Tim Scott p� Company Date Scoff Design and Title 24, Inc, 1211612010 Address CEA # 77-085 Michigan Drive CEPE # N eD _ 3 City/State/Zip Phone Palm Desert, Ca 92211 (760) 200-4780 Principal Lighting Designer's Declaration Statement • 1 am eligible under Division 3 of the California Business and Professional Code to accept responsibility for the lighting design. • This Certificate of Compliance identifies the lighting features and performance specifications required for compliance with Title 24, Pages 1 and 6 of the California Code of Regulations. • The design features represented on this Certificate of Compliance are consistent with the information provided to document this design on the other applicable compliance forms, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application. Name Signature Bill Wenche/l Company Phone MAI Design Group (720) 266-2582 Address License # 3831nvemess Parkway, Suite 190 City/State/Zip Date Englewood, CO 80112-5862 Principal Lighting Designer's Declaration ® I certify that this Certificate of Compliance documentation is accurate and complete, and accounts for all outdoor lighting power, including building mounted, pole mounted, as well as all other lighting designed for the site, and that Additional Lighting Power Allowances for Specific Applications or Additional Lighting Power Allowances for Ordinance Requirements have not been counted more than one time for the same area, in accordance with Section 147 of the Standards. Outdoor Lighting Mandatory Measures Indicate location on building plans of Mandatory Measures Note Block: LIGHTING COMPLIANCE FORMS & WORKSHEETS (check box If worksheets is included) For detailed instructions on the use of this and all Energy Efficiency Standards compliance forms; please refer to the Nonresidential Manual published by the California Energy Commission. ❑ OLTG-1 C Certificate of Compliance. All 4 pages required on plans for all submittals. ❑ OLTG-2C (Pages 1 of 3) Lighting Wattage Allowances for General Hardscape, Sales Frontage, or Ornamental Lighting. Optional on tans. ❑ OLTG-2C (Pages 2 of 3) Lighting Wattage Allowance for Per Application or Per Area. Optional on plans. ❑ OLTG-2C (Pages 3 of 3) Additional Lighting Power Allowance for Ordinance Requirements. Optional on plans. EnergyPrp 5.1 by EnergySoft User Number. 6712 RunCode: 2010-12-16T09:50:29 ID: Page 38 of 89 0 C ' r . CERTIFICATE OF COMPLIANCE Part 2 of 4 OLTG-1 C Project Name r Fitness Building -Tradition Club Assoc. Date 12/16/2010 _ COMPLIANCE FIXTURE / LIGHTING CONTROL SCHEDULE and FIELD INSPECTION CHECKLIST INSTALLATION CERTIFICATE, OLTG-11NST (Retain a copy'and verify form is completed and signed.) Field; ns eCtton s CERTIFICATE OF ACCEPTANCE, OLTG-2A (Retain a copy and verify form is completed and signed.) Ffldtdlllisdti6n..1.6J.. Luminaire Schedule Installed Watts A B C D E F G H Name or Item Ta Luminaire Description' See footnote below i.e.: 1 lam ole -to shoe -box 400 watt metal halide c Uo o•-ro 3� m to How wattage was determinedIns O m z� N m x coo Field ectorz E O m v w oz aw,o i y'P WLL s.....nk,:�. IDC2 3-60w Incandescent '180.01 ❑ El ❑ 1 180 k?❑ IDWI 75w Incandescent 75.0 ❑ m [3' 12 900 & # Q CI 13 0 ❑ ❑ ❑❑ 13 13 ❑ ❑ �f ^�>p t; [3 [3 a [3 [3 o `o a Enter total Into OLTG-1 C; Page 4 of 4: Row H; Total Installed Watts: 1,080 1. Type of luminaire (i.e.: post top, wall pack, surface, shoe box); for non -incandescent luminaires, indicate nominal lamp'wattage and lamp type (i.e.: fluorescent, incandescent, HID); ballast type (i.e.: electronic or magnetic); number of lamps and number of ballasts per luminaire. For incandescent luminaires, the luminaire wattage listed in column D shall be the maximum relamping rated wattage on a permanent factory -installed label on the luminaire, NOT the wattage of the lamp (bulb) used, in accordance with Section 130(d or e). ' 2. If Fail then describe on Page 2 of the Inspection Checklist Form and take appropriate action to correct. Verify building plans if necessary. EXEMPT LUMINAIRES Field Ins' action ❑'k Name or Symbol Description of exempt luminaires in accordance with §147 MANDATORY CONTROLS Freld Ins";ection<.❑ ; # Description Location # Description Location SPECIAL FEATURES INSPECTION CHECKLIST See Page 2 of 4 of OLTG-1C The local enforcement agency should pay special attention to the items specified in this checklist. These items require special written justification and documentation, and special verification. The local enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation submitted. Filed Inspector Notes or Discrepancies: EnergyPro 5.1 by EnergySoft User Number. 6712 RunCode: 2010-12-16709:50:29 ID: Page 39 of 89 • • C CERTIFICATE OF COMPLIANCE Part 3 of 4 OL G-1 C Project Name Date Fitness Building -Tradition Club Assoc. 12/1612010 A. OUTDOOR LIGHTING ZONE OUTDOOR LIGHTING ZONE: ❑ OLZ 1 ❑ OLZ 2 M OLZ 3 ❑ OLZ 4 Is the Outdoor Lighting Zone: m Default in accordance with §10-114, or ❑ Amended by JHA Complete the information below if the default Outdoor Lighting Zone has been amended by the local jurisdiction having authority (JHA): ❑ The site is a government designated park, recreational area, wildlife preserve, or portion thereof, and has been designated as LZ2 or LZ3, in accordance with Table 10-114-A, because the site is contained within such a zone. ❑ The local jurisdiction having authority has officially adopted a change to the State Default Lighting Zone and has notified the Energy Commission by providing the materials required in §10-114(d) to the Executive Director. ❑ The adopted change is posted on the Energy Commission website. B. ADDITIONAL LIGHTING POWER ALLOWANCE FOR ORDINANCE REQUIREMENTS Are additional lighting ower allowances for ordinance in Table 147-C used? ❑ Yes m No Complete the information below if additional lighting power allowances for ordinance requirements are used: ❑ The local jurisdiction having authority has officially adopted specific outdoor light levels, which are expressed as average or minimum footcandle levels, by following a public process that allowed for formal public notification, review, and comment about the proposed change. ❑ The local jurisdiction having authority which adopted specific outdoor light levels and has notified the Commission by providing the following materials required §10-114(f) to the Executive Director. C. ACCEPTANCE FORMS Required Acceptance Tests Designer: This form is to be used by the designer and attached to the plans. Listed below is the acceptance test for the Lighting system, OLTG-2A. The designer is required to check the acceptance tests and list all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for Code Compliance. If all the lighting system or control of a certain type requires a test, list the different lighting and the number of systems. The NA7 Section in the Appendix of the Nonresidential Reference Appendices Manual describes the test. Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work appropriately. Forms can be grouped by type of Luminaire controlled. Enforcement Agency: Systems Acceptance. Before Occupancy Permit is granted for a newly constructed building or space or when ever new lighting system with controls is installed in the building or space shall be certified as meeting the Acceptance Requirements. The OLTG-2A form is not considered a complete form and is not to be accepted by the enforcement agency unless the boxes are checked and/or filled and signed. In addition, a Certificate of Acceptance forms shall be submitted to the enforcement agency that certifies plans, specifications, installation certificates, and operating and maintenance information meet the requirements of §10-103(b) of Title 24 Part 6. The field inspector must receive the properly filled out and signed forms before the building can receive final occupancy. A copy of the OLTG-2A for each different lighting luminaire control(s) must be provided to the owner of the building for their records. Certificate of Acceptance Luminaires Controlled OLTG-2A' Qty. of Equipment Re uirin Testing Like Description Controls Location Outdoor Lighting Acceptance Tests 1. Insert: OMS for Outdoor Motion Sensor; OLSC for Outdoor Lighting Shutoff Controls; OP for Outdoor Photocontrol; ATS for Astronomical Time Switch; and, STS for Standard non -astronomical Time Switch acceptance. EnergyPro 5.1 by EnergySoff User Number: 6712 Run Code: 2010-12-16T09:50:29 ID: Page 40 of 89 Pj • • CERTIFICATE OF COMPLIANCE( 4 of 4 OLTG-1 C -Part Project Name Date Fitness Building -Tradition Club Assoc. 12/16/2010 ALLOWED AND INSTALLED OUTDOOR LIGHTING POWER Lighting Wattage Power Allowance - A Lighting power allowance for general hardscape (from OLTG-2C Page 1 of 3) 1,251 B Specific application lighting wattage allowance per unit length (from OLTG-2C Page 1 of 3) 0 C Specific application lighting wattage allowance for ornamental lighting (from OLTG-2C Page 1 of 3) 0 D Specific application lighting wattage allowance per application (from OLTG-2C Page 2 of 3) 250 E Specific application lighting wattage allowance per area (from OLTG-2C Page 2 of 3) 0 F Specific application lighting wattage allowance for ordinance requirements (from OLTG-2C Page 3 of 3) 0 G Total Allowed Wattage = Sum of rows A through F: 1,501 H Total installed watts (from Compliance Fixture Schedule, (from OLTG-2C Page 1 of 3) 1,080 Complies if wattage in row H is less than or equal to the wattages in row G m Yes ❑ No EnergyPro 5.1 bV EnergySoft User Number., 6712 Run Code: 2010-12-16T09:50:29 ID: Page 41 of 89 OUTDOOR LIGHTING WORKSHEET Part 1 of 3 OLTG-2C Project Name Fitness Building -Tradition Club Assoc. Date 1 12/16/2010 A. LIGHTING POWER ALLOWANCE FOR GENERAL HARDSCAPE AREA WATTAGE ALLOWANCE AWA LINEAR WATTAGE ALLOWANCE LWA INITIAL WATTAGE ALLOWANCE TOTAL GENERAL HARDSCAPE LIGHTING ALLOWANCE A B C D E F G H Illuminated Hardscape Area AWA Per Square Foot AWA A X B Perimeter Length of General Hardscape LWA Per Linear Foot LWA D X E IWA alts C+ F+ G 572 0.092 53 96 0.920 88 770 911 576 0.092 53 120 0.920 110 0 163 108 0.092 10 42 0.920 39 0 49 220 0.092 20 64 0.920 59 0 79 Enter total into OLTG-1 C; Page 4 of 4; Row A; Lighting Power Allowance for General Hardscape 1,251 m Yes AWA, LWA, and IWA from Table 147-A was used as appropriate for the Outdoor Lighting Zone B. SPECIFIC