Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
FNCUW2022-0002 - SilverRockPermit Details
City of La Quinta
Description: PENDRY - CONDOMINIUMS - PRIVATE FIRE MAIN
Type: FIRE NEW COMMERCIAL Subtype:
UNDERGROUND WATER (WEB)
Status: REVISIONS REQUESTED
Applied: 8/2/2022 ECON
Approved: 9/14/2022 KHET
Issued:
Finaled:
Expired:
Parcel No: 777490046 Site Address: TBD,
Subdivision: Block:
Lot Sq Ft: 0 Building Sq Ft: 0
Valuation: $220,000.00 Occupancy Type:
No. Buildings: 0 No. Stories: 0
Lot:
Zoning:
Construction Type:
No. Unites: 0
Details: REVISED THE SURFACE FEATURES AND STORM DRAIN
Applied to Approved
ADDITIONAL
SITES _
CHRONOLOGY
CONDITIONS
CONTACTS
NAME TYPE
NAME
ADDRESS1
CITY
STATE
ZIP
PHONE
FAX
EMAIL
APPLICANT
Kevin Heinichen
3551 Fortuna Ranch
Road
Encinitas
CA
92024
(760)634-6543
kevin@therobertgreen
company.com
BILL TO
The Robert Green Company
3551 Fortuna Ranch
Road
Encinitas
CA
92024
(760)634-6543
kevin@thegreencompn
ay.com
OWNER
THE ROBERT GREEN COMPANY
3551 FORTUNA ROAD
ENCINITAS
CA
92024
(760)634-6543
FINANCIAL INFORMATION
Printed: Friday, March 03, 2023 3:51:58 PM
1 of 3
CRWSYSTEMS
Permit Details PERMIT NUMBER
City of La Quinta FNCUW2022-0002
Aa
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
RECEIPT #
CHECK #
METHOD
PAID
CLTD
BY
FIRE NEW
COMMERCIAL
UNDERGROUND
WATER
101-0000-42421
0
$500.00
$0.00
FIRE NEW
COMMERCIAL
UNDERGROUND
WATER PC
101-0000-42420
0
$417.00
$0.00
Total Paid for FIRE FEES: $917.00 $0.00
RECORDS
MANAGEMENT FEE
101-0000-42416
0
$11.00
$0.00
Total Paid for RECORDS MANAGEMENT FEE: $11.00 $0.00
ENHANCEMENT FEE TECHNOLOGY
502 0000 43611
0
I $5.00
$0.00
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $0.00
TOTALS:
$933.00
$0.00
INSPECTIONS
REVIEWS
REVIEW TYPE
REVIEWER
SENT DATE
DUE DATE
RETURNED
DATE
STATUS
REMARKS
NOTES
1ST PERMIT TECH (1
DAY)
AARON
HICKSON
8/2/2022
8/3/2022
8/3/2022
COMPLETE
ADDED PARCEL RECORD PER FIRE
1ST FIRE (2 WK)
KOHL
HETRICK
8/2/2022
8/16/2022
9/14/2022
REVISIONS REQUIRED
SEE ATTACHMENTS
BOND INFORMATION
Printed: Friday, March 03, 2023 3:51:58 PM
2 of 3
CRWSYSTEMS
Permit Details
City of La Quinta
PERMIT NUMBER
FNCUW2022-0002
ATTACHMENTS
Attachment Type
CREATED
OWNER
DESCRIPTION
PATHNAME
SUBDIR
ETRAKIT ENABLED
DOC
8/2/2022
Etrakit Contractor
1ST SUBMITTAL PLANS
2502 Private Fire SET
2022 08 02.pdf
1
DOC
8/2/2022
Etrakit Contractor
1ST SUBMITTAL
APPLICATION
2502 LQRC REVISED PVT
FIRE APPLICATION 2022-
07-28.pdf
1
DOC
9/14/2022
KOHL HETRICK
FNCUW2022-0012 - 1ST
REVIEW - FIRE PLAN
COMMENTS.pdf
FNCUW2022-0012 - 1ST
REVIEW - FIRE PLAN
COMMENTS.pdf
1
Printed: Friday, March 03, 2023 3:51:58 PM 3 of 3
CRWSYSTEMS
Oa -
AVENUE e
SITE
—
VICINITY MAP
ABBREVIATIONS
LUTH
WEST
LEGEND
--
0
ER EIS' 22TE.Em.
TV CABLE TELEVISION
EDGE OF PAVEMENT
INVERT
LINE
CONSTRUCTION NOTES
0 ay.'natorn ALEss M ON PI°A° r' PIPE 157
0
Oro 2 1 /T DI BENDw/THR LNoLH
1 EA
C) RNISH AND INSTALL X 451 DI BEND w/«ORJoRDLOHE3-1N I/ENT TR KRESTRAIwa EETAON SHEET s
C) FURNISH E VI/TRUST
BLOCK OR RESTRAINED ,DINTS PER DETAIL OR SHEET 3
C) FINNISH AND INSTALL e. DI CROSS VURRUST B.. OR RESTRNED JOINTS PER DUAL ON SHEET 3
SD CO IT LA
12LA
ZZ17; 7. �AELL"Ej°Lavx °;21 AA°�R°fcC'NWTLR°VEACToxi oAI °. B oI A ° 5 EA
E RO NOTE TO CONTRACTORS QUANTITY ESTIMATE
0
PROP. STORM D.IN
PRO, PRIVATE SEWER MAN
PROP, PRIVATE WATER MAIN
PRO, PRIVATE FIRE LINE
PROP. PRIVATE FIRE SERVICE LINE
PROP. FIRE HYD.NT ASSEMBLY
PRO, GATE VALVE OR BUTTERFLY VRVE
EC WATER WON
EC SEWER MAIN
EX. UTILITIES, GAS. TELEPHONE. TV. ETC.
PROP. WAT. SERVICE
PRO, SEVIER LATERAL
AIR/VACUUM RELIEF 0200E
PROP. DETECTOR CHECK
PROP. CL.N OUT
PROP. MANHOLE
PROP. WATER SERVICE W. EUCKfLOW DEVICE
PRO, REDUCER VALVE AND BLOW -OFF ASSEMBLY
PROP. REDUCER
PROP. STORM DRAIN MANHOLE
BOUNDARY
CENTERLINE
NE
BWACY/COUNTY BOUNDARY MMus
OLE
FTC POINT ON CURVE
PRC
raF081614F6REVERSE CURVE
"`" mOHT DF 4AY EMENT
TOP OEFEMEANHOLE
VITRIFAC CLAY PIPE
EVEETBARREL
QUANTITY UESTIIMATEOR
(FOR PEIT
IT 5.LL BE THE CONTRACTOR'S RESPONSIBILITY TO PREPARE HIS OWN OUANTITY EST1AATE FOR CON.RUOTION OR COST
A E THE THE OF CONSRUnIOu.
UTILITIES
IRRI.TION COACHELLA V.L. WATER DISTRICT (760) 3ee-2651
WATER COACHELLA VALLEY WA.R DISTRICT 760) 3B
DISTRICTSEWER CO.HELLA VALLEY WATER (760) See 2651
ELECTRIC EDSON (780) 2024291
CAS THE .S COMPANY 760) 323-1651
TELEPHONE TROTTER COMMUNICATIONS (BOO) 921-6104
CABLE .v. TIME WARNER CABLE - SPECTRUM (800) 892-4.357
USA UNTEROROUND SERVICE ALERT
NOTE TO CONTRACTOR. EXISTING UTILITIES
RPEDITIOUS MANNER. THE CONTRACTOR FURTHER AGREES TO PURSUE DILIGENTLY THE COMPLETION OF
ANY DISCREPANCY BETWEEN THE PLANS AND FIELD SHALL BE BROUGHT TO THE ...ON OF ANA CONSULTING. INC. THE
NOTE SR RrnslOxs ARE evvRovED.TO CONTRACTOR. SITE CONDITIONS
CONSULTING. Inc.
NOTE TO CONTRACTOR. CONSTRUCTION OBSERVATION
ixm[ ouwxs wmE PREPARED BY 11.
mE wmw.crms mwisM) 'I nox IS cpwLOm Ix ACCORwxcE
IN THE CITY OF LA QUINTA, COUNTY OF RIVERSIDE, STATE OF CALIFORNIA
SILVEROCK RESORT
LO RESORT CONDOMINIUMS
TRACT MAP NO. 37930
PRIVATE FIRE SERVICE PLAN
LOCATED IN THE SOUTHWEST 1/4 OF THE NORTHEAST 1/4 OF SECTION 6, TOWNSHIP 6 SOUTH,
RANGE 7 EAST, SAN BERNARDINO BASE AND MERIDIAN
PREPARED FOR.
SILVEROCK DEVELOPMENT COMPANY
79-179 AHMANSON LANE
LA QUINTA, CA 92253
(780) 634-6643
kiln e111101111 �p qV �
-1mIhi ie
+ll!lfn IBba; i:, iH
- ♦
ilw
Ire
INDEX MAP
SCALE I-=I00'
SHEET INDEX
SHEET
DESCRIPTION
2-5
6-7
COVER SHEET
PLAN VIEW
SIGNAGE AND STRIPING
UNDERGROUND REQUIREMENTS
DIG ALERT
Dig ISefely
DIAL TOLL FREE
1-8
-2600
"TuDEBGM°-227AM
BENCHMARK M #430
ELEVATION .467' (NAVOSS)
PROJECT ELEVATION
AT BM 430
TION
OOf LA °UINTA NM OM
PRIT 1-1/E a"WD D
STANPEO F AVENUE 54 MID ej)METuPEMONUMENT.
ORATION (RAYONS) AT EN f4.30 = REV. 3.003'
10 OMR PROJECT ELEVATIONS IN WOMB DA
98
PENSIONS
A REVISED SURFACE FEATURES
DRAWN BY
CD
ORECKRO BY
MTC
It is necessary for the system designerto provde
the Hydraulic modeling for required flows b.ed
on perceived demands of the Fire Sprinkler
systems.
