CE-17-2312 - 78370 Highway 111, Ste 2154/11/23, 1:19 PM Print Code Enforcement Case
Code Enforcement Case: CE -17-2312
L Entered on: 06/25/2018 00:00
Printed on: 04/11/2023
Topic:
FIRE
Status:
Open
Due Date:
06/01/20
Assigned To:
Kohl Hetrick
Initiated bv:
Fire
Area #:
(Select)
Permit #: Business name: License #:
Property Location
Occupant Name: CAULFIELD COUNSELING & EDUCATION Lic: DOB:
Address: 78370 HIGHWAY 111 # 215, 92253
Phone: Cell #:
APN : 604-050-068
Owner Information
Owner Name: POINT HAPPY REALTY
Address:
Phone: Cell #:
Actions
Action By Date Time Hours Note/Observation
FIRE INSPECTION
Jose Delgado
01/01/2006
0.00
FIRE INSPECTION
Jose Delgado
01/30/2007
0.00
OK
FIRE INSPECTION
Jose Delgado
05/20/2008
0.00
Provide suite number at front door
FIRE INSPECTION
Jose Delgado
03/18/2015
0.00
FIRE INSPECTION
Jose Delgado
06/01/2017
0.00
FIRE INSPECTION
Reyna
06/25/2018 1:40 pm
0.25
Re -Inspection 7/25/18
Camarena
FIRE INSPECTION
Jose Delgado
08/06/2018 1:30 pm
0.00
Fines to be assed on next visit if compliance is not met.
FIRE REINSPECTION Jose Delgado 09/18/2018 0.00 Non-compliant, customer is to call back for follow up. Work is to be
conducted by
Violations
N Violation Type Due Date Status 11111M Closed Date
Inspection Notes
Date: Time:
Findings
https:Huser.govoutreach.com/laquintaca/ceeditcase.php 1 /1
VERSIDE COUNTY FIRE DEPA [ENT wq
FIRE PROTECTION PLANNING SECTION
FIRE & LIFE SAFETY NOTICE =F,,
C
Inspection Date: 67 � Inspection Time: / -,yo /m Occupancy Class: C?
Inspected By: Phone (Ica) S9,5 F"v4' 47"1 -
Facility Name: -c..wG Facility Phone:
Site Address: .170 �j/ �` /S City: State: �� Zip: �1� S�:e
Owner/Contact Name:Contact Phone: Fax: (•y ) -,-.
Mailing Address: » City: !, -, =:p State:e.4 Zip: '?.?Z
-A�e est/ Received Date 9 - 6 - / 8 Signature of Recipient:x
At this time a notice was issued indicating the corrections required to provide compliance with the applicable codes, regulation and ordinances. All items shall be
corrected IMMEDIATELY. If you have any questions regarding this information, please contact the Riverside County Fire Department at (760) 863-8886
PREMISES IDENTIFICATION
nbers plainly visible and legible. (CFC 505.1)
access at Gate and Main Door. (CFC 506.1)
Emergency Information (CFC 404.2)
HYDRANT, FDC, PCV
Caps missing. (CFC 508.5.2, 912.6)
-Obstructions. (CFC 508.5.4)
Blue Dots. (RCoStandard)
Signage. ( CFC 510.1)
FIRE APPARATUS ACCESS ROADS
Red curb or signs. (CFC 503.3)
Obstructions (Width 20', Vertical 13'6'"). (CFC 503.2.1)
Minimum 2A I OBC. (CFC 906.3)
ervicing due. (CFC 906.2)
punting <5 feet from Floor. (CFC 906.9)
Obstructions. (CFC 906.6)
Commercial kitchen. (CFC 904.11.5)