APPLICATION LIGHTING WATTAGE ALLOWANCE PER UNIT LENGTH Available only for sales fronts e DETERMINE WATTAGE ALLOWANCE LUMINAIRE TYPE DESIGN WATTS A B C D E F G H I J Specific Lighting Application Linear Foot of Frontage Sales Frontage Allowance for OLZ alts per LF Wattage Allowance B X C Name or Symbol Luminaire Type Lumin QTY Watts Per Luminaire Design Watts G X H Allowed Watts Minimum of D or Enter total into OLTG-1 Q Page 4 of 4; Row B; Specific Application Lighting Wattage Allowance Per Unit Length 0 C. SPECIFIC APPLICATION WATTAGE ALLOWANCE FOR ORNAMENTAL LIGHTING DETERMINE WATTAGE ALLOWANCE LUMINAIRE TYPE DESIGN WATTS A B C D E F G H I J Specific Lighting Application Square feet of Harsc a Ornamental Lighting Allowance for OLZ alts per ftz Wattage Allowance BXC Name or S mbol Luminaire Type Lumin QTY Watts Per Luminaire Design Watts G X H Allowed Watts Minimum of D or I Enter total into OLTG-1 C; Page 4 of 4; Row C; Specific Application Wattage for Ornamental Lighting 0 EnergyPro 5.1 by EnergySoft User Number: 6712 Run Code: 2010-12-16T09:50:29 ID: Page 42 of 89 .7 OUTDOOR LIGHTING WORKSHEET Part 1 of 3 OLTG-2C Project Name Fitness Building -Tradition Club Assoc. Date 1 12/16/2010 A. LIGHTING POWER ALLOWANCE FOR GENERAL HARDSCAPE AREA WATTAGE ALLOWANCE AWA LINEAR WATTAGE ALLOWANCE LWA INITIAL WATTAGE ALLOWANCE TOTAL GENERAL HARDSCAPE LIGHTING ALLOWANCE A B C D E F G H Illuminated Hardscape Area AWA Per Square Foot AWA A X B Perimeter Length of General Hardscape LWA Per Linear Foot LWA D X E IWA Watts C+ F+ G 108 0.092 10 42 0.920 39 0 49 Enter total into OLTG-1 C; Page 4 of 4; Row A; Lighting Power Allowance for General Hardscape 1.251 m Yes AWA, LWA, and IWA from Table 147-A was used as appropriate for the Outdoor Lighting Zone B. SPECIFIC APPLICATION LIGHTING WATTAGE ALLOWANCE PER UNIT LENGTH Available only for sales fronts e DETERMINE WATTAGE ALLOWANCE LUMINAIRE TYPE DESIGN WATTS A B C D E F G H I J Specific Lighting Application Linear Foot of Frontage Sales Frontage Allowance for OLZ alts per LF Wattage Allowance B X C Name or Symbol Luminaire Type Lumin QTY Watts Per Luminaire Design Watts G X H Allowed Watts Minimum of D or Enter total into OLTG-1 C; Page 4 of 4; Row B; Specific Application Lighting Wattage Allowance Per Unit Length 0 C. SPECIFIC APPLICATION WATTAGE ALLOWANCE FOR ORNAMENTAL LIGHTING DETERMINE WATTAGE ALLOWANCE LUMINAIRE TYPE DESIGN WATTS A B C D E F G H I J Specific Lighting Application Square feet of Harsc a Ornamental Lighting Allowance for OLZ alts per ftp Wattage Allowance B X C Name or Symbol Luminaire Type Lumin QTY Watts Per Luminaire Design Watts G X H Allowed Watts Minimum of D or Enter total into OLTG-1 C; Page 4 of 4; Row C; Specific Application Wattage for Ornamental Lighting 0 EnergyPro 5.1 by EnergySoft User Number., 6712 Run Code: 2010-12-16T09:50:29 ID: Page 43 of 89 0 OUTDOOR LIGHTING WORKSHEET Part 2 of 3 OLTG-2C Project Name Fitness Building -Tradition Club Assoc. Date 12/16/2010 D. SPECIFIC APPLICATION LIGHTING WATTAGE ALLOWANCE PER APPLICATION DETERMINE WATTAGE ALLOWANCE DESIGN WATTS ALLOWANCE A B C D E F G H I J Specific Lighting Application Number of Applications Specific Application Allowance watts Wattage Allowance B X C Luminaire Symbol Luminaire Type Lumin QTY Watts Per Luminaire Design Watts G X H Allowed Watts Minimum of D or I Building Entry 1 100 100 IDC2 3-60w Incandescent 1 180.0 180 100 Mech Room Entry 1 100. 100 IDW1 75w Incandescent 1 75.0 75 75 Mech/Elec Entry 1 100 100 IDW1 75w Incandescent 1 75.0 75 75 Enter total into OLTG-1 C; Page 4 of 4; Row D; Specific Application Wattage Allowance Per Application 250 E. SPECIFIC APPLICATION LIGHTING WATTAGE ALLOWANCE PER AREA DETERMINE WATTAGE ALLOWANCE LUMINAIRE TYPE DESIGN WATTS A B C D E F G H I J Specific Lighting Application Illuminated Area of Application Specific Application Allowance watts per ft2 Wattage Allowance B X C Code for Luminaire Type' Luminaire Type Lumin QTY Watts Per Luminaire Design Watts G X H Allowed Watts Minimum of D or I Enter total into OLTG-1 C; Page 4 of 4; Row E; Specific Application Lighting Wattage Allowance Per Area 0 EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2010-12-16709:50:29 ID: Page 44 of 89 • • MECHANICAL MANDATORY MEASURES: NONRESIDENTIAL MECH-MM Project Name Date Fitness Building -Tradition Club Assoc. 12/16/2010 Equipment and System Efficiencies §111: Any appliance for which there is a California standard established in the Appliance Efficiency Regulations will comply with the applicable standard. §115(a): Fan type central furnaces shall not have a pilot light. §123: Piping, except that conveying fluids at temperatures between 60 and 105 degrees Fahrenheit, or within HVAC equipment, shall be insulated in accordance with Standards Section 123. §124: Air handling duct systems shall be installed and insulated in compliance with Sections 601, 602, 603, 604, and 605 of the CMC Standards. Controls §122(e): Each space conditioning system shall be installed with one of the following: 1A. Each space conditioning system serving building types such as offices and manufacturing facilities (and all others not explicitly exempt from the requirements of Section 112 (d)) shall be installed with an automatic time switch with an accessible manual override that allows operation of the system during off -hours for up to 4 hours. The time switch shall be capable of programming different schedules for weekdays and weekends and have program backup capabilities that prevent the loss of the device's program and time setting for at least 10 hours if power is interrupted; or 1 B. An occupancy sensor to control the operating period of the system; or 1 C. A 4 -hour timer that can be manually operated to control the operating period of the system. 2 Each space conditioning system shall be installed with controls that temporarily restart and temporarily operate the system as required to maintain a setback heating and/or a setup cooling thermostat setpoint. Each space conditioning system serving multiple zones with a combined conditioned floor area more than 25,000 §122(8)' square feet shall be provided with isolation zones. Each zone: shall not exceed 25,000 square feet; shall be provided with isolation devices, such as valves or dampers that allow the supply of heating or cooling to be setback or shut off independently of other isolation areas; and shall be controlled by a time control device as described above. §122(c): Thermostats shall have numeric setpoints in degrees Fahrenheit (F) and adjustable setpoint stops accessible only to authorized personnel. 22 b §1 ()' Heat pumps shall be installed with controls to prevent electric resistance supplementary heater operation when the heating load can be met by the heat pump alone Each space conditioning system shall be controlled by an individual thermostat that responds to temperature within the zone. Where used to control heating, the control shall be adjustable down to 55 degrees F or lower. For cooling, the §122(a&b): control shall be adjustable up to 85 degrees F or higher. Where used for both heating and cooling, the control shall be capable of providing a deadband of at least 5 degrees F within which the supply of heating and cooling is shut off or reduced to a minimum. Ventilation §121(e): Controls shall be provided to allow outside air dampers or devices to be operated at the ventilation rates as specified on these plans. §122(f): All gravity ventilating systems shall be provided with automatic or readily accessible manually operated dampers in all openings to the outside, except for combustion air openings. Ventilation System Acceptance. Before an occupancy permit is.granted for a newly constructed building or space, or a §121(f): new ventilating system serving a building or space is operated for normal use, all ventilation systems serving the building ors ace shall be certified as meeting the Acceptance Requirements for Code Compliance Service Water Heating Systems §113(c) Installation 3. Temperature controls for public lavatories. The controls shall limit the outlet Temperature to 110° F. 2 Circulating service water -heating systems shall have a control capable of automatically turning off the circulating pump when hot water is not required. LE,ergyPrp 5.1 by EnergySoft User Number: 6712 RunCode: 2010-12-16T09:50:29 ID: Pa a 45 of 89 4 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name itness Building -Tradition Club Assoc. Date 12/16/2010 System Name HP 1 Floor Area 673 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 1 COIL COOLING CFM Sensible Total Room Loads 1,167 13,734 Return Vented Lighting 0 Return Air Ducts 687 Return Fan 0 Ventilation 481 18,476 Supply Fan 0 Supply Air Ducts 1 687 TOTAL SYSTEM LOAD 1 33,583 PEAK COIL HTG. PEAK Heating System Latent CFM Sensible Output perSystem 47,000 6,8621 193 8,294 Total Output Btuh 47,000 Output Btuh/s ft 69.8 415 Cooling System 0 Output perSystem 48,000 1,187 481 23,748 Total Output Btuh 48,000 8,049 0 Total Output Tons 4.0 415 Total Output Btuh/s ft 71.3 Total Output s ft/Ton 168.3 1 32,871 Air System CFM perSystem 1,600 HVAC EQUIPMENT SELECTION Airflow cfm 1,600 Lennox XP17-048-230' 38,682 8,468 27,762 Airflow cfm/s ft 2.38 1 27,762 Jan 1 AM Airflow cfmrron 400.0 Outside Air % 30.0% Total Adjusted System Output 1 38,682 (Adjusted for Peak Design conditions) TIME OF SYSTEM PEAK 8,468 Jul 3P ml Outside Air cfm/s ft)__0.71 Note: values above given at ARI conditions HEATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak 24 OF 56 OF Outside Air 481 cfm Supply Fan 1,600 cfm 70 OF 56 OF 110 OF Heating Coil 110 OF I– —. Z= ROOM 70 OF COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak 112 / 79 OF 87171 OF 87 / 71 OF 65 / 63 OF (`©' » Outside Air 3 Supply Fan 481 cfm pp y Cooling Coil 65 / 63 OF 1,600 cfm t1 66.7% ROOM 76 / 68 of 76 ! 