7.somced installing contractor would late
only need to resubmit the to -be approved plans
with their int'om,ation added to me provided box
(all sheets) and the manuf .. spec sheets for
all materials to be used, This will bereviewed
40IY for final wmplianw, n end, card issuance.
a*LQ 0FM has not received the CV WD
off-site/on-she public water main and Pre
hydrant flow modeling yet, as is required. This
modeling shallilutify that the meet
hydraulically remotedemanding fine hydrant is
able to provide a fire flow of 1,625 gem at 20
psi residual curve pressure.
a. Kohl Hetrick
FNCUW2022-0012
SHEETTHIS SHEET SUPERSEDES THE
PREVIOUSLY APPROVED REVISIONS ',CLOUDED. AND APPROVED 10/55/2020 AND IS
IDENNCAL EiCEPT FOR THOSE
REASIOX t£s ^ O D
NBA CConau�TRlnq'0 na.
® MSA CONSULTING, NC.
11oiEngineetinog - Lartl Surveyirg . Larasrpe Arctllcenum
a� I p xVII nmaxca sawna, . Dly unldycwlm x.cls
REPARED UNDER THE
Ll���r-mod
DIRECT SUPERNSION OR
06/01/202.2
RIVERSIDE tOUNTY FIRE DEPARTMENT PRIVATE FIRE MAIN NOTES1. THE Of THE ON -SITE WATER SYSTEM S.LL COMPLY W. AR REQUIREMENTS Of THE CURRENT EornoN OF NEPA zc
EN z2wNIHzt (csL x-r + NOE EIR
2 ALL BRE FLOW REOUIREMENTS. HATNANT TYPE. NUMBER OF HYDRANTS. AND SPACING OF HYDRANTS SHALL BE PROVIDED AS PER THE
3. 80".EUME.ES°VACT2NE8UPPLY FOR FIRE PROTECTION. EITHER TEMPO.. OR PERMANENT. SW. BE MADE AVALABLE A
TABLE D STANCE AS SOON AS COMBUSTBLE MATERIAL ARRIVES ON THE JOE SITE. THIS WATER SUPPLY SHALL BE APPROVED BY
ENE RIVERSIDE' COUNT( FIRE DEPARLATENT - OFFICE OF THE FIRE MARSHAL.
54. WET -SIGNED STAMP SEAL 5.LL BE PLACED ON THE PLANS.
5. THE FIRE FLOW CALCULATIONS SHALL BE BASED ON WATER ROW TEST INFORM.. CONDUCTED WITHIN ONE YEAR OF THE PRIVATE
FIRE MAN P. SUBMITTAL APPLICATION DATE.
6. ANY PIPING NOT SHOWN ON MIS APPROVED P. IS NOT0,46PART Of THIS APT.. B TtNM TnE OTFmS • "014E1174 rot; sERgsN sw M ass A uxcxe'soF
g. Ta. [BNDTe
10. ;.3°TiA°01EEEpIL4E.NE3r6SE:E°6/11°D°NG UNTEREERE= S'EAUNMSS SHRL HAVE A MINIMUM COVER OF 35-INCHES M.SURED FROM THE TOP OF
12. FIRE HYDRANTS' THE MINIMUM SIZE fIRE HYDRANTS 024482E X).DEPENDING
PaarA0 SHALL
4L2 4•SUPER
x z A) un. eL 800E irzm. 20 vx a r,re voxu2rs swu ee
• gicK iow svarµvFpxno°wa°lig° vRl niiwrlAi Mattis s�us elisvrzavlolio =r-Ilsio rzw,w vxe
C THE
PART OF ABOVE- ROASSEMBLIES.
LL OF SHE . ERC AOSDa0DE0 SHALL NOT EE LOWED wNHIN .8070E. OR THEMORE APPURTENANCES. SECTIO.L CONTROL VALVES SHALL BE
L.AAT D vesT `35.7 a VALVES AND FIRE DEPARTMENT CONNECTORS
ALL GUARD POSTS SHRL BE PANTED SAFETY YELLOW.
IGH
17. AUTOMATIC FIRE SPRINKLER SYSTEM RISERS SHE. NOT BE OBSTRUCTED IN ANY If A SYSTEM RISER IS TO BE
I�s� F��E;°� TMEE �:E=Ix��B,°�B�p�HrMe�Tl��IloEE��°M�Ns DF A DODB
rIR: �I:P Mr°�='° �ATTNToH EPARTE RRE BPRIN0DER B0RM RIBER (NOT DN MANIFDIO) RHAEE FF PROVIDED WITH A FIRE
DN TO%,7 ZU BB rocq,FD ,;,IN ,D _
SYST.S SERVING 50 GALLONS PERS SHALL BE MINUTE REQUIRED.ZED TD SUPPLY AT A MINIMUM,TEM A 2 X , u. XREQUIREMENTS4DA EN Co NECTOR
FACIUTY TESTING.
r'ETENUSEIELJECIE PePEON. EVECTTIMEGEVAVEEL.635ACH. AND MCNEILL INSPECTION REQUIRED PRIOR TO BACKFIRING.
: ,u1,442EZ2Mng fLITSTrEEEIL AfFSEGETEEDETANEGE IETETIL CLEAR. REQUIRED PRIOR TO CONNECTION OF ANY OVERHEAD PIPING
• UNDERGROUND FINAL - A CORY OF THE 'CONTRACTORS ARTERIAL AND TEST CEROFICATE FOR 31.11.ERGROUND PIPING 6.R.31+066E63
- CONTACT PRIVATE TMREOFFICE OFETHE FIRE MARSHAL A MINIMUM Of 48
WATER RIMPROVEMENT DPLANSHOURS IN ADVANCE TO SCHEDULE INSPECTORS.
ALL WORKS SHRL CONFORM WITH THE STANDARD SPECIFICATIONS FOR PUBLIC WORKS CONSTRUCTION (GREEN BOON) LATEST EDITION.
AW.W.A. STANDARDS. UNIFORM PLUMBING CODE .7E5T EDITION AND THESE PLANS.
2. ALL WATER MAINS , THRU 12. SHALL BE C-900 CLASS 200. 1, AND .GER SHALL BE C-905 C.S 150. WATER PIPE RODER
y-,pro 07,80 STANow6. FIRE
MANUFACTURED EY SPEAR
; MINIMUM covle Jog,srwasen 11,11063A311,61467,16781/6C6E93 S6,143.1.166_880.35. INCHES STREET SHALL BE BROUGHT TO SUBGRADE AND
T. THE MIN IN OVER FOR WATER MANS AND WATER SERVICES S.LL BE 35 INCHES. STREET SHALL BE BROUGHT TO SUBGRADE AND
a EXTEMINEEIOPTCENVESS,E,16,1104 EATTETNEIETEEE :ATP IgistrilEYTEI MAINS SHALL BE BY ONE 1-FOOT FROM OUTSIDE WRI TO
OUTSIDE WALL. MINOAN VER., S16.1,4,4r006N 3786.WAT. AND SEWER .NS AT PERPENDICU. CROSSING SHRL BE l'-FOOT FROM
10. IZEH"EEEELARVEAVREE°11E4PBEETiolViCEE:61`171ACKTILL SHALL BE CERTIFIED BY A REGISTERED SOILS ENGINEER PRIOR TO PLACEMENT OF
A.C. OR CONCRETE.
II. IT SHALL BE THE WATER CONTRACTOR'S RESPONSIBILITY TO SET WATER VALVE RISER. FRAME AND COVER T066FINISIL 006RAQA66.7.6.Z
P6/6C6114,C664133r.CORDANCE WITH CURD STAN.RD DRAWING NO. W-17A MODIFY VALVE COVER TO ONLY READ ATER
E,E4LE `COETETEZE01° ITLEL EIT°467°AEL ZalguTTE EtAFELIZsE°E1OREREEEI TEJEEEMS a DETAIL 1.11 THE ENGINEER PRIOR TO START
• OTTERMSE NOTED ON PLANS. JOINT RESTRANT SHALL BE 'MEGA LUG. BY EB. IRON WORKS. SERIES 1500 BELL RESOVAINT .RNESS.
OR ENGINEER APPROVED EQUR
17. LENGTH Of RESTRAINED PIPE SHALL BE MINIM. Of 54-LINEAL FEET IN .CH DIRECTION Of RTTING B.NCH Of TEE OR AS
INDICATED ON PLAY
0111ENOTES =AEI SEPTILEBTPLEAcli LACEEVEIECETENIEEPYDRANTS LOCATED ON THE CENTERLINE Of THE STREET OR DRIVEWAY
20. TIE CONTRACTOR AGREES T.7 HE SH._ ASSUME SOLE AND COMPLETE RESPONSIBILITY6 FOR TOB3SITE 3CONDITIONS DURING ME
INSTALLING CONTRACTOR ACCEPTANCE
........................
NOTE.
THIS PLAN IS FOR PLANMWS/BLLUNG wwssa
PERMIT ONLY. THE INSTALLING
CONTRACTOR MUST HOLD A VALID'N°ammr
CM LICENSE. THEN
SYSTEM CONSTRUCTION PERMIT.
LASOUNTA OFFICE OF THE FIRE MARSHAL
RIVERSIDE COUNTY FIRE DEPARTMENT
DATE
IN THE CITY OF LA QUINTA, CALIFORNIA
SILVERROCK RESORT - LQ RESORT CONDOMINIUMS
TRACT MAP NO. 37930
PRIVATE FIRE SERVICE PLAN
COVER SHEET
PORTIONS CFI,T4EOFWS I/4O .0 RYE S.B.M. ' AND SE
SHEET
1
OF
SHEETS
1
Lu
1-
AVENUE 52
VICINITY MAP
NTS Oz.
OW
ABBREVIATIONS
E
N
S
W
NE
NW
SE
SW
A/V
ASSY.
BC
BCR
BO
BV
C#
C/L
C&G
C.B.
ELEC
CO
EAST
NORTH
SOUTH
WEST
NORTHEAST
NORTHWEST
SOUTHEAST
SOUTHWEST
AIR VACUUM
ASSEMBLY
BEGINNING OF CURVE
BEGIN CURB RETURN
BLOW -OFF
BUTTERFLY VALVE
CURVE
CENTERLINE
CURB AND GUTTER
CATCH BASIN
ELECTRIC
CLEAN OUT
D
DEFL.
DI
DWG.
DWY
EA.
EC
ECR
CAN
EP
ESMT.
EX
FH
GB
GV
HZ
INV
L#
LAT.
L.F.
