BSOL2015-0236 Solar Plans-compressed
ABBREVIATIONS ELECTRICAL NOTES JURISDICTION NOTES A AMPERE AC ALTERNATING CURRENT BLDG BUILDING CONC CONCRETE DC DIRECT CURRENT EGC EQUIPMENT GROUNDING CONDUCTOR (E) EXISTING EMT ELECTRICAL METALLIC TUBING FSB FIRE SET —BACK GALV GALVANIZED GEC GROUNDING ELECTRODE CONDUCTOR GND GROUND HDG HOT DIPPED GALVANIZED Imp Isc kVA kW LBW MIN (N) NEUT N TS OC PL P01 PV SCH S STC TYP UPS V Vmp Voc W 3R CURRENT CURRENT AT MAX POWER SHORT CIRCUIT CURRENT KILOVOLT AMPERE KILOWATT LOAD BEARING WALL MINIMUM NEW NEUTRAL NOT TO SCALE ON CENTER PROPERTY LINE POINT OF INTERCONNECTION PHOTOVOLTAIC SCHEDULE STAINLESS STEEL STANDARD TESTING CONDITIONS TYPICAL UNINTERRUPTIBLE POWER SUPPLY VOLT VOLTAGE AT MAX POWER VOLTAGE AT OPEN CIRCUIT WATT NEMA 3R, RAINTIGHT LICENSE CA # 888104 C-10 MODULE GROUNDING METHOD: ZEP SOLAR AHJ: La Quinta UTILITY: Imperial Irrigation District 1. THIS SYSTEM IS GRID—INTERTIED VIA A UL—LISTED POWER —CONDITIONING INVERTER. 2. THIS SYSTEM HAS NO BATTERIES, NO UPS. 3. A NATIONALLY —RECOGNIZED TESTING LABORATORY SHALL LIST ALL EQUIPMENT IN COMPLIANCE WITH ART. 110.3. 4. WHERE ALL TERMINALS OF THE DISCONNECTING MEANS MAY BE ENERGIZED IN THE OPEN POSITION, A SIGN WILL BE PROVIDED WARNING OF THE HAZARDS PER ART. 690.17. 5. EACH UNGROUNDED CONDUCTOR OF THE MULTIWIRE BRANCH CIRCUIT WILL BE IDENTIFIED BY PHASE AND SYSTEM PER ART. 210.5. 6. CIRCUITS OVER 250V TO GROUND SHALL COMPLY WITH ART. 250.97, 250.92(B). 7. DC CONDUCTORS EITHER DO NOT ENTER BUILDING OR ARE RUN IN METALLIC RACEWAYS OR ENCLOSURES TO THE FIRST ACCESSIBLE DC DISCONNECTING MEANS PER ART. 690.31(E). 8. ALL WIRES SHALL BE PROVIDED WITH STRAIN RELIEF AT ALL ENTRY INTO BOXES AS REQUIRED BY UL LISTING. 9. MODULE FRAMES SHALL BE GROUNDED AT THE UL—LISTED LOCATION PROVIDED BY THE MANUFACTURER USING UL LISTED GROUNDING HARDWARE. 10. MODULE FRAMES, RAIL, AND POSTS SHALL BE BONDED WITH EQUIPMENT GROUND CONDUCTORS. GENERAL NOTES 1. ALL WORK TO BE DONE TO THE 2013 CALIFORNIA BUILDING CODE AND THE 2013 CALIFORNIA RESIDENTIAL CODE. 2. ALL ELECTRICAL WORK SHALL COMPLY WITH THE 2011 NATIONAL ELECTRIC CODE AS AMENDED BY THE 2013 CALIFORNIA ELECTRIC CODE. CONFIDENTIAL — THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT SOLARCITY INC., NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE THE RECIPIENT'S ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF SOLARCITY INC. JOB NUMBER: J 3-9224941 00 MOUNTING SYSTEM: Comp Mount Type C MODULES: (20) KYOCERA # KU2656ZPA INVERTER: ABB # PVI-3.6—OUTD—S—US—Z—A ALL CONSTRUCTION SHALL COMPLY WITH THE 2013 CALIFORNIA BUILDING, RESIDENTIAL, MECHANICAL, ELECTRICAL, PLUMBING, ENERGY, AND GREEN BUILDING CODES AND THE LA QUINTA MUNICIPAL CODE VICINITY MAP Pff M. t - I .F i� .Wn yM1' -iiit�I - µ -'Imo. -' tt Ioogle Imagery C12015 , DigitalGlobe, USDA Farm Service Agency PREMISE OWNER: WAINIO, DANIEL 51525 AVENIDA MENDOZA LA QUINTA, CA 92253 APN: 773142025 7608996959 DESCRIPTION: WAINIO RESIDENCE 5.3 KW PV ARRAY PAGE NAME: COVER SHEET INDEX Cutsheets Attached REV BY DATE COMMENTS REV B REASON 11/5/2015 SYSTEM UPSIZE r DESIGN: Vidyashree Rajasekar KetilotAhret NizSolarCit y 1 SHEET: REV: DATE: PV 1 B 10/26/2015 3055 Clearview Way San Mateo, CA 94402 T:(650) 638-1028 F:(650) 638-1029 (888)—SOL—CITY (765-2489) www.solarcity.com TRANSFORMER INFORMATION: KVA PHASE HIGH KV LOW 120/240V — METER#** "PROPOSED BI—DIRECTIONAL METER# *DISCONNECT CUTTLER HAMMER 30A — AC DISCONNECT: 5 FT FROM MAIN PANEL — INVERTER: ABB PVI 3.6 51525 Avenida Mendoza (E) DRIVEWAY Front Of House n oc AC LL 0 200A, 240V, SINGLE PHASE, 2 WIRES, 22kAiC EXISTING BI DIRECTIONAL METER# ******** 0 0 0 ' -0-0- v —J 3' FSB L- - 3' FSB Locked Gated B PITCH: 12 ARRAY PITCH: 12 AZIMUTH: 180 ARRAY AZIMUTH: 180 MATERIAL: Comp Shingle STORY: 1 Story PITCH: 12 ARRAY PITCH: 12 AZIMUTH: 270 ARRAY AZIMUTH: 270 MATERIAL: Comp Shingle STORY: 1 Story LEGEND CD DC AC 0 r, II L .-2J (E) UTILITY METER & WARNING LABEL INVERTER W/ INTEGRATED DC DISCO & WARNING LABELS DC DISCONNECT & WARNING LABELS AC DISCONNECT & WARNING LABELS DC JUNCTION/COMBINER BOX & LABELS DISTRIBUTION PANEL & LABELS LOAD CENTER & WARNING LABELS DEDICATED PV SYSTEM METER STANDOFF LOCATIONS CONDUIT RUN ON EXTERIOR CONDUIT RUN ON INTERIOR GATE/FENCE HEAT PRODUCING VENTS ARE RED INTERIOR EQUIPMENT IS DASHED SITE PLAN Scale: 3/32" = 1' 01' 10' 21' I%• w N S E CONFIDENTIAL — THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT SOLARCITY INC., NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE THE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF SOLARCITY INC. JOB NUMBER: J 3-9224941 00 MOUNTING SYSTEM: Comp Mount Type C MODULES: (20) KYOCERA # KU2656ZPA INVERTER: ABB # PVI-3.6—OUTD—S—US—Z—A PREMISE OWNER: WAINIO, DANIEL 51525 AVENIDA MENDOZA LA QUINTA, CA 92253 7608996959 DESCRIPTION: WAINIO RESIDENCE 5.3 KW PV ARRAY PAGE NAME: SITE PLAN DESIGN: Vidyashree Rajasekar s c-1 can h ree = SalarCity 1 SHEET: REV: DATE: PV 2 B 10/26/2015 3055 Clearview Way San Mateo, CA 94402 T:(650) 638-1028 F:(650) 638-1029 (888)—SOL—CITY (765-2489) www.solarcity.com 4'' PV MODULE 5/16" BOLT WITH LOCK & FENDER WASHERS ZEP LEVELING FOOT ZEP ARRAY SKIRT ZEP COMP MOUNT C ZEP FLASHING C (E) COMP. SHINGLE (E) ROOF DECKING 5/16" DIA STAINLESS STEEL LAG BOLT WITH SEALING WASHER (2-1/2" EMBED, MIN) (E) RAFTER 4' 3" (E) LBW 6' SIDE VIEW OF MP1 NTS MP1 X-SPACING X-CANTILEVER Y-SPACING Y-CANTILEVER NOTES LANDSCAPE 48" 