68 OF EnergyPro 5.1 by EnergySoft User Number: 6712 Run Code: 2010-12-16T09:50:29 ID: Page 46 of 89 r 4 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY / Project Name Fitness Building -Tradition Club Assoc. Date 12/16/2010 System Name HP2&3 Floor Area 2,021 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 2 COIL CFM Total Room Loads' 4,680 Return Vented Lighting Return Air Ducts Return Fan Ventilation 1,071 Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COOLING Sensible 43,978 0 2,199 01 41,024 0 2,199 1 89,400 PEAK COIL HTG. PEAK Heating System Latent CFM Sensible Output perSystem 53,000 17,476 590 25,284 Total Output Btuh 106,000 Output Btuh/s ft 52.4 1,264 Cooling System 0 Output perSystem 55,500 -2,911 1,071 52,833 Total Output Btuh 111,000 14.5651 0 Total Output ons 9.3 1,264 Total Output Btuh/s ft 54.9 Total Output s ft/Ton 218.5 80,646 Air System CFM perSystem 2,000 HVAC EQUIPMENT SELECTION Airflow cfm 4,000 Lennox XP17-060-230' Total Adjusted System Output (Adjusted for Peak Design conditions) TIME OF SYSTEM PEAK 83,008 83,008 27,268 62,613 27,268 62,613 Jul 3 PM Jan 1 AM Alrflow cfm/s ft 1.98 Airflow cfm/Ton 432.4 Outside Air % 26.8% Outside AIr cfm/s ft 0.53 Note: values above given at ARI conditions HEATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak 24 °F 57 OF Outside Air 1,071 cfm Supply Fan 4,000 cfm 70 OF 57 OF 110 OF Heating Coil 110 OF ROOM. 70 OF COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak 112/79°F 86/72°F 86!72°F 67/65°F ,`& Outside Air 1,071 cfm Supply I Fan Cooling Coil 4.000 cfm 77/70°F ( �A 67 / 66 F L 72.1 L RdOtt►1 76!69°F EnergyPro 5.1 by EnergySoff User Number: 6712 Run Code: 2010-12-16709:50:29 ID: Page 47 of 89 4 4 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name fitness Building -Tradition Club Assoc. Date 12/16/2010 System Name HP 4 Floor Area 1,179 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 1 COIL CFM Total Room Loads 2.811 Return Vented Lighting Return Air Ducts Return Fan Ventilation 296 Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COOLING PEAK Sensible 31,615 0 1,581 0 11,263 0 1,581 1 46,040 COIL HTG. Latent CFM 8,509 407 311 296 8,821 PEAK Heating System Sensible Output perSystem 53,000 17,406 Total Output Btuh 53,000 Output Btuh/s ft 45.0 870 Cooling System 0 Output perSystem 55,500 14,562 Total Output Btuh 55,500 0 Total Output Tons 4.6 870 Total Output Btuh/s ft 47.1 Total Output s ft/Ton 254.9 1 33,709 Air System CFM perSystem 2,000 HVAC EQUIPMENT SELECTION Airflow cfm 2,000 Lennox XP17-060-230' 36,921 16,537 31,306 Alrflow cfm/s ft 1.70 31,306 Jan 1 AM Airflow cfm/Ton 432.4 Outside Air % 14.8% Total Adjusted System Output 36,921 (Adjusted for Peak Design conditions) TIME OF SYSTEM PEAK 16,537 Jul 3M Outside Air cfm/s ft 0.25 Note: values above given at ARI conditions HEATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak 24 OF 63 OF Outside Air 296 cfm Supply Fan AL 2,000 cfm 70 OF 63 OF 110 OF Heating Coil 110 °F ROOM 70 OF COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak 112/79°F 82/70°F 82/70°F 65/64°F �sQst:z . Outside Air 296 cfm Supply Fan Cooling Coil 2,000 cfm. 77 / 69 OF - 68.2% 66 / 64 OF ......................., � ROO :' 76 / 68 OF EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2010-12-16709:50:29 ID: Page 48 of 89 4 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name fitness Building -Tradition Club Assoc. Date 12/16/2010 System Name HP 5 Floor Area 563 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 1 COIL COOLING PEAK CFM Sensible Total Room Loads 950 12,452 Return Vented Lighting 0 Return Air Ducts 623 Return Fan 0 Ventilation 402 15,473 Supply Fan 0 Supply Air Ducts -6231 TOTAL SYSTEM LOAD 1 29,170 COIL HTG. Latent CFM 5,768 129 2,202 402 7,970 PEAK Heating System Sensible Output per System 47,000 5,563 Total Output Btuh 47,000 Output Btuh/s ft 83.5 278 Cooling System 0 Output per System 48,000 19,900 Total Output Btuh 48,000 0 Total Output Tons 4.0 278 Total Output Btuh/s ft 85.3 Total Output s ft/Ton 140.8 1 26,019 Air System CFM per System 1,600 HVAC EQUIPMENT SELECTION Airflow cfm 1,600 Lennox XP17-048-230' 37,687 8,599 27,762 Airflow cfm/s ft 2.84 Total Adjusted System Output 37,687 (Adjusted for Peak Design conditions) 1 TIME OF SYSTEM PEAK 8,599 27,762 Jul 3 PM Jan 1 AM Airflow cfm/Ton 400.0 Outside Air % 25.1 % Outside Alr cfm/s ft 0,71 Note: values above given at ARI conditions HEATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak 24 OF 58 OF Outside Air 402 cfm Supply Fan 1,600 cfm 70 OF 58 OF 110 OF Heating Coil 110 OF :ROOM 70 OF COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak 112/79°F 85/70°F 85/70°F 63/62°F oc Outside Air 402 cfm Supply Fan Cooling Coil 63.5% 76/67°F 64 / 62 OF ......... { . !:ROOM, AN 76/67°F EnergyPro 5.1 by EnergySoft User Number. 6712 Run Code: 2010-12-16T09:50:29 ID: Page 49 of 89 4 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name_ Fitness Building -Tradition Club Assoc. Date 12/16/2010 System Name H P 6 Floor Area 660 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 1 COIL COOLING PEAK CFM Sensible Total Room Loads 1,162 13,828 Return Vented Lighting 0 Return Air Ducts 691 Return fan 0 Ventilation 1 471 18,118 Supply Fan 0 Supply Air Ducts 691 TOTAL SYSTEM LOAD 1 33,328 COIL HTG. Latent CFM 6,761 188 1,309 471 8,070 PEAK Heating System Sensible Output perSystem 47,000 8,077 Total Output Btuh 47,000 Output Btuh/s ft 71.2 404 tooling System 0 Output perSystem 48,000 23,292 Total Output Btuh 48,000 0 Total Output ons 4.0 404 Total Output Btuh/s ft 72.7 Total Output s ft/Ton 165.0 1 32,177 Air System CFM perSystem 1,600 HVAC EQUIPMENT SELECTION Airflow cfm 1,600 Lennox XP17-048-230' 38,547 8,512 27,762 Airflow cfm/s ft 2.42 Total Adjusted System Output 38,547 (Adjusted for Peak Design conditions) TIME OF SYSTEM PEAK F 8,512 27,762 Jul 3 PM Jan 1 AM Airflow cfm/Ton 400.0 Outside Air % 29.5% Outside Air cfm/s ft 0.71 Note: values above given at ARI conditions HEATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak 24 OF 56 OF Outside Air 471 cfm Supply Fan 1,600 cfm 70 OF 56 OF 110 OF Heating Coil Ld 110 OF :ROOM 70 OF COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak 112 / 79 OF 87 / 71 OF 87 / 71 OF 65 ! 63 OF 4. Outside Air Supply Fan 471 cfm pp y Cooling Coil 1,600 cfm 66.4% 76 / 68 OF 65 / 63 OF .................................... ROOM 76 ! 68 OF EnefyyPro 5.1 by EnergySoft . User Number: 6712 Run Code: 2010-12-16709:50:29 ID: Page 50 of 89 • ZONE LOAD SUMMARY Project Fitness Building- Tradition C• Assoc. 1211612010 Name HP 1 FloorSystem 673 ZONE LOAD SUMMARY COOLINGNEW (BLOCK LOAD) EnergyPro2010-12-16TO9:50:29 ID: Page 51 of 89 ZONE LOAD SUMMARY Project Name Fitness Building -Tradition Club Assoc. Date 12116/2010 System Name HP 2 & 3 Floor Area 2,021 ZONE LOAD SUMMARY ZONAL SYSTEM COOLING PEAK HEATING PEAK ZONE NAME SYSTEM NAME Mult. CFM Sensible Latent Heating OA CFM Peak Hr CFM Sensible Latent CFM Sensible Cardio/Circuit - 1.0 870 Ju13PM, 3,901 70,470 31,636 494 64,376 Free Weights 1.0 201 Jul 3 PM 779 15,121 6,708 96 14,080 TOTALS 0 01 01 1,0711 Jul3 PM 1 85,5911 38,344 78,456 BLOCK LOAD EnergyPro5.1.by EnergySoft User Number: 6712 RunCode: 2010-12-16709:50:29 ID: Page 52 of 89 • ZONE LOAD SUMMARY Project Name Fitness Building -Tradition Club Assoc. Date 12/16/2010 System Name HP 4 Floor Area 1,179 ZONE LOAD SUMMARY ZONAL SYSTEM COOLING PEAK HEATING PEAK ZONE NAME SYSTEM NAME Mult. CFM Sensible Latent Heating OA CFM Peak Hr CFM Sensible Latent CFM Sensible Relaxation Room 1.0 129 Jul3 PM 837 14,408 5,662 118 11,440 Therapy 1 1.0 37 Jul3 PM 249 4,245 1,646 60 4,425 Therapy 2 1.0 34 Jul3 PM 211 3,684 1,487 45 3,598 FoyeNReception 1.0 96 Jul 3PM 1,514 20,775 5,480 184 12,634 TOTALS 01 0 0 296 Jul 3PM 43,112 14,275 32,097 BLOCK LOAD EnergyPry5.1 by EnergySoft User Number: 6712 Run Code: 2010-12-16709:50:29 ID: Page 53 of 89 0 orkel •�� �' Project Name Fitness Building- Tradition C. Assoc. Date 1211612010 Name IHP5 FloorSystem 563 ZONE LOAD -SUMMARY COOLING . ... .. ,., Page 54 of 89 • ZONE LOAD SUMMARY Name Building- Tradition Club Assoc. —DateProject 1211612010 —System Name HP 6 FloorFitness ..0 ZONE LOAD SUMMARY ZONAL.. NAME (BLOCKSYSTEM LOAD) • • • ROOM LOAD SUMMARY Project Name Fitness Building -Tradition Club Assoc. System Name HP2&3 Date 12/16/2010 Floor Area 2,021 ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK Zone Name Room Name Mult. CFM Sensible Latent CFM Sensible Latent CFM Sensible Cardio/Ciruit Cardio/Circuit 1 3,901 36,658 14,679 3,901 36,658 14,405 494 21,172 Free Weights Free Weights 1 1 779 7,320 2,797 779 7,320 2,771 96 4,112 PAGE TOTAL TOTAL " 4,6801 43,9781 17,177 ' 590 25,2 4,680 43,978 17,476 590 25,284 ' Total includes ventilation load for zonal systems. EnergyPro 5.1 by EnemySoft User Number: 6712 RunCode: 2010-12-16709:50:29 ID: Page 57 of 89 • ROOM LOAD SUMMARY Project Name Fitness Buildina-Tradition Club Assoc. 12/16/2010 HP 4 1,179 ROOM LOAD SUMMARY Total includes PAGE TOTAL TOTAL " 2,811 31,615 8,342 ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK Zone Name Room Name Mult. CFM Sensible Latent CFM Sensible Latent CFM Sensible Relaxation Room Relaxation Room 1 837 9,411 3,156 837 9,411 3,118 118 5,055 Therapy 1 Therapy 1 1 249 2,800 921 249 2,800 910 60 2,577 Therapy 2 Therapy 2 1 211 2,378 8321 2111 Z3781 8221 451 1,929 Foyer/Reception FoyerlReception 1 1,5141 17,0271 3,600 1, 5141 17,0271 3,4921 1841 7,844 Total includes PAGE TOTAL TOTAL " 2,811 31,615 8,342 407 17,406 2,811 31,615 8,509 407 17,406 C] • • ROOM LOAD SUMMARY Project Name Date Fitness Buildinq-Tradition Club Assoc. 12/16/2010 HP 5 563 ROOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK Zone Name I Room Name I Mult. I CFM I Sensible I Latent CFM I Sensible I `Latent CFM I Sensible Men's Locker Room I Men's Locker Room 1 1 1 9501 1Z4521 5,7681 9501 12,452 5, 707 1291 5,563 PAGE TOTAL TOTAL' 950 1Z4521 5,7071 129 5,563 950 12, 452 5,7681 1291 5, 563 Total includes ventilation load for zonal systems. EnemyPro 5.1 by EnemySoft User Number: 6712 Run Code: 2010-12-16T09:50:29 ID: Page 59 of 89 • C� J C]A ROOM'HEATING PEAK LOADS Project Name Fitness Building -Tradition Club Assoc. Date 12/16/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name yoga Floor Area 6 73. 0 ft' Indoor Dry Bulb Temperature 70 OF Time of Peak Jan 1 AM Outdoor Dry Bulb Temperature 24 OF Conduction Area U -Value 673.0 X 0.0260 742.0 X 0.0690 32.0 X 0.2500 perim = 59.0 X 0.7300 X X X X X X X X X X X X X X X X X X X X X X X X X X X through an interior surface to another room 1.080 X 673 X 10.00 X 0.500 Area Ceiling Height ACH X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X AT °F Btu/hr 46 = 805 46 = 2,355 46 = 368 46 = 1,981 = = = = = = = = = - = = = = = = = = = = _ = = = Page Total 5,509 /60] X AT R-38 Roof(R.38.2x12.16) R-21 Wall (W. 21.2x6.16) Double Non Metal Tinted Slab -On -Grade Items shown with an asterisk (') denote conduction Infiltration:[ 1.00 X Schedule Air Sensible Fraction TOTAL HOURLY HEAT LOSS FOR ROOM 8,294 Energ Pro 5.1 by Energ Sof User Number. 