CONSTRUCTION NOTES
LEGEND
s
w
-FS-
0
- W
- S
- U -
I`
ICI
DEPTH
DEFLECTION
DUCTILE IRON
DRAWING
DRIVEWAY
EACH
END OF CURVE
END CURB RETURN
CABLE TELEVISION
EDGE OF PAVEMENT
EASEMENT
EXISTING
FIRE HYDRANT
GRADE BREAK
GATE VALVE
HORIZONTAL
INVERT
LINE
LATERAL
LINEAL FEET
FURNISH AND INSTALL 8" C-900, CLASS 200 PVC PIPE
(42" TYPICAL COVER UNLESS NOTED ON PLAN)
DELETED
DELETED
/vI
O
0
MH
N.T.S.
P/L
PCC
POC
PRC
PROP.
PUE
R/W
S/W
SER.
SWR.
TCO
TELE
TMH
TYP.
VCP
VERT
WB
WTR.
PROP. STORM DRAIN
PROP. PRIVATE SEWER MAIN
PROP. PRIVATE WATER MAIN
PROP. PRIVATE FIRE LINE
PROP. PRIVATE FIRE SERVICE LINE
PROP. FIRE HYDRANT ASSEMBLY
PROP. GATE VALVE OR BUTTERFLY VALVE
EX. WATER MAIN
EX. SEWER MAIN
EX. UTILITIES: GAS, TELEPHONE, TV, ETC.
PROP. WATER SERVICE
PROP. SEWER LATERAL
PROP. AIR/VACUUM RELIEF VALVE
PROP. DETECTOR CHECK
PROP. CLEAN OUT
PROP. MANHOLE
PROP. WATER SERVICE WITH BACKFLOW DEVICE
PROP. REDUCER VALVE AND BLOW -OFF ASSEMBLY
PROP. REDUCER
PROP. STORM DRAIN MANHOLE
BOUNDARY
CENTERLINE
PHASE LINE
CITY/COUNTY BOUNDARY LIMITS
MANHOLE
NOT TO SCALE
PROPERTY LINE
POINT OF COMPOUND CURVE
POINT ON CURVE
POINT OF REVERSE CURVE
PROPOSED
PUBLIC UTILITY EASEMENT
RIGHT OF WAY
SIDEWALK
SERVICE
SEWER
TOP OF CLEAN OUT
TELEPHONE
TOP OF MANHOLE
TYPICAL
VITRIFIED CLAY PIPE
VERTICAL
WET BARREL
WATER
QUANTITY ESTIMATE
(FOR PERMIT PURPOSES ONLY)
1573 L.F.
FURNISH AND INSTALL 8" X 22 1/2' DI BEND W/ THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3 6 EA.
FURNISH AND INSTALL 8" X 45' DI BEND W/ THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3 31 EA.
FURNISH AND INSTALL 8" X 90' DI BEND W/ THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3 15 EA.
FURNISH AND INSTALL 8" DI TEE W/THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3 5 EA.
FURNISH AND INSTALL 8" DI CROSS W/THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3 1 EA.
CONSTRUCT POST INDICATOR VALVE AND FIRE DEPARTMENT CONNECTION PER DETAIL ON SHEET 2 12 EA.
CONTRACTOR TO CONNECT 8" PVC C-900 PIPE TO BUILDING SPRINKLER SYSTEM, IF BUILDING
SPRINKLER SYSTEM IS UNAVAILABLE INSTALL 8" DI BLIND FLANGE AND MARKER POST MARKED "F" 12 EA.
CONTRACTOR TO CONNECT TO BOTTOM ELBOW OF ABOVE GROUND DOUBLE CHECK DETECTOR
ASSEMBLY (DCDA INSTALLED BY PUBLIC WATER CONTRACTOR) AND INSTALL 8" DI REDUCER 5 EA.
FURNISH AND INSTALL RAISED BLUE REFLECTIVE PAVEMENT MARKERS
PER RIVERSIDE COUNTY FIRE DEPARTMENT STANDARD NO. 06-11 6 EA.
NOTE TO CONTRACTOR. QUANTITY ESTIMATE
MSA CONSULTING, INC. MAKES NO REPRESENTATION CONCERNING THE ESTIMATED QUANTITIES ON THESE PLANS, EXCEPT THAT
ALL SUCH FIGURES, INCLUDING ALL EARTHWORK QUANTITIES, ARE PRELIMINARY ESTIMATES AND FOR PERMIT PURPOSES ONLY.
IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PREPARE HIS OWN QUANTITY ESTIMATE FOR CONSTRUCTION OR COST
PURPOSES. MSA CONSULTING, INC. SHALL NOT BE RESPONSIBLE FOR ANY DEVIATIONS BETWEEN ESTIMATED QUANTITIES AND
ACTUAL QUANTITIES AT THE TIME OF CONSTRUCTION.
UTILITIES
IRRIGATION
WATER
SEWER
ELECTRIC
GAS
TELEPHONE
CABLE T.V.
USA
COACHELLA VALLEY WATER DISTRICT
COACHELLA VALLEY WATER DISTRICT
COACHELLA VALLEY WATER DISTRICT
SOUTHERN CALIFORNIA EDISON
THE GAS COMPANY
FRONTIER COMMUNICATIONS
TIME WARNER CABLE - SPECTRUM
UNDERGROUND SERVICE ALERT
(760) 398-2651
(760) 398-2651
(760) 398-2651
(760) 202-4291
(760) 323-1851
(800) 921-8104
(800) 892-4357
811
NOTE TO CONTRACTOR. EXISTING UTILITIES
THE LOCATIONS OF UNDERGROUND UTILITIES SHOWN ON THE PLANS WERE OBTAINED FROM A REVIEW OF AVAILABLE RECORD
DATA. WHILE DUE CARE WAS TAKEN IN PREPARATION OF THIS INFORMATION, MSA CONSULTING, INC. CANNOT AND DOES NOT
GUARANTEE THE ACCURACY NOR THE COMPLETENESS OF THE INFORMATION. THE LOCATIONS OF EXISTING UNDERGROUND
UTILITIES ARE SHOWN IN AN APPROXIMATE WAY ONLY. THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATIONS OF ALL
EXISTING UTILITIES BEFORE COMMENCING WORK.
THE CONTRACTOR AGREES TO BE FULLY RESPONSIBLE FOR ANY AND ALL DAMAGES, WHICH RESULT FROM HIS FAILURE TO
LOCATE EXACTLY AND PRESERVE ANY AND ALL UNDERGROUND UTILITIES. THE CONTRACTOR SHALL POTHOLE PROPOSED
CROSSINGS OF EXISTING UTILITIES PRIOR TO CONSTRUCTION AND SHALL VERIFY THEIR HORIZONTAL AND VERTICAL LOCATIONS.
IN THE EVENT, DURING CONSTRUCTION, THAT UNKNOWN UTILITIES OR UNKNOWN STRUCTURES ARE FOUND AT UNEXPECTED
ELEVATIONS OR LOCATIONS, MSA CONSULTING, INC. IS TO BE NOTIFIED OF SUCH CONDITION AT ONCE. MSA CONSULTING, INC.
WILL MAKE REQUIRED DESIGN CHANGES AND THE CONTRACTOR AGREES TO COMPLETE ALL WORK, INCLUDING REPAIRS
REQUIRED, IN AN EXPEDITIOUS MANNER. THE CONTRACTOR FURTHER AGREES TO PURSUE DILIGENTLY THE COMPLETION OF
SAID WORK.
ANY DISCREPANCY BETWEEN THE PLANS AND FIELD SHALL BE BROUGHT TO THE ATTENTION OF MSA CONSULTING, INC. THE
CONTRACTOR SHALL NOTIFY MSA CONSULTING, INC. PRIOR TO POTHOLING. IF NECESSARY, MSA CONSULTING, INC. SHALL
REVISE THE PLANS. THE CONTRACTOR SHALL BEGIN CONSTRUCTION AFTER REVISIONS ARE APPROVED.
NOTE TO CONTRACTOR. SITE CONDITIONS
CONTRACTOR AGREES TO ASSUME SOLE AND COMPLETE RESPONSIBILITY FOR THE JOB SITE CONDITION DURING THE COURSE
OF CONSTRUCTION OF THIS PROJECT, INCLUDING THE SAFETY OF ALL PERSONS AND PROPERTY. THIS REQUIREMENT APPLIES
CONTINUOUSLY AND IS NOT LIMITED TO NORMAL WORKING HOURS.
THE CONTRACTOR ALSO AGREES TO DEFEND, INDEMNIFY, AND HOLD THE OWNER AND THE MSA CONSULTING, INC., HARMLESS
FROM ANY AND ALL LIABILITY, REAL OR ALLEGED, IN CONNECTION WITH THE PERFORMANCE OF WORK ON THIS PROJECT,
EXCEPTING FOR LIABILITY ARISING FROM THE SOLE NEGLIGENCE OF THE OWNER OR MSA CONSULTING, INC.
NOTE TO CONTRACTOR. CONSTRUCTION OBSERVATION
THESE DRAWINGS WERE PREPARED BY MSA CONSULTING, INC. (MSA) USING CURRENTLY ACCEPTED INDUSTRY AND AGENCY
STANDARDS. MSA HAS NO CONTROL OVER THE CONTRACTOR'S MEANS OR METHODS; AND UNLESS MSA IS ENGAGED TO PERFORM
FULL-TIME, ON -SITE OBSERVATION, MSA CANNOT REPRESENT THAT THE CONSTRUCTION IS COMPLETED IN ACCORDANCE WITH THE
APPROVED DRAWINGS OR APPROPRIATE SPECIFICATIONS.
UNLESS MSA IS PERFORMING FULL-TIME, ON -SITE OBSERVATION, MSA'S RESPONSIBILITY AS THE CIVIL ENGINEER OF RECORD IS LIMITED
TO THE DESIGN AT THE ONSET OF CONSTRUCTION. IN ACCORDANCE WITH GENERALLY ACCEPTED CONSTRUCTION PRACTICES, THE
CONSTRUCTION CONTRACTOR WILL BE REQUIRED TO ASSUME SOLE AND COMPLETE RESPONSIBILITY FOR JOB SITE CONDITIONS DURING
THE COURSE OF CONSTRUCTION OF THE PROJECT, INCLUDING SAFETY, AND AGREES TO DEFEND, INDEMNIFY AND HOLD MSA HARMLESS
FROM ANY AND ALL LIABILITY, REAL OR ALLEGED, IN CONNECTION WITH THE PERFORMANCE OF WORK ON THIS PROJECT, EXCEPTING
LIABILITY ARISING FROM THE SOLE NEGLIGENCE OF MSA EMPLOYEES. MSA DOES NOT GUARANTEE THE COMPLETION OR QUALITY OF
PERFORMANCE OF CONTRACTS BY THE CONSTRUCTION CONTRACTOR, OR OTHER THIRD PARTIES, NOR IS MSA RESPONSIBLE FOR THEIR
ACTS OR OMISSIONS.