24" STAGGERED PORTRAIT 48" 20" TOP CHORD 2x4 @ 24" OC BOT CHORD 2x4 @24" OC ROOF AZI 180 PITCH 12 ARRAY AZI 180 PITCH 12 STORIES: 1 Comp Shingle (6) (4) (5) LOWEST MODULE SUBSEQUENT MODULES STAN DOFF Scale: 1 1/2" = 1' INSTALLATION ORDER LOCATE RAFTER, MARK HOLE LOCATION, AND DRILL PILOT HOLE. SEAL PILOT HOLE WITH POLYURETHANE SEALANT. INSERT FLASHING. (4) PLACE MOUNT. (5) () INSTALL LAG BOLT WITH SEALING WASHER. INSTALL LEVELING FOOT WITH BOLT & WASHERS. S1 4'-4" (E) LBW SIDE VIEW OF MP2 Nrs MP2 X-SPACING X-CANTILEVER Y-SPACING Y-CANTILEVER NOTES LANDSCAPE 48" 24" STAGGERED PORTRAIT 48" 20" RAFTER 2x4 @ 24"STORIES: OC C.J. 2x4 ©24" OC ROOF AZI 270 PITCH 12 1 ARRAY AZI 270 PITCH 12 Comp Shingle CONFIDENTIAL — THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT SOLARCITY INC., NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE THE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF SOLARCITY INC. JOB NUMBER: J 3-9224941 00 MOUNTING SYSTEM: Comp Mount Type C MODULES (20) KYOCERA # KU2656ZPA INVERTER: ABB # PVI-3.6—OUTD—S—US—Z—A PREMISE OWNER: WAINIO, DANIEL 51525 AVENIDA MENDOZA LA QUINTA, CA 92253 7608996959 DESCRIPTION: WAINIO RESIDENCE 5.3 KW PV ARRAY PAGE NAME: STRUCTURAL VIEWS DESIGN: Vidyashree Rajasekar -='SoIa 1 City SHEET: REV: DATE: PV 3 B 10/26/2015 3055 Clearview Way San Mateo, CA 94402 T:(650) 638-1028 F:(650) 638-1029 (888)—SOL—CITY (765-2489) www.solarcity.com UPLIFT CALCULATIONS SolarCrty PV System Structural Desian Software 11.05.2015 Version *52.8 Project Information & Table Of Contents Risk Category: PV System Type Comp Roof Layers of Comp Roofing II SolarOty SleekMount"` Comp Roof 2 Roof Slope Rafter Sparing 12' 24" O.C. PV System Module Orientation PV Module Area PV Module Width PV Module Length Standoff (Attachment Hardware) Landscape and Portrait 407 sf 39" 65" Comp Mount Type C Reduced Ground/Roof Live/Snow Loads Ground Snow Load Surrounding Roof Snow Roof Snow Over PV Modules pg 100% 100% 10.0 psf 10.0 psf 10.0 psf ' ' ' ASCE Table 7-1 ASCE Eq: 7.4-1 ASCE Eq: 1.4-1 Wind Design Criteria Wind Design Code ASCE 7-10 = Y Fig. 26.5-IA Section 26.7 rig. 3e.4-2A/B/C-5A;B Section 26.2 IBC 1509.7.1 Wind Design Method Basic Wind Speed Exposure Category Roof Style Mean Roof Height Effective Wind Area (1 Module) V h A Partially/Fully Enclosed Method 110 mph C Gable Roof 15 ft 17.7 5f Wind Pressure Calculation Coefficients Wind Pressure Exposure Topographic Factor Wind Directionality Factor Importance Factor Kz Kzt Kd I 0.85 1.00 0.85 NA Table 30.3-1 Section 26.8 Section 26.6-1 Velocity Pressure qh qh = 0.00256 (Ki) (ICzt) (Kd) (V 22.4psi -2) Equation 30.3-1 Ext. Pressure Coefficient (Up) Ext. Pressure Coefficient (Dawn) GCp (Lip) GCp (Down) •0.88 0.45 Fg.30.4.2A/eJC-5A+B F. 30.4-2AIBIC-5/VB Design Wind Pressure e p = qh (GCp) Equation 30.4-1 Wind Pressure Up Wind Pressure Down p(np) p(down) -19.6 psi 16.0 psi Allowable Standoff Spacings X-Dk ection Y-Direction Max Allowable Standoff Spadng Max Allowable Cantilever Standoff Configuration Landscape Landscape Landscape 48" 24" Staggered 39" NA Max Standoff Tributary Area PV Assembly Dead Load Net Wind Uplift at Standoff Uplift Capacity of Standoff Standoff Demand/Capacity Trlb W-PV T-actual T-allow DCR 13 sf 3 psf -130 Ibs 500 lbs 25.9% Max Allowable Standoff Spacing Max Allowable Cantilever Standoff Configuration Portrait Portrait Portrait 48" 20" Staggered 65" NA Max Standoff Tributary Area PV Assembly Dead Load Net Wind Uplift at Standoff Uplift Capacity of Standoff Standoff Demand/Capacity Trib W-PV T-actual T-allow DCR 22 sf 3 psf -218 Ibs 500 Ibs 43.5% CONFIDENTIAL — THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT SOLARCITY INC., NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE THE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF SOLARCITY INC. JOB NUMBER: J 3-9224941 00 MOUNTING SYSTEM: Comp Mount Type C MODULES (20) KYOCERA # KU2656ZPA INVERTER: ABB # PVI-3.6—OUTD—S—US—Z—A PREMISE OWNER: WAINIO, DANIEL 51525 AVENIDA MENDOZA LA QUINTA, CA 92253 7608996959 DESCRIPTION: WAINIO RESIDENCE 5.3 KW PV ARRAY PAGE NAME: UPLIFT CALCULATIONS DESIGN: Vidyashree Rajasekar R. V ict1 co I,, 41:ir SoIar 1 City SHEET: REV: DATE: PV 4 B 10/26/2015 3055 Clearview Way San Mateo, CA 94402 T:(650) 638-1028 F:(650) 638-1029 (888)—SOL—CITY (765-2489) www.solarcity.com GROUND SPECS MAIN PANEL SPECS GENERAL NOTES INVERTER SPECS MODULE SPECS LICENSE BOND (N) #8 GEC TO (E) UFER AT PANEL WITH IRREVERSIBLE CRIMP Panel Number: NoLabel Meter Number: 1B4SR-148440 Overhead Service Entrance Inv 1: DC Ungrounded IN 1 - (1 )SOLAREDGE ##SE5000A-US-ZB-U LABEL: A Inverter; 5000W, 240V, 97.5%; w/Unifed Disco and ZB, AFC' - (23) KYOCERA # KU2656ZPA PV Module; 265W, 238.1W PTC, 40MM, Blk Frm, H4, ZEP, 1000V, Blk Cell,no Voc: 38.3 Vpmax: 31 Isc AND Imp ARE SHOWN IN THE DC STRINGS IDENTIFIER CA # 888104 Backbar C-10 INV IN 3 (E) 200A MAIN SERVICE PANEL (E)200A/2P MAIN CIRCUIT BREAKER SolarCity Inverter 1 CUTLER -HAMMER 0A SOLAREDGE 200A/2P Disconnect •- A DC+ SE5000A-US-ZB-U D DC_ y MP 3,MP 1: 1x1 AS, '� (E) LOADS B I I zaov I EGC • J n LI �- V • 1 L2 �- DC+ I I I • N •� DC- I 3 2 I w w [1A/2P �� GND EGC/ DC+ a o r� ��� GEC A DC_ C MP 1: 1x12 �A 6 GND I EGC I G J • • 1 �1/Lr - - -■ r _ * 1 N ( 1 ) Conduit Kit; 3/4" EMT 1 TO 120/240V SINGLE UTILITY PHASE SERVICE z-z c.O EGC/GEC j PHOTOVOLTAIC SYSTEM CONDUCTORS SHALL BE IDENTIFIED AND GROUPED. THE MEANS OF IDENTIFICATION SHALL BE PERMITTED BY