BSOL2022-0649 Plans
SCOPE OF WORK GENERAL NOTES TABLE OF CONTENTS PAGE # DESCRIPTION SYSTEM SIZE: 17220W DC 1140OW AC PV 1.0 COVER SHEET MODULES: (42) PHONO SOLAR PS410M1H-24/TH LOCAL UTILITY PROVIDER SHALL BE NOTIFIED PRIOR TO USE AND ACTIVATION OF ANY INVERTER(S): (1) SOLAREDGE SE1140OH-US [240V] SOLAR PHOTOVOLTAIC INSTALLATION OPTIMIZER (S): (42) SOLAREDGE P505 THIS PROJECT SHALL COMPLY LOCAL ORDINANCES PV 2.0 SITE PLAN RACKING: IRONRIDGE XR10 PROPER ACCESS AND WORKING CLEARANCE WILL BE PROVIDED ATTACHMENT: QUICK MOUNT PV QMHLS ALL ELECTRICAL WORK SHOWN ON THESE PLANS WILL BE COMPLETED BY THE PV 3.0 - 3.1 DETAIL LAYOUT OCCUPANCY: PRIMARY RESIDENCE CONTRACTOR ALL APPLICABLE PV EQUIPMENT LISTED AND COMPLIANT WITH UL2703 AND UL1703 PV 4.0 MOUNTING DETAIL PV 5.0 ELECTRICAL DIAGRAM CONSTRUCTION TYPE: RESIDENTIAL ALL ROOF PENETRATIONS TO BE SEALED WITH A HIGH PERFORMANCE ROOF SEALANT SUCH AS GeoCel 2300 CLEAR SEALANT PV 6.0 WARNING LABELS This approval is for compliance to the current adopted building codes for the proposed 0 THE SYSTEM WILL NOT BE INTERCONNECTED UNTIL APPROVAL FROM THE LOCAL Solar System only. It is the owner's/applicant's responsibility to ensure that the proposed JURISDICTION AND THE UTILITY IS OBTAINED installation of solar systems and associated equipment is on legally permitted structures. 0 THE SOLAR PHOTOVOLTAIC INSTALLATION SHALL NOT OBSTRUCT ANY PLUMBING, If determined by inspection staff the proposed solar system is installed on non -permitted MECHANICAL, OR BUILDING ROOF VENTS structures, any required modifications needed for code compliance will be at the . IF THE EXISTING MAIN PANEL DOES NOT HAVE VERIFIABLE GROUNDING ELECTRODE, IT IS owner's/applicant's expense THE INSTALLERS RESPONSIBILITY TO INSTALL A SUPPLEMENTAL GROUNDING ELECTRODE • EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED ON THE MODULE AND THE MANUFACTURER'S INSTALLATION INSTRUCTIONS • INSTALLATION OF A PV SYSTEM MOUNTED ON . A LADDER SHALL BE IN PLACE FOR THE INSPECTION IN COMPLIANCE WITH CALOSHA RESIDENTIAL BUILDING. REGULATIONS • ALL WORK SHALL COMPLY WITH 2022 CEC, 2022 CRC, MUNICIPAL CODE, AND ALL • CEC 2022, CRC 2022 MANUFACTURERS' LISTINGS AND INSTALLATION INSTRUCTIONS. • PHOTOVOLTAIC SYSTEM WILL COMPLY WITH 2022 CEC. • ELECTRICAL SYSTEM GROUNDING WILL COMPLY WITH 2022 CEC. • PHOTOVOLTAIC SYSTEM IN UNGROUNDED, NO CONDUCTORS ARE SOLIDLY GROUNDED IN • MAIN BREAKER DERATE: REPLACE EXISTING MAIN THE INVERTER, SYSTEM COMPLIES WITH 690.35. BREAKER WITH NEW 175 AMP MAIN BREAKER. 0 MODULES CONFORM TO AND ARE LISTED UNDER UL 1703. • INVERTER CONFORMS TO AND IS LISTED UNDER UL 1741. • ELECTRICAL EQUIPMENT AND MATERIAL TO BE LISTED, LABELED, AND INSTALLED PER THE CEC, THE INSTALLATION STANDARDS/MANUFACTURER'S RECOMMENDATIONS AND, IF REQUIRED A RECOGNIZED ELECTRICAL TESTING LABORATORY. BSOL2022-0649 CI TY OF LA QU N TA BU LEI N GCI VI 9 ON VICINITY MAP REM EYED FOR COME CMLI M CE dmk Coachella E, A. oma: 02/23/2023 OWNER INSTALLED ECTOR 17.2kW SOLAR ARRAY - e n o l n e e R s (42) 41 OW PHONO SOLAR lei 657 W. GALENA PARK "VD. STE. 781 PHONE (80 7) 990-7775 PANELS+SOLAREDGE DRAPER, UTAH 84828 WWW.VECTOR5E.COM �FESSI P505 OPTIMIZERS W/(1) NSC 55515 Southern Hill, La 4� �© pN ,� cry, SOLAREDGE �� ANTONIO DIAS �iI a, CA 92253, USA � � �y SE11400H-US INVERTER 55515 SOUTHERN HILLS x"'00 Sandy Korner Thermal ��' J ' AND DERATING OF 175A LA QUINTA CA 92253 Ar _7 SERVICE TO 150A Email: antonio.m.dias@outlook.com r 041 Vista ED * * [907SF] 2019 CALIFORNIA Phone: 714-376-5708 Santa RosasT STRUCTuaP�. ELECTRICAL CODE. REV tiP E OF DATE 01 FEBRUARY 2023 GA1-1F 02/02/2023 VSE Project Number: U2557.0801.221 COVER SHEET Vector Structural Engineering has reviewed the existing structure with loading from the solar array and screw connections to the existing framing. The design of the racking system, racking connections, and all other is by Mechanical, PV 1. structural others. architectural, and all other nonstructural aspects of the design are by others. Electrical is by others, unless stamped by Dean Levorsen. SITE PLAN: 1/32" = 1'-0" z DRIVEWAY ROOF ACCESS POINT (N) ARRAY AR -01 (N) ARRAY AR -02 55515 SOUTHERN HILLS (E) POOL — (E) FENCE (E) RESIDENCE (N) ARRAY AR -03 BSOL2022-0649 CI TY OF LA Qll N TA BU LCl N GO VI S ON REVI EVED FOR COCE COIWLI AV CE W A, 6-4j,, ME: 02/23/2023 ROOF MODULE LAYOUT + EQUIPMENT LOCATIONS: 1 /16" = 1'-0" N (E) UTILITY METER (E) MAIN SERVICE PANEL, 200A RATED, 240V (E) SUB PANEL (N) AC DISCONNECT (N) IQ COMBINER (N) JUNCTION BOX (N) ARRAY AR -01 (N PATH (ACROSS THE ROOF) (E) CHIMNEY (N) ARRAY AR -03 OWNER INSTALLED LEGEND �M METER MP MAIN SERVICE PANEL AC AC DISCONNECT FIQI IQ COMBINER JB JUNCTION BOX ROOF (E) CHIMNEY (N) ARRAY AR -03 OWNER INSTALLED ANTONIO DIAS 55515 SOUTHERN HILLS LA QUINTA CA 92253 Email: antonio.m.dias@outlook.com Phone: 714-376-5708 REV A DATE: 01 FEBRUARY 2023 SITE PLAN PV 2.0 SOLAR ROOF ROOFAREA ROOF ARRAY ROOF AREA COVERAGE SOLAR AREA SLOPE TILT AZIMUTH (LBS) #MOD (SQFT) (SQFT) AR -01 18° 18° 270° 605.76 5780 15.72 1388.8 28 AR -02 18° 18° 270° 173.07 396.8 8 AR -03 18° 18° 180° 129.81 297.6 6 ANTONIO DIAS 55515 SOUTHERN HILLS LA QUINTA CA 92253 Email: antonio.m.dias@outlook.com Phone: 714-376-5708 REV A DATE: 01 FEBRUARY 2023 SITE PLAN PV 2.0 # MODULES PER ROOF TYPE I ATTACHMENT ROOF HEIGHT FRAME MATERIAL FRAME TYPE FRAME SIZE OC SPACING ARRAY AR -01 AR -01 SCALE: 1/8" = V-0" PITCH: 18' AZIMUTH: 270° Z DESIGN CRITERIA MODULES: 42 MAX DISTRIBUTED LOAD: 3 PSF SNOW LOAD: 0 PSF WIND SPEED: 97 MPH 3 -SEC GUST. LAG SCREWS: 5/16"x 2.5" MIN EMBEDMENT INSTALLERS TO VERIFY RAFTER SIZE, SPACING AND SLOPED SPANS, AND NOTIFY E.O.R. OF ANY DISCREPANCIES BEFORE PROCEEDING. 