DIG ALERT
DigSafely
DIAL TOLL FREE
1-800-227-2600
AT LEAST TWO DAYS BEFORE YOU DIG
UNDERGROUND SERVICE ALERT
OF SOUTHERN CALIFORNIA
BENCHMARK BM #430
PROJECT ELEVATION
ELEVATION 5.467' (NAVD88) AT BM *430 3.903'
LOCATION
CITY OF LA QUINTA BM #430: 1-1/2" COPPERWELD MONUMENT,
STAMPED "LS-98", FLUSH AT THE CENTERLINE INTERSECTION OF
AVENUE 54 AND JEFFERSON STREET.
ELEVATION = 5.467' (NAVD88)
PROJECT ELEVATION AT BM #430 = ELEV. 3.903'
TO OBTAIN PROJECT ELEVATIONS IN NAVD88 DATUM,
ADD 1.564' TO ELEVATIONS SHOWN.
BASIS OF BEARINGS
EASTERLY LINE OF SECTION 8, TOWNSHIP 6 SOUTH, RANGE 7
EAST, S.B.M., AS SHOWN ON PARCEL MAP 37207, ON FILE IN
BOOK 242, AT PAGES 72-87, OF PARCEL MAPS, O.R. TAKEN
AS: N 0212'49" W
IN THE CITY OF LA QUINTA, COUNTY OF RIVERSIDE, STATE OF CALIFORNIA
SIL I/EROCK RESORT
LQ RESORT CONDOMIMUMS
TRACT MAP NO. 37930
PRIVATE RRE SERVICE PLAN
LOCATED IN THE SOUTHWEST 1/4 OF THE NORTHEAST 1/4 OF SECTION 8, TOWNSHIP 6 SOUTH,
RANGE 7 EAST, SAN BERNARDINO BASE AND MERIDIAN
REVISIONS
/ \ REVISED SURFACE FEATURES
PREPARED FOR.
SILVEROCK DEVELOPMENT COMPANY
79-179 AHMANSON LANE
LA QUINTA, CA 92253
(760) 634-6543
0'
dO R� '
INDEX MAP
100'
200'
300'
400'
SCALE 1"=100'
SHEET INDEX
SHEET
DESCRIPTION
1
2-5
6-7
8
COVER SHEET
PLAN VIEW
SIGNAGE AND STRIPING
UNDERGROUND REQUIREMENTS
APPR. DATE
DESIGNED BY
MP
DRAWN BY
CC
CHECKED BY
MTC
© Copyright 2022
MSA Consulting, Inc.
All Ri • hts Reserved
THIS SHEET SUPERSEDES THE
PREVIOUSLY APPROVED SHEET 1
APPROVED 10/26/2020 AND IS
IDENTICAL EXCEPT FOR THOSE
REVISIONS "CLOUDED" AND LABELED
WITH REVISION TRIANGLES. / \
CO T. CELEDIN
R.C.E. C75478 EXP 6-30-24
Civil Engineering • Land Surveying • Landscape Architecture
Planning • Environmental Services • Dry Utility Coordination • GIS
34200 Bob Hope Drive Rancho Mirage, CA 92270 1760.320.9811MSAConsultinginc.com
PREPARED UNDER THE DIRECT SUPERVISION OF:
08/02/2022
DON, R.C. . NO. 75478 DATE
RIVERSIDE COUNTY FIRE DEPARTMENT PRIVATE FIRE MAIN NOTES
1. THE INSTALLATION OF THE ON -SITE WATER SYSTEM SHALL COMPLY WITH ALL REQUIREMENTS OF THE CURRENT EDITION OF NFPA 24
AND CALIFORNIA FIRE CODE. INSTALLATION WORK SHALL BE DONE BY FULLY EXPERIENCED AND RESPONSIBLE CONTRACTORS.
CONTRACTORS SHALL BE APPROPRIATELY LICENSED IN THE STATE OF CALIFORNIA TO INSTALL PRIVATE FIRE SERVICE MAINS AND THEIR
APPURTENANCES (CSLB: C-16, C-34, C-36, CLASS A). JOB CARDS WILL BE ISSUED TO THESE LICENSED CONTRACTORS ONCE
ADEQUATE DOCUMENTATION AND APPROVAL FOR THE WORK HAS BEEN OBTAINED BY THE OFFICE OF THE FIRE MARSHAL.
2. ALL FIRE FLOW REQUIREMENTS, HYDRANT TYPE, NUMBER OF HYDRANTS, AND SPACING OF HYDRANTS SHALL BE PROVIDED AS PER THE
CALIFORNIA FIRE CODE.
3. AN APPROVED WATER SUPPLY FOR FIRE PROTECTION, EITHER TEMPORARY OR PERMANENT, SHALL BE MADE AVAILABLE WITHIN A
REASONABLE DISTANCE AS SOON AS COMBUSTIBLE MATERIAL ARRIVES ON THE JOB SITE. THIS WATER SUPPLY SHALL BE APPROVED BY
THE RIVERSIDE COUNTY FIRE DEPARTMENT - OFFICE OF THE FIRE MARSHAL.
4. THE CIVIL ENGINEER OR LICENSED CONTRACTOR WHO DESIGNED THE WATER SYSTEM HEREBY CERTIFIES THAT THIS WATER SYSTEM IS IN
ACCORDANCE WITH THE REQUIREMENTS AS PRESCRIBED BY THE OFFICE OF THE FIRE MARSHAL, THE CALIFORNIA FIRE CODE AND NFPA
24. WET -SIGNED STAMP SEAL SHALL BE PLACED ON THE PLANS.
5. THE FIRE FLOW CALCULATIONS SHALL BE BASED ON WATER FLOW TEST INFORMATION CONDUCTED WITHIN ONE YEAR OF THE PRIVATE
FIRE MAIN PLAN SUBMITTAL APPLICATION DATE.
6. ANY PIPING NOT SHOWN ON THIS APPROVED PLAN IS NOT A PART OF THIS APPROVAL. ANY ADDITIONAL PIPING THAT IS TO BE
INSTALLED WILL REQUIRE A SEPARATE PLAN SUBMITTAL REQUIRING THE APPROVAL FROM THE OFFICE OF THE FIRE MARSHAL.
7. DUCTILE IRON PIPE SHALL BE INSTALLED WITHIN FIVE FEET OF THE BUILDING.
8. NO JOINTS SHALL BE INSTALLED UNDER THE BUILDING. THE SUPPLY LINE TO THE FIRE SPRINKLER RISER(S) SHALL BE A UL LISTED
ONE PIECE SOLID SWEEP. FIRE SPRINKLER RISERS THROUGH FLOOR SLABS SHALL HAVE A SLEEVE WITH A MINIMUM OF 2-INCHES OF
CLEARANCES FOR PIPES UP TO 3 36" IN SIZE AND 4 INCHES OF CLEARANCE FOR PIPE SIZES 4 INCHES AND GREATER.
9. ALL METAL MECHANICAL RESTRAINTS, UNDERGROUND BOLTS AND STAINLESS STEEL SWEEPS SHALL BE WRAPPED IN PROTECTIVE PLASTIC
OR OTHER APPROVED CORROSION RETARDING MATERIAL.
10. ALL WATERLINES EXTENDING UNDER ROADWAY SURFACES SHALL HAVE A MINIMUM COVER OF 36-INCHES MEASURED FROM THE TOP OF
PIPE TO FINISH GRADE.
11. THERE SHALL BE A MINIMUM VERTICAL CLEARANCE OF 12-INCHES BETWEEN FIRE LINES AND ALL OTHER UNDERGROUND UTILITIES. THE
12-INCHES OF CLEARANCE IS MEASURED FROM OUTSIDE OF PIPE TO OUTSIDE OF OTHER UTILITY.
12. FIRE HYDRANTS: THE MINIMUM SIZE FIRE HYDRANT SHALL BE SUPER FIRE HYDRANTS (6" X 4" X 2 1,6" X 2 1/6"). DEPENDING ON FLOW
REQUIREMENTS AN ENHANCED SUPER HYDRANT (6" X 4" X 4" X 2 ,A") MAY BE REQUIRED. ALL PRIVATE FIRE HYDRANTS SHALL BE
PAINTED RED AND PROVIDED WITH OSFM "NEW" SERVICE TAG AT TIME OF FINAL INSPECTION.
13. BACKFLOW PREVENTION ASSEMBLIES: PRIVATE FIRE MAINS SHALL BE PROVIDED WITH A LISTED BACKFLOW PREVENTER ACCEPTED BY THE
PUBLIC WATER AGENCY TO WHICH THE PRIVATE FIRE MAIN IS BEING SUPPLIED AT LEAST ONE INDICATING VALVE SHALL BE INCLUDED AS
PART OF ABOVE- GROUND ASSEMBLIES. BACKFLOW PREVENTION ASSEMBLIES SHALL NOT BE LOCATED WITHIN 40-FEET, OR THE HEIGHT
OF THE FACING WALL, OF THE BUILDING(S) THAT IT SERVES.
14. SECTIONAL VALVES: WHEN A PRIVATE FIRE MAIN SERVES SIX OR MORE APPURTENANCES, SECTIONAL CONTROL VALVES SHALL BE
INSTALLED. CONTROL VALVES SHALL BE INDICATING UNLESS OTHERWISE APPROVED BY THE AHJ. SECTIONAL CONTROL VALVES SHALL BE
LOCATED SO THAT NO MORE THAN FIVE FIRE APPURTENANCES ARE AFFECTED BY SHUT -DOWN OF ANY SINGLE PORTION OF THE FIRE
SERVICE MAIN.