FIRE ALARM
_ Serviced (CFC 907.20.5)
FACP Room Signage (CFC 510.1)
AUTOMATIC FIRE SPRINKLER SYSTEMS
5 yr. riser/sprinkler servicing. (NFPA 25, Table 5.1)
18" clearance below sprinkler head deflectors. (CFC 315.2.1)
_ Inspectors valve lest. (NFPA 13)
Sprinkler wrench. (NFPA 13)
6-12 spare sprinkler heads. (NFPA 13)
_Missing escutcheon. (NFPA 13)
Riser Room Signage (CFC 510.1)
HOOD AND DUCT SYSTEMS
Service with in 6 months. (CFC 904.11.6.4)
Proper nozzle position, caps, coverage. (NFPA 25, 10.2.5.3)
_ Fusible links, cables, conduits. (CFC 904.11.6.5)
Filters/ducts clean. (CFC 904.11.6.3)
FLAMMABLE LIQUIDS (CLASS 1, II, H -A)
Approved safety cans. (CFC 3404.3.1.1)
Approved cabinets exceeding 10 gals. (CFC 3404.3.4.4)
_ Legible labeling. (CFC 3403.5)
Placard/NFPA 704 (CFC 3404.2.3.1)
Secondary Containment (CFC 3405.3.7.5.3)
GENERAL HOUSEKEEPING
_ Rubbish/trash buildup. (CFC 304.1)
_ Secure pressurized cylinders. (CFC 3003.5.3)
Clearance around water heater. (CFC 305.1)
_ Storage not within 24 inches ceiling. (CFC 315.2.1)
_ Storage under stairs prohibited. (CFC)
Storage, use and handling of combustible materials in attic, under floor &
concealed spaces. (CFC 315.2.4)
Storage in boiler rooms, mechanical rooms or electrical equipment rooms
not allowed. (CFC 315.2.3)
WALLS AND CEILING
_ Holes in fire rated walls sealed. (CFC 703.1)
Tiles in fire rated ceilings in place and undamaged. (CFC 703.1)
EXITS
Common knowledge hardware. (CFC 1008.1.8)
Sign above door stating "This Door To Remain Unlocked When Business Is
Occupied. (CFC 1008.1.8.3)
Illuminated EXIT sign(s) operable. (CFC 1028.4) C -f 0&11nal-e)
44" clear access width to exits. (CBC)
Exit obstruction. (CFC 1028.3)
Maintain fire rated doors, windows, dampers and hardware. (CFC 703.1)
Emergency lighting operable. (CFC )
Panic hardware operable. (CFC 1008.1.9)
OCCUPANT LIMIT/SIGN
_ Occupant load sigu(s) posted. (CFC 1004.3)
Required NO SMOKING signs. (CFC 310.3)
ELECTRICAL
_ Multiplug adapters not allowed, (CFC 605.4)
_ Circuit breaker panel - Clear and labeled. (CFC 605.3)
_ Abatement of electrical hazards. (CFC 605.1)
Extension cords not allowed as permanent wiring. (CFC 605.5)
Outlet faceplate/covers in place. (CFC 605.6)
Comments: Q.s TE.rd-v yin !.-6x7 !vi J/7 z,Ir vaY7 )®L'GN{e /- A,a7 -7 t- 7. ;5�6_Z l-
9 - i 6- /8 c -'e /.r M eAvez_ d o c- c/P.
02,
WGI,aC 74r !'b sE cs�vavc.s�
Inspection Date:_
Inspected By:
Facility Name:
R BIDE COUNTY FIRE DEPART. iT
FIRE PROTECTION PLANNING SECTION
FIRE & LIFE SAFETY NOTICE
Inspection Time: / 11,,
Site Address: ' ' 'If '-' .-
Owner/Contact
Owner/Contact Name:
Mailing Address:
Phone C, }
Occupancy Class: Z?
