CITY OF LA QUINTA, COUNTY OF RIVERSIDE, STATE OF CALIFORNIA
SILVERROCK RESORT -GOLF CLUBHOUSE
�,, ! PRIVATE UTILITY PLANS
�r
0 Indio yj
U 17
a
' AVE
AVE
54TH AVE
VICINITY MAP
N.T.S.
PROPOSED
W
WATER MAIN
PROPOSED -
- S
SEWER MAIN
EXISTING WATER MAIN
EXISTING SEWER MAIN
AIR / VAC ASSEMBLY
SEWER LATERAL
{
STORM DRAIN
-
S
CENTERLINE
-�
PROPERTY LINE
CURB
PAVEMENT EDGE
SEWER MANHOLE
0
WATER VALVE
0
WATER METER
SEWER CLEANOUT
o
BLOW -OFF ASSEMBLY
O
FIRE HYDRANT
>c<
TEE WITH 3-VALVES
is
BEND (SIZE & DEFLECTION)
SECTION LINE,
-
1 /4 SECTION LINE
EX. FORCE MAIN
EX. DETECTOR CHECK ASS'Y
PIV/FDC
04
THRUST BLOCK
w
WATER CONSTRUCTION NOTES
ABBREVIATIONS
ASS'Y
ASSEMBLY
A/V
AIR & VACUUM RELIEF VALVE
BLDG
BUILDING
BO
BLOW OFF ASSEMBLY
C&C
CURB AND GUTTER
D
DEPTH
DEFL
DEFLECTION
DIP
DUCTILE IRON PIPE
EA.
EACH
EXIST
EXISTING
FF
FINISHED FLOOR
FDC
FIRE DEPARTMENT CONNECTION
FH
FIRE HYDRANT
HORZ
HORIZONTAL
INV.
INVERT
LF
LINEAR FEET
MH
MANHOLE
P/A
PLANTER AREA
PIV
POST INDICATOR VALVE
PVC
POLYVINYL CHLORIDE
ROW
RIGHT OF WAY
SD
STORM DRAIN
STD
STANDARD
VCP
VITRIFIED CLAY PIPE
VERT
VERTICAL
W/ WITH
1$
1 CONNECT TO EXISTING BACKFLOW PREVENTER
2 FURNISH AND INSTALL 4" PVC C-900 FIRE LATERAL (INCLUDING BENDS AND FITTINGS)
3 CONNECT TO EXISTING DETECTOR CHECK ASSEMBLY
4 FURNISH AND INSTALL 2" PVC SCH. 40 WATER SERVICE (INCLUDING BENDS AND FITTINGS)
5 CONNECT TO WATER SUPPLY WITHIN BUILDING. SEE ARCHITECTURAL PLANS
6 CONNECT TO FIRE RISER WITHIN BUILDING. SEE ARCHITECTURAL PLANS
7 INSTALL INLINE PIV PER RIVERSIDE COUNTY FIRE REQUIREMENTS AND DETAIL ON SHEET 3
INSTALL 4" FDC PER RIVERSIDE COUNTY FIRE REQUIREMENTS AND DETAIL ON SHEET 3
SEWER CONSTRUCTION NOTES
FURNISH AND INSTALL 6" SDR-35 SEWER (INCLUDING BENDS AND FITTINGS)
FURNISH AND INSTALL CLEANOUT TO GRADE
REMOVE PLUG AND CONNECT TO EXISTING SEWER STUB -OUT
NOTE: QUANTITIES SHOWN ARE ENGINEER'S ESTIMATE ONLY. THE
CONTRACTOR SHALL VERIFY ALL. QUANTITIES FOR BID SUBMITTAL.
CONSTRUCTION contractor agrees that in accordance with generally accepted
construction practices, construction contractor will be required to assume sole
and complete responsibility for job site conditions during the course of
construction of the project, including safety of all persons and property, that
this requirement shall be made to apply continuously and not be limited to
normal working hours, and construction contractor further agrees to defend,
indemnify and hold design professional harmless from any and all liability, real
or alleged, in connection with the performance of work on this project, excepting
41
`Z ikn 4
200 100 0 200 400 600
Now
SCALE: 1"=200'
UTILITIES/SERVICES
1
EA
106
LE
WATER COACHELLA VALLEY WATER DISTRICT
(760)398-2651
1
EA
SEWER COACHELLA VALLEY WATER DISTRICT
(760)398-2651
GAS SOUTHERN CALIFORNIA GAS (760)341-9581
41
LF
TELEPHONE FRONTIER 1-800-483-4000
1
EA
ELECTRICAL IMPERIAL IRRIGATION DISTRICT (800)303-7756
CABLE T. V. SPECTRUM (760)340-2225
1
EA
1
EA
1
EA
OWNER/DEVELOPER
APN
SILVERROCK DEVELOPMENT COMPANY, L.L.C.
777-050-012
3551 FORTUNA RANCH ROAD
777-050-031
ENCINITAS, CA. 92024
777-050-036
230
LF
(760) 634-6543
777-050-045
4
EA
777-050-065
1
EA
FIRE CONTRACTOR CHANGES TO APPROVED PLANS
PRIOR TO THE FIRE CONTRACTOR EDITING OR CHANGING THE
APPROVED PLANS, THE CONTRACTOR SHALL CONTACT MICHAEL
BAKER PRIOR TO SUCH CHANGES. MICHAEL BAKER SHALL NOT BE
RESPONSIBLE FOR ANY CHANGES MADE TO THE PLANS WITHOUT THE
CONSENT OF MICHAEL BAKER AND THE APPROVAL OF THE CITY OF LA
QUINTA.
liability arising from the sole negligence of design professional.
BENCHMARK: BASIS OF BEARINGS:
CITY OF LA QUINTA BM #430 - Description: 1 112' COPPERWELD THE BEARINGS SHOWN HEREON ARE BASED
G4(� LQMONUMENT, STAMPED LS-98', FLUSH AT THE CENTERLINE UPON THE CALIFORNIA COORDINATE SYSTEM
DINTERSECTION OF AVENUE 54 AND JEFFERSON STREET.
ELEVATION = 5.467 (NAVD88] CCS 83, ZONE 6, AS DETERMINED LOCALLY
DIAL TWO WORKING ELEVATION =3.218'(NGVD29) BY THE LINE BETWEEN USC8&GS STATIONS LA
BEFORE I�, DAYS BEFORE PROJECT ELEVATION ATBM#430 QUINTA CS2005 (P491) AND COLLEGE OF
YOU DIG YOU DIG (To obtain Project Elevations in NAVD88 Datum, Subtract 1.564' THE DESERT (COTD) , (POSITIONS PER
( the el from shown).
o e elevations e ) NATIONAL GEODETIC SURVEY, NAD83, EPOCH
TOLL FREE TELEPHONE: 811 (To obtain Project Elevations in NGVD29. Add 0.687' to the 2011 .00) AS SHOWN ON THE NATIONAL
A PUBLIC SERVICE BY eievat{ons shown). GEODETIC SURVEY PUBLISHED DATA SHEETS
UNDERGROUND SERVICE ALERT ELEVATION s 3.903' AI-TNr NI An, 1F' -gin ?o"W
SHEET INDEX MAP
SHEET INDEX
SHEET No. DESCRIPTION
1 TITLE SHEET
2 UTILITY IMPROVEMENT PLAN
3 DETAIL SHEET
DATE
BY
DESCRIPTION
APP'D
DATE
R E V I S 1 0 N S
�a Q�°F ass tay��
� No- C36718
L.J
U
LO
SCOPE OF WORK - UNDERGROUND FIRE SYSTEM
ALL INSTALLATION OF THE UNDERGROUND FIRE PROTECTION FACILITIES FROM
THE DOUBLE DETECTOR CHECK ASSEMBLY TO THE BUILDING FIRE RISER (6"
ABOVE FINISHED FLOOR) SHALL BE IN ACCORDANCE WITH THE LATEST NFPA
CODES AND REGULATIONS.
LA QUINTA OFFICE OF THE FIRE MARSHAL (OFM) HAS REVIEWED THE
"PRIVATE ON -SITE UTILITY IMPROVEMENT PLAN"
CONCEPTUALLY:
FSS KOHL HETRICK
DATE
SPECIAL FIRE NOTES
1. THE DETAILS FOR THE PRIVATE FIRE MAIN ARE APPROVED CONCEPTUALLY AND FIRE
CLEARANCE IS GRANTED FOR THE LQ ENGINEERING PLAN CHECK SW2019-0002.