15. IMPACT PROTECTION: ON SITE FIRE HYDRANTS, POST INDICATOR VALVES AND FIRE DEPARTMENT CONNECTIONS LOCATED LESS THAN
THREE FEET BEHIND THE FACE OF CURB OR WHEN NO CURB IS PROVIDED SHALL BE PROTECTED BY GUARD POSTS SET IN CONCRETE
TO THE FOLLOWING SPECIFICATIONS:
• CONSTRUCTION OF STEEL NOT LESS THAN 4-INCHES IN DIAMETER AND CONCRETE FILLED.
• SPACED NOT MORE THAN 3-FEET BETWEEN POSTS ON CENTER.
• SET NOT LESS THAN 3-FEET DEEP IN CONCRETE FOOTING OF NOT LESS THAN A 15-INCH DIAMETER.
• SET WITH THE TOP OF THE POSTS NOT LESS THAN 3 FEET ABOVE GROUND.
• LOCATED NOT LESS THAN 3-FEET FROM THE FIRE HYDRANTS, POST INDICATOR VALVES AND FIRE DEPARTMENT CONNECTIONS.
• ALL GUARD POSTS SHALL BE PAINTED SAFETY YELLOW.
16. BACKFILL: BACKFILL SHALL BE WELL TAMPED IN LAYERS OR PUDDLE UNDER AND AROUND PIPES TO PREVENT SETTLEMENT OR LATERAL
MOVEMENT. BACKFILL SHALL CONSIST OF CLEAN FILL SAND OR PEA GRAVEL TO A MINIMUM 6-INCHES BELOW AND TO A MINIMUM OF
12-INCHES ABOVE THE PIPE AND SHALL CONTAIN NO ASHES, CINDERS, REFUSE, ORGANIC MATTER, OR OTHER CORROSIVE MATERIALS.
OTHER BACKFILL MATERIALS ARE PERMITTED WHERE DESIGNED BY A REGISTERED PROFESSIONAL ENGINEER AND APPROVED BY THE
ENFORCING AGENCY.
17. FIRE RISER ACCESS: AUTOMATIC FIRE SPRINKLER SYSTEM RISERS SHALL NOT BE OBSTRUCTED IN ANY IF A SYSTEM RISER IS TO BE
CONCEALED BY MEANS OF A WALL, SOFFIT, COLUMN, OR OTHER BUILDING CONSTRUCTION, IT SHALL BE PROVIDED WITH EIGHTEEN (18)
INCH CLEARANCE TO EACH SIDE AND TO THE FRONT OF THE SYSTEM RISER. ACCESS SHALL BE PROVIDED BY MEANS OF A DOOR WITH
THE MINIMUM DIMENSIONS TWO FEET SIX (6) INCHES IN WIDTH BY SIX (6) FEET EIGHT (8) INCHES IN HEIGHT.
18. FIRE DEPARTMENT CONNECTIONS: EACH SEPARATE FIRE SPRINKLER SYSTEM RISER (NOT ON MANIFOLD) SHALL BE PROVIDED WITH A FIRE
DEPARTMENT CONNECTION (FDC). THE FDC SHALL BE LOCATED WITHIN 200-FEET OF A PUBLIC OR APPROVED FIRE HYDRANT, WHEN
MEASURED AS A HOSE WOULD LAY ALONG AN APPROVED ROUTE. THE FDC SHALL BE LOCATED ON THE STREET SIDE OF BUILDINGS.
SYSTEMS SERVING STANDPIPES SHALL BE SIZED TO SUPPLY THE SYSTEM PRESSURE AND FLOW REQUIREMENTS BASED ON ONE 2 1,6"
CONNECTION FOR EACH 250 GALLONS PER MINUTE REQUIRED. AT A MINIMUM, A 2 1,6" X 2 4" X 4" FIRE DEPARTMENT CONNECTION
SHALL BE PROVIDED.
19. APPLICANT SHALL COORDINATE POINT OF CONNECTION OF UNDERGROUND WATER SYSTEMS WITH APPLICABLE WATER AGENCY. SUCH
COORDINATION MAY INCLUDE, BUT NOT BE LIMITED TO: ADDITIONAL FINANCIAL ARRANGEMENTS, FACILITY DESIGN, PLAN REVIEW, AND
FACILITY TESTING.
20. INSPECTIONS: THE FOLLOWING INSPECTIONS ARE REQUIRED:
• THRUST BLOCK PRE -POUR, RESTRAINT, PIPING MATERIAL, TRENCH, AND BACKFILL INSPECTION REQUIRED PRIOR TO BACKFILLING.
• UNDERGROUND HYDROSTATIC TEST PER NFPA 24 FOR 2 HOURS.
• UNDERGROUND FLUSH OF ALL AFFECTED PIPING UNTIL CLEAR. REQUIRED PRIOR TO CONNECTION OF ANY OVERHEAD PIPING.
• UNDERGROUND FINAL - A COPY OF THE "CONTRACTORS MATERIAL AND TEST CERTIFICATE FOR UNDERGROUND PIPING" SHALL BE
PROVIDED. VALVE AND CONNECTION SIGNAGE IS IN PLACE. BLUE REFLECTOR HYDRANT MARKERS ARE INSTALLED IN THE ADJOINING
ROADWAY. PRIVATE FIRE HYDRANTS ARE PAINTED RED AND PROVIDED WITH OSFM "NEW" SERVICE TAGS.
- CONTACT THE OFFICE OF THE FIRE MARSHAL A MINIMUM OF 48 HOURS IN ADVANCE TO SCHEDULE INSPECTIONS.
PRIVATE WATER IMPROVEMENT PLANS
1. ALL WORKS SHALL CONFORM WITH THE STANDARD SPECIFICATIONS FOR PUBLIC WORKS CONSTRUCTION (GREEN BOOK) LATEST EDITION,
A.W.W.A. STANDARDS, UNIFORM PLUMBING CODE LATEST EDITION AND THESE PLANS.
2. ALL WATER MAINS 4" THRU 12" SHALL BE C-900 CLASS 200, 14" AND LARGER SHALL BE C-905 CLASS 150. WATER PIPE SMALLER
THAN 4" SHALL BE SCHEDULE 40 OR SCHEDULE 80 PVC OR CPVC WITH A PRESSURE RATING GREATER THAN 200 PSI UNLESS
OTHERWISE INDICATED ON THE PLANS. SIZES AS INDICATED ON THE PLANS. AS MANUFACTURED BY JM EAGLE, PACIFIC -WESTERN
MANUFACTURING COMPANY OR ENGINEER APPROVED EQUAL. PIPE
3. FIRE HYDRANTS SHALL BE 6" WET BARREL TYPE WITH ONE 4" OPENING AND TWO 2-1/2" OPENING PER CVWD STANDARD. FIRE
HYDRANT SHALL BE JONES MODEL NO. J-3765 OR AVK MODEL CALIFORNIA 24-50 HP OR APPROVED EQUAL.
4. GATE VALVES 4" THRU 12" SHALL BE RESILIENT -SEATED WITH NON -RISING STEMS CONFORMING TO A.W.W.A. C-509-80. VALVES
LARGER THAN 12" SHALL BE BUTTERFLY VALVES. VALVES SHALL BE FLANGED X FLANGED. AS MANUFACTURED BY AMERICAN AVK, CLOW,
M&H, STOCKHAM, U.S. PIPE, OR ENGINEER APPROVED EQUAL
5. BALL VALVE MATERIAL SHALL BE AS INDICATED ON PLAN. BALL VALVE MATERIAL TO BE EITHER BRONZE BODY OR PVC SCHEDULE 80.
BRONZE VALVE SHALL HAVE NPT THREADS ON BOTH ENDS RATED AT 600 PSI AS MANUFACTURED BY CONBRACO INDUSTRIES OR
ENGINEER APPROVED EQUAL. PVC VALVE SHALL HAVE NPT THREADS ON BOTH ENDS RATED AT 200 PSI AS MANUFACTURED BY SPEAR
OR ENGINEER APPROVED EQUAL.
6. THE MINIMUM COVER FOR WATER MAINS AND WATER SERVICES SHALL BE 36 INCHES. STREET SHALL BE BROUGHT TO SUBGRADE AND
SEWER MAIN SHALL BE INSTALLED BEFORE WATER MAIN LINE IS INSTALLED.
7. THE MINIMUM COVER FOR WATER MAINS AND WATER SERVICES SHALL BE 36 INCHES. STREET SHALL BE BROUGHT TO SUBGRADE AND
SEWER MAIN SHALL BE INSTALLED BEFORE WATER MAIN LINE IS INSTALLED.
8. MINIMUM HORIZONTAL SEPARATION FROM PRIVATE WATER TO PRIVATE SEWER MAINS SHALL BE BY ONE 1-FOOT FROM OUTSIDE WALL TO
OUTSIDE WALL. MINIMUM VERTICAL SEPARATION FOR WATER AND SEWER MAINS AT PERPENDICULAR CROSSING SHALL BE 1'-FOOT FROM
OUTSIDE WALL TO OUTSIDE WALL OF PIPE PER U.P.C.
9. THE CONTRACTOR SHALL TEST AND CHLORINATE PROPOSED WATER MAINS AND SERVICES BACTERIOLOGICAL SAMPLES SHALL BE CLEARED
BY A CERTIFIED TESTING LAB AND SHALL PROVIDE THE WRITTEN RESULTS TO THE ENGINEER. TESTS ON FIRE SYSTEM SHALL MEET FIRE
DEPARTMENT REQUIREMENTS AND S.S.P.W.C.
10. TRENCH EXCAVATION, PIPE BEDDING AND BACKFILL SHALL BE CERTIFIED BY A REGISTERED SOILS ENGINEER PRIOR TO PLACEMENT OF
A.C. OR CONCRETE.
11. IT SHALL BE THE WATER CONTRACTOR'S RESPONSIBILITY TO SET WATER VALVE RISER, FRAME AND COVER TO FINISH GRADE AFTER
PAVING IN ACCORDANCE WITH CVWD STANDARD DRAWING NO. W-17A MODIFY VALVE COVER TO ONLY READ "WATER" OR "FIRE" AS
APPROPRIATE.
12. ALL CONNECTIONS MADE TO EXISTING FACILITIES WILL BE AT CONTRACTOR'S EXPENSE.
13. THE CONTRACTOR SHALL OBTAIN ALL NECESSARY STANDARDS AND REVIEW THE PLANS IN DETAIL WITH THE ENGINEER PRIOR TO START
OF CONSTRUCTION.
14. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK AND SHALL MAINTAIN ALL FACILITIES UNTIL PROJECT IS COMPLETED.
15. EXISTING UTILITIES MAY OR MAY NOT BE SHOWN ON THESE DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO
VERIFY AND PROTECT ALL UTILITIES IN THE CONSTRUCTION AREA WHETHER SHOWN OR NOT SHOWN HEREON. THE CONTRACTOR SHALL
VERIFY LOCATION OF ALL EXISTING UTILITIES AND NOTIFY COMPANIES 48 HOURS IN ADVANCE OF THE BEGINNING OF CONSTRUCTION AND
CALL U.S.A. UNDERGROUND SERVICE ALERT AT 1-800-227-2600.
16. ALL FITTINGS SHALL BE DUCTILE IRON PUSH -ON BY PUSH -ON EQUIPPED WITH "TYTON" PUSH -ON OR MECHANICAL JOINTS UNLESS
OTHERWISE NOTED ON PLANS. JOINT RESTRAINT SHALL BE "MEGA LUG" BY EBAA IRON WORKS, SERIES 1600 BELL RESTRAINT HARNESS,
OR ENGINEER APPROVED EQUAL.
17. LENGTH OF RESTRAINED PIPE SHALL BE A MINIMAL OF 54-LINEAL FEET IN EACH DIRECTION OF FITTING AND BRANCH OF TEE OR AS
INDICATED ON PLAN.
18. ALL NUTS, WASHERS AND BOLTS SHALL BE STAINLESS STEEL.
19. BLUE DOT MARKERS SHALL BE PLACED ADJACENT TO FIRE HYDRANTS LOCATED ON THE CENTERLINE OF THE STREET OR DRIVEWAY.
20. THE CONTRACTOR AGREES THAT HE SHALL ASSUME SOLE AND COMPLETE RESPONSIBILITY FOR JOB SITE CONDITIONS DURING THE
COURSE OF CONSTRUCTION OF THIS PROJECT, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY; THAT THIS REQUIREMENT SHALL
APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS; AND THAT THE CONTRACTOR SHALL DEFEND, INDEMNIFY AND
HOLD THE OWNER AND THE ENGINEER HARMLESS FROM ANY AND ALL LIABILITY, REAL OR ALLEGED, IN CONNECTION WITH THE
PERFORMANCE OF WORK ON THIS PROJECT, EXCEPTING FOR LIABILITY ARISING FROM THE SOLE NEGLIGENCE OF THE OWNER OR THE
ENGINEER.
NOTE.
THIS PLAN IS FOR PLANNING/BUILDING
PERMIT ONLY. THE INSTALLING
CONTRACTOR MUST HOLD A VALID
C-16 LICENSE. THE INSTALLING
CONTRACTOR SHALL SUBMIT PLANS
AND PRESSURE LOSS CALCULATIONS
TO FIRE FOR APPROVAL AND A FIRE
SYSTEM CONSTRUCTION PERMIT.
CASE # - APPROVAL:
RIVERSIDE COUNTY FIRE DEPARTMENT
LA QUINTA OFFICE OF THE FIRE MARSHAL
THE FIRE DEPT. APPROVAL IS VALID FOR
ONE YEAR -SUBJECT TO COMPLIANCE WITH
APPLICABLE CODES
INSTALLING CONTRACTOR ACCEPTANCE
BUSINESS NAME:
ADDRESS:
RESPONSIBLE
MANAGING OFFICER:
SIGNATURE: DATE:
EXP DATE:
IN THE CITY OF LA QUINTA, CALIFORNIA
SILVERROCK RESORT - LQ RESORT CONDOMINIUMS
TRACT MAP NO. 37930
PRIVATE FIRE SERVICE PLAN
COVER SHEET
PORTIONS OF THE SW 1/4 OF SEC. 5, AND NW, NE, AND SE
1/4 OF SEC. 8, T.6S., R.7E., S.B.M.
SHEET
1
OF
8
SHEETS
g, 7/28/2022 10:52:20 AM, mpompa, MSA Consulting, Inc.
0
N
O
CN
N
U
c
a)
a)
D
c
92
a)
• 0
`
c
0
:\2502\ACAD\Improvemen
CONSTRUCTION NOTES
10
11
12
SD BOP 17.67
FIRE TOP 16.66
11+14.46
FIRE RISER
PROP. 6" PVC
SEWER LINE
FIRE BOP 16.35
SWR TOP 14.59
FIRE BOP 16.54/
SWR TOP 14.04
1 1 +49.01
11 +58.26
11 +80.37
FIRE BOP 17.28
SWR TOP 15.60
PROP. 6" PVC
SEWER LINE
BLDG 11
FF 22.67
FIRE RISER
SD BOP 18.92
FIRE TOP 17.87
12+39.45
FIRE BOP 17.09
SWR TOP 16.05
SD BOP 18.54
FIRE TOP 17.54
12+20.62
FURNISH AND INSTALL 8" C-900, CLASS 200 PVC PIPE
(42" TYPICAL COVER UNLESS NOTED ON PLAN)
DELETED
DELETED
FURNISH
FURNISH
FURNISH
FURNISH
FURNISH
AND INSTALL
AND INSTALL
AND INSTALL
AND INSTALL
AND INSTALL
PROP. S/W
PROP. 3" PVC
WATER LINE
8" X 22 1/2' DI BEND W/ THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
8" X 45' DI BEND W/ THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
8" X 90' DI BEND W/ THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
8" DI TEE W/THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
8" DI CROSS W/THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
CONSTRUCT POST INDICATOR VALVE AND FIRE DEPARTMENT CONNECTION PER DETAIL ON SHEET 2
CONTRACTOR TO CONNECT 8" PVC C-900 PIPE TO BUILDING SPRINKLER SYSTEM, IF BUILDING
SPRINKLER SYSTEM IS UNAVAILABLE INSTALL 8" DI BLIND FLANGE AND MARKER POST MARKED "F"
CONTRACTOR TO CONNECT TO BOTTOM ELBOW OF ABOVE GROUND DOUBLE CHECK DETECTOR
ASSEMBLY (DCDA INSTALLED BY PUBLIC WATER CONTRACTOR) AND INSTALL 8" DI REDUCER
FURNISH AND INSTALL RAISED BLUE REFLECTIVE PAVEMENT MARKERS
PER RIVERSIDE COUNTY FIRE DEPARTMENT STANDARD NO. 06-11
DIG ALERT
DigSafely
DIAL TOLL FREE
1-800-227-2600
AT LEAST TWO DAYS BEFORE YOU DIG
UNDERGROUND SERVICE ALERT
OF SOUTHERN CALIFORNIA
BENCHMARK BM #430
ELEVATION 5.467' (NAVD88)
PROJECT ELEVATION
AT BM *430 3.903'
LOCATION
CITY OF LA QUINTA BM #430: 1-1/2" COPPERWELD MONUMENT,
STAMPED "LS-98", FLUSH AT THE CENTERLINE INTERSECTION OF
AVENUE 54 AND JEFFERSON STREET.
ELEVATION = 5.467' (NAVD88)
PROJECT ELEVATION AT BM #430 = ELEV. 3.903'
TO OBTAIN PROJECT ELEVATIONS IN NAVD88 DATUM,
ADD 1.564' TO ELEVATIONS SHOWN.
PROP. ALT
6 R PAVING AMMR
PROP. 6" PV
SEWER LINE
SD BOP 17.
FIRE TOP 16
SD
PROP. S/W
0+89.13 EC
PROP. 2" PVC
WATER LINE
20'
17.68
40'
SCALE 1 "=20'
GARAGE 11
60'
LINE DATA
NO.
LENGTH
BEARING
L1
4.00'
N20'
09'
06.25"W
L2
4.00'
N20'
09'
06.25"W
L3
4.00'
S69'
50'
53.75"W
L4
4.00'
S69'
50'
53.75"W
L5
13.59'
S69'
50'
53.75"W
L6
84.87'
N62'
53'
34.07"W
L7
12.80'
S72'
06'
25.93"W
L8
4.00'
S69'
50'
53.75"W
L9
4.00'
S69'
50'
53.75"W
L10
24.37'
S69'
50'
53.75"W
L11
59.88'
S75'
16'
09.36"W
BASIS OF BEARINGS
EASTERLY LINE OF SECTION 8, TOWNSHIP 6 SOUTH, RANGE 7
EAST, S.B.M., AS SHOWN ON PARCEL MAP 37207, ON FILE IN
BOOK 242, AT PAGES 72-87, OF PARCEL MAPS, O.R. TAKEN
AS: N 0212'49" W
PROP. 6" PVC
SEWER LINE
FIRE RISER
10+97.43
SD BOP 16.89
FIRE TOP 15.65
SD BOP 16.21
FIRE TOP 15.21
10+73.42
10+59.18
10+39.67
SEE DETAIL A
EX. 8" PVC
SEWER MAIN
80'
LINE DATA
NO.
LENGTH
BEARING
L12
9.25'
N59' 43' 50.64"W
L13
22.11'
S75' 16' 09.36"W
L14
40.26'
S14' 43' 50.64"E
L15
18.83'
S75' 16' 09.36"W
L16
4.00'
N69' 50' 53.75"E
L17
10.03'
S65' 09' 06.25"E
L18
4.00'
S65' 09' 06.25"E
L19
3.69'
S65' 09' 06.25"E
L20
19.51'
N42' 30' 32.69"E
L21
24.02'
N62' 53' 26.04"W
7
EX. 8" DI
WATER MAIN //
//
/ //
PRrP. S/W
PRO". 'URB
EX. 12" DI
WATER MAIN
GARAGE 10
CURVE DATA
NO.