6712 RunCode: 2010-12-16709:50:29 ID: Page 61 of 89 E, ROOM HEATING PEAK LOADS Project Name Fitness Building -Tradition Club Assoc. Date 12/16/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name Cardio/Circuit Floor Area 1,740.0 ft2 Indoor Dry Bulb Temperature 70 T Time of Peak Jan 1 AM Outdoor Dry Bulb Temperature 24 OF Conduction 1.080 Area U -Value 1,740.0 X 0.0260 902.2 X -0.0690 255.8 X 0.2500 perm = 74.0 X 0.7300 X X X X X X X X X X X X X X X X X X X X X X X X X X X through an interior surface to another room X 1,740 X 15.00 X 0.500 Area Ceiling Height ACH X X X X X X X X X X X X X X X X X X X X X X X X X X X X .X X X AT °F Btu/hr 46 = 2,081 46 = 2,864 46 = 2,942 46 = 2,485 = = = = = = = = = = = = = = = = = = = = = = = = = = Page Total 10,371 /60] X 46 = 10,801 AT R-38 Roof(R.38.2x12.16) R -21W6/1 (W.21.2x6.16) Double Non Metal Tinted Slab -On -Grade Items shown with an asterisk (') denote conduction Infiltration:[ 1.00 X Schedule Air Sensible Fraction TOTAL HOURLY HEAT LOSS FOR ROOM 21,172 Energ Pro 5.1 by EnergySoft User Number: 6712 Run Code: 2010-12-16T09:50:29 ID: Page 62 of 89 0 1� • ROOM HEATING PEAK LOADS Project Name Fitness Building -Tradition Club Assoc. Date 12/16/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name Free Weights Floor Area 281.0 ftZ Indoor Dry Bulb Temperature 70 °F Time of Peak Jan 1 AM Outdoor Dry Bulb Temperature 24 OF Conduction Area U -Value 281.0 X 0.0260 470.6 X 0.0690 7.4 X 0.2500 perim = 36.0 X 0.7300 X X X X X X X X X X X X X X X X X X X X X X X X X X X through an interior surface to another room 1.080 X 281 X 8.50 X 0.500 Area Ceiling Height ACH X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X AT °F Btu/hr 46 = 336 46 = 1,494 46 = 85 46 = 1,209 = = = = = = = = = = = = = — = = = = = = = = = = = = Page Total 3.124 /60] X 46 = 988 AT R-38 Roof(R.38.2x12.16) R-21Wa11 (W.21.2x6.16) Double Non Metal Tinted Slab -On -Grade Items shown with an asterisk (') denote conduction Infiltration:[ 1.00 X Schedule Air Sensible Fraction TOTAL HOURLY HEAT LOSS FOR ROOM "4 112 Energ Pro 5.1 by EnergySoft User Number: 6712 RunCode: 2010-12-16709:50:29 ID: Page 63 of 89 • 1� ROOM HEATING PEAK LOADS Project Name Fitness Building -Tradition Club Assoc. K Date 12/16/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name Relaxation Room Floor Area 300.0 ft2 Indoor Dry Bulb Temperature 70 OF Time of Peak Jan 1 AM Outdoor Dry Bulb Temperature 24 OF Conduction Area U -Value 300.0 X 0.0260 357.6 X 0.0690 98.4 X 0.2500 perim = 28.0 X 0.7300 • X X X X X X X X X X X X X X X X X X X X X X X X X X X through an interior surface to another room 1.080 X 300 X 12.00 X 0.500 Area Ceiling Height ACH X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X AT °F Btu/hr 46 = 359 46 = 1,135 46 = 1,132 46 = 940 = = = = = = = = = = = = = = = = = = = = = = = = = Page Total 3,566 /60] X 46 = 1,490 AT R-38 Roof(R.38.2x12.16) R-21Wall (W.21.2x6.16) Double Non Metal Tinted Slab -On -Grade Items shown with an asterisk (') denote conduction Infiltration:[ 1.00 X Schedule Air Sensible Fraction TOTAL HOURLY HEAT LOSS FOR ROOM 5,055 Energ Pro 5.1 by Energ Soft User Number: 6712 Run Code: 2010-12-16T09:50:29 ID: Page 64 of 89 • C ROOM HEATING PEAK LOADS Project Name Fitness Building -Tradition Club Assoc. ' � . • Date 12116/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name Therapy 1 Floor Area 124.0 ft2 Indoor Dry Bulb Temperature 70 OF Time of Peak Jan 1 AM Outdoor Dry Bulb Temperature 24 OF Conduction Area U -Value AT `F Btu/hr 46 = 148 46 = 751 46 = 488 46 = 739 = = = = = = = = = = = = _ - = = = _ = = = = = - I= = = Page Total 2,126 /60] X 48 = 452 AT R-38 Roof(R.38.2x12.16) 124.0 X X X 0.0260 X X X R-21Wall (W.21.2x6.16) 236.6 0.0690 Double Non Metal Tinted 42.4 0.2500 Slab -On -Grade perim = 22.0 X 0.7300 X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X to another room 8.80 X 0.500 Ceiling Height ACH Items shown with an asterisk (') denote conduction Infiltration:[ 1.00 X Schedule Air Sensible Fraction through an interior surface 1.080 X 124 X Area TOTAL HOURLY HEAT LOSS FOR ROOM 2,577 Energ Pro 5.1 by Energ Soft User Number: 6712 RunCode: 2010-12-16709:50:29 ID: Page 65 of 89 • .7 ROOM HEATING PEAK LOADS Project Name Fitness Building -Tradition Club Assoc. Date 12/16/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name Therapy 2 Floor Area 112.0 ft2 Indoor Dry Bulb Temperature 70 OF Time of Peak Jan 1 AM Outdoor Dry Bulb Temperature 24 OF Conduction Area U -Value X 0.0260 X 0.0690 X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X AT 'F Btu/hr = 134 = 329 = 488 = 571 = = = = = = = = = = = = = = = = = - 1,521 46 = 408 R-38 Roof(R.38.2x12.16) 112.0 46 R-21Wall (W.21.2x6.16) 103.6 46 Double Non Metal Tinted 42.4 X 0.2500 46 Slab -On -Grade perim = 17.0 X 0.7300 46 X X X X X X X X X X X X X X X X X X X X X X X X X X X to another room 8.80 X 0.500 Ceiling Height ACH Items shown with an asterisk (') denote conduction Infiltration:[ 1.00 X Schedule Air Sensible Fraction through an interior surface 1.080 X 112 X Area Page Total /60] X AT TOTAL HOURLY HEAT LOSS FOR ROOM 1,929 EnergyPro 5.1 by Energ Soft User Number: 6712 RunCode: 2010-12-16709:50:29 ID: Page 66 of 89 LA • ROOM HEATING PEAK LOADS Project Name Fitness Building -Tradition Club Assoc. Date 12/16/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name Foyer/Reception Floor -Area 643.0 ft2 Indoor Dry Bulb Temperature 70 OF Time of Peak Jan 1 AM Outdoor Dry Bulb Temperature 24 OF Conduction Area U -Value X 0.0260 X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X AT °F Btu/hr 46 = 769 46 = 1,119 46 = 994 46 = 705 - = = = - = = = = = = = = = = = = = = = = = = = = Page Total 1 3,587 /60] X 46 = 4,258 AT R-38 Roof(R.38.2x12.16) 643.0 R-21Wall (W.21.2x6.16) 352.6 X X 0.0690 Double Non Metal Tinted 86.4 0.2500 Slab -On -Grade perim = 21.0 X 0.7300 X X X X X X X X X X X X X X X X X X X X X X X X X X X to another room 16.00 X 0.500 Ceiling Height ACH Items shown with an asterisk (') denote conduction Infiltration:[ 1.00 X 1.080 Schedule Air Sensible Fraction through an interior surface X 643 X Area TOTAL HOURLY HEAT LOSS FOR ROOM 7,844 EnergyPro 5.1 by Energ Soft User Number. 6712 Run Code: 2010-12-16709:50:29 ID: Page 67 of 89 • 17J ROOM HEATING PEAK LOADS Project Name Fitness Building -Tradition Club Assoc. Date 12/16/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name Men's Locker Room Floor Area 563.0 ft2 Indoor Dry Bulb Temperature 70 OF Time of Peak Jan 1 AM Outdoor Dry Bulb Temperature 24 OF Conduction Area U -Value 563.0 X 0.0260 X 380.6 X 0.0690 X 3.4 X 0.2500 X perm = 37.0 X 0.7300 . X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X' X X X X X X X X X X X. X X X X X X X X X through an interior surface to another room X 563 X 10.30 X 0.500 Area Ceiling Height ACH AT °F = .= = = = = = _ = _ = = = = = = = _ _ = = = = _ _ = 46 Btu/hr R-38 Roof(R.38.2x12.16) 46 673 R-21Wall (W.21.2x6.16) 46 1,208 Double Non Metal Tinted 46 .39 Slab -On -Grade 46 1,242 Items shown with an asterisk (') denote conduction Infiltration:[ 1.00 X 1.080 Schedule Air Sensible Fraction Page Total /60] X AT 1 3,163 = 2,400 TOTAL HOURLY HEAT LOSS FOR ROOM 5,563 Energ Pro 5.1 by EnergySoft User Number: 6712 Run Code: 2010-12-16709:50:29 ID: Page 68 of 89 • • • ROOM HEATING PEAK LOADS Project Name Fitness Building -Tradition Club Assoc. Date 12/16/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name Women's Locker Room Floor Area 660.0 ft2 Indoor Dry Bulb Temperature 70-F, Time of Peak Jan 1 AM Outdoor Dry Bulb Temperature 24 OF Conduction Area U -Value 660.0 X 0.0260 769.8 X 0.0690 10.2 X 0.2500 peri. 57.0 X 0.7300 X X X X X X X X X X X X X X X X X X X X X X X X X X X through an interior surface to another room 1.080 X 660 X 10.30 X 0.500 Area Ceiling Height ACH X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X AT °F Btu/hr = 789 = 2,443 = 117 = 1,914 = = = = = = = = = = = = = = = = = = = = = = = = = = 5,264 46 R-38 Roof(R.38.2x12.16) 46 R-21Wa/l (W.21.2x6.16) 46 Double Non Metal Tinted 46 Slab -On -Grade 46 Items shown with an asterisk (') denote conduction Infiltration:[ 1.00 X Schedule Air Sensible Fraction Page Total /60] X AT TOTAL HOURLY HEAT LOSS FOR ROOM 8,077 EnergYPro 5.1 by Energ Soft User Number: 6712 RunCode: 2010.12-16709:50:29 ID: Page 69 of 89 C� J • ROOM COOLING PEAK LOADS Project Name Date Fitness Building -Tradition Club Assoc. F 12/16/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name Yoga Time of Peak Jul 3 PM Floor Area 673.0 ft' Outdoor Dry Bulb Temperature 112 OF Indoor Dry Bulb Temperature 76 OF, Outdoor Wet Bulb Temperature 79 OF Conduction Area U -Value DETD' Btu/hr R-38 Roof(R.38.2x12.16) 673.0 X 0.0260 X 27.4 = 479 R-21Wa/l (W.21.2x6.16) 232.0 X 0.0690 X 31.0 = 496 Double Non Metal Tinted 32.0 X 0.2500 X 29.2 = 233 R-21Wall (W.21.2x6.16) 62.0 X 0.0690 X 31.0 = 132 R-21Wa/1 (W.21.2x6.16) 248.0 X 0.0690 X 31.4 = 537 R-21Wall (W.21.2x6.16) 200.0 X 0.0690 X 31.0 = 428 X X = X X = X X = Page Total 2,306 1. Design Equivalent Temperature Difference (DETD) Items shown with an asterisk (') denote conduction through an interior surface to another room. Weighting Solar Gain Orientation Area SGF SC Factor Btu/hr B (E) 16.01 X 0 X 0.434 X 0.000 = 13 B (S) 16.0 X 0 X 0.434 X 0.000 = 13 X X X = X X X = X X X = X X X = X X X = X X X = X X X = Page Total 26 Sched. Weighting Internal Gain Frac. Area Heat Gain Factor Btu/hr Li hts 1.00 X 673 X 1.004 Watts/Sgft X 3.413 Btu/Watt X 0.999 = 2,305 Occupants 1.00 X 673 X 300 Btu/occ. / 35 SgfUOCc. X 1.000 = 5,769 Receptacle 1.00 X '673 X 0.500 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 1,148 Process 1.00 X 673 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 0 Process Lighting 1.00 X 673 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 0.000 = 0 Infiltration:[ 1.00 X 1.080 X 673 X 10.00 X 0.50 / 60 ] X 36 = 2,180 Schedule Air Sensible Area Ceiling Height ACH AT Fraction TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 13,734 Sched. Latent Gain Frac. Area Heat Gain Btu/hr -Occupants 1.00 X 673 X 300 Btuh/occ. / 35 Sgft/occ. = 5,769 Receptacle 1.00 X 673 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Process 1.00 X 673 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Infiltration:[ 1.00 X 4,840 X 673 X 10.00 X 0.50 /60] X 0.00377 = 1,023 Schedule Air Sensible Area Ceiling Height ACH AW Fraction TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 6,791 EnergyPro 5.1 by EnergySoft User Number: 6712 Run Code: 2010-12-16T09:50:29 ID: Page 70 of 89 • • I ROOM COOLING PEAK LOADS I Fitness Building -Tradition Club Assoc. 