2. SEPARATE AND COMPLETE SUBMITTAL IS STILL REQUIRED FOR THE SPECIFIC SCOPE OF
THE PRIVATE FIRE MAIN DIRECTLY TO THE LA QUINTA OFM FOR PERMITTING AND
SHALL BE COMPLETED PRIOR TO ANY WORK BEING COMPLETED ON THE PRIVATE FIRE
MAIN.
3. LICENSED CONTRACTOR SHALL PROVIDE REVISED AND ADEQUATE PLAN DETAILS,
HYDRAULIC CALCULATIONS AND MANUFACTURER'S SPECIFICATIONS IN COMPLIANCE WITH
NFPA 24 CURRENT EDITION AND AS OTHERWISE REQUESTED BY LQ OFM. PERMIT FEES
WILL BE REQUIRED TO PAID.
N T E R N AT I Q N A L
75-410 Gerald Ford Drive, Suite 100
Palm Desert, CA 92211
Phone: (760) 346-74 1 - MBAKERINTL.COM r
DANIEL KORAVOS R'CE NO. C36718, EXP. 6-30--22
APPROVAL BY.
GENERAL NOTES
1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH LATEST EDITION OF THE STANDARD PLANS OF THE CITY OF LA QUINTA AND LATEST EDITION OF THE
STANDARD SPECIFICATIONS FOR PUBLIC WORKS CONSTRUCTION.
2. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO APPLY TO THE CITY OF LA QUINTA PUBLIC WORKS DEPARTMENT FOR THE NECESSARY PERMITS AND
TO BE RESPONSIBLE FOR SATISFACTORY COMPLIANCE FOR ALL CURRENT ENVIRONMENTAL REGULATIONS DURING THE LIFE OF CONSTRUCTION ACTIVITIES FOR
THIS PROJECT. ADDITIONAL STUDIES AND/OR PERMITS MAY BE REQUIRED.
3. THE CONTRACTOR SHALL OBTAIN ALL PERMITS AS REQUIRED BY THE CITY OF LA QUINTA OR OTHER GOVERNING AGENCIES.
4. THE CONTRACTOR SHALL NOTIFY THE CITY PUBLIC WORKS DEPARTMENT 48 HOURS PRIOR TO ANY GRADING, BRUSHING, OR CLEARING AND EACH PHASE OF
CONSTRUCTION AT (760) 777-7075 AND 48 HOURS PRIOR TO REQUIRING INSPECTIONS.
5. THE LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE WAY ONLY. THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATION
OF ALL EXISTING UTILITIES BEFORE COMMENCING WORK. HE AGREES TO BE FULLY RESPONSIBLE FOR ANY AND ALL DAMAGES WHICH MIGHT BE OCCASIONED
BY HIS FAILURE TO EXACTLY LOCATE AND PRESERVE ANY AND ALL UTILITIES.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL, REPLACEMENT, OR RELOCATION OF ALL REGULATORY, WARNING AND GUIDE SIGNS.
7, THE CITY ENGINEER SHALL APPROVE ALL STREET NAME SIGNS, TRAFFIC CONTROL SIGNS, TRAFFIC STRIPING, LEGENDS, AND PAVEMENT MARKERS TYPE AND
LOCATION.
8. THE CONTRACTOR SHALL NOT DISTURB EXISTING SURVEY MONUMENTS OR BENCH MARKS NOTED ON THE PLANS, OR FOUND DURING CONSTRUCTION. REMOVAL AND
REPLACEMENT SHALL DE DONE BY A REGISTERED CIVIL ENGINEER WITH AN R.C.E. NUMBER BELOW 33,966, OR A LICENSED LAND SURVEYOR ONLY.
9. CONSTRUCTION OPERATIONS AND MAINTENANCE OF EQUIPMENT WITHIN ONE HALF MILE OF HUMAN OCCUPANCY SHALL BE PERFORMED ONLY DURING THE TIME
PERIODS AS FOLLOWS:
OCTOBER 1ST TO APRIL 30TH: MONDAY-FRIDAY T.00 AM TO 5:30 PM
MAY 1ST TO SEPTEMBER 30TH: MONDAY-FRIDAY 6:00 AM TO 7:00 PM
WORK SHALL BE PROHIBITED ANY TIME ON SUNDAYS OR ON FEDERAL HOLIDAYS.
10. ALL TRAVELED WAYS MUST BE CLEANED DAILY OF ALL DIRT, MUD, AND DEBRIS DEPOSITED ON THEM AS A RESULT OF THE GRADING OPERATION. CLEANING IS
TO BE DONE TO THE SATISFACTION OF THE CITY ENGINEER.
11. ALL CONSTRUCTION AREAS SHALL BE PROPERLY POSTED AND LIGHTED IN CONFORMANCE WITH THE STATE MANUAL OF WARNING SIGNS, LIGHTS, AND DEVICES
FOR USE IN THE PERFORMANCE OF WORK UPON HIGHWAYS IN ORDER TO ELIMINATE ANY HAZARDS.
12. CONSTRUCTION PROJECTS DISTURBING MORE THAN 1-ACRE MUST OBTAIN A NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES) PERMIT.
OWNERS/DEVELOPERS ARE REQUIRED TO FILE A NOTICE OF INTENT (NOI) WITH THE WATER RESOURCES CONTROL BOARD (SWRCB), PREPARE A STORM WATER
POLLUTION PREVENTION PLAN (SWPPP), AND MONITORING PLAN FOR THE SITE.
THE NPDES IS A NATIONAL PROGRAM TO CONTROL NON -POINT SOURCE POLLUTANTS CARRIED BY STORM WATER. THE PROGRAM IS IMPLEMENTED AND ENFORCED
BY THE SWRCB.
13. THE CITY RETAINS THE RIGHT TO REQUIRE PLAN REVISIONS, AS NECESSARY, SUBSEQUENT TO PLAN APPROVAL, BUT PRIOR TO COMPLETION OF THE
IMPROVEMENTS SHOWN ON THESE PLANS, IF ANY NEW STREET IMPROVEMENTS HAVE BEEN INSTALLED BY THE CITY OR A THIRD PARTY WITHIN THE IMMEDIATE
VICINITY OF THE IMPROVEMENTS PROPOSED BY THESE PLANS THAT IMPACT THE DESIGN INTEGRITY OF THE IMPROVEMENT PROPOSED IN THESE PLANS AS
ORIGINALLY APPROVED. ALL COSTS, INCLUDING, BUT NOT LIMITED TO, DESIGN AND IMPROVEMENT COSTS, INCURRED AS A RESULT OF ANY DESIGN
REVISIONS SHALL BE BORNE BY THE IMPROVEMENT SPONSORS.
14. THESE PLANS ARE VALID FOR A PERIOD NOT TO EXCEED EIGHTEEN (18) MONTHS FROM DATE OF APPROVAL. THE IMPROVEMENT SPONSOR SHALL BEAR ALL
COSTS ASSOCIATED WITH UPDATING THE PLANS, INCLUDING, BUT NOT LIMITED TO, DESIGN AND IMPROVEMENT COSTS, TO AFFECT COMPLIANCE WITH ANY NEW
CITY STANDARDS, ORDINANCES, OR LAWS AND REGULATIONS, ENACTED OR ADOPTED BY THE CITY OR OTHER JURISDICTIONS WITH AUTHORITY SUBSEQUENT TO
THE PLAN APPROVAL DATE.
15. CONTRACTOR SHALL REMOVE AND REPLACE EXISTING SIDEWALK AS NEEDED AT ALL LOCATIONS WHERE IT IS CRACKED, UNEVEN AT JOINTS, OR OTHERWISE
DAMAGED, PURSUANT TO STREET $t HIGHWAYS CODE SECTION 5610. THIS REQUIREMENT APPLIES TO ALL SIDEWALK LOCATED IN PUBLIC RIGHT OF WAY
ADJACENT TO PROPERTY BEING DEVELOPED.
16. GRADING SHALL BE IN ACCORDANCE WITH THE ENGINEERED GRADING REQUIREMENTS OF THE UNIFORM BUILDING CODE, LATEST EDITION, AND SOILS REPORT
NO. 8227-04, DATED:SEPTEMBER 4, 2019, PREPARED BY: GLOBAL GEO-ENGI NEER ING, INC., TELEPHONE NO. (949) 221-0900.