SEPARATE COLOR CODING, MARKING TAPE, - TAGGING, OR OTHER APPROVED MEANS. THE MEANS OF GROUPING SHALL BE WIRE TIES OR SIMILAR MEANS AT LEAST ONCE, AND THEN AT INTERVALS NOT TO EXCEED SIX (6) FEET. PHOTOVOLTAIC EQUIPMENT AND SYSTEMS AND ALL ASSOCIATED WIRING AND INTERCONNECTIONS SHALL BE INSTALLED ONLY BY QUALIFIED PERSONS CONDUCTOR SIZING IS CALCULATED IN ACCORDANCE WITH NEC 690.8(A)(1)-(4) & (B)(2)(B). Voc* = MAX VOC AT MIN TEMP POI - (1) SQUARE D ji Q4230 PV BACKFEED BREAKER Breaker; A 2P, 2 Spaces, Plug -On 6 - (1)CUTLER-HAMMER# DG221URB n Disconnect; 30A, 240Vac, Non -Fusible, NEMA 3R /y A -(1 )SolarCit # 4 STRING JUNCTION BOX DC 2x2 S1yR(GS, UNFUSED, GROUNDED -(1)CUTLER-HAMMER # DGO3ONB Ground/Neutral Kit; 30A, General Duty (DG) - (4)Shoals STG.ILF.15.MC4 Inline fuse and holder; 15A, MC4, Unserviceable, Wtherproof PV (23)SOLAREDGE J�P300-2NA4AZS PowerBox Optimizer, 300W, H4, DC to DC, ZEP nd (1) AWG #6, Solid Bare Copper (N) ARRAY FI FCTRODE - ( 1) Ground Rod; 5/8" x 8', Copper GROUND PER 690.47(D). NOTE: PER EXCEPTION NO. 2, ADDITIONAL MAY NOT BE REQUIRED DEPENDING ON LOCATION OF (E) ELECTRODE. O 4 (1)AWG #8, THWN-2, Black Voc* = 500 VDC Isc = 15 ADC (4- (1)AWG #8, THWN-2, Red Vmp = 350 VDC Imp= 8.97 ADC • (1)AWG #10, THHN/THWN-2, Green EGC (1)AWG #8, THWN-2, Black Voc* = 500 VDC Isc = 15 ADC 1 AWG #8,VmpImp= - ( ) THWN-2, Red = 350 VDC 8.22 ADC OIA O (2) AWG #10, PV Wire, 600V, Black Voc* = 500 VDC Isc = 15 ADC (1,AWG #10, Solid Bare Copper EGC Vmp = 350 VDC Imp= 8.22 ADC (2) AWG #10, PV Wire, 600V, Black Voc* = 500 VDC Isc = 15 ADC (1)AWG #10, Solid Bare Copper EGC Vmp = 350 VDC Imp= 8.97 ADC 0(1) o- AWG #10, THWN-2, Black (1)AWG #10, THWN-2, Red CONFIDENTIAL - THE INFORMATION HEREIN CONTAINEDTSHALL NOT BEE USEDO FOR THE BENEFIT OF ANYONE EXCEPT SOLARCITY INC., NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE THE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF SOLARCITY INC. JOB NUMBER: J-9224941 00 PREMISE OWNER: DESCRIPTION: DANIEL WAINIO RESIDENCE 51525 AVENIDA MENDOZA 5.3 KW PV ARRAY LA QUINTA, CA 92253 PAGE NAME: 7608996959 THREE LINE DIAGRAM DESIGN:WAINIO, Vidyashree Vld ashree Rajasekar �`�A ��I�I --,,SolarCity ��� r �I+■ . MOUNTING SYSTEM: Comp Mount Type C {� T 4 t ctl NODDLES: (20) KYOCERA # KU2656ZPA 3055 Clearview Way to , CA 94402 ST:(650) SanMateo, 50) 638-1029 (888)-SOL-CITY (765-2489) www.solarcity.com SHEET: REV: DATE: PV 5 B 10/26/2015 INVERTER: ABB # PVI-3.6-OUTD-S-US-Z-A EXISTING UNDERGROUND PHOTOVOLTAIC SYSTEM UTILITY ELECTRICAL SERVICE ENTRANCE DISCONNECT SWITCH PV ARRAY # 11 MODULES 200A/2P MAIN PANEL RATING CUTLER -HAMMER #DG221URB a 1 KYOCERA 30A, 240VAC ® #KU2656Z' 265 WATT D (E) LOADS AC 2915 WATT DV PV ARRAY #2 f + 30A/2P I s 2 12 MODULES �' KYO DC #KU2656ZCER p B 5000 TT UTILITY INTERACTIVE INVERTER A 265 WATT DC 3180 WATT Dr 5t1 VDC TO 120/240 SOLAREDGE SE5000A-US-ZB-U VAC 1 0 To 120/ SINGLE UTILITY PHASE SERVICE 6 (1)CUTLER-HAMMER # DG221URB n Disconnect; 30A, 240Vac, Non -Fusible, NEMA 3R A A (1)SolarCity # 4 STRINCNW9CT10N BOX D� 2x2 STRINGS, UNFUSED, GROUNDED - (1) Ground/Neutral Kit D30A General Duty (DG) - (4) )Shoals fusel and5holder; 15A, MC4, Unserviceable, Wtherproof O_ 5 0 'r ( (1) AWG #10, THWN-2, Black (1) AWG #10, THWN-2, Red (1) AWG #8, THWN-2, Black Voc* = 500 VDC Isc = 15 ADC (4- (1) AWG #8, THWN-2, Red Vmp = 350 VDC Imp = 8.97 ADC rt (1)AWG #10, THHN/THWN-2, Green EGC I (1) AWG #8, THWN-2, Black Voc* = 500 VDC Isc = 15 ADC ILL (1 )AWG #8, THWN-2, Red Vmp = 350 VDC Imp = 8.22 ADC II (1)AWG #10, THHN/THWN-2, Green EGC 1 O (2) AWG #10, PV Wire, 600V, Black Voc* = 500 VDC Isc = 15 ADC (4- (1) AWG #10, Solid Bare Copper EGC Vmp = 350 VDC Imp = 8.22 ADC •- (2) AWG #10, PV Wire, 600V, Black Voc* = 500 VDC Isc = 15 ADC R- (1 )AWG #10, Solid Bare Copper EGC Vmp = 350 VDC Imp = 8.97 ADC CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE OF ANYONE EXCEPT SOLARCITY INC., NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE THE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF SOLARCITY INC. JOB NUMBER: J -9224941 00 PREMISE OWNER: DESCRIPTION: WAINIO, DANIEL WAINIO RESIDENCE 51525 AVENIDA MENDOZA 5.3 KW PV ARRAY QUINTA, CA 92253 PAGE NAME: 7608996959 ONE LINE DIAGRAM DESIGN: Vidyashree Rajasekar `!! SolarCityBENEFIT �f� MOUNTING SYSTEM: Comp Mount Type C li'Le,�jc,.>'1Yet �j MODULES:LA (20) KYOCERA # KU2656ZPA 3055 Clearview Way to , CA 94402 ST:(650) SanMateo, 50) 638-1029 (888)-SOL-CITY (765-2489) www.solarcity.com SHEET: REV: DATE: PV 6 B 10/26/2015 INVERTER: ABB # PVI-3.6-OUTD-S-US-Z-A ELECTRICAL CALCULATIONS Module: 23 Kyocera 265W 1000V 238.1 Inv Power WPTC Voltage Drop Calculations Version 5_8.0 Inverter 1: 1 SolarEdge 5000 AFCI 0.98 5000 5366.77 Vdrop = Imp) " (2 * Length) " (Resistance) / (Vmp) Module: Kyocera 265W 1000V 238.1 Imp (A) Max. Length (ft) Wire Inverter 2: String: 8.22 50 AWG #10 at Max Ave Hi:109 deg F Vdrop = (8.22 100 0.00124 Ohms) / 350 0.36 Module: Kyocera 265W 1000V 238.1 Branch: 23 15 AWG #10 at Max Ave Hi:109 deg F Inverter 3: Vdrop = (23 30 0.00124 Ohms) / 240 0.12 Module: Kyocera 265W 1000V 238.1 Total voltage drop in DC conductors = Inverter 4: Inverter: at 240V Vdrop = Ohms) / 240 V Total: 23 Modules Total Inv Pwr: 5000 5366.77 PTC Combined: at 240V Photovoltaic Module Electrical Specifications: Total STC: 6095 Vdrop = Ohms) / 240 V Voc: 38.3 V deg F deg C Vmp: 31 V Record Low Temp: 14 -10 Total voltage drop in AC conductors = Isc: 9.26 