28 CLAY TILE 2"X4" RAFTERS @ 24" O.C. ARRAY AR -01 iXECTOR :/ nO I n E E R S 65 1 W. GALENA PARK BLVD. 5TE. 1 D' PHONE (BOY) 99D-1 775 DRAPER, UTAH 64020 WWW. VEDTOR5E. COM Q¢OFESSION oN '[? IrX QUICK MOUNT PV QMHLS 1285'-84" l ffm� QUICK MOUNT PV QMHLS ATTACHMENTS ONE STORY IRONRIDGE XR10 RAIL SYSTEM * * Vector Structural Engineering has reviewed the existing S \, structure with loading from the solar array and screw s TRUCTUconnections to the existing framing. The design of the f racking system, racking connections, and all other TE, aF CAj 4ti structural is by others. Mechanical, architectural, and all other nonstructural aspects of the design are by others. Electrical is by others, unless stamped by Dean Levorsen. 02/02/2023 VSE Project Number: U2557.0801.221 13'-34" 6'-74" 0;18 6'-74" 1-114" 4 3.34.. 0. -0-0„ NOTE:- MAX. ATTACHMENT SPACING IS 4'-0" (NON -STAGGERED) ❑■ WOOD RAFTERS ii (28) OPTIMIZER P505 24" MAX. SPACING REQUIRED WHERE SHOWN IN DIAGRAM ABOVE (ALONG EAVE WHERE ONLY A SINGLE ROW OF PANELS OCCURS) POINT LOAD CALCULATION 2"X4" 13'-64" 6'-74" 16'-74" 24" O.C. CI TY OF LA QU N TA BU LEI NGEIVISON REVI EVIED FOR COCE COIWLI AV CE ar: A, � oaE: 02/23/2023 OWNER INSTALLED WEIGHT PER SQ FT 2311.0 / 908.46 sq.ft.= 2.5 Ibs/sq.ft. PV 3.0 #OR WEIGHT TOTAL WEIGHT ITEM LIN FT PER (lbs) (lbs) MODULES 42 49.60 2083.20 RAILS 279.53 0.4 111.81 ANTONIO DIAS 55515 SOUTHERN HILLS ATTACHMENTS 88 0.65 57.20 LA QUINTA CA 92253 TILT LEGS 0 3.5 0 Email: antonio.m.dias@outlook.com ENPHASE 42 1.4 58.8 Phone: 714-376-5708 INVERTER REV TOTAL WEIGHT 2311.0 lbs DATE: 01 FEBRUARY 2023 MODULE DIMENSION (LxW) 79.13 x 39.37= 21.63 sq.ft WEIGHT PER MOUNT 2311.0 / 88 = 26.3 Ibs/Mount LAYOUT DETAIL WEIGHT PER SQ FT 2311.0 / 908.46 sq.ft.= 2.5 Ibs/sq.ft. PV 3.0 z ARRAY AR -02 2"X4" RAFTEF AR -003 SCALE: 1/8" = V-0" PITCH: 18° AZIMUTH: 180° z QUICK 5'-84" ARRAY AR -03 2"X4" RAFTERS @ 24" O.C. QUICK MOUNT PV QMHLS ATTACHMENTS IRONRIDGE XR10 RAIL SYSTEM (6) OPTIMIZER P505 7'-42" 13'-34" 2'-102" 6-74" 3, -34„ 2 Vector Structural Engineering has reviewed the existing structure with loading from the solar array and screw connections to the existing framing. The design of the 4'-74" 6'-7-1" racking system, racking connections, and all other 1 structural is by others. Mechanical, architectural, and all i4 other nonstructural aspects of the design are by others. Electrical is by others, unless stamped by Dean Levorsen. 4'-0n 1' 0" i/ELL0R. E no l n€ E R s NOTE:- MAX. ATTACHMENT SPACING IS 4'-0" • 651 W GALENA PARK BLVD. STE, 101 PHONE (BO 1) 990-1 775 (NON -STAGGERED) DRAPER, UTAH 04020 WWW.VEDTORSE.DOM Q4pFESSlp�yq� oN ,aR�y�y� 2. BSOL2022-0649 J 7l7 ,s�gsr0U u���`P 02/02/2023 VSE Project Number: U2557.0801.221 OWNER INSTALLED 1 4' 0-- # MODULES PER • -74" 6'-7 ROOF TYPE ATTACHMENT ROOF HEIGHT FRAME MATERIAL FRAME TYPE FRAME SIZE OC SPACING ARRAY AR -02 8 CLAY TILE QUICK MOUNT PV QMHLS ONE STORY WOOD RAFTERS 2"X4" 24" O.C. AR -03 6 CLAY TILE QUICK MOUNT PV QMHLS ONE STORY WOOD RAFTERS 2"X4" 24" O.C. AR -02 SCALE: 1/8" = 1'-0" PITCH: 18 5'-04" 26'-54" 14'-64" 0 270° AZIMUTH: z ARRAY AR -02 2"X4" RAFTEF AR -003 SCALE: 1/8" = V-0" PITCH: 18° AZIMUTH: 180° z QUICK 5'-84" ARRAY AR -03 2"X4" RAFTERS @ 24" O.C. QUICK MOUNT PV QMHLS ATTACHMENTS IRONRIDGE XR10 RAIL SYSTEM (6) OPTIMIZER P505 7'-42" 13'-34" 2'-102" 6-74" 3, -34„ 2 Vector Structural Engineering has reviewed the existing structure with loading from the solar array and screw connections to the existing framing. The design of the 4'-74" 6'-7-1" racking system, racking connections, and all other 1 structural is by others. Mechanical, architectural, and all i4 other nonstructural aspects of the design are by others. Electrical is by others, unless stamped by Dean Levorsen. 4'-0n 1' 0" i/ELL0R. E no l n€ E R s NOTE:- MAX. ATTACHMENT SPACING IS 4'-0" • 651 W GALENA PARK BLVD. STE, 101 PHONE (BO 1) 990-1 775 (NON -STAGGERED) DRAPER, UTAH 04020 WWW.VEDTORSE.DOM Q4pFESSlp�yq� oN ,aR�y�y� 2. BSOL2022-0649 J 7l7 ,s�gsr0U u���`P 02/02/2023 VSE Project Number: U2557.0801.221 OWNER INSTALLED 1 4' 0-- 3'-34" -7, • -74" 6'-7 11 011 NOTE:- MAX. ATTACHMENT SPACING IS 4'-0" (NON -STAGGERED) ANTONIO DIAS L" 55515 SOUTHERN HILLS I LA QUINTA CA 92253 Email: antonio.m.dias@outlook.com Phone: 714-376-5708 REV A DATE: 01 FEBRUARY 2023 LAYOUT DETAIL PV 3.1 1 ATTACHMENT DETAIL PV -3.1 SCALE: V=1' PV -3.1 IRONRIDGE INTEGRATED GOUNDING & END/MID CLAMP IRONRIDGE XR10 RACKING SYSTEM QUICK MOUNT PV C ATTACH 2"X4" RAFTE ATTACHMENT DETAIL ( section view) SCALE: NTS "L" BRACKET ;S BOLT & NUT N TILE QUICK MOUNT QMHLS FLASHING 4" X 3-1/2" SS LAG REWS THREADED P 1 LAG PER TACHMENT 2.5" MIN BEDMENT VECTOR E nO I n E E R S 651 W. GALENA PA ftK BLVD. - 101 PHONE (BO I1 90-1775 011-1, UTAH 84020 WWW. VEGT 1 -COM Q�"pf ESSJQNq` ON AR�y�y� y ST sTRlJ�TURp� �P `EOfi CAUF� 02/02/2023 VSE Project Number: U2557.0801.221 Vector Structural Engineering has reviewed the existing structure with loading from the solar array and screw connections to the existing framing. The design of the racking system, racking connections, and all other structural is by others. Mechanical, architectural, and all other nonstructural aspects of the design are by others. Electrical is by others, unless stamped by Dean Levorsen. BSOL2022-0649 CI TY OF LAQU N TA BU LEI NGClVISON REM EV'ED FOR COCE (SLI M CE Ew A. m: 02/23/2023 PHONO SOLAR PS41 OM1 H-24/TH (14) P505 OPTIMIZER (1) STRING OF (14) MODULES STRING A, ARRAY 1 PHONO SOLAR PS41 OM1 H-24/TH (14) P505 OPTIMIZER (1) STRING OF (14) MODULES STRING B, ARRAY 1 PHONO SOLAR PS41 OM1 H-24/TH (14) P505 OPTIMIZER (1) STRING OF (14) MODULES STRING C, ARRAY 2 & 3 INVERTER RATINGS MAKE SOLAREDGE Imax (690.8(A)) SE1140OH-US MODEL [240V] MAX INPUT 30.5A CURRENT EXISTING MAX POWER Imp (AC) 1140OW NOM. AC UTILITY VOLTAGE 240V MAX AC © 10.53A 47.5A CURRENT Voc CEC 99% EFFICIENCY PV SOURCE SYSTEM SIZE: 17220W DC, 11 40O AC NOTE: MAIN BREAKER DERATE: SOLAREDGE INVERTER IS EQUIPPED WITH REPLACE EXISTING MAIN BREAKER RAPID SHUTDOWN AS PER CEC 690.12 WITH NEW 175 AMP MAIN BREAKER. INTERCONNECTION- SUBPANEL Per 705.12(b)(2)(3)(b): 125%(INVERTER OUTPUT)+BUSBAR OCPD<=120% BUSBAR 125%(47.5A)+70A<=120%(125A) 129.375A<=150A, => OK INTERCONNECTION- MAIN SERVICE PANEL Per 705.12(b)(2)(3)(b): 125%(INVERTER OUTPUT)+BUSBAR OCPD<=120% BUSBAR 125%(47.5A)+175A<=120 %(200A) 234.38A<=240A, => OK Cl TY OF LA QU N TA BU LEI N GO VI 9 ON REV] EVED FOR COCE COWLI AN CE BY: A. naE: 02/23/2023 CONDUCTOR SIZING CALCULATIONS CIRCUIT EXISTING WIRING Imax (690.8(A)) Icont (690.8(6)(1) Calc SPECIFIED AMPACITY @ (N) LOCKABLE CURRENT CARRYING COND. OF USE APPLIED EXISTING METER Imp BLADE TYPE CONDUCTOR UNDERGROUND UTILITY 2 AC DISCONNECT © © 10.53A SERVICE ❑E Voc 50.25V COND. 480V PV SOURCE 410W ❑D 15.00A x 1.25 = %Voc/C -0.30% 1 40A x 0.82 (am b. temp.) x0.8 STRING A, B & C 15.00A 15.00A REFER TO LABEL ~, 3 3 41-45 2P (raceway fill) = 26.24A w SCHEDULE ON I\V/I A Pv 6.0 47.50A x 1.25 = 175A 75A x 0.82 (am b. temp.) x1 INVERTER OUTPUT NEW 47.50A 59.38A #6 THWN-2 75A 2P 1-3 (raceway fill) = 61.5A 60A SOLAR © 2P BREAKER 70A BREAKER AT OPPOSITE FEED TO SUB END OF PANEL JUNCTION BOX MIN BUSBAR RATED NEMA3R NEW 60A AC EXISTING EXISTING NEW SOLAR INVERTER DISCONNECT SUB PANEL MAIN SERVICE PANEL i � SOLAREDGE (2 -POLE UNFUSED) 125A BUSBAR 200A BUSBAR SE11400H-US [24OV] END FED 400V 47.5A MAX CURENT BSOL2022-0649 Cl TY OF LA QU N TA BU LEI N GO VI 9 ON REV] EVED FOR COCE COWLI AN CE BY: A. naE: 02/23/2023 CONDUCTOR SIZING CALCULATIONS CIRCUIT CURRENT Imax (690.8(A)) Icont (690.8(6)(1) Calc SPECIFIED AMPACITY @ AMBIENT CURRENT CARRYING COND. OF USE APPLIED DESCRIPTION 1 Imp 9.82A CONDUCTOR 90c TEMP c 41.76V (690.8(B)(2) calc 400V Isc 10.53A Isc 15A Voc 50.25V COND. 480V PV SOURCE 410W Pmax 15.00A x 1.25 = %Voc/C -0.30% 40A x 0.82 (am b. temp.) x0.8 STRING A, B & C 15.00A 15.00A 18.75A #10 THWN-2 40A 41-45 4-6 (raceway fill) = 26.24A 47.50A x 1.25 = 75A x 0.82 (am b. temp.) x1 INVERTER OUTPUT 47.50A 47.50A 59.38A #6 THWN-2 75A 41-45 1-3 (raceway fill) = 61.5A MODULE AND ARRAY RATINGS: (42) MODULES) SOLAR MODULE RATINGS (STC) CIRCUIT DESCRIPTION LENGTH I Ohms/kFt V CALC STRING A, B & C MAKE PHONO SOLAR SERIES 14 MODEL PS410M1H-24/TH PARALLEL 1 Imp 9.82A Imp 14.4A Vmp 41.76V Vmp 400V Isc 10.53A Isc 15A Voc 50.25V Vo c 480V Pmax 410W Pmax 5740W %Voc/C -0.30% TERMINAL TEMPERATURE RATING CONSIDERATIONS CIRCUIT DESCRIPTION LENGTH I Ohms/kFt V CALC Vdrop PV SOURCE STRING A, B & C 50Ft 15.00A 0.9989 400V 50'x 15.00A x 2 x 0.9989/1000'/400V= 0.37% AMPACITY @ CIRCUIT DESCRIPTION TERMINAL TEMP CURRENT Icont SPECIFIED TERMINAL TEMP. RATING CONDUCTOR RATING PV SOURCE STRING A, B & C 15.00A 15.00A x 1.25 = 18.75A 75C #10 35A INVERTER OUTPUT 47.50A 47.50A x 1.25 = 59.38A 75C #6 65A VOLTAGE DROP CALCULATIONS CIRCUIT DESCRIPTION LENGTH I Ohms/kFt V CALC Vdrop PV SOURCE STRING A, B & C 50Ft 15.00A 0.9989 400V 50'x 15.00A x 2 x 0.9989/1000'/400V= 0.37% INVERTER OUTPUT 30Ft 47.50A 0.3951 240V 30' x 47.5OA x 2 x 0.3951/1000'/240V= 0.47% OWARNING �q THIS SERVICE METER 101 IS ALSO SERVED BY A PHOTOVOLTAIC SYSTEM RAPID SHUTDOWN I& PV ARRAY TO BE INSTALLED IN ACCORDANCE WITH SECTION 690.56(C): RATED AC OUTPUT CURRENT: 47.50A NOMINAL OPERATING AC VOLTAGE: 240V PHOTOVOLTAIC SOLAR AC DISCONNECT OWARNING FD I ELECTRIC SHOCK HAZARD FBI I" ACAUTION SOLAR ELECTRIC SYSTEM CONNECTED TO BE INSTALLED IN ACCORDANCE WITH 705.12(b)(2)(3)(b): OWARNING © POWER SOURCE OUTPUT CONNECTION. DO NOT RELOCATE THIS OVERCURRENT DEVICE PHOTOVOLTAIC SOLAR BREAKER DO NOT RELOCATE THIS OVERCURRENT DEVICE ID 011 TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY © RATED MAXIMUM POWER- A POINT CURRENT (Imp) RATED MAXIMUM POWER- V POINT VOLTAGE (Vmp) MAXIMUM SYSTEM VOLTAGE (VOC) V MAXIMUM CIRCUIT m CURRENT (Isc) A D 0 OWARNING I ELECTRIC SHOCK HAZARD I DO NOT TOUCH TERMINALS TERMINALS ON BOTH THE LINE AN LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION OWARNING I ELECTRIC SHOCK HAZARD IF GROUND FAULT IS INDICATED ALL NORMALLY GROUNDED CONDUCTORS MAY BE UNGROUNDED AND ENERGIZED INSTALL EVERY 10 FEET ON EXTERIOR CONDUIT. z CAUTION: POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN: - • - - 11111111111111. UTILITY METER INVERTER MAIN SERVICE AC DISCONNECT PANEL SUB PANEL BSOL2022-0649 Cl TY OF LA QlJ N TA BU LEI N GCI VI 9 ON REV] EV'ED FOR CCEE COLLI AV CE w A w: 02/23/2023 55515 SOUTHERN HILLS, LA QUINTA, CA 922531 Phono°Solar TWINPLUS MODULE SERIEs HIGH EFFICIENCY MONO-PERC M1-513-11 395-415W OUTSTANDING PRODUCT PERFORMANCE • Competitive high-temperature performance with ameliorated temperature coefficient • Minimized power loss in cell connection • Better performance under shading effect • Decreased nominal operating cell temperature to 43 ± 2°C TRUSTWORTHY QUALITY AND RELIABILITY • Guaranteed 0—+5W positive tolerance secures reliable power output • 5400Pa maximum snow load, 2400Pa maximum wind load • Optimized electrical design lowers hot spot risk and operating current PID RESISTANT • Industry-leading cell processing technology and electrical design ensure solid PID resistance MANAGEMENT SYSTEM CERTIFICATES IEC 61215, IEC 61730 ISO 9001:2015 / Quality management system ISO 14001:2015 / Standards for environmental management system OHSAS 18001:2007 / International