17, THE SOILS ENGINEER AND THE ENGINEERING GEOLOGIST SHALL EXERCISE SUFFICIENT SUPERVISORY CONTROL DURING GRADING TO INSURE COMPLIANCE WITH
THE PLANS, SPECIFICATIONS, AND CODE WITHIN THEIR PURVIEW.
18. THE DESIGN CIVIL ENGINEER SHALL EXERCISE SUFFICIENT CONTROL DURING GRADING AND CONSTRUCTION TO ENSURE COMPLIANCE WITH THE PLANS,
SPECIFICATIONS, AND CODE WITHIN HIS PURVIEW.
19. DURING ROUGH GRADING OPERATIONS AND PRIOR TO CONSTRUCTION OF PERMANENT DRAINAGE STRUCTURES, TEMPORARY DRAINAGE CONTROL SHALL BE PROVIDED
TO PREVENT PONDING WATER AND DAMAGE TO ADJACENT PROPERTY.
20. AFTER CLEARING, EXISTING GROUND SMALL BE SCARIFIED TO A MINIMUM OF 6" ON THE ENTIRE SITE OR AS RECOMMENDED BY THE SOILS REPORT..
21. THE MAXIMUM CUT AND FILL SLOPES SHALL BE 2: 1.
22. ALL STREET SECTIONS ARE TENTATIVE. THE MINIMUM SECTION IS 3" A.C. OVER 4.5" CRUSHED A.B. FOR THE CONFERENCE AND SHARED SERVICES SITE,
EXCEPT FOR THE FIRE ACCESS ROUTE AS NOTED ON PLAN, WHICH IS 4.5" A.C. OVER 5.5" CHRUSHED A.B. ADDITIONAL SOIL TEST(S) SHALL BE REQUIRED
AFTER ROUGH GRADING TO DETERMINE EXACT SECTION REQUIREMENTS. THE CITY ENGINEER SHALL APPROVE THE FINAL STREET SECTION.
23. THE CITY ENGINEER WILL REVIEW FOR APPROVAL THE FINAL STREET SECTIONS AFTER SUBMITTAL OF "R" VALUE TESTS FOR ROADWAY SUBBASE.
24. LOCATIONS OF FIELD DENSITY TESTS SHALL BE DETERMINED BY THE SOIL ENGINEER OR APPROVED TEST AGENCY AND SHALL BE SUFFICIENT IN BOTH
HORIZONTAL AND VERTICAL PLACEMENT TO PROVIDE REPRESENTATIVE SAMPLINGS.
25. THE FINAL UTILITY LINE BACKFILL REPORT FROM THE PROJECT SOILS ENGINEER SHALL INCLUDE AN APPROVAL STATEMENT THAT THE BACKFILL IS SUITABLE
FOR THE INTENDED USE.
26. THE CONTRACTOR IS RESPONSIBLE TO PREVENT SILT CONTAMINATION OF STORMWATER INFILTRATION FACILITIES DURING CONSTRUCTION OF SUBSEQUENT
IMPROVEMENTS BY THE CONTRACTOR. IMMEDIATELY PRIOR TO FINAL ACCEPTANCE OF STORM DRAINAGE RETENTION/INFILTRATION FACILITIES, THE
CONTRACTOR SHALL CONDUCT, IN THE PRESENCE OF THE CITY INSPECTOR, A PERFORMANCE TEST DESIGNED TO CLEARLY DEMONSTRATE THE FUNCTIONAL
ADEQUACY OF THE FACILITIES.
27, THE CONTRACTOR SHALL PROVIDE WIND EROSION AND DUST CONTROL MEASURES AS REQUIRED BY THE FUGITIVE DUST CONTROL PLAN APPROVED FOR THIS
PROJECT.
TRENCH BACKFILL FOR STORM DRAINS SHALL BE IN CONFORMANCE WITH THE SOILS REPORT NO. 8227-04, DATED:SEPTEMBER 4, 2019, PREPARED BY: GLOBAL
GEO-ENGINEERING, INC., TELEPHONE NO. (949) 221-0900.
PAVING NOTES
1. ALL UNDERGROUND FACILITIES, INCLUDING SERVICE LATERALS, SHALL BE IN PLACE WITH TRENCHES COMPACTED AND TESTED PRIOR TO BASE GRADE
INSPECTION AND PAVING. THE CONTRACTOR SHALL SUBMIT WRITTEN EVIDENCE TO THE CITY ISSUED BY THE CONTRACTOR SHALL SUBMIT WRITTEN EVIDENCE
TO THE CITY ISSUED BY THE RESPECTIVE UTILITY PURVEYOR INDICATING THE SUBSURFACE PORTION OF THEIR UNDERGROUND FACILITIES HAVE BEEN
INSTALLED AND ACCEPTED.
2. A SEPARATE PERMIT IS REQUIRED FOR ALL EXCAVATIONS WITHIN EXISTING ROADWAYS AND TRAVELWAYS. LANE CLOSURES AND DETOURS SHALL BE POSTED,
DELINEATED, AND LIGHTED IN CONFORMANCE WITH THE CALTRANS "MANUAL OF TRAFFIC CONTROLS FOR CONSTRUCTION AND MAINTENANCE WORKZONES" AND
ANY ADDITIONAL REQUIREMENTS DEEMED NECESSARY BY THE CITY ENGINEER.
3. ASPHALT CONCRETE PAVING, EXCEPT FOR OVERLAYS, SHALL BE INSTALLED IN TWO (2) OR MORE COURSES WITH MIX DESIGNS THAT CONFORM TO SECTION 400
OF THE REVISED STANDARD SPECIFICATIONS, COACHELLA VALLEY VERSION (GREEN BOOK), NOTED AS FOLLOWS:
WEARING COURSE (UPPER COURSE); PG 70-10
BASE COURSE (LOWER COURSES): PG 70-10
THE WEARING COURSE SHALL BE A 0.1 FEET THICK; THE BASE COURSE(S) SHALL CONTAIN THE BALANCE OF THE REQUIRED ASPHALT CONCRETE THICKNESS.
4. MIX DESIGN REQUIRED. SEVEN (7) DAYS PRIOR TO COMMENCEMENT OF PAVING OPERATIONS, THE CONTRACTOR SHALL SUBMIT FOR CITY APPROVAL, A
COMPLETE PROPOSED MIX DESIGN IDENTIFYING THE MIX CHARACTERISTICS SUCH AS AGGREGATE GRADATIONS, VOIDS IN MINERAL AGGREGATE (VMA), AIR
VOIDS, AND S-VALUE FOR VARIOUS OIL CONTENTS FOR EACH MIX. TO ENSURE TIMELY APPROVAL, THE CONTRACTOR/SUPPLIER IS ENCOURAGED TO REFER TO
LA QUINTA'S DESIGN MIX APPROVAL CHECKLIST (FORM F082) TO ENSURE ALL REQUIRED LAT TESTS ARE PERFORMED, CERTIFIED, AND SUBMITTED FOR
REVIEW.
5. A TACK COAT SHALL BE APPLIED TO EXISTING PAVEMENT, P.C.C. SURFACES, AND THE A.C. BASE COURSE, IF TRAFFIC HAS DRIVEN ON IT. THE TACK
COAT SHALL BE SLOW SETTING ANIONIC EMULSIFIED ASPHALT TYPE "SS-1H" CONFORMING TO SECTION 203-3 OF THE STANDARD SPECIFICATIONS. THE
LIQUID ASPHALT SHALL BE GRADE 60-70 AND APPLIED AT THE RATE OF 0.1 GALLONS/YARD.
6. NEW IMPROVEMENTS THAT JOIN EXISTING IMPROVEMENTS SHALL JOIN OR MATCH IN A MANNER SATISFACTORY TO THE CITY ENGINEER. CONSTRUCTION
OPERATIONS REQUIRED TO ACHIEVE A SAFE, DURABLE, AESTHETICALLY PLEASING TRANSITION BETWEEN THE NEW AND EXISTING IMPROVEMENTS MAY INCLUDE
SAW CUTTING, REMOVAL, REPLACEMENT, CAPPING, AND/OR COLD PLANING, AS NEEDED.
7. ALL MANHOLES AND VALVE BOX FRAMES SHALL BE ADJUSTED TO FINAL GRADES AFTER PAVEMENT INSTALLATION IS COMPLETED.
8 THE CURB SHALL BE ETCHED OR STAMPED SHOWING UTILITY SERVICE LATERAL LOCATIONS AS FOLLOWS: "S" FOR SEWER, "G" FOR GAS, AND "E" FOR
ELECTRICAL POWER.