A Max Average Hi Temp: 109 43 Total voltage drop in AC and DC conductors = Imp: 8.55 A Record Hi Temp: Tvoc: -0.14 V/deg C Tisc: 5.56 mA/deg C String Type A and 2 Combined Strings Type A Voc Correction Method: Manuf TVoc Data Branch Circuit Type A 1 way wire length: 50 SolarEdge 5000 AFCI Voc Correction Factor: 1 strings per branch 1 strings per branch 2 Kyocera 265W 1000V Inverter Min Vdc Input: 350 11 modules per series string modules per series string 11 Voc= 500 Min Vmp at Max Temp: 282.69 Voc= 500 V Voc= V Vmp= 350 Max Voc at Min Temp: 500 Vmp= 350 V Vmp= V Isc= Inverter Max Vdc Input: 500 Isc= 15 A Isc= A 15 Imp= 8.22 Max String Size: 19 Imp= 8.22 A Imp= A Icont= 15 1-way wire length: Art 690.8(A)(1) 50 Icont= 15 A Icont= A Art 690.8(A)(1) 1.a Conductor: AWG #10 PV Wire 2.a Conductor 1: AWG #8 Conductor 2: Icont * 1.25 = (Amps) 15 Conductor 1 Conductor2 30 deg C ampacity = 40 Icont * 1.25 = (Amps) 18.75 1.b Icont= (Amps) 15 30 deg C ampacity = 55 Start ampacity 40 2.b Icont= (Amps) 15 Temperature derate (%=F) 0.41 Start ampacity 55 Conduit fill derate (%=#) 1 Temperature derate (%=F) 0.41 Derated ampacity 16.4 Conduit fill derate (%_#) 0.8 1.c Derated ampacity 18.04 Icont * 1.25 = (Amps) 15 2.c Term 1 Term 2 Ampacity 40 Temp table 90 °C:Tab e 310.15(6 (16) Icont*1.25= (Amps) 18.75 1.d Icont * 1.25 = (Amps) 15 Ampacity 55 OCP Size = 15 Inverter Type A Output 2.d OCP Size = 20 SolarEdge 5000 AFCI 1 way wire length: 15 ft Combined Inverter Output Icont = 23 A Art 690.8(A)(1) Service Voltage- Total Inverter Power= 1 way wire length= Icont = # of inverters*max inverter current Art 690.8(A)(1) Icont = (Amps) 15 3.a Icont * 1.25 = (Amps) 28.75 Art 690.8(B)(1) OCP Size = 30 Art 240.6(A) 3.b Conductor: AWG #10 THWN-2 at 90 deg C: Table 310.16 4.a Icont*1.25 = (Amps) 28.75 Art 690.8(B)(1) Icont * 1.25 = (Amps) 28,75 OCP size = 30 Art 240.6(A) 30 deg C ampacity = 40 4.b Conductor: AWG #10 THWN-2 at 90 deg C: Table 310.16 3.c Icont = (Amps) 23 Icont * 1.25 = (Amps) 28.75 Start ampacity 40 30 deg C ampacity = 40 Temperature derate (%=F) 0.82 4.c Icont = (Amps) 23 Conduit fill derate (%_#) 1 Start ampacity 40 Derated ampacity 32.8 Temperature derate (%=F) 0.82 3.d Icont * 1.25 = (Amps) 28.75 Conduit fill derate (%_#) 1 Ampacity 35 Derated ampacity 32.8 4.d Icont * 1.25 = (Amps) 28.75 CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT SOLARCITY INC., NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE THE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF SOLARCITY INC. JOB NUMBER:J -PREMISE 9224941 00 OWNER: DESCRIPTION: WAINIO, DANIEL WAINIO RESIDENCE 51525 AVENIDA MENDOZA 5.3 KW PV ARRAY LA QUINTA, CA 92253 PAGE NAME: 7608996959 ELECTRICAL CALCULATIONS DESIGN: Vidyashree Rajasekar +� ��•�`'!! SoIarCity MOUNTING SYSTEM: Comp Mount Type C � L�j �,, rim MODULES: (20) KYOCERA # KU2656ZPA 3055 Clearview Way to , CA 94402 ST:(650) SanMateo, 50) 638-1029 (888)-SOL-CITY (765-2489) www.solarcity.com SHEET: REV: DATE: PV 7 B 10/26/2015 INVERTER: ABB # PVI-3.6-OUTD-S-US-Z-A CAUTION POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN: - Address: 51525 Avenida Mendoza INVERTER AND DC DISCONNECT AC DISCONNECT UTILITY SERVICE SOLAR PHOTOVOLTAIC ARRAY(S) PHOTOVOLTAIC BACK -FED CIRCUIT BREAKER IN MAIN ELECTRICAL PANEL IS AN A/C DISCONNECT PER NEC 690.17 OPERATING VOLTAGE = 240V JB-9224941-00 CONFIDENTIAL — THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT SOLARCITY INC., NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE THE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF SOLARCITY INC. JOB NUMBER: J 3-9224941 00 MOUNTING SYSTEM: Comp Mount Type C MODULES: (20) KYOCERA # KU2656ZPA INVERTER: ABB # PVI-3.6—OUTD—S—US—Z—A PREMISE OWNER: WAINIO, DANIEL 51525 AVENIDA MENDOZA LA QUINTA, CA 92253 7608996959 DESCRIPTION: WAINIO RESIDENCE 5.3 KW PV ARRAY PAGE NAME: SITE PLAN PLACARD DESIGN: Vidyashree Rajasekar `4%`IftSolarCi 4 SHEET: REV: DATE: PV 8 B 10/26/2015 3055 Clearview Way San Mateo, CA 94402 T:(650) 638-1028 F:(650) 638-1029 (888)—SOL—CITY (765-2489) www.solarcity.com WARNING; PHOTOVOLTAIC POWER SOURCE PHOTOVOLTAIC DC DISCONNECT MAXIMUM POWER - POINT CURRENT (Imp) MAXIMUM POWER - POINT VOLTAGE (Vmp) MAXIMUM SYSTEM VOLTAGE (Voc) SHORT-CIRCUIT CURRENT (Ise) WARNING ELECTRICAL SHOCK HAZARD DO NOT TOUCH TERMINALS TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION DC VOLTAGE IS ALWAYS PRESENT WHEN SOLAR MODULES ARE EXPOSED TO SUNLaGHT WARNING ELECTRIC SHOCK HAZARD IF A GROUND FAULT IS INDICATED NORMALLY GROUNDED CONDUCTORS MAY BE UNGROUNDED AND ENERGIZED PHOTOVOLTAIC AC DISCONNECT MAXIMUM AC OPERATING CURRENT MAXIMUM AC OPERATING VOLTAGE Label Location: (C)(IC)(CB) Per Code: CRC R331.2 Label Location: (DC) (INV) Per Code: CEC 690.14.C.2 Label Location: (DC) (INV) Per Code: CEC 690.53 Label Location: (DC) (CB) Per Code: CEC 690.17 Label Location: (INV) Per Code: CEC 690.5(C) Label Location: (AC) (P01) Per Code: CEC 690.14.C.2 Label Location: (AC) (P01) Per Code: CEC 690.54 PV SYSTEM DISCONNECT FOR UTILITY OPERATION WARNING ELECTRIC SHOCK HAZARD DO NOT TOUCH TERMINALS TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION WARNING INVERTER OUTPUT CONNECTION DO NOT RELOCATE THIS OVERCURRENT DEVICE PHOTOVOLTAIC POINT OF INTERCONNECTION WARNING: ELECTRIC SHOCK HAZARD. DO NOT TOUCH TERMINALS. TERMINALS ON BOTH THE LINE AND LOAD SIDE MAY BE ENERGIZED IN THE OPEN POSITION. FOR SERVICE DE -ENERGIZE BOTH SOURCE AND MAIN BREAKER. PV