DELTA
RADIUS
LENGTH
TANGENT
Cl
5'25'16"
600.00'
56.77'
28.41'
C2
5'08'41 "
200.00'
17.96'
8.99'
C3
4'11'03"
195.00'
14.24'
7.12'
DATE
REVISIONS
APPR. DATE
D7/28/22
/ ' \ REVISED SURFACE FEATURES & STORM DRAIN
DESIGNED BY
MP
DRAWN BY
CC
CHECKED BY
MTC
YASEME
\
1/2" RADIUS
RED
PROP. ALT
PAVING AMMR
4"H X 8"W MINIMUM
REFLECTORIZED SIGN
CONSTRUCTED OF
PORCELAIN STEEL WITH
BEADED TEXT OR EQUAL
4"/6"/8" SCH. 40
GALVANIZED
STEEL PIPE
SEE PLAN -\
SIZES
ADDRESS
\ 010+12.00
®10+04.00
10+04.00 (N&S)=
10+00.00 (W)
CVWD EASEMENT
PROP. S/W
PROP. 3" PVC
WATER LINE
WTR BOP 16.32
FIRE TOP 15.57
10+04.00®
10+14.00
10+21.71®
PROP. S/W
CVWD EASEMENT
EX. 8" CVWD
BACKFLOW DEVICE
IN VAULT
EX. 12" DI
WATER MAIN
BUILDING ADDRESS
NUMBER 3" MINIMUM
(WHITE)
POST INDICATOR/FIRE DEPT.
CONNECTION SIGN DETAIL
NTS
ADDRESS
4"X2.5"X2.5" SIAMESE CONNECTION
W/ CLAPPER INTERNAL CHECK VALVE
(POTTER-ROEMER # 5731) (LARGER
SPRINKLER FLOW WILL REQUIRE
ADDITIONAL 2.5" CONNECTIONS.
COORDINATE WITH BUILDING
SPRINKLER DESIGNER.)
�vv/vv/v�
TEE WITH FLANGE JOINT
SIZE PER PLAN
i
CHECK VALVE
SIGN
(SEE SIGN
DETAIL)
GALVANIZED
I# FLANGE
INDICATOR POST
FINISHED GRADE
SEE PLAN FOR SIZES
4'
z
lo
r7
INSTALL P.I.V.
TAMPER SWITCH.
VALVE
- SEE PLAN FOR SIZES
POST INDICATOR/FIRE DEPT. CONNECTION DETAIL 9
NTS
© Copyright 2022
MSA Consulting, Inc.
All Ri hts Reserved
MSA CONSULTING, INC.
Civil Engineering • Land Surveying • Landscape Architecture
Planning • Environmental Services • Dry Utility Coordination • GIS
34200 Bob Hope Drive Rancho Mirage, CA 922701760.320.98111 MSAConsultinginc.com
PREPARED UNDER THE DIRECT SUPERVISION OF:
MA CO
08/02/2022
� CEDON, R.C.E. NO. 75478 DATE
IF REQUIRED DEFLECT
DOMESTIC WATER PIPE
AS NEEDED (WITHIN
MANUFACTURERS
RECOMMENDATIONS)
o'
5'
DETAIL A
10'
15'
20'
SCALE 1 "=5'
\> ice\> \> \> \> \> \> \> \> \>
NOTE: 90% RELATIVE
RECOMPACTION, 95%
WHEN TRENCHES ARE
WITHIN 10 FEET OF
ANY BUILDING
RECOMPACTION
z
2
0
'\\%\\%\\%/\\%\\%/\\%\\%\\%\\' \`
2"/3" DOMESTIC
WATER LINE
\
PROP. F
SERVICE
\ \
\ \
\ \
\ 6" MINI
T CLEAR
\ \ - - - - - /
IRE
CROSSING DETAIL
FIRE SERVICE TO
DOMESTIC WATER
NTS
7
INSTALLING CONTRACTOR ACCEPTANCE
THIS SHEET SUPERSEDES THE
PREVIOUSLY APPROVED SHEET 1
APPROVED 10/26/2020 AND IS
IDENTICAL EXCEPT FOR THOSE
REVISIONS "CLOUDED" AND LABELED
WITH REVISION TRIANGLES.
R.C.E. C75478
CASE # - APPROVAL:
RIVERSIDE COUNTY FIRE DEPARTMENT
LA QUINTA OFFICE OF THE FIRE MARSHAL
DATE
THE FIRE DEPT. APPROVAL IS VALID FOR
ONE YEAR -SUBJECT TO COMPLIANCE WITH
APPLICABLE CODES
T. CELED•N
EXP 6-30-24
BUSINESS NAME:
ADDRESS:
RESPONSIBLE
MANAGING OFFICER:
SIGNATURE: DATE:
uc #:
EXP DATE:
SEAL
IN THE CITY OF LA QUINTA, CALIFORNIA
SILVERROCK RESORT - LQ RESORT CONDOMINIUMS
TRACT MAP NO. 37930
PRIVATE FIRE SERVICE PLAN
PLAN VIEW
PORTIONS OF THE SW 1/4 OF SEC. 5, AND NW, NE, AND SE
1/4 OF SEC. 8, T.6S., R.7E., S.B.M.
SHEET
2
OF
8
SHEETS
R:\2502\ACAD\Improvement Plansorivate Fire-endry Residences\2502 Private Fire 02.dwg, 7/28/2022 10:53:46 AM, mpompa, MSA Consulting, Inc.
TOP VIEW
TOP VIEW
THRUST BLOCK BEARING AREA
CASE
TEE, VALVES, & DEAD ENDS
90' BEND
45' BEND
22-1/2*
11 1/4*
8"
20 S.F.
28 S.F.
15 S.F.
8 S.F.
4 S.F.
12"
42 S.F.
59 S.F.
32 S.F.
17 S.F.
9 S.F.
DETAIL A
THRUST BLOCK DETAIL
N.T.S.
GENERAL NOTES FOR THRUST BLOCK.
1. THRUST BLOCK BEARING AREAS ARE BASED ON THE FOLLOWING (NFPA 24):
A. TEST PRESSURE: 200 PSI
B. COVER: 3 FEET
C. SOIL TYPE: SOFT CLAY (1,000 PSF)
D. FACTOR OF SAFETY: 1.5
2. CONCRETE THRUST BLOCK SHALL BE CONSTRUCTED OF 450-C-2000 CONCRETE.
3. IN COMPLIANCE WITH NFPA 24.
�IC�IC;;�Co
TOP VIEW
TOP VIEW
TOP VIEW
RESTRAINED JOINT REQUIREMENTS
PIPE SIZE
TEE
DEAD ENDS
90' BEND
45' BEND
22-1/2'
11 1/4'
6"
81 ET.
99 FT.
41 FT.
17 FT.
8 ET.
4 FT.
8"
111 FT.
129 FT.
53 FT.
22 FT.
11 ET.
6 FT.
12"
164 FT.
182 FT.
73 FT.
31 FT.
15 FT.
8 ET.
DETAIL B
RESTRAINED JOINT DETAIL
N.T.S.
GENERAL NOTES FOR RESTRAINED JOINTS.
1. LENGTHS SHOWN ARE BASED ON THE FOLLOWING (NFPA 24):
A. TEST PRESSURE: 200 PSI
B. COVER: 3 FEET
C. SOIL TYPE: SOFT CLAY (ML) (1,000 PSF)
D. FACTOR OF SAFETY: 1.5
C. TYPE 3 LAYING CONDITION: PIPE BEDDED IN 4 INCHES MINIMUM LOOSE SOIL.
BACKFILL LIGHTLY CONSOLIDATED TO TOP OF THE PIPE.
2. ALL JOINTS WITHIN LENGTH "L" SHALL BE RESTRAINED.
3. RESTRAINED JOINT LENGTHS SHOWN ARE FOR HORIZONTAL INSTALLATIONS ONLY.
4. IN COMPLIANCE WITH NFPA 24.
NOTE TO CONTRACTOR RESTRAINED JOINTS.
IF PIPELINE IS COMPLETELY RESTRAINED AT ALL JOINTS, THRUST BLOCKS WILL NOT BE
REQUIRED. ANY ADDITIONAL THRUST BLOCKS INSTALLED WILL INCREASE THE SAFETY FACTOR
OF THE SYSTEM.
LINE DATA
NO.
LENGTH
BEARING
L1
4.00'
S69' 50' 04.28"W
L2
4.00'
N20' 09' 55.72"W
L3
4.00'
N20' 09' 55.72"W
L4
32.60'
N20' 09' 55.72"W
L5
61.25'
N43' 10' 09.40"W
L6
23.03'
S46' 49' 50.60"W
L7
5.00'
S20' 09' 55.72"E
L8
4.00'
S20' 09' 55.72"E
L9
2.00'
S20' 09' 55.72"E
L10
21.05'
S77' 52' 23.12"W
CURVE DATA
NO.
DELTA
RADIUS
LENGTH
TANGENT
Cl
6'55'59"
300.00'
36.30'
18.17'
CONSTRUCTION NOTES
0
10
11
12
FURNISH AND INSTALL 8" C-900, CLASS 200 PVC PIPE
(42" TYPICAL COVER UNLESS NOTED ON PLAN)
DELETED
DELETED
FURNISH
FURNISH
FURNISH
FURNISH
FURNISH
AND INSTALL
AND INSTALL
AND INSTALL
AND INSTALL
AND INSTALL
8" X 22 1/2' DI BEND W/ THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
8" X 45' DI BEND W/ THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
8" X 90' DI BEND W/ THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
8" DI TEE W/THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
8" DI CROSS W/THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
CONSTRUCT POST INDICATOR VALVE AND FIRE DEPARTMENT CONNECTION PER DETAIL ON SHEET 2
CONTRACTOR TO CONNECT 8" PVC C-900 PIPE TO BUILDING SPRINKLER SYSTEM, IF BUILDING
SPRINKLER SYSTEM IS UNAVAILABLE INSTALL 8" DI BLIND FLANGE AND MARKER POST MARKED "F"
CONTRACTOR TO CONNECT TO BOTTOM ELBOW OF ABOVE GROUND DOUBLE CHECK DETECTOR
ASSEMBLY (DCDA INSTALLED BY PUBLIC WATER CONTRACTOR) AND INSTALL 8" DI REDUCER
FURNISH AND INSTALL RAISED BLUE REFLECTIVE PAVEMENT MARKERS
PER RIVERSIDE COUNTY FIRE DEPARTMENT STANDARD NO. 06-11
DIG ALERT
DigSafely
DIAL TOLL FREE
1-800-227-2600
AT LEAST TWO DAYS BEFORE YOU DIG
UNDERGROUND SERVICE ALERT
OF SOUTHERN CALIFORNIA
BENCHMARK BM #430
ELEVATION 5.467' (NAVD88)
PROJECT ELEVATION
AT BM *430 3.903'
LOCATION
CITY OF LA QUINTA BM #430: 1-1/2" COPPERWELD MONUMENT,
STAMPED "LS-98", FLUSH AT THE CENTERLINE INTERSECTION OF
AVENUE 54 AND JEFFERSON STREET.