Facility Phone:
City: 44 State:
Contact Phone: Fax: { �-
City: 1- J�:
State
Zip:
Zip:
Request 1 Received Date Signature of Reciplent:k
At this time a notice was issued indicating the corrections required to provide compliance with the applicable codes, regulation and ordinances. All items shall be
corrected IMMEDIATELY. If you have any questions regarding this information, please contact the Riverside County Fire Department at (760) 863-8886
PREMISES IDENTIFICATION
—Numbers plainly visible and legible. (CFC 505.1)
KNOX ACCESS
Knox access at Bete and Qa(CFC 506.1)
EMERGENCY INFORMATION
Emergency Information (CFC 404.2)
HYDRANT, FDC, PIV
_ Caps missing. (CFC 508.5.2; 912.6)
Obstructions. (CFC 508.5.4)
Blue Dots. (RCoStandard)
Signage. ( CFC 510.1)
FIRE APPARATUS ACCESS ROADS
Red curb or signs. (CFC 503.3)
Obstructions (Width 20', Vertical 13'6"). (CFC 503.2.1)
Minimum 2A IOBC. (CFC 906.3)
-rvicing due. (CFC 906.2)
Iy(ounting <5 feet from floor. (CFC 906.9)
/Obstructions. (CFC 906.6)
Commercial kitchen. (CFC 904.11.5)
FIRE ALARM
Serviced (CFC 907.20.5)
FACP Room Signage (CFC 510.1)
AUTOMATIC FIRE SPRINKLER SYSTEMS
5 yr. riser/sprinkler servicing. (NFPA 25, Table 5.1)
18" clearance below sprinkler head deflectors. (CFC 315.2.1)
_ Inspectors valve test. (NFPA 13)
Sprinkler wrench. (NFPA 13)
6-12 spare sprinkler heads. (NFPA 13)
Missing escutcheon. (NFPA 13)
Riser Room Signage (CFC 510.1)
HOOD AND DUCT SYSTEMS
_ Service with in 6 months. (CFC 904.11.6.4)
_ Proper nozzle position, caps, coverage. (NFPA 25, 10.2.5.3)
Fusible links, cables, conduits. (CFC 904.11.6.5)
Filters/ducts clean. (CFC 904.11.6.3)
Comments:
FLAMMABLE LIQUIDS (CLASS 1, 11, II -A)
Approved safety cans. (CFC 3404.3.1.1)
Approved cabinets exceeding 10 gals. (CFC 34043.4.4)
Legible labeling. (CFC 3403.5)
Placard/NFPA 704 (CFC 3404.2.3.1)
Secondary Containment (CFC 3405.3.7.5.3)
GENERAL HOUSEKEEPING
Rubbishltrash buildup. (CFC 304.1)
_ Secure pressurized cylinders. (CFC 3003.5.3)
Clearance around water heater. (CFC 305.1)
_ Storage not within 24 inches ceiling. (CFC 315.2.1)
Storage under stairs prohibited. (CFC)
Storage, use and handling of combustible materials in attic, under floor &
concealed spaces. (CFC 315.2.4)
Storage in boiler rooms, mechanical rooms or electrical equipment rooms
not allowed. (CFC 315.2.3)
WALLS AND CEILING
_ Holes in fire rated walls scaled. (CFC 703.1)
Tiles in fire rated ceilings in place and undamaged. (CFC 703.1)
EXITS
Common knowledge hardware. (CFC 1008.1.8)
Sign above door stating "This Door To Remain Unlocked When Business Is
A—Aumi ed. (CFC sign( .8.3)
aminated EXIT sign(s) operable. (CFC 1028.4)+-," ,��- "�•
44" clear access width to exits. (CSC)
Exit obstruction. (CFC 1028.3)
Maintain fire rated doors, windows, dampers and hardware. (CFC 703.1)
_ Emergency lighting operable. (CFC )