POWER SOURCE MAXIMUM AC OPERATING CURRENT MAXIMUM AC OPERATING VOLTAGE A CAUTION PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED CAUTION DUAL POWER SOURCE SECOND SOURCE IS PHOTOVOLTAIC SYSTEM Label Location: (AC) Label Location: (DC) Per Code: CEC 690.17 Label Location: (P01) Per Code: CEC 705.12.D.7 Label Location: (P01) Per Code: CEC 690.54; CEC 690.17 Label Location: (D) (P01) Per Code: CEC 690.64.B.4 Label Location: (P01) Per Code: CEC 705.12.D.7 WARNING ELECTRIC SHOCK HAZARD THE DC CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM ARE UNGROUNDED AND MAY BE ENERGIZED Label Location: (DC)(INV)(CB) Per Code: CEC 690.35(F) TO BE USED WHEN INVERTER IS UNGROUNDED (AC): AC Disconnect (C): Conduit (CB): Combiner Box (D): Distribution Panel (DC): DC Disconnect (IC): Interior Run Conduit (INV): Inverter With Integrated DC Disconnect (LC): Load Center (M): Utility Meter (P01): Point of Interconnection CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT SOLARCITY INC., NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE THE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF SOLARCITY INC. Label Set 'r!-So lar'Clty 3055 Clearview Way San Mateo, CA 94402 T:(650) 638-1028 F:(650) 638-1029 (888)-SOL-CITY (765-2489) www.solarcity.com SolarCity 0 ZepSolar Next -Level PV Mounting Technology ill for composition shingle roofs p 9 Zep System LISTED zepsolar.com Description • PV mounting solution for composition shingle roofs • Works with all Zep Compatible Modules • Auto bonding UL-listed hardware creates structual and electrical bond • Zep System has a UL 1703 Class "A" Fire Rating when installed using modules from any manufacturer certified as "Type 1" or "Type 2" Specifications • Designed for pitched roofs • Installs in portrait and landscape orientations • Zep System supports module wind uplift and snow load pressures to 50 psf per UL 1703 • Wind tunnel report to ASCE 7-05 and 7-10 standards • Zep System grounding products are UL listed to UL 2703 and ETL listed to UL 467 • Zep System bonding products are UL listed to UL 2703 • Engineered for spans up to 72" and cantilevers up to 24" • Zep wire management products listed to UL 1565 for wire positioning devices • Attachment method UL listed to UL 2582 for Wind Driven Rain This document does not create any express warranty by Zep Solar or about its products or services. Zep Solar's sole warranty is contained in the written product warranty for each product. The end -user documentation shipped with Zep Solar's products constitutes the sole specifications referred to in the product warranty. The customer is solely responsible for verifying the suitability of Zep Solar's products for each use. Specifications are subject to change without notice. Patents and Apps: zspats.com. 02 27 15 ZS for Comp Shingle Cutsheet Rev 04.pdf Page: 1 of 2 1•SolarCity 0 ZepSolar Components zepsolar.com Next -Level PV Mounting Technology Comp Mount Part No. 850-1382 Listed to UL 2582 & Mounting Block to UL 2703 Interlock Part No. 850-1388 Listed to UL 2703 Leveling Foot Part No. 850-1397 Listed to UL 2703 Ground Zep Part No. 850-1172 Listed to UL 2703 and ETL listed to UL 467 Array Skirt, Grip, End Caps Part Nos. 500-0113, 850-1421, 850-1460, 850-1467 Listed to UL 2703 DC Wire Clip Part No. 850-1448 Listed UL 1565 This document does not create any express warranty by Zep Solar or about its products or services. Zep Solar's sole warranty is contained in the written product warranty for each product. The end -user documentation shipped with Zep Solar's products constitutes the sole specifications referred to in the product warranty. The customer is solely responsible for verifying the suitability of Zep Solar's products for each use. Specifications are subject to change without notice. Patents and Apps: zspats.com. 02 27 15 ZS for Comp Shingle Cutsheet Rev 04.pdf Page: 2 of 2 Solar inverters ABB string inverters PVI-3.0/3.6/3.8/4.2-TL-OUTD 3.0kW to 4.2kW This family of single-phase string inverters complements the typical number of rooftop solar panels enabling home -owners to get the most efficient energy harvesting for the size of the property. This inverter offers a dual input section that processes two strings with independent Multiple Power Point Tracking (MPPT). This is especially useful for rooftop installations with two different orientations from two sub -arrays oriented in different directions. (For example: East and West) The dual input sections with independent MPPT enable a more optimal energy harvesting condition. The high-speed MPPT offers real- time power tracking and improved energy harvesting. The flat efficiency curve ensures high efficiency at all output levels allowing a consistent and stable performance across the entire input voltage and output power range. The transformerless operation gives the highest efficiency of up to 97.0%. The wide input voltage range makes the inverter suitable to low power installations with reduced string size. This rugged outdoor inverter has been designed to be a completely sealed unit able to withstand the harshest environmental conditions. Highlights: — Single phase and split phase output grid connection. — Wide input range for increased stringing flexibility. — The high speed and precise MPPT algorithm offers real time power tracking and improved energy harvesting. — Outdoor NEMA 4X rated enclosure for unrestricted use under any environmental