standards for occupational health & safety IEC TS 62941: 2016 Terrestrial photovoltaic (PV) modules -guidelines for increased confidence in PV module design qualification and type approval 0EK) Sid c C E �� DS Ei� _ oy,r PVN` CLE C US LISTED 1--k \V GL -EN -Version 2021.05.20 © Phono Solar Co., Ltd All Rights Reserved 100% M Phono Solar Industry Standard 3 97% d 90% -o w a p 70 L7 1 5 10 15 20 25 Year 12 -year Product Warranty I 25 -year Linear Performance Warranty Bloomberg Tie r1 NEW ENERGY FINANCE �oP pERFor?4,' 2021 M•PVEL PV MODULE RELIABILITY SCORECARD Cell Type PS395M 1 -24/TH PS400M 1 -24/TH PS405M 1 -24/TH PS410M1-24/TH PS415M1-24/TH Model Height: 35mm (1.38 inch) Weight 22.5kg (49.60 lbs) Front Glass 3.2mm Toughened Glass Frame PS395M 1 H-24/TH PS400M 1 H-24/TH PS405M1H-24/TH PS410M1H-24/TH PS415M1H-24/TH Testing Condition STC NOCT STC NOCT STC NOCT STC NOCT STC NOCT Rated Power (Pmpp) 395 294 400 298 405 302 410 306 415 309 Rated Current (Impp) 9.67 7.78 9.72 7.82 9.77 7.86 9.82 7.91 9.87 7.95 Rated Voltage (Vmpp) 40.85 37.80 41.16 38.09 41.46 38.36 41.76 38.64 42.05 38.91 Short Circuit Current (Isc) 10.29 8.28 10.37 8.35 10.45 8.41 10.53 8.48 10.61 8.54 Open Circuit Voltage (Voc) 49.41 46.74 49.69 47.01 49.97 47.27 50.25 47.54 50.53 47.80 Module Efficency (%) 19.65 19.90 20.15 20.40 20.65 STC(Standard Testing Conditions): Irradiance 1000W/m2, AM 1.5, Cell Temperature 25'C NOCT (Nominal Operation Cell Temperature): Irradiance 800W/m2, Ambient Temperature 20'C, Spectra at AM1.5, Wind at 1 m/S Cell Type Monocrystalline 158.75mm x 79.38mm Current Temperature Coefficient Length: 2010mm (79.13 inch) Dimension (Lx W x H) Width: 1000mm (39.37 inch) Tolerance Height: 35mm (1.38 inch) Weight 22.5kg (49.60 lbs) Front Glass 3.2mm Toughened Glass Frame Anodized Aluminium Alloy Cable 4m m2 (IEC), (Including Connector) (+):450mm,(4250mm or Customized Length Junction Box IP 68 Rated Voltage Temperature Coefficient -0.30%/'C Current Temperature Coefficient +0.05%/'C Power Temperature Coefficient -0.38%/'C Tolerance 0-+5w NOCT 43±2'C Operating Temperature From -40 to +85'C Hail Diameter @ 80km/h Up to 25mm Front Side Maximum Static Loading 5400Pa Rear Side Maximum Static Loading 2400Pa Maximum Series Fuse Rating 20A PV Module Classification II Fire Rating (IEC 61730) C Maximum System Voltage DC 1000V/1500V 50 40 2 30 3 a 20 10 V Celt temp. 25C - Incident Irrad.=1000W/m2 0�incirIentirrad-.E00W/me_____________ _____ ___________ - Incident Inrad,600W/m2 0 -_n Icident Irrad.=400W/m2 _ _ - ---- ------------ --------- Incident Irrad.=200W/m2- 0 --- --- ------ ----------- -- ------- 0- ------------ -------- 0 0 10 20 30 40 50 6 12 10 a 8 6 U 4 2 n11110 Voltage [VI Cell to p.25C Incident Irrad.=1000W/m2 ------------------------------- Incident Irrad.=800W/m2 Incident Irrad.=600W/m2 Incident Irrad.=400W/m2 Incident Irrad,200W/m2 Voltage M 35 11.381 95112 137.441 PACKING 4 , , ' 9 10.351 Container 20' GP 40' HQ v� Pieces/Container 255 726 a Note:mm (inch) ----------- 35 11.381 A -A I PHONO SOLAR TECHNOLOGY CO.,LTD reserves the right to make necessary adjustments to the Ph on , Sohn- information described herein at any time without further notice. The specifications and certificates contained in this datasheet may deviate slightly from our actual products due to the on-going innovation and product enhancement. Please be sure to use the most recent version of data. Single Phase Inverter with HD -Wave Technology for North America SE3000H-US / SE380OH-US / SE5000H-US / SE6000H-US / SE760OH-US / SE1000OH-US / SE1140OH-US ® o a ® solar= �fti�,::. � e Bohr. --C -HD__ � s► v o 0 : Optimized installation with HD -Wave technology / Specifically designed to work with power optimizers / Record-breaking 99% weighted efficiency / Quick and easy inverter commissioning directly from a smartphone using the SolarEdge SetApp / Fixed voltage inverter for longer strings / Integrated arc fault protection and rapid shutdown for NEC 2014, NEC 2017 and NEC 2020 per article 690.11 and 690.12 / UL1741 SA certified, for CPUC Rule 21 grid compliance / Small, lightweight, and easy to install both outdoors or indoors / Built-in module -level monitoring / Optional: Faster installations with built-in consumption metering (1% accuracy) and production revenue grade metering (0.5% accuracy, ANSI C12.20) solaredge.com solar• . z Single Phase Inverter with HD -Wave Technology for North America SE3000H-US / SE380OH-US / SE5000H-US / SE6000H-US/ SE760OH-US / SE1000OH-US / SE1140OH-US OUTPUT Rated AC Power Output 3000 3800 @ 240V 5000 6000 @ 240V 7600 10000 11400 @ 240V VA 11800 15500 3300 @ 208V W 5000 @ 208V 5100 10000 @ 208V 7750 Maximum AC Power Output 3000 3800 @ 240V 5000 6000 @ 240V 7600 10000 11400 @ 240V VA 480 3300 @ 208V Nominal DC Input Voltage 5000 @ 208V 400 Vdc 10000 @ 208V 8.5 10.5 AC Output Voltage Min. -Nom. -Max. ✓ ✓ ✓ ✓ ✓ ✓ ✓ Vac (211 - 240 - 264) 27 Adc Max. Input Short Circuit Current 45 Adc Reverse -Polarity Protection Yes AC Output Voltage Min. -Nom. -Max. ✓ 600kQ Sensitivity ✓ _ _ ✓ Vac (183 - 208 - 229) CEC Weighted Efficiency gg 99 @ 240V 98.5 @ 208V % Nighttime Power Consumption < 2.5 AC Frequency (Nominal) 59.3 - 60 - 60.50) Hz Maximum Continuous Output 12.5 16 21 25 32 42 47.5 A Current @240V Maximum Continuous Output - 16 - 24 - - 48.5 A Current @208V Power Factor 1, Adjustable - 0.85 to 0.85 GFDI Threshold 1 A Utility Monitoring, Islanding Protection, Yes Country Configurable Thresholds INPUT Maximum DC Power @240V 4650 5900 7750 9300 11800 15500 17650 W Maximum DC Power @208V 5100 - 7750 - 15500 W Transformer -less, Ungrounded Yes Maximum Input Voltage 480 Vdc Nominal DC Input Voltage 380 