Panic hardware operable. (CFC 1008.1.9)
OCCUPANT LIMIT/SIGN
Occupant load sign(s) posted. (CFC 1004.3)
Required NO SMOKING signs. (CFC 310.3)
ELECTRICAL
Multiplug adapters not allowed. (CFC 605.4)
Circuit breaker panel — Clear and labeled. (CFC 605.3)
Abatement of electrical hazards. (CFC 605.1)
Extension cords not allowed as permanent wiring. (CFC 605.5)
Outlet faceplate/covers in place. (CFC 605.6)
AS;RSIDE COUNTY FIRE DEP NTS z
FIRE PROTECTION PLANNING SECTIONAl
FIRE & LIFE SAFETY NOTICE
Inspection Date:-� % Inspection Time: Occupancy Class:
Inspected By: 6 OAZ Phone (%j} 77Z -7D%1
Facility Name: _ Facility Phone: ( }
Site Address: 17&376 Ykl"-1 /it 4 16 City:__ A State:",gq — Zip: '
Owner/Contact Name: Contact Phone: (
Mailing Address:
Request 1 Received Date
City:
Signature of Recipient:
} Fax: {
State:
Zip:
At this time a notice was issued indicating the corrections required to provide compliance with the applicable codes, regulation and ordinances. All items shall be
corrected IMMEDIATELY. If you have any questions regarding this information, please contact the Riverside County Fire Department at (760) 863-8886
PRENIISES IDENTIFICATION
Numbcrs plainly N isible and legible. (CFC 505.1)
KNOX ACCESS
Knox access at Gate and Main Door. (CFC 506.1)
EMERGENCY INFORMATION
Emergency Information (CFC 404.2)
HYDRANT, FDC, PIV
Caps missing. (CFC 508.5.2, 912.6)
Obstructions. (CFC 508.5.4)
Blue Dots. (RCoStandard)
Signage. ( CFC 510.1)
FIRE APPARATUS ACCESS ROADS
Red curb or signs. (CFC 503.3)
Obstructions (Width 20', Vertical 13'6"). (CFC 503.2.1)
FIRE EXTINGUISHERS
_ Minimum 2Al OBC. (CFC 906.3)
_ Servicing due. (CFC 906.2)
_ Mounting <5 feet from floor. (CFC 9069)
Obstructions. (CFC 906.6)
Commercial kitchen. (CFC 904.11.5)
FIRE ALARM
_ Serviced (CFC 907.20.5)
FACP Room Signage (CFC 510.1)
.AUTOMATIC FIRE SPRINKLER SYSTEMS
5%r rkcr'sprinklor sur%icing, (NFPA 25, Table 5.1)
18" clearance below sprinkler head deflectors. (CFC 315.2.1)
Inspectors valve test. (NFPA 13)
_ Sprinkler wrench. (NFPA 13)
_ 6-12 spare sprinkler heads. (NFPA 13)
Missing escutcheon. (NFPA 13)
Riser Room Signage (CFC 510.1)
HOOD AND DUCT SYSTEMS
Service with in 6 months. (CFC 904.11.6.4)
Proper nozzle position, caps, coverage. (NFPA 25, 10.2.5.3)
_ Fusible links, cables, conduits. (CFC 904.11.6.5)
Filters/ducts clean. (CFC 404.11.6.3)
Comments:
FLAMMABLE LIQUIDS (CLASS I, I1, II -A)
Approved safety cans. (CFC 3404.3.1.1)
Approved cabinets exceeding 10 gals. (CFC 3404.3.4.4)
_ Legible labeling. (CFC 3403.5)
Placard/NFPA 704 (CFC 3404.23.1)
Secondary Containment (CFC 3405.3.7.5.3)
GENERAL HOUSEKEEPING
Rubbish/trash buildup. (CFC 304.1)
Secure pressurized cylinders. (CFC 3003.5.3)
Clearance around water heater. (CFC 305.1)
Storage not within 24 inches ceiling. (CFC 315.2.1)
Storage under stairs prohibited. (CFC.)