conditions. — Integrated DC disconnect switch in compliance with international Standards (-S Version). Power and productivity „ ,1 ,1 for a better world'F+,.,. Additional highlights: — RS-485 communication interface (for connection to laptop or data logger). — Integrated Arc Fault Detection and Interruption (-A Version). Technical data and types Type code PVI-3.0-OUTD-US PVI-3.6-OUTD-US PVI-3.8-OUTD-US PVI-4.2-OUTD-US Mechanical specifications Nominal output power Maximum output power wattage 3000 W 3000W 3300 W 3300 W 3600 W 3600W 4000 W 4000 W 3300 W 3300 W 3800W 42001 W 42001 W 4200 W 4200W 46001 w 4600 W Rated •rid AC voltage Input side (DC) Number of independent MPPT channels 208V 240V 277V 208V 240V 277V 208V 240V 277V 208V 240V 277V Maximum usable power for each channel 2000W 3000W 3000W 3000W Absolute maximum voltage (Vmax) 600V Start-up voltage (Vstart) 200V (adj. 120-350V) Full power MPPT voltage range Operating MPPT voltage range Maximum current (Idcmax) for both MPPT in .parallel Maximum usable current per channel 160-530V 20A 10A 120-530V 140-530V 0.7 x Vstart - 580V (>=90V) 32A 16A 32A 16A 140-530V 32A 16A Maximum short circuit current limit per channel 12.5A 20.0A 20.0A 20.0A Number of wire landing terminals per channel Array wiring termination Output side (AC) Grid connection type 10/ 2W Split- 0/3W 10/ 2W 2 pairs Terminal block, pressure clamp, AWG10-AWG4 10/ 2W Split- 0/3W 10/ 2W 10/ 2W Split- 0/3W 10/ 2W 10/ 2W Split- 0/3W 10/ 2W Adjustable voltage range (Vmin-Vmax) (V) 183 - 228V 211 - 264V 244- 304V 183- 228V 211- 264V 244- 304V 183- 228V 211- 264V 244- 304V 183- 228V 211- 264V 244- 304V Grid frequency 60Hz Adjustable grid frequency range 57-60.5Hz Maximum current (la°,m) Power factor 14.5 ARMS 14.5 ARMS 12.0 ARMS 17.2 P`RMs 16.0 ARMS 16.0 16.0 ARMS P`RMs > 0.995 16.0 A 16.0 ARMS 20.0 ARMS 20.0 ARMS 20.0 A Total harmonic distortion at rated power < 2% Grid wirin. termination type Input protection devices Reverse polarity protection Terminal block, Pressure clamp, AWG10-AWG4 Yes Over -voltage protection type Varistor, 2 for each channel PV array ground fault detection Pre start-up Riso and Dynamic GFDI (requires floating arrays) Output protection devices Anti-islanding protection Over -voltage protection type Meets UL 1741/IEEE1547 requirements Varistor, 2 (L, - L2 / L, - G) Maximum AC OCPD Rating Efficiency 20Aq„, ; 20A 15Ap„, 25Ap„, 20Aq„, 20Aq„, ; 20Ap„, i 20An„, 20Aq„ 25Aq„, Maximum efficiency CEC efficiency Operating performance 96.9% 97% 97% 96 % 97% Night time consumption Stand-by consumption Communication User -interface < 0.6W, <8Wn„, 16 characters x 2 lines LCD display Remote monitoring (1xRS485 incl.) Environmental Ambient air operating temperature range Ambient air storage temperature range VSN700 Data Logger (opt.) 13°F to +140°F with derating above 122°F (50°C) -40°F to +176°F (-40°C to +80°C) Relative humidity 0-100% RH condensing Acoustic noise emission level <50db(A)WIm Maximum operating altitutde without derating 6560 ft (2000 m) 1. Capability enabled at nominal AC voltage and with sufficient DC power available. 2 ABB Solar Inverters I Product flyer for PVI-3.0/3.6/3.8/4.2-TL-OUTD ■ KYOCER2 CUTTING EDGE TECHNOLOGY As a pioneer with four decades of experience in the development of photovoltaic systems, Kyocera drives the market as a leading provider of PV products. We demonstrate our Kaizen philosophy, or commitment to continuous improvement, by setting the industry standard in the innovation of best -in -class solar energy equipment. QUALITY BUILT IN • UV -stabilized, anodized aluminum frame in black • Supported by major mounting structure manufacturers • Easily accessible grounding points on all four corners for fast installation • Proven junction box technology with 12 AWG PV wire works with transformerless inverters • Amphenol H4-UTX locking plug-in connectors provide safe, quick connections PROVEN RELIABILITY • Kyocera modules confirmed by the Desert Knowledge Australia Solar Centre to have the highest average output of any crystalline module • First module manufacturer in the world to pass long- term sequential testing performed by TUV Rheinland • Only module manufacturer to achieve the rank of "Performance Leader" in all six categories of GTM Research's 2014 PV Module Reliability Scorecard CERTIFICATIONS • UL1703 Certified and Registered, UL Module Fire Performance: Type 2, CEC • NEC 2008 Compliant, IEC 61215/61730, and ISO 14001 US KU-60 1 000V Z Series KU265-6ZPA HIGH EFFICIENCY MULTICRYSTAL PHOTOVOLTAIC MODULE SOLAR by KYOCERA KU-60 1000V Series ELECTRICAL SPECIFICATIONS Standard Test Conditions (STC) STC=1000 W/M3 irradiance, 25°C module temperature, AM 1.5 spectrum* KU265-6ZPA Pma. 265 w V,p 31.0 mp 8.55 A voc MODULE CHARACTERISTICS Cells per module: 60 (6 x 10) Dimensions: length/width/height 65.43in/38.98in/ 1.57in (1662mm/990mm/40mm) Weight: 45.21bs (20.5kg) PACKAGING SPECIFICATIONS Modules per pallet: 20 38.3 V Pallets per 53' container. 36 9.26 A +5 / -0 Pallet box dimensions: length/width/height 66in/40in/43in (1675mm / 1005mm / 1055mm) % Pallet box weight: Nominal Operating Cell Temperature Conditions (NOCT) NOCT=800 W/M2 irradiance, 20°C ambient temperature, AM 1.5 spectrum* TNocr 45 °C 191 w V^p 27.9 V Imp 6.85 A 35.1 V 7.49 A PTC 238.1 w Temperature Coefficients Pm" -0.45 V^p -0.48 %/°C Irnp 0.02 %/°C V� -0.3 6 %/°C 44 0.06 %/°C Operating Temp -40 to +90 °C System Design Series Fuse Rating 15A Maximum DC System Voltage (UL) 1 000 V Hailstone Impact in (25mm) @ 51 mp (23m/s) `Subject to simulator measurement uncertainty of +l- 3%. KYOCERA reserves the right to modify these specifications without notice. WARNING: Read the instruction manual in its entirety prior to handling, installing & operat- ing Kyocera Solar modules. 