400 Vdc Maximum Input Current @240V(2) 8.5 10.5 13.5 16.5 20 27 30.5 Adc Maximum Input Current @208V- - 9 13.5 - - 27 Adc Max. Input Short Circuit Current 45 Adc Reverse -Polarity Protection Yes Ground -Fault Isolation Detection 600kQ Sensitivity Maximum Inverter Efficiency 99 99.2 % CEC Weighted Efficiency gg 99 @ 240V 98.5 @ 208V % Nighttime Power Consumption < 2.5 W (1) For other regional settings please contact SolarEdge support (2) A higher current source may be used; the inverter will limit its input current to the values stated Single Phase Inverter with HD -Wave Technology for North America SE3000H-US / SE380OH-US / SE5000H-US / SE6000H-US/ SE760OH-US / SE1000OH-US / SE1140OH-US ADDITIONAL FEATURES Supported Communication Interfaces RS485, Ethernet, ZigBee (optional), Cellular (optional) 1" Maximum /14-4 AWG Revenue Grade Metering, ANSI C12.20 Optionall3) T' Maximum / 1-2 strings / 14-6 AWG Consumption metering Inverter Commissioning With the SetApp mobile application using Built-in Wi-Fi Access Point for Local Connection 21.3 x 14.6 x 7.3 / 540 x 370 x 185 Rapid Shutdown - NEC 2014, NEC 2017 and NEC 2020, 690.12 Automatic Rapid Shutdown upon AC Grid Disconnect 22110 25.1 / 11.4 26.2/11.9 STANDARD COMPLIANCE Safety Grid Connection Standards Emissions INSTALLATION SPECIFICATIONS UL1741, UL1741 SA, UL169913, CSA C22.2, Canadian AFCI according to T.I.L. M-07 IEEE1547, Rule 21, Rule 14 (HI) FCC Part 15 Class B AC Output Conduit Size / AWG Range 1" Maximum / 14-6 AWG 1" Maximum /14-4 AWG DC Input Conduit Size / # of Strings / AWG Range T' Maximum / 1-2 strings / 14-6 AWG 1" Maximum / 1-3 strings / 14-6 AWG Dimensions with Safety Switch (HxWxD) 17.7 x 14.6 x 6.8 / 450 x 370 x 174 21.3 x 14.6 x 7.3 / 540 x 370 x 185 in/mm Weight with Safety Switch 22110 25.1 / 11.4 26.2/11.9 38.8/17.6 Ib / kg Noise < 25 1 <50 dBA Cooling Natural Convection Operating Temperature Range -40 to +140 / -40 to +60(4) F / °C Protection Rating NEMA 4X (Inverter with Safety Switch) (3) Inverter with Revenue Grade Meter P/N: SExxxxH-US00013NC4; Inverter with Revenue Grade Production and Consumption Meter P/N: SExxxxH-US000BNI4. For consumption metering, current transformers should be ordered separately: SEACT0750-20ONA-20 or SEACT0750-40ONA-20. 20 units per box (4) Full power up to at least 50"C / 122°F for power de -rating information refer to: https://www.solaredge.com/sites/default/files/se-temperature-derating-note-na.pdf How to Enable Consumption Monitoring By simply wiring current transformers through the inverter's existing AC conduits and connecting them to the service panel, homeowners will gain full insight into their household energy usage helping them to avoid high electricity bills Service Panel Single phase inverter with HD -wave technology and built-in RGM and consumption monitoring AC Conduit J- I Z ® SolarEdge Technologies, Inc. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc. All Ro H S other trademarks mentioned herein are trademarks of their respective owners. Date: 12/2020/VO1/ENG NAM. Subject to change without notice. Power Optimizer For North America P370 / P400 / P401 / P485 / P505 0 MOIN M PV power optimization at the module level Specifically designed to work with SolarEdge inverters Up to 25% more energy I Superior efficiency (99.5%) Mitigates all types of module mismatch losses, from manufacturing tolerance to partial shading Flexible system design for maximum space utilization solaredge.com Fast installation with a single bolt Next generation maintenance with module - level monitoring I Meets NEC requirements for arc fault protection (AFCI) and Photovoltaic Rapid Shutdown System (PVRSS) I Module -level voltage shutdown for installer and firefighter safety solare s Power Optimizer For North America P370 / P400 / P401 / P485 / P505 INPUT Rated Input DC Power -0) 370 400 430 485 505 W Absolute Maximum Input Voltage (Voc at lowest temperature) 60 80 60 125(2) 83121 Vdc MPPT Operating Range 8-60 8-80 8-60 12.5 -105 12.5 - 83 Vdc Maximum Short Circuit Current (Isc) 11 10.1 12.5 11 14 Adc Maximum DC Input Current 13.75 12.5 14.65 12.5 17.5 655/1.5 845/1.9 Maximum Efficiency 99.5 % Weighted Efficiency 98.8 % Overvoltage Category II OUTPUT DURING OPERATION (POWER OPTIMIZER CONNECTED TO OPERATING SOLAREDGE INVERTER) Maximum Output Current I 15 Adc Maximum Output Voltage 1 60 1 80 Vdc OUTPUT DURING STANDBY (POWER OPTIMIZER DISCONNECTED FROM SOLAREDGE INVERTER OR SOLAREDGE INVERTER OFF) Safety Output Voltage per Power 1 +0.1 Vdc Optimizer STANDARD COMPLIANCE EMC FCC Part 15 Class 3, IEC61000-6-2, IEC61000-6-3 Safety IEC62109-1 (class II safety), UL1741, NEC/PVRSS Material UL94 V-0, UV Resistant Compatible inverters ROHS Yes Single Phase and Three Phase inverters INSTALLATION SPECIFICATIONS Maximum Allowed System Voltage 1000 Vdc Compatible inverters All SolarEdge Single Phase and Three Phase inverters Dimensions (W x L x H) 129x153x27.5/ 5.1x6x1.1 129x153x33.5/ 5.1x6x1.3 129 x 153 x 29.5 / 129x159x49.5/ 5.1x6x1.16 5.1 x6.3 x1.9 129x162x59/ 5.1x6.4x2.3 mm /in Weight (including cables) 630/1.4 750/1.7 655/1.5 845/1.9 1064/2.3 gr/lb Input Connector MC4(3) MC40) MC4(1) Input Wire Length(^� 0.16/0.5 m / ft Output Wire Type / Connector Double Insulated / MC4 Output Wire Length 1.2/3.9 m / ft Operating Temperature Range(sl -40 to +85 / -40 to +185 -C / -F Protection Rating IP68 / NEMA613 Relative Humidity 0-100 % (1) Rated power of the module at STC will not exceed the optimizer "Rated Input DC Power. Modules with up to +5% power tolerance are allowed (2) NEC 2017 requires max input voltage be not more than 80V (3) For other connector types please contact SolarEdge (4) Longer inputs wire lengths are available for use. For 0.9m input wire length order P401-)=L)m (5) For ambient temperature above +85°C /+185°F power de -rating is applied. Refer to Power Optimizers Temperature De -Rating Technical Note for more details: httos://www.solaredge.com/sites/default/files/se- temperature-derating-note-na.ldf Minimum String Length P370, P400, P401 8 10 18 (Power Opti I P485, P505 6 8 14 Maximum String Length (Power Optimizers) 25 25 50 Maximum Power per String 57001a)(6000 with 5250ia1 60000) 12750(10) W SE7600-US - SE11400-US) Parallel Strinas of Different Lenaths or Orientations Yes (6) For detailed string sizing information, refer to htto://www.solaredge.com/sites/defaukAles/string sizing na. J�df (7) It is not allowed to mix P485/P505 with P370/P400/P401 in one string (8) A string with more than 30 optimizers does not meet NEC rapid shutdown requirements, safety voltage will be above the 30V requirement (9) For the 208V grid, it is allowed to install up to 6,500W per string when the maximum power difference between each string is 1,000W (10) For 277/480V grid: it is allowed to install up to 15,000W per string when the maximum power difference between each string is 2,0000 4 © SolarEdge Technologies, Ltd. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc AW. Rill All other trademarks mentioned herein are trademarks of their respective owners. Date: July 12, 2022 DS -000044 -NAM. Subject to change without notice. Intertek I RON RI DGE Flush Mount System Built for solar's toughest roofs. IronRidge builds the strongest mounting system for pitched roofs in solar. Every component has been tested to the limit and proven in extreme environments. Our rigorous approach has led to unique structural features, such as curved rails and reinforced flashings, and is also why our products are fully certified, code compliant and backed by a 20 -year warranty. Strength Tested PE Certified All components evaluated for superior® Pre -stamped engineering letters structural performance. available in most states. Class A Fire Rating Design Assistant Certified to maintain the fire resistance ® Online software makes it simple to rating of the existing roof. create, share, and price projects. UL 2703 Listed System 20 -Year Warranty ® Entire system and components meet �� Twice the protection offered by newest effective UL 2703 standard. competitors. XR Rails O XR10 Rail s A low -profile mounting rail for regions with light snow. • 6' spanning capability • Moderate load capability • Clear and black finish XR100 Rail XR1000 Rail Bonded Splices The ultimate residential solar mounting rail. • 8' spanning capability • Heavy load capability • Clear and black finish Clamps & Grounding O — UFOs Universal Fastening Objects bond modules to rails. • Fully assembled & lubed • Single, universal size • Clear and black finish Attachments O — FlashFoot2 1 Flash and mount XR Rails with superior waterproofing. • Twist -on Cap eases install • Wind -driven rain tested • Mill and black finish Resources Stopper Sleeves _L Snap onto the UFO to turn into a bonded end clamp. • Bonds modules to rails • Sized to match modules • Clear and black finish A heavyweight mounting All rails use internal splices rail for commercial projects. for seamless connections. • 12' spanning capability • Extreme load capability • Clear anodized finish Grounding Lugs Connect arrays to equipment ground. • Low profile • Single tool installation • Mounts in any direction Slotted L -Feet Bonding Hardware Drop-in design for rapid rail Bond and attach XR Rails attachment. to roof attachments. • Secure rail connections T & Square Bolt options • Slot for vertical adjusting Nut uses 7/16" socket • Clear and black finish Assembled and lubricated Design Assistant Go from rough layout to fully engineered system. For free. to IronRidge.com/design • Self -drilling screws • Varying versions for rails • Forms secure bonding Microinverter Kits Mount MIs or POs to XR Rails. • Bonds devices to rails • Kit comes assembled • Listed to UL 2703 Flush Standoffs Raise Flush Mount System to various heights. • Works with vent flashing • 4" and 7" lengths • Ships assembled 0 2016 IronRidge, Inc. All rights reserved. Visit www.ironridge.com or call 1-800-227-9523 for more information. Version 1.30 NABCEP Certified Training aw Earn free continuing education credits, 01,1711 while learning more about our systems. Go to Iron Ridge.com/training 0 2016 IronRidge, Inc. All rights reserved. Visit www.ironridge.com or call 1-800-227-9523 for more information. Version 1.30 //r IRON RIDGE Simplified Grounding for Every Application Tha l 1Fn family of rmmnnnantG aliminatPq tha naarl Mr UFO Family of Components i System Diagram 0 UFO C Stopper Sleeve ■ Grounding Lug Bonded Splice Ground Wire 4 Approved Enphase microinverters can provide equipment grounding of Iran Ridge systems, eliminating the need for grounding lugs and field installed equipment ground conductors (EGC). A minimum of two microinverters mounted to the same rail and connected to the same Engage cable is required. Refer to installation manuals for additional details. UL Certification The IronRidge Flush Mount, Tilt Mount, and Ground Mount Systems have been listed to UL 2743 by Intertek Group plc. UL 2733 is the standard for evaluating solar mounting systems. It ensures these devices will maintain strong electrical and mechanical connections over an extended period of time in extreme outdoor environments. (B Go to IronRidge.comlUFO XR Rails UFQtStopper Bonded Splice .r Grounding Lugs 1 per Row d XR1000 Only NIA 1 per Row 1 per Array Microinverters Enphase - M250-72, M250-60, M215-60, C250-72 & Power Darton - MIG240, MIG300, G320, 6640 Optimizers SolarEdge - P300, P320, P400, P405, P600, P700, P730 Fire Rating I Class A Class A NIA ModulesI Tested or Evaluated with over 400 Framed Modules Refer to installation manuals for a detailed list. 0 2016 IronRidge, Inc. All rights reserved. Visit www.ironrldge.com ar call 100-227-9523 for mare information. Version i.0 /lr IRONRIDGE Background All roofing products are tested and classified for their ability to resist fire Recently, these fire resistance standards were expanded to include solar equipment as part of the roof system. Specifically, this requires the modules, mounting hardware and roof covering to be tested together as a system to ensure they achieve the same fire rating as the original roof covering. Adoption of these new requirements will begin in California in 2015 and extend to the rest of the country in 2016. IronRidge Certification In August 2014, IronRidge was the first company to receive a Class A Fire Rating — the highest possible rating—from Intertek Group plc., a Nationally Recognized Testing Laboratory. IronRidge Roof Mount products were tested on flat and sloped roofs in accordance with the new UL 1703 & UL 2703 test standards. The testing evaluated the system's ability to resist flame spread, buming material and structural damage to the roof. Refer to the table below to determine the requirements for achieving a Class A Fire Rating on your next project. Class A Fire Rating Test Setup Solar Modules Solar modules are given a Type classification based on their materials and construction. Mounting System Mounling is tested as part of a system that includes type -tested modules and fire -rated root covering. Roof Covering Roof covering products are given a Fire Class Rating of A, B or C based on their tested fire resistance. Burning grand Test A burning wooden block is placed on module as a fan blows at 12 mph. Flame cannot be seen on underside of roof within 90 minutes. Spread of Flame Test Flame at southern edge of roof is aimed up the roof as a fan blows at 12 mph. The flame cannot spread 6 feet or more in 10 minutes. Roof Sllopp.,: .. - Steep Slope {> 9.5 deg.} Rush Type 1 & 2 Class A Flush Type 1 Class A Low Slope (< 9.5 deg.) Tft [FJ] l Type 1 Class A 'Can be installed on Class A, B. & C roots. Frequently Asked (questions What is a "module type"? The new UL1703 standard introduces the concept of a PV module type, based on 4 construction parameters and 2 fire performance parameters. The purpose of this classification is to certify mounting systems without needing to test it with every module. What roofing materials are covered? All fire rated roofing materials are covered within this certification including composition shingle, clay and cement tile, metal, and membrane roofs. What if I have a Class C roof, but the jurisdiction now requires Class A or B? Generally, older roofs will be "grandfathered in", and will not require re -roofing. However, if 50% or more of the roofing material is replaced for the solar installation the code requirement will be enforced. Where is the new fire rating requirement code listed? 2012 IBC: 1509.7.2 Fire classification. Rooftop mounted photovoltaic systems shall have the same fire classification as the roof assembly required by Section 1505. Where is a Class A Fire Rating required? The general requirement for roofing systems in the IBC refers to a Class C fire rating. Class A or B is required for areas such as Wildland Urban Interface areas (WUI) and for very high fire severity areas. Many of these areas are found throughout the western United States. California has the most ClassA and B roof fire rating requirements, due to wild fire concerns. Are standard mid clamps covered? Mid clamps and end clamps are considered part of the PV "system", and are covered in the certification. More Resources — Fire Rating Certificate Visit our website to download the official UL 2703 certification document. Go to ironRidge.com What attachments and flashings are deemed compatible with Class A? Attachments and their respective flashings are not constituents of the rating at this time. All code -compliant flashing methods are acceptable from a fire rating standpoint. What mounting height is acceptable? The UL testing was performed at a height of 5 The code does not specify minimum or maximum height. The Iron Ridge Class A rating covers all heights as long as they fit within the "flush mounted" category. Am I required to install skirting to meet the fire code? No, Iron Ridge achieved a Class A fire rating without any additional racking components. What determines Fire Classification? Fire Classification refers to a fire -resistance rating system for roof covering materials based on their ability to withstand fire exposure. Gass A - effective against severe fire exposure Class B - effective against moderate fire exposure Class C - effective against light fire exposure What if the roof covering is not Class A rated? The Iron Ridge Class A rating will not diminish the fire rating of the roof, whether Class A, B, or C. What tilts is the tilt mount system fire rated for? The tilt mount system is rated for 1 degrees and up and any roof to module gap, or mounting height. Engineering Certification Letters We offer complete engineering resources and pre -stamped certification letters. Go to IronRidge.com 0 2016 Iran Ridge, Inc. All rights reserved. Visit www. i ron ridge. com or cell 1 -WD -227 9623 for more infarmation. Version 1.10 Quick Hook'SS & LS Instructions for Installing Standard and Low Height Hooks for Side Mount Rails Installation Tools Required: stud