BRYA MCKINNEY
CITY ENGINEER
R.C.E. NO. 49418
DRAWN KE DESIGNED KE
SCALE AS NOTED CHECKED RV
PRIVATE WATER, SEWER, AND
RIVERSIDE COUNTY PRIVATE FIRE LINE NOTES
SEE SHEET 3
I I
CITY OF LAQUINTA I CITY OF LA QUINTA, COUNTY OF RIVERSIDE, STATE OF CALIFORNIA S H E E T C
C
PRIVATE ON -SITE UTILITY IMPROVEMENT PLAN C
��3f SILVERROCK RESORT of SHEETS
DATE
GOLF CLUBHOUSE DWG. NAME r
EXP. 09/ {}f20 TITLE SHEET - SDP2016-0009
JOB NUMBER 173977 LOCATED WITHIN SW 1/4 OF SEC. 5 & NW, NE & SE 1/4 OF SEC, 8, T.6S.,R.7E., S.B.B.& M. FILE N O. C
FOR: O
DATE JULY 2020 S1LVERROCK DEVELOPMENT COMPANY, L.L.C.
20 10
40 60
s
r I-
-P r r}] (—� F
r RE. _ --- F' I RE.
9
S___ I . S
S S
REMOVE
12, FIRE MAIN PER All
RATE PLAN SET 519--0401 S=0.2453 18 51II
F i RE
8PVC SEWER MAIN PER SEPARATE 6.06INV 6 PVC
PLAN SETT SW2019-OW I 4. 89I NV 8 PVC
- S
--
SCALE: 1 "=20'
,r
\ ,1^2, WATER MAIN PER ✓✓
�4 tEPER PLAN SET
Ld
t
a
i fll
5`T
122 DIP PUBLIC WATER MAIN
PER SEPARATE PLAN SET
1 f i
I � I
WATER CONSTRUCTION NOTES
r) �' r J 1 CONNECT TO EXISTING BACKFLOW PREVENTER
2 FURNISH AND INSTALL 6" PVC C-900 'FIRE LATERAL (INCLUDING BENDS AND FITTINGS)
3 CONI+ECT TO EXISTING DETECTOR CHECK ASSEMBLY
4 FURNISH AND INSTALL 2' PVC SCH. 40 WATER SERVICE (INCLUDING BENDS AND FITTINGS)
5 CONNECT TO HATER SUPPLY WITHIN BUILDING. SEE ARCHITECTURAL PLANS
`':. �..... 6 CONFECT TO FIRE RISER WITHIN BUILDING. SEE ARCHITECTURAL PLAIDS
11WD WATER EASEMENT"'-. 7 INSTALL INLINE PIV PER RIVERSIDE COUNTY FIRE REQUIREMENTS AND DETAIL ON SHEET 3
`.' \ !` 8 INSTALL 4' FDC PER RIVERSIDE COUNTY FIRE REQUIREMENTS AND DETAIL ON SHEET 3
WATER METER AND BACKFLAII PREVENTER
PER SEPARATE PUBLIC WATER PLAN SET ," ~
RUING CLUBHOUSE k PROSIIOP \/ ` j
t
REPARAI� PUi I C
; .� �
SEWER CONSTRUCTION NOTES
�, , `( '��, � / `'� s ,_ =•I `�� �� � �1 FURNISH AND INSTALL 60 SDR-35 SEWER (INCLUDING FIENDS AND FITTINGS)
TECTOR CHECK ASSEMBLY" . ` ,� �`iti `
. �. C"� -., �, � --.,� � FURNISH AND INSTALL CLEANOUT TO GRADE
RVING MOINTAGE HOTEL
R SEPARATE PUBLIC. 4 Fxr- � _, 3� MOVE PLUG AND CONNECT TO EXISTING SEWER STUB -OUT
TER PLJ�Nf �,, 8, ' j
2
PROPOSED PUBLIC 122 DIP WATER MIAIN
PER SEPARATE ITT PLANS
S, =.._._.- S
L_
yf
L
jam( BENCHMARK: BASIS OF BEARINGS: APPROVAL BY: CITY OF LA QUINTA CITY OF LA QUINTA, COUNTY OF RIVERSIDE, STATE OF CALIFORNIA S H E E T
CITY OF LA QUINTA BM #430 - Description: 1 112" COPPERWELD
D[� " MONUMENT, STAMPED "LS-98", FLUSH AT THE CENTERLINE T� BEARINGS SHOWN HEREON ARE BASED Q�Qf Q Michael
r� Baker
. e
INTERSECTION OF AVENUE54ANDJEFFERSONSTREET. UPON THE CALIFORNIA COORDINATE SYSTEM, �cp( / / PRIVATE ON -SITE UTILITY IMPROVEMENT PLAN
ELEVATION = 5.467' (NAVD88) CCS 83, ZONE 6, AS DETERMINED LOCALLY ` 2
.�`� L 0q9" `rye �i /'��
ELEVATION = 3.216'(NGVD29) BY THE LINE BETWEEN USC8cGS STATIONS LA _� o a I N T E R N A T 1 O N A L S I LVE R ROC K RESORT
DIAL TWO WORKING ca � � m DATE OF 3 SHEETS
BEFORE % DAYS BEFORE PROJECT ELEVATION AT BM #4aa QUINTA CS2005 (P491) AND COLLEGE OF a No. C36718 75 eralti F d Drive, Suite 100 B AN cKINNEY
I GOLF CLUBHOUSE
YOU DIG �n YOU DIG (To obtain Project Elevations in NAV088 Datum, Subtract 1.564' THE DESERT (COTD) , (POSITIONS PER P Sett, C 2211 CITY ENGINEER DWG. NAME
from the elevationsshown). NATIONAL GEODETIC SURVEY, NAD83, EPOCH *�jq C]Vy1 ��q on 760) 74 1 - MBAKERINTL,COM R.C.E. N0. 49418 EXP. D9/30/20 PLAN SHEET
TOLL FREE TELEPHONE: 811 (To obtain Project Elevations in NGVD29. Add 0.687'tc the 2011.00) AS SHOWN ON THE NATIONAL PF �Q� DRAWN DESIGNED JOB NUMBER FILE NO.
A PUBLIC SERVICE BY elevations shown). DATE BY DESCRIPTION APP'D DATE OF CALF KE KE 173977 LOCATED WITHIN SW 1/4 OF SEC. 5 k NW. NE k SE 1/4 OF SEC. 8, T.6S.,R.7E., S.B.BA M.
UNDERGROUND SERVICE ALERT GEODETIC SURVEY PUBLISHED DATA SHEETS SCALE CHECKED DATE FOR:
ELEVATION = 3,9173' BEING N.40' 16',30.20"W. R E V I S 1 0 N S D EL KORA RCE NO. C36718, EXP. 6--30-22 DATE: AS NOTED RV DULY Joao SILVERROCK DEVELOPMENT COMPANY, L.L.C.
UNPAVED -----PA
24"
VARIES
0`7')
VARIES
12" M I N
PIPE
DIA.
PIPE CENTERED TRENCH WIDTHS
PIPE DIA.
MIN.
-MAX.
8"
30"-45"
12"
36"-49"
18"
42 `5F"
24"
48"-62"
PAVEMENT SECTION AND/OR
NATIVE SOIL OR SELECT
MATERIAL PLACED IN 8" LIFTS
(LOOSE) AND COMPACTED TO AT
LEAST 95% COMPACTION PER
ASTM D1557 OR AS PER THE
LOCAL GOVERNING AUTHORITY
TRENCH/BACKFILL TO BE IN COMPLIANCE
WITH NFPA 24 SECTION 10.9.1 AS
AMENDED BY CFC CHAPTER 80.
BACKFILL SHALL BE WELL TAMPED IN
LAYERS OR PUDDLE UNDER AND AROUND
PIPES TO PREVENT SETTLEMENT OR
LATERAL MOVEMENT. BACKFILL SHALL
CONSIST OF CLEAN FILL SAND OR PEA
GRAVEL TO A MINIMUM 6" BELOW AND TO A
MINIMUM OF 12" ABOVE TO PIPE AND
SHALL CONTAIN NO ASHES, CINDERS,
REFUSE, ORGANIC MATTER, OR CORROSIVE
MATERIALS. OTHER BACKFILL MATERIALS
AND METHODS ARE PERMITTED WHERE
DISIGNATED BY A REGISTERED
PROFESSIONAL ENGINEER AND APPROVE BY
THE ENFORCING AGENCY.
6" MIN.
PIPE TRENCH BACKFILL DETAIL
N.T.S.