040215 10151bs (460kg) 1 57" (4-) 7 65.43" (1662mn) gg CABLE W/ CONNECTOR (_) 1. 10" (28mn) POTTED JUNCTION BOX(IP65) 1[(+) LABEL 38. 98" (990mm) / G ounding Hole 0.16" (4mm) FRAME CROSS SECTION DIAGRAM 0.41- 00. L1.3 (35mm) LONG/SHORT SIDE OUR VALUED PARTNER Slotted Mounting Hole 0. 35"x0. 47" ( mmx12mm) KYOCERA Solar, Inc. 800-223-9580 800-523-2329 fax www.kyocerasolar.com } CO T. REVISION A AAA, .99 [25] « ° .67 pm .63 ne -> o » / 1)\)/ \ \ w (\ (\\\ 2 ~\\ e Si'-Vl—S6ox 143 \\ 0 \ 0 03 / DG321NRB DG322URB Switching Devices Safety Switches 8.1 120/240 Vac General -Duty, Fusible, Single -Throw, continued Maximum Horsepower Ratings 1 NEMA1 NEMA 3R Ampere Fuse Type Single -Phase AC Three -Phase AC DC Enclosure Indoor Enclosure Rainproof System Rating Provision 120V 240V 240V 250V Catalog Number Catalog Number Cartridge Type —Three -Pole, Three -Wire (Three Blades, Three Fuses)-240 Vac €€v 30 60 100 200 400 H 50-125 DG325FGK00 DG325FRK00 600 H 75-200 DG326FGKOW DG326FRK00 Cartridge Type —Four -Wire (Three Blades, Three Fuses, S/N)-120/240 Vac 30 H 1-1/2-3 3-7-1/2 DG321NGB DG321NRB p 6 p v' 60 100 3-10 7-1/2-15 DG322NGB DG322NRB 7-1/2-15 15-30 DG323NGB DG323NRB 200 H 15 25-60 DG324NGK DG324NRK 400 H 50-125 DG325NGK DG325NRK 600 H 75-200 D6326NGK DG326NRK 120/240 Vac General -Duty, Non -Fusible, Single -Throw Maximum Horsepower Ratings NEMA 1 NEMA 3R Ampere Single -Phase AC Three -Phase AC DC Enclosure Indoor Enclosure Rainproof System Rating 120V 240V 240V 250V Catalog Number Catalog Number Two -Pole, Two -Wire (Two Blades)-240 Vac 30 2 3 DG221UGB O DG221UR6 60 3 10 DG222UGB 0 DG222URBO 100 15 DG223UGB© DG223URBO 200 CO Three -Pole, Three -Wire (Three Blades)-240 Vac 30 2 3 7-1/2 DG321UGB ® DG321URB 0 60 3 10 15 DG322UGB ® DG322URB ® 100 15 30 DG323UGB O DG323URB 200 15 60 DG324UGK 0 DG324URK 400 125 DG325UGK0 DG325URK© 600 200 DG326UGK0 DG326URK© Notes D Maximum hp ratings apply only when dual element time delay fuses are used. O Use four -wire catalog numbers below. O Solid neutral bars are not included. Order separately from table on Page 15. O WARNING! Switch is not approved for service entrance unless a neutral kit is installed. O Use three -wire catalog numbers below. ® Drilled to accept field installed neutral kits. All general -duty safety switches are individually packaged. Accessories are limited in scope on general -duty safety switches. See Page 15 for availability. In addition, clear line shields are available as an accessory on 200-600A general -duty switches. Catalog Numbers: 200A = 70-7759-11, 400A = 70-8063-8, 600A = 70-8064-8. Volume 2—Commercial Distribution CA08100003E—Febniary 2011 www.eaton.com 27 rFT.N Powenny Business Wald wide "' 30A 24� D0221 URB General Duty Safety Switch Interruptor de seguridad servicio ligero 2 Pole Non -Fusible polos sin fusibles Type 3R Rainproof (NEMA) Tipp 3R a pruet a de LI 7 82113 2 Series: Series: B Oty: Cant.: M*DE 1 N u.s .A, HECNIOPN E.U.A. 03/16/2012 S531430 } _ T. REVISION 11/12/98 .99 [25] « o .67 pm 63 ne - > »Fo. / / 1)\ \ 0 \ w (\ _0 ~\\ e Si'-Vl—S6ox _ / ®.. Zep Solar ZS CompTM I Grounding and Bonding This document describes the mechanics of how the electrical bonding is accomplished between the UL Listed hardware components used in Zep Solar's ZS Comp mounting solution for composition shingle roofs. Zep Compatible" systems do not require running copper conductors to each module. The act of physically installing each component simultaneously establishes an electrical bond, as described in the following pages. Ground Zep Down -roof ZS Comp Cutaway Illustration Interlock (Key side shown) Zep Compatible module with Zep Groove Leveling Foot Document 800-1478-001 Rev A www.zepsolar.com © 2013/EN Zep Solar, Inc. Zep Solar reserves the right to make specifications chnages without any prior notice. All rights reserved. Date Last Exported: June 25, 2013 4:45 PM PAGE: 1 of 5 CI ZepSo[a ZS COMP I GROUNDING AND BONDING Interlock Part No. 850-1388 UL Listed to UL 2703 Key Side Bonding Key side in closed position Cutting "tooth" Cutting "tooth" Tongue Side Bonding Tongue side in closed position Cutting "teeth" Interlock Zep Key side Side view Interlock Module Bonding locations on Key side Bonding location on Tongue side Forced interference during rotation of Interlock Zep causes teeth to cut through anodization on module frame, resulting in robust and UL certified bonding path Forced interference between mating parts from module rock -in motion cuts into module frame, removing anodization and resulting in robust and UL certified bonding path Document 800-1478-001 Rev A www.zepsolar.com © 2013/EN Zep Solar, Inc. Zep Solar reserves the right to make specifications chnages without any prior notice. Alt rights reserved. Date Last Exported: June25, 20134:45 PM PAGE: 2 of 5 0 ZepSuLar ZS COMP I GROUNDING AND BONDING Interlock, continued Part No. 850-1388 UL Listed to UL 2703 Bonding Path - Key and Tongue Module Interlock Bonding Path - Array The Interlock bonds modules on all 4 sides to create a hyper - bonded array where every module is structurally