12/16/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name Cardio/Circuit Time of Peak Jul 3 PM Floor Area 1,740.0 ft-- Outdoor Dry Bulb Temperature 112 OF Indoor Dry Bulb Temperature 76 OF Outdoor Wet Bulb Temperature 79 OF Area R-38 Roof(R.38.2x 12.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) Double Non Metal Tinted Double Non Metal Tinted R-21Wa/l (W.21.2x6.16) R-21 Wall (W.21.2x6.16) 1,740.0 38.0 460.2 233.6 22.2 174.0 230.0 X X X X X X X X X U -Value X X X X X X X X X DETD' = = = = = = = = = 0.0260 27.5 0.0690 31.0 0.0690 31.0 0.2500 29.2 0.2500 29.2 0.0690 31.4 0.0690 31.0 0.000 3 3.7 0.000 3 Page Total 1. Design Equivalent Temperature Difference (DETD) Items shown with an asterisk (') denote conduction through an interior surface to another room. I Solar Gain Window Window Window Window Window Window Window Window Window Orientation (S) (S) (S) (S) (S) (S) (S) (S) (S) Btu/hr 1,244 81 983 1,703 162 377 493 Area SGF X 0 X X 0 X X 0 X X 0 X X 0 X X 0 X X 0 X X 0 X X 0 X SC 0.434 X 0.434 � X 0.434 X 0.434 X 0.4341 X 0.434 X 0.434 X 0.434 X 0.434 X Weighting Factor = = = = = = = = = Btu/hr 58.4 0.000 47 58.4 0.000 47 58.4 0.000 47 58.4 0.000 47 3.7 0.000 3 3.7 0.000 3 3.7 0.000 3 3.7 0.000 3 3.7 0.000 3 Page Total 203 Sched. Weighting Internal Gain Frac. Area Heat Gain Factor Btu/hr Lights 1.00 X 1,740 X 1.609 Watts/Sgft X 3.413 Btu/Watt X 0.999 = 9,547 Occupants 1.00 X 1,740 X 300 Btu/OCC. / 50 Sqf /occ. X 1.000 = 10,440 Receptacle 1.00 X 1,740 X 0.500 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 2,969 Process 1.00 X 1,740 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 0 Process Lighting 1.00 X 1 1,740 X 0.000 Watts/Sgft X 3.413 Btu/Watt X Infiltration:[ 1.00 X 1.080 X 1,740 X 15.00 X 0.50 / 60 ] X 36 = 8,453 Schedule Air Sensible Area Ceiling Height ACH AT Fraction TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 36,658 Sched. Latent Gain Frac. Area Heat Gain Btu/hr Occupants 1.00 X 1,740 X 300 Btuh/occ. / 50 Sgft/occ. = 10,440 Receptacle 1.00 X 1,740 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Process 1.00 X 1,740 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Infiltration:[ 1.00 X 4,840 X 1,740 X 15.00 X 0.50 /60] X 0.00377 = 3,965 Schedule Air Sensible Area Ceiling Height ACH AW Fraction TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 14,405 EnergyPro 5.1 by EnergySoft User Number: 6712 Run Code: 2010-12-16T09:50:29 ID: Page 71 of 89 ROOM COOLING PEAK LOADS Project Name Date Fitness Building -Tradition Club Assoc. 12/16/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name Cardio/Circuit Time of Peak Jul 3 PM Floor Area 1, 740.0 ft' Outdoor Dry Bulb Temperature 112 OF Indoor Dry Bulb Temperature 76 OF Outdoor Wet Bulb Temperature 79 OF Conduction Area U -Value DETD' Btu/hr X X = X X = X X = X X = X X = X X = X X = X X = X X = Page Total D 1. Design Equivalent Temperature Difference (DETD) Items shown with an asterisk (') denote conduction through an interior surface to another room. Weighting Solar Gain Orientation Area SGF SC Factor Btu/hr Window (S) 3.71 X 0 X 0.434 X 0.000 = 3 X X X = X X X = X X X = X X X = X X X = X X X = X X X = X X X = Page Total 3 Sched. Weighting Internal Gain Frac. Area Heat Gain Factor Btu/hr Li hts 1.00 X 1,740 X 1.609 Watts/Sgft X 3.413 Btu/Watt X 0.999 = 9,547 Occupants 1.00 X 1,740 X 300 Btu/occ. / 50 Sgft/occ. X 1.000 = 10,440 Receptacle 1.00 X 1,740 X 0.500 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 2,969 Process 1.00 X 1,740 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 0 Process Lighting 1.00 X 1,740 X 0.000 Watts/Sgft X 1 3.413 Btu/Watt X 0.0001 = 1 0 Infiltration:[ 1.00 X 1.080 X 1,740 X 15.00 X 0.50 / 60 ] X 36 = 8,453 Schedule Air Sensible Area Ceiling Height ACH AT Fraction TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 36,658 Sched. Latent Gain Frac. Area Heat Gain Btu/hr Occupants 1.00 X 1,740 X 300 Btuh/OCC. / 50 Sgft/occ. = 10,440 Receptacle 1.00 X 1,740 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Process 1.00 X 1,740 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Infiltration:[ 1.00 X 4,840 X 1,740 X 15.00 X 0.50 /60] X 0.00377 = 3,965 Schedule Air Sensible Area Ceiling Height ACH AW Fraction TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 14,405 EnergyPro 5. 1 by EnergySoft User Number: 6712 Run Code: 2010-12-16709:50:29 ID: Pae 72 of 89 r, r1 L, -A ROOM COOLING PEAK LOADS Project Name Date Fitness Building -Tradition Club Assoc. 12/1612010 ROOM INFORMATION DESIGN CONDITIONS Room Name Free Weights Time of Peak Jul 3 PM Floor Area 281.0 ft' Outdoor Dry Bulb Temperature 112 OF Indoor Dry Bulb Temperature 76 OF Outdoor Wet Bulb Temperature 79 OF Conduction Area U -Value DETD' Btu/hr R-38 Roof(R.38.2x12.16) 281.0 X 0.0260 X 27.4 = 200 R-21WaY (W.21.2x6.16) 77.6 X 0.0690 X 31.0 = 166 Double Non Metal Tinted 7.4 X 0.2500 X 29.2 = 54 R-21Wall (W.21.2x6.16) 219.0 X 0.0690 X 31.0 = 469 R-21Wa/l (W.21.2x6.16) 174.0 X 0.0690 X 31.4 = 377 X X = X X = X X = X X = Page Total 1,266 1. Design Equivalent Temperature Difference (DETD) Items shown with an asterisk (') denote conduction through an interior surface to another room. Weighting Solar Gain Orientation Area SGF SC Factor Btu/hr Window (E) 3.71 X 0 X 0.434 X 0.000 = 3 Window (E) 3.7 X 0 X 0.434 X 0.000 = 3 X X X = X X X = X X X = X X X = X X X = X X X = X X X = Page Total 6 Sched. Weighting Internal Gain Frac. Area Heat Gain Factor Btu/hr Li hts 1.00 X 281 X 2.491 Watts/Sgft X 3.413 Btu/Watt X 0.999 = 2,387 Occupants 1.00 X 281 X 300 Btu/occ. / 35 Sgft/occ. X 1.000 = 2,409 Receptacle 1.00 X 281 X 0.500 Watts/Sgtt X 3.413 Btu/Watt X 1.000 = 480 Process 1.00 X 281 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 0 Process Lighting 1.00 X 281 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 0.000 = 0 Infiltration:[ 1.00 X 1.080 X 281 X 8.50 X 0.50 / 60 ] X 36 = 774 Schedule Air Sensible Area Ceiling Height ACH AT Fraction TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 7,320 Sched. Latent Gain Frac. Area Heat Gain Btu/hr Occupants 1.00 X 281 X 300 Btuh/occ. / 35 Sgft/occ. = 2,409 Receptacle 1.00 X 281 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Process 1.00 X 281 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Infiltration:[ 1.00 X 4,840 X 281 X 8.50 X 0.50 /60] X 0.00377 = 363 Schedule Air Sensible Area Ceiling Height ACH AW Fraction TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 2,771 EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2010-12-16709:50:29 ID: Pae 73 of 89 C • ROOM COOLING PEAK LOADS Project Name Date Fitness Building -Tradition Club Assoc. 12/16/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name Relaxation Room Time of Peak Jul 3 PM Floor Area 300.0 ft' Outdoor Dry Bulb Temperature 112 OF Indoor Dry Bulb Temperature 76 OF Outdoor Wet Bulb Temperature 79 OF Conduction Area U -Value DETD' Btu/hr R-38 Roof(R.38.2x12.16) 300.0 X 0.0260 X 27.5 = 214 R-21Wall (W.21.2x6.16) 60.0 X 0.0690 X 31.0 = 128 R-21Wall (W.21.2x6.16) 33.0 X 0.0690 X 31.4 = 71 R-21WaY (W.21.2x6.16) 264.6 X 0.0690 X 31.0 = 567 Double Non Metal Tinted 98.4 X 0.2500 X 29.2 = 717 X X X X = X X X X = Page Total 1,698 1. Design Equivalent Temperature Difference (DETD) Items shown with an asterisk (') denote conduction through an interior surface to another room. Weighting Solar Gain Orientation Area SGF SC Factor Btu/hr Window (N) 98.4 X 0 X 0.434 X 0.000 = 122 X X X = X X X = X X X = X X X = X X X = X X X = X X X = X X X = Page Total 122 Sched. Weighting Internal Gain Frac. Area Heat Gain Factor Btu/hr Lights 1.00 X 300 X 3.267 Watts/Sgft X 3.413 Btu/Watt X 0.999 = 3,342 Occupants 1.00 X 300 X 300 Btu/OCC. / 35 SgfVocc. X 1.000 = 2,571 Receptacle 1.00 X 300 X 0.500 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 512 Process 1.00 X 300 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 0 Process Lighting 1.00 X 300 X 0.000 Watts/Sgft X 3.413 Btu/Watt X1 0.000 = 0 Infiltration:[ 1.00 X 1.080 X 300 X 12.00 X 0.50 / 60 ] X 36 = 1,166 Schedule Air Sensible Area Ceiling Height ACH AT Fraction TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 9,411 Sched. Latent Gain Frac. Area Heat Gain Btu/hr Occupants 1.00 X 300 X 300 Btuh/occ. / 35 Sgft/occ. Receptacle 1.00 X 300 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Process 1.00 X 300 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Infiltration:[ 1.00 X 4,840 X 300 X 12.00 X 0.50 /60] X 0.00377 = 547 Schedule Air Sensible Area Ceiling Height ACH AW Fraction TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 3,118 EnergyPro 5. 1 by EnergySoft User Number. 6712 Run Code: 2010-12-16709:50:29 ID: Page 74 of 89 U C C ROOM COOLING PEAK LOADS Project Name Date Fitness Building -Tradition Club Assoc. 12/16/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name Therapy 1 Time of Peak Jul 3 PM Floor Area 124.0 ft' Outdoor Dry Bulb Temperature 112 OF Indoor Dry Bulb Temperature 76 OF, Outdoor Wet Bulb Temperature 79 OF Conduction Area U -Value DETD' Btu/hr R-38 Roof(R.38.2x12.16) 124.0 X 0.0260 X 27.5 = 89 R-21Wall (W.21.2x6.16) 85.0 X 0.0690 X 31.0 = 182 R-21Wall (W.21.2x6.16) 88.0 X 0.0690 X 31.4 = 191 R-21Wall (W.21.2x6.16) 63.6 X 0.0690 X 31.0 = 136 Double Non Metal Tinted 42.4 X 0.2500 X 29.2 = 309 X X = X X = X X = X X = Page Total 906 1. Design Equivalent Temperature Difference (DETD) Items shown with an asterisk (') denote conduction through an interior surface to another room. Weighting Solar Gain Orientation Area SGF SC Factor Btu/hr Window (N) 42.41 X 0 X 0.434 X 0.000 = 53 X X X = X X X = X X X = X X X = X X X = X X X = X X X = X X X = Page Total 53 Sched. Weighting Internal Gain Frac. Area Heat Gain Factor Btu/hr Li hts 1.00 X 124 X 1.258 Watts/Sgft X 3.413 Btu/Watt X 0.999 = 532 Occupants 1.00 X 124 X 300 Btu/occ. / 1 50 Sgft/occ. X 1.000 = 744 Receptacle 1.00 X 124 X 0.500 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 212 Process 1.00 X 124 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 0 Process Lighting 1.00 X 124 X 0.000 Watts/Sgft X 1 3.413 Btu/Watt X1 0.000 = 0 Infiltration:[ 1.00 X 1.080 X 124 X 8.80 X 0.50 160 ] X 36 = 353 Schedule Air Sensible Area Ceiling Height ACH AT Fraction TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 2,800 Sched. Latent Gain Frac. Area Heat Gain Btu/hr Occupants 1.00 X 124 X 300 Btuh/OCC. / 50 Sgtt/occ. = 744 Rece tacle 1.00 X 124 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Process 1.00 X 124 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Infiltration:[ 1.00 X 4,840 X 124 X 8.80 X 0.50 /60] X 0.00377 = 166 Schedule Air Sensible Area Ceiling Height ACH AW Fraction TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 910 EnergyPro 5.1 by EnergySoft User Number. 