MINIMUM REQUIRED AREA (SF) PER TABLE A-10.6.1(b)
"HORIZONTAL BEARING BLOCK AREA"
NOMINAL PIPED IA. (IN)
DUCTILE IRON AND PVC PIPE
DEAD
END
(0.707)
90 1
45
(0.541)
22.5
(0.276)
11.25
(0.139)
4
10.75
15.20
8.22
4.20
2.11
6
27.34
31.60
17.10
8.72
4.39
8
38.46
54.40
29.43
15.01
7.56
10
57.97
82.00
44.3E
22.63
11.40
12
82.01
116.00
62.76
32.02
16.12
MINIMUM REQUIRED AREA (SF) PER CALCULATION A.10.6.1(a) "GRAVITY THRUST
BLOCKS"
NOMINAL PIPE DIA. (IN)
DUCTILE IRON AND PVC PIPE
DEAD, FND
(0.707)
90
45 (0.541)
22.5
(0.276)
11.25
(0.139)
4
2.72
3.84
2.08
1.06
0.53
6
5.61
7.93
4.29
2.19
1.10
8
9.65
13.65
7.38
3.77
1.89
10
14.52
20.53
11.11
5.66
2.85
12
20.53
29.03
15.71
8.01
4.02
THRUST AT FITTINGS FOR DUCTILE IRON & PVC TABLE A.10.6.1(a).
NOMINAL PIPE DIA. (IN)
DUCTI LF IRON AND PVC PIPE
DFAD END
901,
45'
22-7
11 25.
4
3620
5118
Z770
1412
710
6
7478
10576
5724
2918
1466
8
12866
18194
9946
5020
2522
10
19354
27370
14812
7552
3794
12
27370
38706
Z0948
10680
5366
FIRE MATERIAL LIST
ITEM DESCRIPTION IMANUFAcrURER
I
MODEL / TYPE ICOMMENTS
C-900 PVC PIPE CLASS 165 (DR-25)
JIM EAGLE
BLUE BRUTE
OR APPROVED EQUAL
SUPER FIRE HYDRANT
NOT APPLICABLE
POST INDICATOR VALVE
MUELLER
A-20806 (4"-14")
OR APPROVED EQUAL
FIRE DEPARTMENT CONNECTION
AMERICAN FIRE SUPPLY
220RBSA
ORAPIP ROVED EQUAL
FIRE RISER
AMES FIRE
SERIES IBR
OR APPROVED EQUAL
RESILENT WEDGE GATE VALVE
CLOW VALVE
C-509 2"-12"
OR APPROVED EQUAL
THRUST BLOCK CALCULATIONS INPUT DATA
WORKING WATER PRESSURE 200
SOIL BEARING PRESSURE 2000
SAFETY FACTOR (1.5 TYP.) 1.5
NOTE:
FIRE LINES MUST COMPLY WITH NFPA 2.4, 2019 EDITION.
INSPECTIONS REQUIRED:
1. THRUST BLOCK PRE -POUR, TRENCH AND BACKFILL INSPECTION.
2. UNDERGROUND HYDROSTATIC TEST - 200 PSI FOR TWO HOURS
3. UNDERGROUND FLUSH. (PRIOR TO CONNECTION TO THE OVERHEAD FIRE SPRINKLER SYSTEM.
4. UNDERGROUND FINAL.
ALL INSPECTIONS WILL. BE SCHEDULED WITH THE FIRE PREVENTION BUREAU. SPRINKLER
CONTRACTORS MUST REQUEST INSPECTIONS THROUGH THE PROJECT SUPERINTENDENTS.
2.5" x 2.5" x 4" FDC THE DIRECTION OF THE
W/ DOUBLE CLAPPERS & BRASS CAPS FDC OUTLETS SHALL BE
SUPERVISORY DEVICE 4" GALV. SCH40 STEEL PIPE
CONDUIT & WIRING FROM 4" FLG'D WAFER CHECK ABOVE GRADE
FRCP BY ELECTRICAL POST INDICATOR W/
DIVISION PER CEC. REFER BREAKABLE PADLOCK
TO FIRE ALARM DWGS FOR OUTDOOR LISTED, CSFM 2� x
CONTINUATION APPROVED TAMPER SWITCH P
IV
� o0
FINISH GRADEI
TRACER WIRE TO BE
LAID ON TOP OF PIPE
4" PVC
D.I. KEY VALVE, �� 48" -
RESTRAINED JOINT
APPROVED BY THE FIRE
INSPECTOR.
zx
NOTE:
a 6" OF CLEAN SAND ON
+� ALL SIDES OF PIPE
c° W.l.
4" D.I. RESTRAINED JOINT PIPE
4" PVC
4" M.J. x FL TEE
LOST INDICATOR / FIRE DEPT. CONNECTION DETAIL
N.T.S.
* SOIL BEARING PRESSURE
CAPACITY PER PAGE 13
OF SOILS REPORT
5'
MIN.
FINISH GRADE a .-
/,,/i,
4" STAINLESS STEEL
W/ FLANGED END FOR
BACKFLOW PREVENTER.
- INSTALL PER NFPA 24
P VC
PRIVATE WATER LINE NOTES
1. ALL WORKS SHALL CONFORM WITH THE STANDARD SPECIFICATIONS FOR PUBLIC WORKS CONSTRUCTION (GREEN BOOK) LATEST EDITION, A.W.W.A. STANDARDS,
2013 CALIFORNIA PLUMBING CODE AND THESE PLANS.
2. ALL WATER MAINS 4" THRU 12" SHALL BE C-900 CLASS 200, 14" AND LARGER SHALL BE C-905 CLASS 150, WATER PIPE SMALLER THAT 4" SHALL BE
SCHEDULE 40 OR SCHEDULE 80 PVC OR CPVC WITH A PRESSURE RATING GREATER THAN 200 PSI UNLESS OTHERWISE INDICATED ON THE PLANS. SIZES AS
INDICATED ON THE PLANS AS MANUFACTURED BY JM EAGLE, PACIFIC -WESTERN MANUFACTURING COMPANY OR ENGINEER APPROVED EQUAL.
3. FIRE HYDRANTS SHALL BE 6" WET BARREL TYPE WITH ONE 4" OPENING AND TWO 2-1/2" OPENINGS PER CVWD STANDARDS. FIRE HYDRANT SHALL BE JONES
MODEL NO. J-3765 OR AVK MODEL CALIFORNIA 24-50 HP OR APPROVED EQUAL.
4. GATE VALVES 4" THRU 12" SHALL BE RESILIENT -SEATED WITH NON -RISING STEMS CONFORMING TO A.W.W.A. C-509-80. VALVES LARGER THAN 12" SHALL
BE BUTTERFLY VALVES. VALVES SHALL BE FLANGED X FLANGED AS MANUFACTURED BY AMERICAN AVK, CLOW, M&H, STOCKHAM, U.S. PIPE, OR ENGINEER
APPROVED EQUAL.
5. BALL VALVE MATERIAL SHALL BE AS INDICATED ON PLAN. BALL VALVE MATERIAL TO BE EITHER BRONZE BODY OR PVC SCHEDULE 80. BRONZE VALVE SHALL
HAVE NPT THREADS ON BOTH ENDS RATED AT 600 PSI AS MANUFACTURED BY CONBRACO INDUSTRIES OR ENGINEER APPROVED EQUAL, PVC VALVE SHALL HAVE
NPT THREADS ON BOTH ENDS RATED AT 200 PSI AS MANUFACTURED BY SPEAR OR ENGINEER APPROVED EQUAL.
6. THE MINIMUM COVER FOR WATER MAINS AND WATER SERVICES SHALL BE 36 INCHES. STREET SHALL BE BROUGHT TO SUBGRADE AND SEWER MAINS SHALL BE
INSTALLED BEFORE WATER MAIN IS INSTALLED.
7. MINIMUM HORIZONTAL SEPARATION FROM PRIVATE WATER TO PRIVATE SEWER MAINS SHALL BE 10 FEET FROM OUTSIDE TO OUTSIDE WALL. MINIMUM VERTICAL
SEPARATION FOR WATER AND SEWER MAINS AT PERPENDICULAR CROSSING WATER SHALL BE 1 FOOT ABOVE SEWER FROM OUTSIDE WALL TO OUTSIDE WALL OF
PIPE PER C.P.C.