and electrically bonded to the surrounding modules. I I Tongue side \ 1 Keyside f fi fi W of \a f fi l b a b a b fi Interlock Y Bonding path Down -roof Document 800-1478-001 Rev A www.zepsolar.com © 2013/EN Zep Solar, Inc. Zep Solar reserves the right to make specifications chnages without any prior notice. All rights reserved. Date Last Exported: June 25, 2013 4:45 PM PAGE: 3 of 5 ®. ZepSolar ZS COMP I GROUNDING AND BONDING Leveling Foot Part No. 850-1397 UL Listed to UL 2703 Tongue side 4 Key side The Leveling Foot top portion (the Rockit) has a stainless steel spring clip that bonds to the adjacent module frame on both Key and Tongue sides. Leveling Foot - Bonding With Module Frame Key side inserts into Zep Groove (rock -in) Module in next row drops in on the Tongue side Bonding Path - North and South Modules . Leveling Foot Bonding path Down -roof Bonding location on Tongue side Spring clip Bonding location on Key side Module rotation during drop -in creates forced interference between Zep Groove and spring clip, cutting into module frame, removing anodization and resulting in robust and UL certified bonding path Document 800-1478-001 Rev A www.zepsolar.com © 2013/EN Zep Solar, Inc. Zep Solar reserves the right to make specifications chnages without any prior notice. All rights reserved. Date Last Exported: June25, 20134:45 PM PAGE: 4 of 5 Zep ZS COMP I GROUNDING AND BONDING Ground Zep Set screw ill/ Key side Part No. 850-1172 UL Listed to UL 467 and UL 2703 Ground Zep Installation Ground wire channel The Ground Zep provides a single point of connection for the Equipment Grounding Conductor (EGC) from the array to a building ground. Insert Ground Zep into Zep Groove of module frame, Use the Flat Too to rotate the Ground Zep 90 degrees, so that set screw Insert copper EGC into ground wire channel. Tighten set screw using torque values shown in the ZS Comp Installa- tion Manual. on array perimeter is pointing straight up. Bonding Path - Array to Ground r Ground Zep Equipment Ground Conductor Bonding path Down -roof Document 800-1478-001 Rev A www.zepsolar.com © 2013/EN Zep Solar, Inc. Zep Solar reserves the right to make specifications chnages without any prior notice. All rights reserved. Date Last Exported: June 25, 2013 4:45 PM PAGE: 5 of 5 SolarCity Standard Box 4J The SolarCity Standard Box 4J is a 4-String unfused Junction Box. The box is highly configurable and adaptable using the (4) jumper blocks included in each box. A factory installed cordgrip enhances installer productivity. 4/ 4 y 31 4,j x`3 3ie SolarCity October 2013 • Manufactured to meet UL 1741 Standards. • Non -Metallic, Corrosion Resistant NEMA 4X Enclosure. • Factory -Installed Cordgrip Enhances Installation Speed. • Break-Thru Skinned -Over Glands on Cordgrip Provide Weathertight Seal for All Configurations. • Easily Configurable Terminal Blocks Permit Adaptation to Site -Specific Stringing Needs. Technical Data / Specifications Voltage Rating [VDC] : 600V B Maximum DC Current [A]: 57A C Maximum Continuous Current [A]: 42A D Maximum Voltage [VDC]: 600V E Wire Size Range [AWG]: #6 to #14 F Enclosure Rating: NEMA 4X G Operating Temperature Range [°C]: -40 to 50 H Typical Overall Dimensions [in]: 8"x6"x4" NOTICE OF COMPLETION AND AUTHORIZATION TO APPLY THE UL MARK Solarcity Corp Alex Yang 3055 Clearview Way San Mateo Ca 94402-3709, Us Our Reference: Your Reference: Project Scope: Dear Alex Yang: 12/21 /2913 E31 8537, Volume 1 Project Number 4786083586 A.Yang 1017 Investigation of Photovoltaic (PV) System Combiner Box, model "SolarCity Standard Box 4C" and Photovoltaic (PV) System Transition Box, model "SolarCity Standard Box 4.1' to UL 1741 Standard. Congratulations! UL's investigation of your product(s) has been completed under the above Reference Number and the product was determined to comply with the applicable requirements. This letter temporarily supplements the UL Follow -Up Services Procedure and serves as authorization to apply the UL Mark at authorized factories under UL's Follow -Up Service Program. To provide your manufacturer(s) with the intended authorization to use the UL Mark, you must send a copy of this notice to each manufacturing location currently authorized under E318537, Volume 1 and including any special instructions as indicated in the addendum to this letter. Records in the Follow -Up Services Procedure covering the product are now being prepared and will be sent in the near future. Until then, this letter authorizes application of the UL Mark for 90 days from the date indicated above. Additional requirements related to your responsibilities as the Applicant can be found in the document "Applicant responsibilities related to Early Authorizations' that can be found at the following web -site' http:llwww. ul. comlEAResponsi biriti es Any information and documentation provided to you involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. We are excited you are now able to apply the UL Mark to your products and appreciate your business_ Feel free to contact me or any of our Customer Service representatives if you have any questions_ Very truly yours. Reviewed by: Jon Adonay 408-754-6630 Engineering Associate Lead Jon.Adonay@ul.com NBKD9C5-90BA67 William R. Carney 847/664-1088 Chief Engineer Director I William.R.Carney@ul.com This rs an electronically generated letter Signatures are not required for this document to be valid. Page 1 of 1