6712 Runcode: 2010-12-16709:50:29 ID: Pae 75 of 89 • • • ROOM COOLING PEAK LOADS Project Name Date Fitness Building -Tradition Club Assoc. 12/16/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name Therapy 2 Time of Peak Jul 3 PM Floor Area 112.0 ft' Outdoor Dry Bulb Temperature 112 OF Indoor Dry Bulb Temperature 76 OF Outdoor Wet Bulb Temperature 79 OF Conduction Area U -Value DETD' Btu/hr R-38 Roof(R.38.2x12.16) 112.0 X 0.0260 X 27.5 = 80 R-21Wa11 (W.21.2x6.16) 40.0 X 0.0690 X 31.0 = 85 R-21Wall (W.21.2x6.16) 63.6 X 0.0690 X 31.0 = 136 Double Non Metal Tinted 42.4 X 0.2500 X 29.2 = 309 X X = X X = X X = X X = X X = Page Total 611 1. Design Equivalent Temperature Difference (DETD) Items shown with an asterisk (") denote conduction through an interior surface to another room. Weighting Solar Gain Orientation Area SGF SC Factor Btu/hr Window (N) 42.4 X 0 X 0.434 X 0.000 = 53 X X X = X X X = X X X = X X X = X X X = X X X = X X X = X X X = Page Total 53 Sched. Weighting Internal Gain Frac. Area Heat Gain Factor Btu/hr Li hts 1.00 X 112 X 1.393 Watts/Sgft X 3.413 Btu/Watt X 0.999 = 532 Occupants 1.00 X 112 X 300 Btu/OCC. / 50 Sgft/occ. X 1.000 = 672 Receptacle 1.00 X 112 X 0.500 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 191 Process 1.00 X 112 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 0 Process Lighting 1.00 X 112 X 0.000 Watts/Sgft X 3.413 Btu/Watt X1 0.000 = 0 Infiltration:[ 1.00 X 1.080 X 112 X 8.80 X 0.50 / 60 ] X 36 = 319 Schedule Air Sensible Area Ceiling Height ACH AT Fraction TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 2,378 Sched. Latent Gain Frac. Area Heat Gain Btu/hr Occupants 1.00 X 112 'X 300 Btuh/occ. / 50 Sgft/occ. = 672 Receptacle 1.00 X 112 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Process 1.00 X 112 X 0.000 Watts/Sgft X 3.413 Btu/Waft = 0 Infiltration:[ 1.00 X 4,840 X 112 X 8.80 X 0.50 /60] X 0.00377 = 150 Schedule Air Sensible Area Ceiling Height ACH AW Fraction TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 822 EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2010-12-16709:50:29 ID: Pae 76 of 89 LJ • C ROOM COOLING PEAK LOADS Project Name Date Fitness Building -Tradition Club Assoc. 12/16/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name Foyer/Reception Time of Peak Jul 3 PM Floor Area 643.0 ft' Outdoor Dry Bulb Temperature 112 OF Indoor Dry Bulb Temperature 76 OF, Outdoor Wet Bulb Temperature 79 OF Conduction Area U -Value DETD' Btu/hr R-38 Roof(R.38.2x12.16) 643.0 X 0.0260 X 27.5 = 460 R-21Wall (W.21.2x6.16) 352.6 X 0.0690 X 31.0 = 753 Double Non Metal Tinted 58.4 X 0.2500 X 29.2 = 426 Double Non Metal Tinted 28.0 X 0.2500 X 29.2 = 204 X X = X X = X X = X X = X X = Page Total 1,843 1. Design Equivalent Temperature Difference (DETD) Items shown with an asterisk (') denote conduction through an interior surface to another room. Weighting Solar Gain Orientation Area SGF SC Factor Btu/hr window (S) 20.4 X 0 X 0.434 X 0.000 = 16 Window (S) 8.8 X 0 X 0.434 X 0.000 = 7 Window (S) 28.0 X 0 X 0.434 X 0.000 = 23 Window (S) 8.8 X 0 X 0.434 X 0.000 = 7 Window (S) 20.41 X 0 X 0.434 X 0.000 = 16 X X X = X X X = X X X = X X X = Page Total 69 Sched. Weighting Internal Gain Frac. Area Heat Gain Factor Btu/hr Li hts 1.00 X 643 X 3.994 Watts/Sgft X 3.413 Btu/Watt X 0.999 = 8,756 Occupants 1.00 X 643 X 300 Btu/OCC. / 100 SgfUOCc. X 1.000 = 1,929 Receptacle 1.00 X 643 X 0.500 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 1,097 Process 1.00 X 643 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 0 Process Lighting 1.00 X 643 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 0.000 = 0 Infiltration:[ 1.00 X 1.080 X 643 X 16.00 X 0.50 / 60 ] X 36 = 3,332 Schedule Air Sensible Area Ceiling Height ACH AT Fraction TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 17,027 Sched. Latent Gain Frac. Area Heat Gain Btu/hr Occupants 1.00 X 643 X 300 Btuh/occ. / 100 SgfUocc. = 1,929 Receptacle 1.00 X 643 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Process 1.00 X 643 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Infiltration:[ 1.00 X 4,840 X 643 X 16.00 X 0.50 /60] X 0.00377 = 1,563 Schedule Air Sensible Area Ceiling Height ACH OW Fraction TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 3,492 EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2010-12-16709:50:29 ID: Pae 77 of 89 • ROOM COOLING PEAK LOADS Project Name Date Fitness Building -Tradition Club Assoc. 712/16/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name Men's Locker Room Time of Peak Jul 3 PM Floor Area 563.0 ft' Outdoor Dry Bulb Temperature 112 OF Indoor Dry Bulb Temperature 76 IF, Outdoor Wet Bulb Temperature 79 OF Conduction Area U -Value DETD' Btu/hr R-38 Roof(R.38.2x12.16) 563.0 X 0.0260 X 27.5 = 402 R-21Wa/l (W.21.2x6.16) 197.6 X 0.0690 X 31.4 = 428 Double Non Metal.T/nted 3.4 X 0.2500 X 29.2 = 25 R-21Wall (W.21.2x6.16) 183.0 X 0.0690 X 31.0 = 392 X X X X X X X X X X = Page Total 1,247 1. Design Equivalent Temperature Difference (DETD) Items shown with an asterisk (") denote conduction through an interior surface to another room. Weighting Solar Gain Orientation Area SGF SC Factor Btu/hr Window (VV) 3.41 X 0 X 0.434 X 0.000 = 14 X X X X X X X X X X X X X X X X X X = X X X X X X Page Total 14 Sched. Weighting Internal Gain Frac. Area Heat Gain Factor Btu/hr Li hts 1.00 X 563 X 1.837 Watts/Sgft X 3.413 Btu/Watt X 0.999 = 3,526 Occupants 1.00 X 563 X 300 Btu/occ. / 35 SgfUocc. X 1.000 = 4,826 Receptacle 1.00 X 563 X 0.500 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 961 Process 1.00 X 563 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 0 Process Lighting 1.00 X 563 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 0.000 = 0 Infiltration:[ 1.00 X 1.080 X 563 X 10.30 X 0.50 / 60 ] X 36 = 1,878 Schedule Air Sensible Area Ceiling Height ACH AT Fraction TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 12,452 Sched. Latent Gain Frac. Area Heat Gain Btu/hr Occupants 1.00 X 563 X 300 Btuh/occ. / 35 SgfUocc. = 4,826 Receptacle 1.00 X 563 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Process 1.00 X 563 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Infiltration:[ 1.00 X 4,840 X 563 X 10.30 X 0.50 /60] X 0.00377 = 881 Schedule Air Sensible Area Ceiling Height ACH AW Fraction TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 5,707 EnergyPro, 5.1 by EnergySoft User Number: 6712 RunCode: 2010-12-16709:50:29 ID: Pae 78 of 89 1 1 LJ • • ROOM COOLING PEAK LOADS Project Name Date Fitness Building -Tradition Club Assoc. 12/16/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name Women's Locker Room Time of Peak Jul 3 PM Floor Area 660.0 ft' Outdoor Dry Bulb Temperature 112 OF Indoor Dry Bulb Temperature 76 OF Outdoor Wet Bulb Temperature 79 OF Conduction Area U -Value DETD' Btu/hr R-38 Roof(R.38.2x12.16) 660.0 X 0.0260 X 27.4 = 470 R -21W611 (W.21.2x6.16) 305.2 X 0.0690 X 31.0 = 652 Double Non Metal Tinted 10.2 X 0.2500 X 29.2 = 74 R-21 Wall (W.21.2x6.16) 185.0 X 0.0690 X 31.0 = 395 R-21 Wall (W.21.2x6.16) 279.6 X 0.0690 X 31.4 = 606 X X = X X = X X = X X = Page Total 2,197 1. Design Equivalent Temperature Difference (DETD) Items shown with an asterisk (') denote conduction through an interior surface to another room. Weighting Solar Gain Orientation Area SGF SC Factor Btu/hr Window (S) 3.4 X 0 X 0.434 X 0.000 = 3 Window (S) 3.4 X 0 X 0.434 X 0.000 = 3 14rindow (V1,9 3.4 X 0 X 0.434 X 0.000 = 14 X X X = X X X = X X X = X X X = X X X = X X X = Page Total 20 Sched. Weighting Internal Gain Frac. Area Heat Gain Factor Btu/hr Lights 1.00 X 660 X 1.167 Watts/Sgft X 3.413 Btu/Watt' X 0.999 = 2,625 Occupants 1.00 X 660 X 300 Btu/occ. / 35 Sgft/occ. X 1.000 = 5,657 Receptacle 1.00 X 660 X 0.500 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 1,126 Process 1.00 X 660 X 0.000 Watts/Sgft X 3.413 Btu/Waft X 1.000 = 0 Process Lighting 1.00 X 660 X 0.000 Wafts/Sgft X 3.413 Btu/Watt X 0.0001 = 0 Infiltration:[ 1.00 X 1.080 X 660 X 10.30 X 0.50 / 60 X 36 = 2,202 Schedule Air Sensible Area Ceiling Height ACH AT Fraction TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 13,828 Sched. Latent Gain Frac. Area Heat Gain Btu/hr Occupants 1.00 X 660 X 300 Btuh/occ. / 35 SgfUocc. = 5,657 Receptacle 1.00 X 660 X 0.000 Watts/Sgft X 3.413 Btu/Waft = 0 Process 1.00 X 660 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Infiltration:[ 1.00 X 4,840 X 660 X 10.30 X 0.50 /60] X 0.00377 = 1,033 Schedule Air Sensible Area Ceiling Height ACH AW Fraction TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 6,690 EnergyPro, 5.1 by EnergySoft User Number: 6712 RunCode: 2010-12-16709:50:29 ID: Page 79 of 89 U • C ROOM COOLING COIL LOADS Projdct Name Date Fitness Building -Tradition Club Assoc. 