8. THE CONTRACTOR SHALL TEST AND CHLORINATE PROPOSED WATER MAINS AND SERVICES BACTERIOLOGICAL SAMPLES SHALL BE CLEARED BY A CERTIFIED
TESTING LAB AND SHALL PROVIDE THE WRITTEN RESULTS TO THE ENGINEER, TESTS ON FIRE SYSTEM SHALL MEET FIRE DEPARTMENT REQUIREMENTS AND
S.S.P.W.C.
9. TRENCH EXCAVATION, PIPE BEDDING AND BACKFILL SHALL BE CERTIFIED BY A REGISTERED SOILS ENGINEER PRIOR TO PLACEMENT OF AC OR CONCRETE.
10. IT SHALL BE THE WATER CONTRACTOR'S RESPONSIBILITY TO SET WATER VALVE RISER, FRAME AND COVER TO FINISH GRADE AFTER PAVING IN ACCORDANCE
WITH CVWD STANDARD DRAWING W-17A MODIFY VALVE COVER TO ONLY READ "WATER" OR "FIRE" AS APPROPRIATE.
11. ALL CONNECTIONS MADE TO EXISTING FACILITIES WILL BE AT CONTRACTOR'S EXPENSE.
12. THE CONTRACTOR SHALL OBTAIN ALL NECESSARY STANDARDS AND REVIEW THE PLANS IN DETAIL WITH THE ENGINEER PRIOR TO START OF CONSTRUCTION.
13. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK AND SHALL MAINTAIN ALL FACILITIES UNTIL PROJECT IS COMPLETED.
14. EXISTING UTILITIES MAY OR MAY NOT BE SHOWN ON THESE DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY AND PROTECT
ALL UTILITIES IN THE CONSTRUCTION AREA WHETHER SHOWN OR NOT SHOWN HEREON. THE CONTRACTOR SHALL VERIFY LOCATION OF ALL EXISTING
UTILITIES AND NOTIFY COMPANIES 48 HOURS IN ADVANCE OF THE BEGINNING OF CONSTRUCTION AND CALL U.S.A. UNDERGROUND SERVICE ALERT AT
1-800-227-2600.
15. ALL FITTINGS SHALL BE DUCTILE IRON PUSH -ON BY PUSH -ON EQUIPPED WITH "TYTON" PUSH -ON OR MECHANICAL JOINTS UNLESS OTHERWISE NOTED ON
PLANS. JOINT RESTRAINT SHALL BE "MEGA -LUG" BY EBAA IRON WORKS, SERIES 1600 BELL RESTRAINT HARNESS, OR ENGINEER APPROVED EQUAL.
16. LENGTHS OF RESTRAINED PIPE SHALL BE A MINIMUM OF 54 LINEAR FEET IN EACH DIRECTION OF FITTING AND BRANCH OF TEE OR AS INDICATED ON PLAN.
17, ALL NUTS, WASHERS AND BOLTS SHALL BE STAINLESS STEEL.
18. BLUE DOT MARKERS SHALL BE PLACED ADJACENT TO FIRE HYDRANTS LOCATED ON THE CENTERLINE OF THE STREET OR DRIVEWAY.
19. THE CONTRACTOR AGREES THAT HE SHALL ASSUME SOLE AND COMPETE RESPONSIBILITY FOR JOB SITE CONDITIONS DURING THE COURSE OF CONSTRUCTION OF
THIS PROJECT„ INCLUDING SAFETY OF ALL PERSONS AND PROPERTY; THAT THIS REQUIREMENT SHALL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL
WORKING HOURS; AND THAT THE CONTRACTOR SHALL DEFEND, INDEMNIFY AND HOLD THE OWNER AND THE ENGINEER HARMLESS FROM ANY AND ALL LIABILITY,
REAL OR ALLEGED, IN CONNECTION WITH THE PERFORMANCE OF WORK ON THIS PROJECT, EXCEPTING FOR LIABILITY ARISING FROM THE SOLE NEGLIGENCE
OF THE OWNER OR ENGINEER.
PRIVATE SEWER LINE NOTES
1. ALL WORKS SHALL CONFORM WITH THE STANDARD SPECIFICATIONS FOR PUBLIC WORKS CONSTRUCTION (GREEN BOOK) LATEST EDITION, A.W.W.A. STANDARDS,
2013 CALIFORNIA PLUMBING CODE AND THESE PLANS.
2. ALL SEWER MAINS 4" THRU 15" SHALL BE SDR 35 SEWER PIPE COLORED GREEN. SIZES AS INDICATED ON THE PLANS. AS MANUFACTURED BY JM EAGLE,
PACIFIC -WESTERN MANUFACTURING COMPANY OR ENGINEER APPROVED EQUAL.
3. SEWER CLEAN -OUT SHALL BE INSTALLED PER DETAIL ON THE PLANS, AND IN CONFORMANCE WITH SSPWC.
4. SEWER MAIN LINE AND GRADE SHALL BE AS INDICATED ON THE PLANS.
5. ALL CONCRETE USED IN SEWER CONSTRUCTION, INCLUDING PRECAST MANHOLE SECTIONS AND MANHOLE BASES SHALL BE CLASS 660-C-4000, PORTLAND TYPE
CEMENT (7 SACKS, 4000 PSI). THE CONTRACTOR SHALL FURNISH A CERTIFICATE OF COMPLIANCE SHOWING THE CEMENT TYPE USED.
6. WYES AND LATERALS SHALL BE PVC SDR-35 OR ABS 1210 DWV SCHEDULE 4 AND INSTALLED AT GRADES AS INDICATED ON PLAN.
7. MINIMUM HORIZONTAL SEPARATION FROM PRIVATE WATER TO PRIVATE SEWER MAINS SHALL BE 10 FEET FROM OUTSIDE TO OUTSIDE WALL. MINIMUM VERTICAL
SEPARATION FOR WATER AND SEWER MAINS AT PERPENDICULAR CROSSING WATER SHALL BE 1 FOOT ABOVE SEWER FROM OUTSIDE WALL TO OUTSIDE WALL OF
PIPE PER C.P.C.
8. FINAL TESTING FOR PIPELINE LEAKAGE SHALL BE MADE IN THE PRESENCE OF THE ENGINEER AFTER BACKFILL HAS BEEN INSPECTED AND APPROVED.
9. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SET MANHOLE COVERS TO FINISH GRADE AFTER PAVING IN ACCORDANCE WITH COACHELLA VALLEY
WATER DISTRICT STANDARD DRAWING S-1A OR S-IB AS APPLICABLE.
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK AND SHALL MAINTAIN ALL FACILITIES COMPLETED AND UNCOMPLETED UNTIL ACCEPTED BY THE
OWNER.
11. THE CONTRACTOR SHALL OBTAIN ALL NECESSARY STANDARDS AND REVIEW THE PLANS IN DETAIL WITH THE ENGINEER PRIOR TO START OF CONSTRUCTION.
12. ALL ELEVATIONS SHOWN TO BE EXISTING WHERE FROM RECENT SURVEY OF THE ENGINEER AD SHALL BE VERIFIED BY THE CONTRACTOR PRIOR TO
CONSTRUCTION.
13. THE CONTRACTOR SHALL NOTIFY ENGINEER 72 HOURS PRIOR TO STARTING ANY WORK. A PRE -CONSTRUCTION MEETING SHALL BE SET UP WITH THE ENGINEER,
THE CONTRACTOR, HIS SUBCONTRACTORS, AND A REPRESENTATIVE FROM EACH OF THE UNDERGROUND UTILITIES SHALL BE PRESENT.
14. THE CONTRACTOR SHALL VERIFY LOCATION OF ALL EXISTING UTILITIES AND NOTIFY COMPANIES 48 HOURS (2 WORKING DAYS) IN ADVANCE OF THE
BEGINNING OF CONSTRUCTION AND CALL U.S.A. UNDERGROUND SERVICE ALERT AT 1-800-227-2600.
15. TREES TO BE PLANTED 10' MINIMUM FROM SEWER LINES.
NOTE: FIRE SERVICE UNDERGROUND
IS CONSIDERED FROM THE DCDA
TO 6" ABOVE FINISH FLOOR WITHIN
1' I 12" OF THE WALL
[--o--SEE FIRE SPRINKLER CONTRACTOR
MIN. DWG'S FOR CONTINUATION
o FLEXIBLE COUPLING
-FLANGED REDUCER, AS REQ'D
+ F.F.
_ 4" NOMINAL CLEARANCE REQ'D
FILL VOID WITH FLEX MASTIC
90' BEND
.. CONCRETE THRUST BLOCK
t .., BEARING AREA PER NFPA 24
1' CLR. MIN.