finder, tape measure, utility knife, drill with 7/32" bit, impact drill with 1/2" socket, #3 phillips power bit (use with drill only), caulking gun, appropriate sealant compatible with roofing materials, roofing bar, hand broom, electric grinder with a 4.5" triple sandwich tuck point blade. Remove the tile at selected location of the mount. Locate and mark the center of the rafter. Rest the base plate over center of rafter and mark center of holes. Drill two 7/32" pilot holes and fill with sealant compatible with roofing materials. Connect hook to base plate and drive lag screws into rafter through the two holes to a solid, snug fit. DO NOT over tighten lag screws, this may compromise their holding strength. Slide hook into desired position within valley of the tile . Hook must not overhang the sides of the base plate. Drive self -tapping screw using a #3 Phillips bit on a screw driver or drill with clutch set at a medium torque, to secure hook to base. Do not use impact gun on screw. a i- Carefully clean the underlayment then apply bead of sealant compatible with roofing materials in the shape of an upside down U on the backside of the sub -flashing, and install flashing over mount. Fasten sub -flashing to deckwith one roofing nail in each top corner. Do not nail bottom corners. Quick Mount PV recommends installation per the Tile Roofing Institute guidelines with a base flashing. Alternative flashing methods may be approved bythe AHJ at their discretion. _41 tiWs Cut a clearance notch in the weather guard lug using a grinder with a tuck point blade. Make sure the tile seats back down in it's original position. Leave at least Ya" oftile to prevent breaking through. Bolt the side-mou nted rail of your choice to the hook, using the rail manufacturer's hardware. BI 7.2.3-34 1 Sep -2018, Rev 10 W Ln m 7 IV O W r m 0 #3 TYPE 1 (PHILLIPS) DRIVE ON SCREW 1❑ 1.50 ¢ O tO O SLIDE TO DESIRED O O LOCATION .75 AI 0.40 6.00 .19 IDENTIFYING MARK ON QMHLS ONLY 2.50 BOTH SIDES OF SLOT SERRATED D DIMENSION QMHSS QMHLS A 6.57 6.30 B 2.21 1.93 C 1.89 1.60 D 6.27 6.00 2 DETAIL E SCALE 1 : 2 5 11-1 DO NOT USE IMPACT DRILL ON SCREW ITEM DESCRIPTION QTY. NO. j�� 1 BASE PLATE, QUICK HOOK, 6', 6061-T6, MILL 1 UIICk Mount t- .. 2 LAG SCREW, HEX HEAD, 5/16' x 3-1/2", 18-8SS 2 TITLE: QMHSS & QMHLS: QUICK HOOK 3 QUICK HOOK, STANDARD/LOW HEIGHT, VERTICAL, 1.5', 6061-T6/6005A-T61, MILL 1 FOR SIDE MOUNTED RAILS 4 SCREW, SELF -TAPPING, #12 X 5/8", 18-8SS, MILL 1 UNLESS OTHERWISE SPECIFIED: SIZE DRAWN BY: RAD REV DIMENSIONS ARE IN INCHES 5 SUBFLASHING, QUICK HOOK, 6' BASE, 9" X 14" X.032", 3003-0, MILL 1 TOLERANCES: A DATE: 1/8/2016 10 FRACTIONAL± 1/8 PROPRIETARY AND CONFIDENTIAL TWO PLACE DECIMAL ±.18 THE INFORMATION A WHOLE WITHOUT THE WRITTEN NIN THIS DRAWING PERMSSION OF OVSPROHIBITED. 15 THE SOLE MOUNT POPRTY OF IDD. MOUNT PV. ANY REPRODUCTION IN PARI OR AS DO NOT SCALE DRAWING THREE PLACE DECIMAL ±.125 SCALE: 1:8 WEIGHT: 1.82 SHEET OF 5 4 3 2 1 co V N W W Ln q RAFTER THIS EDGE TOWARDS ROOF RIDGE 4.50 9" ADJUSTABLE LOCATIOI .75 6.00 3X 1.50 TYP. 98 2.00 4.50 rD 7 N _O W 3J N G O THIS EDGE TOWARDS ROOF RIDGE 14.00 SUBFLASHING (ITEM 5) Quick Mount F - TITLE: QMHSS & QMHLS: QUICK HOOK FOR SIDE MOUNTED RAILS 8431 Murphy Drive Middleton, WI 53562 USA Telephone: 608.836.4400 Facsimile: 608.831.9279 www.intertek.com Test Verification of Conformity In the basis of the tests undertaken, the sample(s) of the below product have been found to comply with the requirements of the referenced specifications at the time the tests were carried out. icant Name & Address Product Description: Ratings & Principle Characteristics: Models Brand Name: Relevant Standards: Verification Issuing Office: Date of Tests: Test Report Number(s): IronRidge, Inc. 28357 Industrial Blvd Hayward, CA 94545 USA Flush Mount System with XR Rails. Fire Class Resistance Rating: -Flush Mount (Symmetrical). Class A Fire Rated for Low Slope applications when using Type 1, 2, 3, 13, 19, 25 and 29 listed photovoltaic modules. Class A Fire Rated for Steep Slope applications with Type1, 2 and 3, listed photovoltaic modules. Tested with a 5" gap (distance between the bottom the module frame and the roof covering), per the standard this system can be installed at any gap allowed by the manufacturers installation instructions. No perimeter guarding is required. This rating is applicable with any IronRidge or 3'rd party roof anchor. IronRidge Flush Mount with XR Rails IronRidge Flush Mount UL 2703 (Section 15.2 and 15.3) Standard for Safety Mounting Systems, Mounting Devices, Clamping/Retention Devices, and Ground Lugs for Use with Flat -Plate Photovoltaic Modules and Panels, First Edition dated Jan. 28, 2015 Referencing UL1703 Third Edition dated Nov. 18, 2014, (Section 31.2) Standard for Safety for Flat -Plate Photovoltaic Modules and Panels. Intertek Testing Services NA, Inc. 8431 Murphy Drive Middleton, WI 53562 08/27/2014 to 03/17/2015 101769343MID-001r1, 101769343MID-001a, 101915978MID-001 & 101999492MID-001ar1-cr1, 104428358MID-001 EEV Revision Summary 18/27/2020 Added type 13, 19, 25 and 29 to system, update address. This verification is part of the full test report(s) and should be read in conjunction with them. This report does not automatically imply product certification. Completed by: Chris Zimbrich Reviewed by: Chad Naggs Title: Technician I, Fire Resistance Title: Technical Team Lead, Fire Resistance Signature: Signature: Date: 08/27/2020 Date: 08/27/2020 This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material, product or service is or has ever been under an Intertek certification program. GFT -OP -11a (24 -MAR -2014)