12/16/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name Yoga Time of Peak Jul 3 PM Floor Area 673.0 ft2 Outdoor Dry Bulb Temperature _ 112 OF Indoor Dry Bulb Temperature 76 OF Outdoor Wet Bulb Temperature 79 OF Conduction Area U -Value DETD' Btu/hr R-38 Roof(R.38.2x12.16) 673.0 X 0.0260 X 27.4 = 479 R-21Wa/l (W.21.2x6.16) 232.0 X 0.0690 X 31.0 = 496 Double Non Metal Tinted 32.0 X 0.2500 X 29.2 = 233 R-21Wall (W.21.2x6.16) 62.0 X 0.0690 X 31.0 = 132 R-21Wall (W.21.2x6.16) 248.0 X 0.0690 X 31.4 = 537 R-21Wall (W.21.2x6.16) 200.0 X 0.0690 X 31.0 = 428 X X = X X = X X = Page Total 2,306 1. Design Equivalent Temperature Difference (DETD) Items shown with an asterisk (') denote conduction through an interior surface to another room. Weighting Solar Gain Orientation Area SGF SC Factor Btu/hr 8 (E) 16.0 X 0 X 0.434 X 0.000 = 13 8 (S) 16.0 X 0 X 0.434 X 0.000 = 13 X X X = X X X = X X X = X X X = X X X = X X X = X X X = Page Total 26 Sched. Weighting Internal Gain Frac. Area Heat Gain Factor Btu/hr Lights 1.00 X 673 X 1.004 Watts/Sgft X 3.413 Btu/Watt X 0.999 = 2,305 Occupants 1.00 X 673 X 300 Btu/OCC. / 35 Sqf /occ. X 1.000 = 5,769 Receptacle 1.00 X 673 X 0.500 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 1,148 Process 1.00 X 673 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 0 Process Lighting 1.00 X 673 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 0.000 = 0 Infiltration:[ 1.00 X 1.080 X 673 X 10.00 X 0.50 / 60 ] X 36 = 2,180 Schedule Air Sensible Area Ceiling Height ACH AT Fraction TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 13,734 Sched. Latent Gain Frac. Area Heat Gain Btu/hr Occupants 1.00 X 673 X 300 Btuh/occ. / 35 Sgft/occ. = 5,769 Receptacle 1.00 X 673 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Process 1.00 X 673 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Infiltration:[ 1.00 X 4,840 X 673 X 10.00 X 0.50 /60] X 0.00377 = 1,023 Schedule Air Sensible Area Ceiling Height ACH AW Fraction TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 6,791 EnergyPro 5.1 by EnergySoft User Number. 6712 Run Code: 2010-12-16T09:50:29 ID: Page 80 of 89 • I ROOM COOLING COIL LOADS I Projdct Name Date Fitness Building -Tradition Club Assoc. 12/16/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name Cardio/Circuit Time of Peak Jul 3 PM Floor Area 1, 740.0 ft' Outdoor Dry Bulb Temperature 112 OF Indoor Dry Bulb Temperature 76 OF Outdoor Wet Bulb Temperature 79 OF Conduction R-38 Roof(R.38.2x12.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) Double Non Metal Tinted Double Non Metal Tinted R-21Wall (W..21.2x6.16) R-21Wa11 (W.21.2x6.16) X X X X X X X X X U -Value X X X X X X X X X DETD' = = = = = = = = = 0.0260 27.5 0.0690 31.0 0.0690 31.0 0.2500 29.2 0.2500 29.2 0.0690 31.4 0.0690 31.0 1. Design Equivalent Temperature Difference (DETD) Items shown with an asterisk (') denote conduction through an interior surface to another room. Rnlar Cain Window Window Window Window Window Window Window Window Window Oriantatinn (S) (S) (S) (S) (S) (S) (S) (S) (S) Page Total Btu/hr 1,244 81 983 1,703 162 377 493 1 5,0431 Area 58.4 58.4 58.4 58.4 3.7 3.7 3.7 3.7 3.7 X X X X X X X X X SGF X X X X X X X X X SC 0.434 0.434 0.434 0.434 0.434 0.434 0.434 0.434 0.4341 X X X X X X X X X Weighting Factor 0.000 = 0.000 = 0.000 = 0.000 = 0.000 = 0.000 = 0.000 = 0.000 = 0.000 = 0 0 0 0 0 0 0 0 01 Page Total Btu/hr 47 47 47 47 3 3 3 3 3 203 Sched. Weighting Internal Gain Frac. Area . Heat Gain Factor Btu/hr Lights 1.00 X 1,740 X 1.609 Watts/Sgft X 3.413 Btu/Watt X 0.999 = 9,547 Occupants 1.00 X 1,740 X 300 Btu/occ. / 50 Sgf /occ. X 1.000 = 10,440 Receptacle 1.00 X 1,740 X 0.500 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 2,969 Process 1.00 X 1,740 X 0.000 Watts/Sgft X 3.413 Btu[Watt X 1.000 = 0 Process Lighting 1.00 X 1,740 X 0.000 Watts/Sgft X 3.413 Btu/Watt X1 0.000 = 1 0 Infiltration:[ 1.00 X 1.080 X 1,740 X 15.00 X 0.50 / 60 ] X 36 = 8,453 Schedule Air Sensible Area Ceiling Height ACH AT Fraction TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 36,658 Sched. Latent Gain Frac. Area Heat Gain Btu/hr Occupants 1.00 X 1,740 X 300 Btuh/occ. / 50 Sgtt/occ. = 10,440 Receptacle 1.00 X 1,740 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Process 1.00 X 1,740 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Infiltration:[ 1.00 X 4,840 X 1,740 X 15.00 X 0.50 /60] X 0.00377 = 3,965 • Schedule Air Sensible Area Ceiling Height ACH AW Fraction TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 14,405 EnerovPro 5.1 by EnerovSoft User Number. 6712 Run Code: 2010-12-16709:50:29 ID: Page 81 of 89 U • ROOM COOLING COIL LOADS Projdtt Name Date .Fitness Building -Tradition Club Assoc. 12/16/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name Cardio/Circuit Time of Peak Jul 3 PM Floor Area 1,740.0 ft-' Outdoor Dry Bulb Temperature 112 OF Indoor Dry Bulb Temperature 76 OF Outdoor Wet Bulb Temperature 79 OF Conduction Area U -Value DETD' Btu/hr X X = X X = X X = X X = X X = X X = X X = X X = X X = Page Total 0 1. Design Equivalent Temperature Difference (DETD) Items shown with an asterisk (') denote conduction through an interior surface to another room. Weighting Solar Gain Orientation Area SGF SC Factor Btu/hr Window (S) 3.71 X 0 X 0.434 X 0.000 = 3 X X X = X X X = X X X = X X X = X X X = X X X = X X X = X X X = Page Total 3 Sched. Weighting Internal Gain Frac. Area Heat Gain Factor Btu/hr Lights 1.00 X 1,740 X 1.609 Watts/Sgft X 3.413 Btu/Watt X 0.999 = 9,547 Occupants 1.00 X 1,740 X 300 Btu/occ. / 50 Sgft/occ. X 1.000 = 10,440 Receptacle 1.00 X 1,740 X 0.500 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 2,969 Process 1.00 X 1,740 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 0 Process Lighting 1.00 X 1,740 X 0.0001 Watts/Sgft X 3.413 BtuMatt X 0.0001 = 1 0 Infiltration:[ 1.00 X 1.080 X 1,740 X 15.00 X 0.50 / 60 ] X 36 = 8,453 Schedule Air Sensible Area Ceiling Height ACH AT Fraction TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 36,658 Sched. Latent Gain Frac. Area Heat Gain Btu/hr Occupants 1.00 X 1,740 X 300 Btuh/oCC. / 50 Sgft/oCC. = 10,440 Receptacle 1.00 X 1,740 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Process 1.00 X 1,740 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Infiltration:[ 1.00 X 4,840 X 1,740 X 15.00 X 0.50 /60] X 0.00377 = 3,965 Schedule Air Sensible Area Ceiling Height ACH AW Fraction TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 14,405 Ene Pro 5.1 b Ene Soft User Number: 6712 RunCode: 2010-12-16T09:50:29 ID: Page 82 of 89 U • • ROOM COOLING COIL LOADS ProjEct Name71211612010 ate Fitness Building -Tradition Club Assoc. ROOM INFORMATION DESIGN CONDITIONS Room Name Free Weights Time of Peak Jul 3 PM Floor Area 281.0 ft' Outdoor Dry Bulb Temperature 112 OF Indoor Dry Bulb Temperature 76 OF Outdoor Wet Bulb Temperature 79 OF Conduction Area U -Value DETD' Btu/hr R-38 Roof(R.38.2x12.16) 281.0 X 0.0260 X 27.4 = 200 R-21Wa11 (W.21.2x6.16) 77.6 X 0.0690 X 31.0 = 166 Double Non Metal Tinted 7.4 X 0.2500 X 29.2 = 54 R-21Wall (W.21.2x6.16) 219.0 X 0.0690 X 31.0 = 469 R-21Wa/l (W.21.2x6.16) 174.0 X 0.0690 X 31.4 = 377 X X = X X = X X = X X = Page Total 1,266 1. Design Equivalent Temperature Difference (DETD) Items shown with an asterisk (') denote conduction through an interior surface to another room. Weighting Solar Gain Orientation Area SGF SC Factor Btu/hr Window (E) 3.7 X 0 X 0.434 X 0.000 = 3 IMndow (E) 3.7 X 0 X 0.434 X 0.000 = 3 X X X = X X X = X X X = X X X = X X X = X X X = X X X = Page Total 6 Sched. Weighting Internal Gain Frac. Area Heat Gain Factor Btu/hr Lights 1.00'X 281 X 2.491 Watts/Sgft X 3.413 Btu/Watt X 0.999 = 2,387 Occupants 1.00 X 281 X 300 Btu/OCC. / 35 Sgft/occ. X 1.000 = 2,409 Receptacle 1.00 X 281 X 0.500 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 480 Process 1.00 X 281 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 0 Process Lighting 1.00 X 281 X 0.000 Watts/Sgft X 3.413 Btu[Watt X Infiltration:[ 1.00 X 1.080 X 281 X 8.50 X 0.50 / 60 ] X 36 = 774 Schedule Air Sensible Area Ceiling Height ACH AT Fraction TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 7,320 Sched. Latent Gain Frac. Area Heat Gain Btuihr Occupants 1.00 X 281 X 300 Btuh/occ. / 35 Sgft/occ. = 2,409 Receptacle 1.00 X 281 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Process 1.00 X 281 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Infiltration:[ 1.00 X 4,840 X 281 X 8.50 X 0.50 /60] X 0.00377 = 363 Schedule Air Sensible Area Ceiling Height ACH AW Fraction TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 2,7711 EnergyPro 5.1 by EnergySoft User Number: 6712 Run Code: 2010-12-16709:50:29 ID: Page 83 of 89 • ROOM COOLING COIL LOADS Project Name Date Fitness Building -Tradition Club Assoc. 12/16/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name Relaxation Room Time of Peak Jul 3 PM Floor Area 300.0 ft' Outdoor Dry Bulb Temperature 112 OF Indoor Dry Bulb Temperature 76 OF Outdoor Wet Bulb Temperature 79 OF Conduction Area U -Value DETD' Btu/hr R-38 Roof(R.38.2x12.16) 300.0 X 0.0260 X 27.5 = 214 R-21 Wall (W.21.2x6.16) 60.0 X 0.0690 X 31.0 = 128 R-21 Wall (W.21.2x6.16) 33.0 X 0.0690 X 31.4 = 71 R-21Wall (W.21.2x6.16) 264.6 X 0.0690 X 31.0 = 567 Double Non Metal Tinted 98.4 X 0.2500 X 29.2 = 717 X X = X X = X X = X X = Page Total 1,698 1. Design Equivalent Temperature Difference (DETD) Items shown with an asterisk (') denote conduction through an interior surface to another room: Weighting Solar Gain Orientation Area SGF SC Factor Btu/hr Window (N) 98.41 X 0 X 0.434 X 0.000 = 122 X X X = X X X = X X X = X X X = X X X = X X X = X X X EE = X X X = Page Total 122 Sched. Weighting Internal Gain Frac. Area Heat Gain Factor Btu/hr Li hts 1.00 X 300 X 3.267 Watts/Sgft X 3.413 Btu/Watt X 0.999 = 3,342 Occupants 1.00 X 300 X 300 Btu/occ. / 35 SgfUocc. X 1.000 = 2,571 Receptacle 1.00 X 300 X 0.500 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 512 Process 1.00 X 300 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 0 Process Lighting 1.00 X 300 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 0.0001 = 1 0 Infiltration:[ 1.00 X 1.080 X 300 X 12.00 X 0.50 / 60 X 36 = F771,j66 Schedule Air Sensible Area Ceiling Height ACH AT Fraction TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 9,411 Sched. Latent Gain Frac. Area Heat Gain Btu/hr Occupants 1.00 X 300 X 300 Btuh/OCC. / 35 SgfVocc. Receptacle 1.00 X 300 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Process 1.00 X 300 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Infiltration:[ 1.00 X 4,840 X 300 X 12.00 X 0.50 /60] X 0.00377 = 547 Schedule Air Sensible Area Ceiling Height ACH AW Fraction TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 3,118 EnergyPro 5.1 by EnergySoft User Number: 6712 Run Code: 2010-12-16709:50:29 ID: Page 84 of 89 0 ROGM COOLING COIL LOADS Project Namete Da Fitness Building -Tradition Club Assoc. 