Storage, use and handling of combustible materials in attic, under floor &
concealed spaces. (CFC 315.2.4)
Storage in boiler rooms, mechanical rooms or electrical equipment rooms
not allowed. (CFC 315.2.3)
WALLS AND CEILING
Holes in fire rated walls sealed. (CFC 703.1)
Tiles in fire rated ceilings in place and undamaged. (CFC 703.1)
EXITS
_ Common knowledge hardware. (CFC 1008.1.8)
Sign above door stating "This Door To Remain Unlocked When Business Is
Occupied. (CFC 1008.1.8.3)
_ Illuminated EXIT sign(s) operable. (CFC. 1028.4)
_ 44" clear access width to exits. (CBC)
Exit obstruction. (CFC 10283)
_ Maintain fire rated doors, windows, dampers and hardware. (CFC 703.1)
_ Emergency lighting operable. (CFC )
Panic hardware operable. (CFC 1008.1.9)
OCCUPANT LIMIT/SIGN
—Occupant load sign(s) posted. (CFC 1004.3)
Required NO SMOKING signs. (CFC 310.3)
ELECTRICAL
Multiplug adapters not allowed. (CFC 605.4)
_ Circuit breaker panel – Clear and labeled. (CFC 605.3)
Abatement of electrical hazards. (CFC 605.1)
Extension cords not allowed as permanent wiring. (CFC 605.5)
Outlet faceplate/covers in place. (CFC 605.6)
t I RSIDE COUNTY FIRE DEPART iT
FIRE PROTECTION PLANNING SECTION
FIRE & LIFE SAFETY NOTICE
Inspection Date: Inspection Time:
Inspected By: i
Phone}
Occupancy Class:
Facility Name: o Facility Phone: ( }
Site Address: 7Z ' City: 4_ 14 /,Y L) o"i r4 Stater'/) Zip:`off,
Owner/Contact Name: Contact Phone: (
Mailing Address:
Request / Received Date
City:
Signature of Recipient:
} Fax: ( )
State: Zip:
At this time a notice was issued indicating the corrections required to provide compliance with the applicable codes, regulation and ordinances. All items shall be
corrected IMMEDIATELY. If you have any questions regarding this information, please contact the Riverside County Fire Department at (760) 863-8886
PREMISES IDENTIFICATION
Numbers plainly visible and legible. (CFC 505.1)
KNOX ACCESS
Knox access at Gate and Main Door. (CFC 506.1)
EMERGENCY INFORMATION
____ Emergency Information (CFC 404.2)
HYDRANT. FDC. PI V
Caps missing. (CFC 508.5.2, 912.6)
Obstructions. (CFC 508.5.4)
_ Blue Dots. (RCoStandard)
Signage. ( CFC 510.1)
FIRE APPARATUS ACCESS ROADS
Red curb or signs. (CFC 503.3)
Obstructions (Width 20', Vertical 13'6"). (CFC 503.2.1)
FIRE EXTINGUISHERS
Minimum 2A1 OBC. (CFC 906.3)
_ Servicing due. (CFC 906.2)
Mounting <5 feet from floor. (CFC 906.9)
Obstructions. (CFC 906.6)
Commercial kitchen. (CFC 904.11.5)
FIRE ALARM
_ Serviced (CFC 907.20.5)
FACP Room Signage (CFC 510.1)
AUTOMATIC FIRE SPRINKLER SYSTEMS
5 yr. riserlsprinkler servicing. (NFPA 25, Table 5.1)
18" clearance below sprinkler head deflectors. (CFC 315.2.1)
_ Inspectors valve test. (NFPA 13)
Sprinkler wrench. (NFPA 13)
6-12 spare sprinkler heads. (NFPA 13)
_ Missing escutcheon. (NFPA 13)
Riser Room Signage (CFC 510.1)
HOOD AND DUCT SYSTEMS
_ Service with in 6 months. (CFC 904.11.6.4)
_ Proper nozzle position, caps, coverage. (NFPA 25, 10.2.5.3)
_ Fusible links, cables, conduits. (CFC 904.11.6.5)
Filtersiducts clean. (CFC 904.11.6.3)
Comments:
FLAMMABLE LIQUIDS (CLASS 1, 11, II -A)
Approved safety cans. (CFC 3404.3.1.1)
Approved cabinets exceeding 10 gals. (CFC 3404.3.4.4)
_ Legible labeling. (CFC 3403.5)
_ Placard/NFPA 704 (CFC 3404.2.3.1)
Secondary Containment (CFC 3405.3.7.5.3)
GENERAL HOUSEKEEPING
_ Rubbish/trasb buildup. (CFC 304.1)
_ Secure pressurized cylinders. (CFC 3003.5.3)