UNLESS SLEEVED
FIRE SPRINKLER RISER CONNECTION DETAIL
N.T.S.
,7
T p TnD
BENCHMARK:
CITY OF LA QUINTA BM #430 Description: 1 112" COPPERWELD
BASIS OF BEARINGS:
THE BEARINGS SHOWN HEREON ARE BASED
o
DIAL 1-WO WORKING
BEFORE �41 DAYS BEFORE
YOU DIG "j% v III YOU DIG
MONUMENT, STAMPED LS 98", FLUSH AT THE CENTERLINE
INTERSECTION OF AVENUE 54 AND JEFFERSON STREET.
ELEVATION = 5.467' (NAvfaa$)
ELEVATION = 3.216' (NGVD29)
PROJECT ELEVATION AT BM #430
(To obtain Project Elevations in NAVD88 Datum, Subtract 1.564'
from the elevations shown).
UPON THE CALIFORNIA COORDINATE SYSTEM,
CCS 83, ZONE 6, AS DETERMINED LOCALLY
BY THE LINE BETWEEN USC&GS STATIONS LA
QUINTA CS2005 (P491) AND COLLEGE OF
THE DESERT COTD } , (POSITIONS PER
NATIONAL GEODETIC SURVEY, NAD83 , EPOCH
DATE
BY
DESCRIPTION
APP"D
DATE
TOLL FREE TELEPHONE: 811
A PUBLIC SERVICE BY
(To obtain Project Elevations in NGVD29, Add 0.681' to the
elevations shown).
2011.00 ] AS SHOWN ON THE NATIONAL
GEODETIC SURVEY PUBLISHED DATA SHEETS
UNDERGROUND SERVICE ALERT
ELEVATION = 3.903`
BEING N. 40' 16 ' 30.20"W .
R E V I S I G N S
rNo.
15)
rn
Lu
Ko
C36718
CfV1�
TF OF CA���`��
NOTES:
1. THE FOLLOWING PRECAUTIONS MUST BE OBSERVED WHEN CONSTRUCTING THRUST
BLOCKS:
A. BLOCKS MUST BE POURED AGAINST UNDISTURBED SOIL.
B. THE PIPE JOINT AND BOLTS MUST BE ACCESSIBLE.
C. CONCRETE SHOULD BE CURED FOR AT LEAST 5 DAYS AND SHOULD HAVE
A COMPRESSION STRENGTH OF 2,000 LBS. AT 28 DAYS.
D. BLOCKS MUST BE POSITIONED TO COUNTERACT THE DIRECTION OF THE
RESULTANT THRUST FORCE.
TABLE 1: BEARING VALUE OF SOIL
SOIL TYPE LBS. S.F.
ALLUVIAL SOIL
1000
SOFT CLAY
2000
FIRM CLAY
4000
WET SAND
4000
SAND AND CLAY MIXED
4000
FINE DRY SAND
6000
HARD CLAY
8000
COARSE DRY SAND
8000
GRAVEL
12000
GRAVEL AND SAND, WELL
16000
CEMENTED
HARDPAN OR HARD SHALE
20000
MEDIUM ROCK
40000
ROCK UNDER CAISSONS
50000
HARD ROCK
160,000
1 N T E R N AT 10 N A L
75-41 O Gerald Ford Drive, Suite 100
Palm Desert, CA 92211
Pkaorl ' {7G0j 346-74 1 • NBAKERINTL.COM
DANIEL KORAVOS RCE NO.'C36718, EXP. 6-30-22
THRU`.
BEARI
AREA
(TYP)
APPROVAL BY:
RIVERSIDE COUNTY PRIVATE FIRE LINE NOTES
1. THE INSTALLATION OF THE ON -SITE WATER SYSTEM SHALL COMPLY WITH ALL REQUIREMENTS OF THE CURRENT EDITION OF NFPA 24 AND
CALIFORNIA FIRE CODE. INSTALLATION WORK SHALL BE DONE BY FULLY EXPERIENCED AND RESPONSIBLE CONTRACTORS. CONTRACTORS
SHALL BE APPROPRIATELY LICENSED IN THE STATE OF CALIFORNIA TO INSTALL PRIVATE FIRE SERVICE MAINS AND THEIR
APPURTENANCES (CSLB: C-16, C34, C-36, CLASS A). JOB CARDS WILL BE ISSUED TO THESE LICENSED CONTRACTORS ONCE ADEQUATE
DOCUMENTATION AND APPROVAL FOR THE WORK HAS BEEN OBTAINED BY THE OFFICE OF THE FIRE MARSHAL.
2. ALL FORE FLOW REQUIREMENTS, HYDRANT TYPE, NUMBER OF HYDRANTS, AND SPACING OF HYDRANTS SHALL BE PROVIDED AS PER THE
CALIFORNIA FIRE CODE.
3, AN APPROVED WATER SUPPLY FOR FIRE PROTECTION, EITHER TEMPORARY OR PERMANENT, SHALL BE MADE AVAILABLE WITHIN A
REASONABLE DISTANCE AS SOON AS COMBUSTIBLE MATERIAL ARRIVES ON THE JOB SITE. THIS WATER SUPPLY SHALL BE APPROVED BY
THE RIVERSIDE COUNTY FIRE DEPARTMENT - OFFICE OF THE FIRE MARSHAL.
4. THE CIVIL ENGINEER OR LICENSED CONTRACTOR WHO DESIGNED THE WATER SYSTEM HEREBY CERTIFIES THAT THIS WATER SYSTEM IS IN
ACCORDANCE WITH THE REQUIREMENTS AS PRESCRIBED BY THE OFFICE OF THE FIRE MARSHAL, THE CALIFORNIA FIRE CODE AND NFPA
24, WET -SIGNED STAMP SEAL SHALL BE PLACED ON THE PLANS.
5. THE FIRE FLOW CALCULATIONS SHALL BE BASED ON WATER FLOW TEST INFORMATION CONDUCTED WITHIN ONE YEAR OF THE PRIVATE
FIRE MAIN PLAN SUBMITTAL APPLICATION DATE.
6. ANY PIPING NOT SHOWN ON THIS APPROVED PLAN IS NOT A PART OF THIS APPROVAL. ANY ADDITIONAL PIPING THAT IS TO BE
INSTALLED WILL REQUIRE A SEPARATE PLAN SUBMITTAL REQUIRING THE APPROVAL FROM THE OFFICE OF THE FIRE MARSHAL.
7. DUCTILE IRON PIPE SHALL BE INSTALLED WITHIN FIVE FEET OF THE BUILDING.
8. NO JOINTS SHALL BE INSTALLED UNDER THE BUILDING. THE SUPPLY LINE TO THE FIRE SPRINKLER RISERS) SHALL BE A UL LISTED
ONE PIECE SOLID SWEEP. FIRE SPRINKLER RISERS THROUGH FLOOR SLABS SHALL HAVE A SLEEVE WITH A MINIMUM OF 2 INCHES OF
CLEARANCES FOR PIPES UP TO 3 J" IN SIZE AND 4 INCHES OF CLEARANCE FOR PIPE SIZES 4 INCHES AND GREATER.
9. ALL METAL MECHANICAL RESTRAINTS, UNDER GROUND BOLTS AND STAINLESS STEEL SWEEPS SHALL BE WRAPPED IN PROTECTIVE PLASTIC
OR OTHER APPROVED CORROSION RETARDING MATERIAL
10, ALL WATERLINES EXTENDING UNDER ROADWAY SURFACES SHALL HAVE A MINIMUM COVER OF 3 INCHES MEASURED FROM THE TOP OF PIPE
TO FINISH GRADE.
11. THERE SHALL BE A MINIMUM VERTICAL CLEARANCE OF 12 INCHES BETWEEN FIRE LINES AND ALL OTHER UNDERGROUND UTILITIES. THE
12 INCHES OF CLEARANCE IS MEASURED FROM OUTSIDE OF PIPE TO OUTSIDE OF OTHER UTILITY.
12. FIRE HYDRANTS: THE MINIMUM SIZE FIRE HYDRANT SHALL BE SUPER FIRE HYDRANTS (6"X 4"X 2J"X21"). DEPENDING ON FLOW
REQUIREMENTS AN ENHANCED SUPER HYDRANT (6"X4"X4"X2j") MAY BE REQUIRED. ALL PRIVATE FIRE HYDRANTS SHALL BE PAINTED RED
AND PROVIDED WITH OSFM "NEW" SERVICE TAG AT TIME OF FINAL INSPECTION.