12/16/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name Therapy 1 Time of Peak Jul 3 PM Floor Area 124.0 ft' Outdoor Dry Bulb Temperature 112 OF Indoor Dry Bulb Temperature 76 °F Outdoor Wet Bulb Temperature 79 OF Conduction Area U -Value DETD' Btu/hr R-38 Roof(R.38.2x12.16) 124.0 X 0.0260 X 27.5 = 89 R-21Wall (W.21.2x6.16) 85.0 X 0.0690 X 31.0 = 182 R-21 MY (W.21.2x6.16) 88.0 X 0.0690 X 31.4 = 191 R-21Wall (W.21.2x6.16) 63.6 X 0.0690 X 31.0 = 136 Double Non Metal Tinted 42.4 X 0.2500 X 29.2 = 309 X X - X X = X X = X X = Page Total 906 1. Design Equivalent Temperature Difference (DETD) Items shown with an asterisk (') denote conduction through an interior surface to another room. Weighting Solar Gain Orientation Area SGF Sc Factor Btu/hr Window (N) 42.4 X 0 X 0.434 X 0.000 = 53 X X X = X X X = X X X = X X X = X X X = X X X = X X X = X X X = Page Total 53 Sched. Weighting Internal Gain Frac. Area Heat Gain Factor Btu/hr Lights 1.00 X 124 X 1.258 Watts/Sgft X 3.413 Btu/Watt X 0.999 = 532 Occupants 1.00 X 124 X 300 Btu/OCC. / 50 Sqft/occ. X 1.000 = 744 Receptacle 1.00 X 124 X 0.500 Watts/Soft X 3.413 Btu/Watt X 1.000 = 212 Process 1.00 X 124 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 0 Process Lighting 1.00 X 124 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 0.000 = 0 Infiltration:[ 1.00 X 1.080 X 124 X 8.80 X 0.50 / 60 ] X 36 = 353 Schedule Air Sensible Area Ceiling Height ACH AT Fraction TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM Z800 Sched. Latent Gain Frac. Area Heat Gain Btu/hr Occupants 1.00 X 124 X 300 Btuh/occ. / 50 SgfVocc. = 744 Receptacle 1.00 X 124 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Process 1.00 X 124 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Infiltration:[ 1.00 X 4,840 X 124 X 8.80 X 0.50 /60] X 0.00377 = 166 Schedule Air Sensible Area Ceiling Height ACH AW Fraction TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 910 EnergyPro 5. 1 by EnergySoft User Number: 6712 Run Code: 2010-12-16709:50:29 ID: Page 85 of 89 • 0 ROGM COOLING COIL LOADS Project Name Date Fitness Building -Tradition Club Assoc. 12/16/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name Therapy 2 Time of Peak Jul 3 PM Floor Area 112.0 ft' Outdoor Dry Bulb Temperature 112 OF Indoor Dry Bulb Temperature 76 OF Outdoor Wet Bulb Temperature 79 OF Conduction Area U -Value DETD' Btu/hr R-38 Roof(R.38.2x12.16) 112.0 X 0.0260 X 27.5 = 80 R-21Wall (W.21.2x6.16) 40.0 X 0.0690 X 31.0 = 85 R-21Wa/1 (W.21.2x6.16) 63.6 X 0.0690 X 31.0 = 136 Double Non Metal Tinted 42.4 X 0.2500 X 29.2 = 309 X X = X X = X X = X X = X X = Page Total 611 1. Design Equivalent Temperature Difference (DETD) Items shown with an asterisk (') denote conduction through an interior surface to another room. Weighting Solar Gain Orientation Area SGF SC Factor Btu/hr Window (N) 42.4 X 0 X 0.434 X 0.000 = 53 X X X = X X X = X X X = X X X = X X X = X X X = X X X = X X X = Page Total 53 Sched. Weighting Internal Gain Frac. Area Heat Gain Factor Btu/hr Li hts 1.00 X 112 X 1.393 Watts/Sgft X 3.413 Btu/Watt X 0.999 = 532 Occupants 1.00 X 112 X 300 Btu/OCC. / 50 Sgft/occ. X 1.000 = 672 Receptacle 1.00 X 112 X 0.500 Watts/Sgft X 3.413 Btu[Waft X 1.000 = 191 Process 1.00 X 112 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 0 Process Lightinq 1.00 X 112 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 0.0001 = 1 0 Infiltration:[ 1.00 X 1.080 X 112 X 8.80 X 0.50 / 60 ] X 36 = 319 Schedule Air Sensible Area Ceiling Height ACH AT Fraction TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 2,378 Sched. Latent Gain Frac. Area Heat Gain Btu/hr Occupants 1.00 X 112 X 300 Btuh/occ. / 50 Sgft/occ. = 672 Receptacle 1.00 X 112 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Process 1.00 X 112 X 0.000 Watts/Sgft X 3.413 Btu/Waft = 0 Infiltration:[ 1.00 X 4,840 X 112 X 8.80 X 0.50 /60] X 0.00377 = 150 Schedule Air Sensible Area Ceiling Height ACH AW Fraction TOTAL HOURLY LATENT HEAT GAIN FOR.ROOM 822 EnergyPro 5. 1 by EnergySoft User Number. 6712 RunCode: 2010-12-16709:50:29 ID: Page 86 of 89 • C ROOM COOLING COIL LOADS Project Name Date Fitness Building -Tradition Club Assoc. 12/16/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name Foyer/Reception Time of Peak Jul 3 PM Floor Area 643.0 ft' Outdoor Dry Bulb Temperature 112 OF Indoor Dry Bulb Temperature 76 OF. Outdoor Wet Bulb Temperature 79 OF Conduction Area U -Value DETD' Btu/hr R-38 Roof(R.38.2x12.16) 643.0 X 0.0260 X 27.5 = 460 R-21Wall (W.21.2x6.16) 352.6 X 0.0690 X 31.0 = 753 Double Non Metal Tinted 58.4 X 0.2500 X 29.2 = 426 Double Non Metal Tinted 28.0 X 0.2500 X 29.2 = 204 X X = X X = X X = X X = X X = Page Total 1,843 1. Design Equivalent Temperature Difference (DETD) Items shown with an asterisk (') denote conduction through an interior surface to another room. Weighting Solar Gain Orientation Area SGF SC Factor Btu/hr Window (S) 20.41 X 0 X 0.434 X 0.000 = 16 Window (S) 8.8 X 0 X 0.434 X 0.000 = 7 Window (S) 28.0 X 0 X 0.434 X 0.000 = 23 Window (S) 8.8 X 0 X 0.434 X 0.000 = 7 Window (S) 20.4 X 0 X 0.434 X 0.000 = 16 X X X = X X X = X X X = X X X = Page Total 69 Sched. Weighting Internal Gain Frac. Area Heat Gain Factor Btu/hr Lights 1.00 X 643 X 3.994 Watts/Sgft X 3.413 Btu/Watt X 0.999 = 8,756 Occupants 1.00 X 643 X 300 Btu/occ. / 100 Sqf /occ. X 1.000 = 1,929 Receptacle 1.00 X 643 X 0.500 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 1,097 Process 1.00 X 643 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 0 Process Lighting 1.00 X 1 643 X 0.0001 Watts/Sgft X 3.413 Btu/Watt X Infiltration:[ 1.00 X 1.080 X 643 X 16.00 X 0.50 / 60 ] X 36 = 3,332 Schedule Air Sensible Area Ceiling Height ACH AT Fraction TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 17,027 Sched. Latent Gain Frac. Area Heat Gain Btu/hr Occupants 1.00 X 643 X 300 Btuh/occ. / 100 SgtVocc. Receptacle 1.00 X 643 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Process 1.00 X 643 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Infiltration:[ 1.00 X 4,840 X 643 X 16.00 X 0.50 /60] X 0.00377 = 1,563 Schedule Air Sensible Area Ceiling Height ACH AW Fraction TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 3,492 EnergyPro 5.1 by EnergySoft User Number. 6712 RunCode: 2010-12-16709:50:29 ID: Page 87 of 89 C ROOM COOLING COIL LOADS Project Name Date Fitness Building -Tradition Club Assoc. 12/16/2010 ROOM INFORMATION DESIGN CONDITIONS Room Name Men's Locker Room Time of Peak Jul 3 PM Floor Area 563.0 ft' Outdoor Dry Bulb Temperature 112 OF Indoor Dry Bulb Temperature 76 OF. Outdoor Wet Bulb Temperature 79 OF Conduction Area U -Value DETD' Btu/hr R-38 Roof(R.38.2x12.16) 563.0 X 0.0260 X 27.5 = 402 R-21Wall (W.21.2x6.16) 197.6 X 0.0690 X 31.4 = 428 Double Non Metal Tinted 3.4 X 0.2500 X 29.2 = 25 R-21Wall (W.21.2x6.16) 183.0 X 0.0690 X 31.0 = 392 X X X X X X X X X X = Page Total 1,247 1. Design Equivalent Temperature Difference (DETD) Items shown with an asterisk (') denote conduction through an interior surface to another room. Weighting Solar Gain Orientation Area SGF SC Factor Btu/hr Window 3.41 X 0 X 0.434 X 0.000 = 14 X X X = X X X = X X X = X X X = X X X X X X X X X = X X X = Page Total 14 Sched. Weighting Internal Gain Frac. Area Heat Gain Factor Btu/hr Li hts 1.00 X 563 X 1.837 Watts/Sgft X 3.413 Btu/Watt X 0.999 = 3,526 Occupants 1.00 X 563 X 300 Btu/occ. / 35 SgfUocc. X 1.000 = 4,826 Receptacle 1.00 X 563 X 0.500 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 961 Process 1.00 X 563 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 1.000 = 0 Process Lighting 1.00 X 563 X 0.000 Watts/Sgft X 3.413 Btu/Watt X 0.0001 = 1 0 Infiltration:[ 1.00 X 1.080 X 563 X 10.30 X 0.50 / 60 ] X 36 = 1,878 Schedule Air Sensible Area Ceiling Height ACH AT Fraction TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 12,452 Sched. Latent Gain Frac. Area Heat Gain Btu/hr Occupants 1.00 X 563 X 300 Btuh/OCC. / 35 Sqf /occ. = 4,826 Receptacle 1.00 X 563 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Process 1.00 X 563 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Infiltration:[ 1.00 X 4,840 X 563 X 10.30 X 0.50 /60] X 0.00377 = 881 Schedule Air Sensible Area Ceiling Height ACH AW Fraction TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 5,707 EnergyPro 5. 1 by EnergySoft User Number: 6712 RunCode: 2010-12-16709:50:29 ID: Page 88 of 89 I ROOM COOLING COIL LOADS I Fitness Building -Tradition Club Assoc. ROOM INFORMATION DESIGN CONDITIONS Room Name Women's Locker Room Time of Peak Floor Area 660.0 ft' Outdoor Dry Bulb Temperature Indoor Dry Bulb Temperature 76 OF Outdoor Wet Bulb Temperature Conduction Area U -Value DETD' R-38 Roof(R.38.2x 12.16) R-21 Wall (W.21.24.16) Double Non Metal Tinted R-21WaY (W..21.2x6.16) R-21Wall (W..21.2x6.16) X X X X X X X X X 0.0260 X X X X X X X X X 27.4 = = = = = = = = = 0.0690 31.0 0.2500 29.2 0.0690 31.0 0.0690 31.4 0.000 1. Design Equivalent Temperature Difference (DETD) Items shown with an asterisk (`) denote conduction through an interior surface to another room. Solar Gain Window Window Orientation (S) Page Total 12/16/2010 Jul 3 PM 112 OF 79 OF Btu/hr 470 652 74 395 606 1 2,1971 Area X X X X X X X X X SGF Sc 0 X 0.434 X 0 X 0.434 X 0 X 0.434 X X X X X X X X X X X X X Weighting Factor = = = = = = = = = Btu/hr 3.41 0.000 3.4 0.000 3.4 0.000 Page Total 3 3 14 20 Sched. Weighting Internal Gain Frac. Area Heat Gain Factor Btu/hr Lights 1.00 X 660 X 1.167 Watts/Sgft X 3.413 Btu/Watt X 0.999 = 2,625 Occupants 1.00 X 660 X 300 Btu/OCC. / 35 Sqft/occ. X 1.000 = 5,657 Receptacle 1.00 X 660 X 0.500 Watts/Sgft X 3.413 Btu[Watt X 1.000 = 1,126 Process 1.00 X 660 X 0.000 Watts/Sgft X 3.413 Btu/Watt X .1.000 = 0 Process Lighting 1.00 X 660 X 0.000 Watts/Sgft X 1 3.413 Btu/Watt X 0.000 = 0 Infiltration:[ 1.00 X 1.080 X 660 X 10.30 X 0.50 / 60 ] X 36 = 2,202 Schedule Air Sensible Area Ceiling Height ACH AT Fraction TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 13,828 Sched. Latent Gain Frac. Area Heat Gain Btu/hr Occupants 1.00 X 660 X 300 Btuh/occ. / 35 SgfUOCc. = 5,657 Receptacle 1.00 X 660 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Process 1.00 X 660 X 0.000 Watts/Sgft X 3.413 Btu/Watt = 0 Infiltration:[ 1.00 X 4,840 X 660 X 10.30 X 0.50 /60] X 0.00377 = 1,033 Schedule Air Sensible Area Ceiling Height ACH AW Fraction TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 6,690 -.. -_ --- .,___Al.-- —4o....�...r,.'3Mti4-1_4arno•an•90 In• Paae89of89