Clearance around water heater. (CFC 305.1)
— Storage not within 24 inches ceiling. (CFC 315.2.1)
�_ Storage under stairs prohibited. (CFC)
Storage, use and handling of combustible materials in attic, under floor &
concealed spaces. (CFC 315.2.4)
Storage in boiler rooms, mechanical rooms or electrical equipment rooms
not allowed. (CFC 315.2.3)
WALLS AND CEILING
Holes in fire rated walls sealed. (CFC 703.1)
Tiles in fire rated ceilings in place and undamaged. (CFC 703.1)
EXITS
Common knowledge hardware. (CFC 1008.1.8)
__ Sign above door stating "This Door To Remain Unlocked When Business Is
Occupied. (CFC 1008.1.8.3)
_.Illuminated EXIT sign(s) operable. (CFC 1028.4)
44" clear access width to exits. (CBC)
Exit obstruction. (CFC 1028.3)
Maintain fire rated doors, windows, dampers and hardware. (CFC 703.1)
_ Emergency lighting operable. (CFC )
Panic hardware operable. (CFC 1008.1.9)
OCCUPANT LIMIT/SIGN
Occupant load sign(s) posted. (CFC 1004.3)
Required NO SMOKING signs. (CFC 310.3)
ELECTRICAL
_ Multiplug adapters not allowed. (CFC 605.4)
Circuit breaker panel — Clear and labeled. (CFC 6053)
Abatement of electrical hazards. (CFC 605.1)
Extension cords not allowed as permanent wiring. (CFC 605.5)
Outlet faceplate/covers in place. (CFC 605.6)
RI SIDE COUNTY FIRE DEPARTAT
FIRE PROTECTION PLANNING SECTION
FIRE & LIFE SAFETY NOTICE
T -ID #
LOCATION
ITEM NEEDING CORRECTION
DATE
1) HYDRANT, FDC PIV
I
rr
a) Caps missing. CFC 100 1.6.2
BUS. NAME
_ a) Approved safety cans. CFC 7902.1.8.1
L,Y.
! UBC TYPE
NOTICE NO.
ADDRESS
'A
.` 7l� f u- i CITY L- .
PHONE
INSPECTED BY
71
C C.Iv TITLE r
STA
RECEIVED BY ? TITLE
At this time a notice was issued indicating the corrections required to provide compliance with the applicable codes, regulations and ordinances. All items shall
be corrected IMMEDIATELY. If you have any questions regarding this information, please contact the Fire Protection Planning Section at (760) 863-8886.
SIGNED
RE -INSPECTION DATE
ITEM NEEDING CORRECTION
LOCATION
ITEM NEEDING CORRECTION
LOCATION
1) HYDRANT, FDC PIV
8) FLAMMABLE LIQUIDS (Class I, II, III -A)
a) Caps missing. CFC 100 1.6.2
_ a) Approved safety cans. CFC 7902.1.8.1
b) Obstructions. CFC 1001.7.1
_ b) Approved cabinets exceeding 10 gal. CFC 7902.5.9
c) Red curb -15' each side. CFC 1001.8
_ c) Legible labeling. CFC 7901.9
2) FIRE APPARATUS ACCESS ROADS
9) GENERAL HOUSEKEEPING
a) Red curb or signs. CFC 901.4
_ a) Rubbish/trash buildup. CFC 1103.2
_
b) Obstructions (Width 20', Vertical 13'6").
b) Secure pressurized cylinders. CFC 7401.6
CFC 902.2.2.1
_ c) 36" clearance around water heater. CMC 304.1
3 PREMISES IDENTIFICATION
_ d) Storage not within 24 inches of ceiling.
CFC 1103.3.2.2
a) Numbers plainly visible and legible. CFC 9014.4
_ e) Storage under stairs prohibited. CFC 1210.3
4) FIRE EXTINGUISHERS
_f) Storage, use and handling of combustible materials
a) Minimum 2A10BC. CFC 1001.10
in attic, under floor 8 concealed spaces.
T b) Servicing due. CFC 1002.1, 7-19
c) Mounting 3-5 feet from floor. CFC Standard 10-1-6.9
CFC 1103.3.2.5
g) Storage in boiler rooms, mechanical rooms or
_
d) Obstructions. CFC Standard 10.1-6.5
electrical equipment rooms not allowed.
e) Commercial kitchen. CFC 1005.2.7
CFC 1103.3.2.4
h) Candles and other open flame devices used in
5) AUTOMATIC FIRE SPRINKLERS SYSTEMS
approved manner. CFC 2501.17
a) 5 yr. riser/sprinkler servicing.