13. BACKFLOW PREVENTION ASSEMBLIES: PRIVATE FIRE MAINS SHALL BE PROVIDED WITH A LISTED BACKFLOW PREVENTER ACCEPTED BY THE
PUBLIC WATER AGENCY TO WHICH THE PRIVATE FIRE MAIN IS BEING SUPPLIED FROM. AT LEAST ONE INDICATING VALVE SHALL BE
INCLUDED AS PART OF ABOVE -GROUND ASSEMBLIES. BACKFLOW PREVENTION ASSEMBLIES SHALL NOT BE LOCATED WITHIN 40 FEET, OR
THE HEIGHT OF THE FACING WALL, OF THE BUILDINGS) THAT IT SERVES.
14, SECTIONAL VALVES: WHEN A PRIVATE FIRE MAIN SERVES SIX OR MORE APPURTENANCES, SECTIONAL CONTROL VALVES SHALL BE
INSTALLED. CONTROL VALVES SHALL BE INDICATING UNLESS OTHERWISE APPROVED BY THE AHJ. SECTIONAL CONTROL VALVES SHALL BE
LOCATED SO THAT NO MORE THAN FIVE FIRE APPURTENANCES ARE AFFECTED BY SHUT -DOWN OF ANY SINGLE PORTION OF THE FIRE
SERVICE MAIN.
15. IMPACT PROTECTION: ON SITE FIRE HYDRANTS, POST INDICATOR VALVES AND FIRE DEPARTMENT CONNECTIONS LOCATED LESS THAN
THREE FEET BEHIND THE FACE OF CURB OR WHEN NO CURB IS PROVIDED SHALL BE PROTECTED BY GUARD POSTS SET IN CONCRETE TO
THE FOLLOWING SPECIFICATIONS:
• CONSTRUCTION OF STEEL NOT LESS THAN 4 INCHES IN DIAMETER AND CONCRETE FILLED
• SPACED NOT MORE THAT 3 FEET BETWEEN POSTS ON CENTER
SET NOT LESS THAN 3 FEET DEEP IN CONCRETE FOOTING OF NOT LESS THAN A 15 INCHED DIAMETER
• SET WITH THE TOP OF THE POSTS NOT LESS THAN 3 FEET ABOVE GROUND
• LOCATED NOT LESS THAN 3 FEET FROM THE FIRE HYDRANTS, POST INDICATOR VALVES AND FIRE DEPARTMENT CONNECTIONS
• ALL GUARD POSTS SHALL BE PAINTED YELLOW.
BACKFILL: BACKFILL SHALL BE WELL TAMPED IN LAYERS OR PUDDLE UNDER AND AROUND PIPES TO PREVENT SETTLEMENT OR LATERAL
MOVEMENT. BACKFILL SHALL CONSIST OF CLEAN FILL SAND OR PEA GRAVEL TO A MINIMUM 6 INCHES BELOW AND TO A MINIMUM OF 12
INCHES ABOVE THE PIPE AND SHALL CONTAIN NO ASHES, CINDERS, REFUSE, ORGANIC MATTER, OR OTHER CORROSIVE MATERIALS.
OTHER BACKFILL MATERIALS ARE PERMITTED WHERE DESIGNED BY A REGISTERED PROFESSIONAL ENGINEER AND APPROVED BY THE
ENFORCING AGENCY.
17. FIRE RISER ACCESS: AUTOMATIC FIRE SPRINKLER SYSTEM RISERS SHALL NOT BE OBSTRUCTED IN ANY MANNER. IF A SYSTEM RISER IS
TO BE CONCEALED BY MEANS OF A WALL, SOFFIT, COLUMN, OR OTHER BUILDING CONSTRUCTION, IT SHALL BE PROVIDED WITH
EIGHTEEN (18) INCH CLEARANCE TO EACH SIDE AND TO THE FRONT OF THE SYSTEM RISER. ACCESS SHALL BE PROVIDED BY MEANS OF
A DOOR WITH THE MINIMUM DIMENSIONS TWO (2) FEET SIX (6) INCHES IN WIDTH BY SIX (6) FEET (8) EIGHT INCHES IN HEIGHT.
18. FIRE DEPARTMENT CONNECTIONS: EACH SEPARATE FIRE SPRINKLER SYSTEM RISER (NOT ON MANIFOLD) SHALL BE PROVED WITH A FIRE
DEPARTMENT CONNECTION (FDC). THE FDC SHALL BE LOCATED WITHIN 200 FEET OF A PUBLIC OR APPROVED FIRE HYDRANT„ WHEN
MEASURED AS A HOSE WOULD LAY ALONG AN APPROVED ROUTE. THE FDC SHALL BE LOCATED ON THE STREET SIDE OF BUILDINGS.
SYSTEMS SERVING STANDPIPES SHALL BE SIZED TO SUPPLY THE SYSTEM PRESSURE AND FLOW REQUIREMENTS BASED ON ONE 2 �"
CONNECTION FOR EACH 250 GALLONS PRE MINUTE REQUIRED. AT A MINIMUM, A 2 J"X2 J"M" FIRE DEPARTMENT CONNECTION SHALL BE
PROVIDED.
19. APPLICANT SHALL COORDINATE 'POINT OF CONNECTION OF UNDERGROUND WATER SYSTEMS WITH APPLICABLE WATER AGENCY. SUCH
COORDINATION MAY INCLUDED, BUT NOT LIMITED TO: ADDITIONAL FINANCIAL ARRANGEMENTS, FACILITY DESIGN, PLAN REVIEW, AND
FACILITY TESTING.
20. INSPECTIONS: THE FOLLOWING INSPECTIONS ARE REQUIRED:
• THRUST BLOCK PRE -POUR, RESTRAINT, PIPING MATERIAL, TRENCH, AND BACKFILL INSPECTION REQUIRED PRIOR TO BACKFILLING
• UNDERGROUND HYDROSTATIC TEST PER NFPA 24 FOR 2 HOURS
• UNDERGROUND FLUSH OF ALL AFFECTED PIPING UNTIL CLEAR. REQUIRED PRIOR TO CONNECTION OF ANY OVERHEAD PIPING.
■ UNDERGROUND FINAL - A COPY OF THE "CONTRACTORS MATERIAL AND TEST CERTIFICATE FOR UNDERGROUND PIPING" SHALL BE
PROVIDED. VALVE AND CONNECTION SIGNAGE IS IN PLACE. BLUE REFLECTOR HYDRANT MARKERS ARE INSTALLED IN THE ADJOINING
ROADWAY. PRIVATE FIRE HYDRANTS ARE PAINTED RED AND PROVIDED WITH OSFM "NEW" SERVICE TAGS.
• CONTACT TO OFFICE OF THE FIRE MARSHAL A MINIMUM OF 48 HOURS IN ADVANCE TO SCHEDULE INSPECTIONS.
THRUST
RING
A
TEE OR PLUG
CROSS WITH VALVE
Y7-V7 r�
BRYAV McKINNEY
CITY ENGINEER
R.C.E. NO. 49418
DRAWN KE DESIGNED
�)/� 0
SCALE CHECKED
DATE: AS NOTED
##4 BARS
('EPDXY
HOOK ENDS
6" MIN.
THRUST
BEARING
AREA
RFNIn
VERTICAL BEND
CONSTRUCT
SYMMETRICAL
AROUND PIPE
12" MIN.
THRUST
BEARING
REDUCER AREA
NOTE:
ALL THRUST BLOCKS
ARE CLASS C CONCRETE
ONCRETE
HRUST
LOCK
Y
rk .
#4 REBAR
1> n
° CONCRETE
a.
,�- THRUST
BLOCK
SECTION
THRUST BLOCK DETAILS
N.T.S.
ciTv QE LA QUINTA CITY OF LA QUINTA COUNTY OF RIVERSIDE, STATE OF CALIFORNIA
DATE t
EXP. 09/30/20
KE JOB NUMBER 173977
RV DATE JULY 2020
PRIVATE ON -SITE UTILITY IMPROVEMENT PLAN
SILVERROCK RESORT
GOLF CLUBHOUSE
UTILITY NOTES AND DETAIL SHEET
LOCATED WITHIN SW 1/4 OF SEC. 5 & NW, NE & SE 1/4 OF SEC. 8, T.6S.,R.7E., S.D.B.& M.
FOR: SILVERROCK DEVELOPMENT COMPANY, L.L.C.
SHEET
OF 3 SHEETS
DWG. NAME