_ i) Candles and other open flame devices in places of
T-19 Art, 4, Sec. 904A
assembly or drinking or dining establishments.
b) Clearance to riser. CFC 1001.7.1
CFC 2501.18
c) 18" clearance below sprinkler head deflectors.
10) WALLS AND CEILINGS
NFPA 13
d) Inspectors valve test. NFPA 13
_ a) Holes in tire rated walls sealed. CFC 1111
e) Sprinkler wrench. NFPA 13
_ b) Tiles in lire rated ceilings in place and undamaged.
6-12 spare sprinkler heads. NFPA 13
CFC 1112
_f)
ig) Missing escutcheon. NFPA 13
11) EXITS
B) HOOD AND DUCT SYSTEMS
n 11i�
_ a) Common knowledge hardware. CBC 1003.3.1.8
"This
a) Service within 6 months. CFC 1005.2.8
41�c`J' V
_ b) Sign above door stating Door To Remain
b) Proper nozzle position, caps, coverage.
Unlocked During Business Hours. CBC 1003.3.1.8
c) Illuminated EXIT sign(s) operable. CBC 1003.2.8.4
CFC 1005.2.8
c) Automatic gas/electric strut off. CFC 1005.2.4.1
_ _
_ c) 44" clear access aisle width to exits. CBC 1014.2
d) Fuseable links, cables, conduits. CFC 1006.2.8
_ d) Exit obstruction. CFC 1203
e) Maintain fire rated doors, windows, dampers, and
— e) Filters/ducts clean. CFC 1005.2.8
hardware. CFC 1112.2
7) ELECTRICAL
_f) Emergency lighting operable. CBC 1003.2.9
a) Zip cords/cube adapters not allowed. CFC 8507
g) Panic hardware operabte. CBC 1003.3.1.9
b) Circuit breaker panel - Clear, unobstructed
12) OCCUPANT LIMIT/SIGN
means of access with a minimum width of 30"
and a minimum of 78". CFC 8509
_ a) Occupant load signs) posted. CFC 2501.16
c) Abatement of electrical hazards. CFC 8504
_ b) Required NO SMOKING signs.
d) Extension cords not allowed as permanent wiring.
13) KNOX BOX/KEYS
CFC 8506_
a) CFC 902.4
e) Outiet faceplate/covers in place. NEC 380-9
b) City Permit required CBC 106.1
_f) Cover open space in circuit breaker panel. CFC 6504
COMMENTS
264-161 FPPS (Rev 11106) COPIES TO: WHITE—BUSINESS; YELLOW—INSPECTOR; PINK—FIRE
TID#
BUS. NAME
ADDRESS
INSPECTED BY
RECEIVED BY
RI1 SIDE COUNTY FIRE DEPARTNItraT
FIRE PROTECTION PLANNING SECTION
FIRE & LIFE SAFETY NOTICE
DATE
UBC TYPE NOTICE NO.
CITY PHONE
TITLE STA
TITLE
At this time a notice was issued indicating the corrections required to provide compliance with the applicable codes, regulations and ordinances. All items shall
be corrected IMMEDILTELY. If you have any questions regarding this information, please contact the Fire Protection Pianning Section at (760) 863-8886.
SIGNED
RE -INSPECTION DATE
ITEM NEEDING CORRECTION
LOCATION
ITEM NEEDING CORRECTION
LOCATION
1) HYDRANT, FOC PIY
8) FLAMMABLE LIQUIDS (Class 1, 11, III -A)
a) Caps missing. CFC 1001.6.2
_a) Approved safety cans. CFC 7902.1.8.1
_ b) Obstructions. CFC 1001.7.1
_ b) Approved cabinets exceeding 10 gal. CFC 7902.5.9
— c) Red curb -15' each side. CFC 1001.8
c) Legible labeling. CFC 7901.9
2) FIRE APPARATUS ACCESS ROADS
9) GENERAL HOUSEKEEPING
a) Red curb or signs. CFC 901.4
a) Rubbish/trash buildup. CFC 1103.2
b) Obstructions (Width 20', Vertical 13'6").
_ b) Secure pressurized cylinders. CFC 7401.6
CFC 902.2.2.1
c) 36" clearance around water heater. CMC 304.1
3) PREMISES IDENTIFICATION
_ d) Storage not within 24 inches of ceiling.
CFC 1103.3.2.2
a) Numbers plainly visible and legible. CFC 901.4.4
e) Storage under stairs prohibited. CFC 1210.3
4) FIRE EXTINGUISHERS
_ f) Storage, use and handling of combustible materials
a) Minimum 2A100C. CFC 1001,10
in attic, under floor & concealed spaces.
b) Servicing due. CFC 1002.1, T-19
CFC 1103.3.2.5
c) Mounting 3-5 feet from floor. CFC Standard 10-1-6.9
_ _ g) Storage in boiler rooms. mechanical rooms or
d) Obstructions. CFC Standard 10-1-6.5
electrical equipment rooms not allowed.
e) Commercial kitchen. CFC 1005.2.7
CFC 1103.3.2.4
h) Candles and other open flame devices used in
5) AUTOMATIC FIRE SPRINKLERS SYSTEMS
approved manner. CFC 2501.17
a) 5 yr riser/sprinkler servicing.
i) Candles and other open lame devices in places of
T-19 Art. 4, Sec. 904A
assembly or drinking or dining establishments.
b) Clearance to riser CFC 1001.7.1
CFC 2501.18
e) 18" clearance below sprinkler head deflectors.
NFPA t3
10) WALLS AND CEILINGS
) Inspectors valve test. NFPA 13
_ a) Holes in tire rated walls sealed. CFC 1111
e
e) Sprinkler wrench. NFPA 13
b Tiles in fire rated ceilings lace undamaged
)gs in
— P and 9
_
t) 6-12 spare sprinkler heads. NFPA 13
CFC 1112
g) Missing escutcheon. NFPA 13
11) EXITS
6) HOOD AND DUCT SYSTEMS
_ a) Common knowledge hardware. CBC 1003.3.1.8
a) Service within 6 months. CFC 1005.2.8
_ b) Sign above door stating "This Door To Remain
b) Proper nozzle position, caps, coverage.
Unlocked During Business Hours. CBC 1003.3.1.6
CFC 1005.2.8
, c) Illuminated EXIT sign(s) operable. CBC 1003.2.8.4
c) Automatic gas/electric shut off. CFC 1005.2.4.1
— c) 44" clear access aisle width to exits. CBC 1014.2
d) Fuseable links, cables, conduits. CFC 1006.2.8
_ d) W obstruction. CFC 1203
e) Filtersiducts clean. CFC 1005.2.8
— e) Maintain tire rated doors, windows, dampers, and
hardware. CFC 1112.2
71 ELECTRICAL
_ f) Emergency lighting operable. CBC 1003.2.9
a) Zip cordsrcube adapters not allowed. CFC 8507
_ g) Panic hardware operable. CBG 1003.3.1.9
b) Circuit breaker panel - Clear, unobstructed
means of access with a minimum width of 30"
12j OCCUPANT LIMIT/SIGN
and a minimum of 78". CFC 8509
_ a) Occupant load sign(s) posted. CFC 2501.16
_ c) Abatement of electrical hazards. CFC 8504
_ b) Required NO SMOKING signs.
d) Extension cords not allowed as permanent wiring.
13) KNOX BOX/KEYS
CFC 8506_
a) CFC 902.4
e) Outlet faceplate/covers in place. NEC 380-9
b) City Permit required CBC 106.1
f) Cover open space in circuit breaker panel. CFC 8504
_
COMMENTS
264-161 FPPS (Rev 11706) COPIES TO. WHITE—BUSINESS; YELLOW INSPECTOR, PINK—FIRE
# IStreet # Street Name
G - 78-370 lHichway 111
193 111
Issue Permit Espiratio Inspection Dat
1111200E
No
Permits subior
Other
Suite loccupaut Name
215 I, C Real Estate
Inspeet 3rd Inspect 4th Inspect
Duc