ELEVATION = 5.467' (NAVD88)
PROJECT ELEVATION AT BM #430 = ELEV. 3.903'
TO OBTAIN PROJECT ELEVATIONS IN NAVD88 DATUM,
ADD 1.564' TO ELEVATIONS SHOWN.
BASIS OF BEARINGS
EASTERLY LINE OF SECTION 8, TOWNSHIP 6 SOUTH, RANGE 7
EAST, S.B.M., AS SHOWN ON PARCEL MAP 37207, ON FILE IN
BOOK 242, AT PAGES 72-87, OF PARCEL MAPS, O.R. TAKEN
AS: N 0212'49" W
•
N
SD BOP 18.03
FIRE TOP 17.03
SD BOP 18.52
FIRE TOP 17.25
11 +28.89
FIRE RISER
SD BOP 18.31
FIRE TOP 17.02
FIRE BOP 16.52
SWR TOP 13.95
BLDG 7
FF 20.97
DATE
REVISIONS
APPR. DATE
D7/28/22
/ ' \ REVISED SURFACE FEATURES & STORM DRAIN
DESIGNED BY
MP
DRAWN BY
CC
CHECKED BY
MTC
PROP. 6" PVC
SEWER LINE
PROP. S/W
CVWD EASEMENT
PROP. C&G
EX. 8" PVC
SEWER MAIN
.010+44.60
SEE DETAIL B
0'
EX. 8" DI
WATER MAIN
PROP. 3" PVC
WATER LINE
10+47.30 EC
20'
SD BOP 16.56
FIRE TOP 15.47
SD BOP 16.53
FIRE TOP 15.47
10+68.35
FIRE RISER
BLDG 8
FF 19.07
40'
PROP. 6" PVC
SEWER LINE
EX. 8" DI
WATER MAIN
PROP. CURB
PROP. S/W
60'
80'
SCALE 1 "=20'
© Copyright 2022
MSA Consulting, Inc.
All Ri • hts Reserved
R
MSA CONSULTING, INC
Civil Engineering • Land Surveying • Landscape Architecture
Planning • Environmental Services • Dry Utility Coordination • GIS
34200 Bob Hope Drive Rancho Mirage, CA 922701760.320.98111 MSAConsultinginc.com
PREPARED UNDER THE DIRECT SUPERVISION OF:
MA CO
08/02/2022
EDON, R.C.E. NO. 75478 DATE
PROP. C&G
EX. 8" PVC
SEWER MAIN
CVWD EASEMENT
W
PROP. 3" PVC
WATER LINE
0'
5'
PROP. C&G
CVWD EASEMENT
DETAIL B
10'
15'
EX. 8" CVWD
BACKFLOW DEVICE
IN VAULT
I.VYYU CHJ GIVIGIVI
PROP. S/W
PROP. C&G
20'
SCALE 1 "=5'
THIS SHEET SUPERSEDES THE
PREVIOUSLY APPROVED SHEET 1
APPROVED 10/26/2020 AND IS
IDENTICAL EXCEPT FOR THOSE
REVISIONS "CLOUDED" AND LABELED
WITH REVISION TRIANGLES.
R.C.E. C75478
CASE # - APPROVAL:
RIVERSIDE COUNTY FIRE DEPARTMENT
LA QUINTA OFFICE OF THE FIRE MARSHAL
DATE
THE FIRE DEPT. APPROVAL IS VALID FOR
ONE YEAR -SUBJECT TO COMPLIANCE WITH
APPLICABLE CODES
T. CELEDON
EXP 6-30-24
INSTALLING CONTRACTOR ACCEPTANCE
BUSINESS NAME:
ADDRESS:
RESPONSIBLE
MANAGING OFFICER:
SIGNATURE: DATE:
LIC #:
EXP DATE:
SEAL
IN THE CITY OF LA QUINTA, CALIFORNIA
SILVERROCK RESORT - LQ RESORT CONDOMINIUMS
TRACT MAP NO. 37930
PRIVATE FIRE SERVICE PLAN
PLAN VIEW
PORTIONS OF THE SW 1/4 OF SEC. 5, AND NW, NE, AND SE
1/4 OF SEC. 8, T.6S., R.7E., S.B.M.
SHEET
3
OF
8
SHEETS
R:\2502\ACAD\Improvement Plansorivate Fire-endry Residences\2502 Private Fire 03.dwg, 7/28/2022 10:55:34 AM, mpompa, MSA Consulting, Inc.
10+24.13
CVWD EASEMENT
EX. 12" DI
WATER MAIN
010+04.00 (N&S)=
10+00.00 (E)
/ 11 10+00.00
CURVE DATA
NO.
DELTA
RADIUS
LENGTH
TANGENT
Cl
3'44'31"
500.00'
32.66'
16.33'
C2
8'16'23"
500.00'
72.19'
36.16'
LINE DATA
NO.
LENGTH
BEARING
L1
4.00'
N 19'
49'
21.12"E
L2
3.75'
N 19'
49'
21.12"E
L3
2.00'
N70'
10'
38.88"W
L4
4.00'
N70'
10'
38.88"W
L5
14.92'
N70'
10'
38.88"W
L6
27.39'
S64'
49'
21.12"W
L7
55.81'
S19'
49'
21.12"W
L8
26.96'
S64'
49'
16.33"W
L9
23.34'
N70'
10'
38.88"W
L10
2.00'
570'
10'
38.88"E
L11
4.00'
S70'
10'
38.88"E
L12
21.84'
S70'
10'
38.88"E
L13
13.08'
S25'
10'
38.88"E
L14
49.54'
S19'
49'
21.12"W
L15
2.00'
570'
10'
38.88"E
L16
4.00'
S70'
10'
38.88"E
CONSTRUCTION NOTES
0
0
10
11
12
DETAIL C
SCALE 1"=5'
LINE DATA
NO.
LENGTH
BEARING
L17
21.27'
S70' 10' 38.88"E
L18
23.55'
N56' 22' 11.80"E
L19
17.86'
N 1 1' 22' 1 1.80"E
L20
20.44'
N33' 37' 48.20"W
L21
7.72'
N78' 37' 48.20"W
L22
4.29'
N70' 10' 38.88"W
L23
8.00'
S19' 49' 21.12"W
L24
18.28'
S25' 10' 38.88"E
L25
4.00'
S47° 40' 38.88"E
L26
4.00'
S2' 40' 38.88"E
L27
21.27'
S70' 10' 38.88"E
L28
21.84'
S70' 10' 38.88"E
L29
27.39'
S64' 49' 21.12"W
L30
4.00'
S2' 40' 38.88"E
L31
18.59'
52' 40' 38.88"E
L32
14.44'
S19' 49' 21.12"W
FURNISH AND INSTALL 8" C-900, CLASS 200 PVC PIPE
(42" TYPICAL COVER UNLESS NOTED ON PLAN)
DELETED
DELETED
FURNISH
FURNISH
FURNISH
FURNISH
FURNISH
AND INSTALL
AND INSTALL
AND INSTALL
AND INSTALL
AND INSTALL
10+09.75®
10+02.00®
10+02.00®
EX. 8" CVWD
BACKFLOW DEVICE
IN VAULT
CVWD EASEMENT
PROP. S/W
PROP. CURB
8" X 22 1/2' DI BEND W/ THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
8" X 45' DI BEND W/ THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
8" X 90' DI BEND W/ THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
8" DI TEE W/THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
8" DI CROSS W/THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
CONSTRUCT POST INDICATOR VALVE AND FIRE DEPARTMENT CONNECTION PER DETAIL ON SHEET 2
CONTRACTOR TO CONNECT 8" PVC C-900 PIPE TO BUILDING SPRINKLER SYSTEM, IF BUILDING
SPRINKLER SYSTEM IS UNAVAILABLE INSTALL 8" DI BLIND FLANGE AND MARKER POST MARKED "F"
CONTRACTOR TO CONNECT TO BOTTOM ELBOW OF ABOVE GROUND DOUBLE CHECK DETECTOR
ASSEMBLY (DCDA INSTALLED BY PUBLIC WATER CONTRACTOR) AND INSTALL 8" DI REDUCER
FURNISH AND INSTALL RAISED BLUE REFLECTIVE PAVEMENT MARKERS
PER RIVERSIDE COUNTY FIRE DEPARTMENT STANDARD NO. 06-11
DIG ALERT
DigSafely
DIAL TOLL FREE
1-800-227-2600
AT LEAST TWO DAYS BEFORE YOU DIG
UNDERGROUND SERVICE ALERT
OF SOUTHERN CALIFORNIA
BENCHMARK BM #430
ELEVATION 5.467' (NAVD88)
PROJECT ELEVATION
AT BM *430 3.903'
LOCATION
CITY OF LA QUINTA BM #430: 1-1/2" COPPERWELD MONUMENT,
STAMPED "LS-98", FLUSH AT THE CENTERLINE INTERSECTION OF
AVENUE 54 AND JEFFERSON STREET.
ELEVATION = 5.467' (NAVD88)
PROJECT ELEVATION AT BM #430 = ELEV. 3.903'
TO OBTAIN PROJECT ELEVATIONS IN NAVD88 DATUM,
ADD 1.564' TO ELEVATIONS SHOWN.
BASIS OF BEARINGS
EASTERLY LINE OF SECTION 8, TOWNSHIP 6 SOUTH, RANGE 7
EAST, S.B.M., AS SHOWN ON PARCEL MAP 37207, ON FILE IN
BOOK 242, AT PAGES 72-87, OF PARCEL MAPS, O.R. TAKEN
AS: N 0212'49" W
SD BOP 19.99
FIRE TOP 18.74
BLDG 5
FF 22.77
FIRE RISER
11+62.17
SD BOP 20.12
FIRE TOP 18.56
SD BOP 18.41
FIRE TOP 17.42
,--IsROP. 3" PVC
WATER LINE
)7/28/22
/
SD BOP 21.01
FIRE TOP 19.13
11+11.87
\-a
PROP. ALT
PAVING
MR
PROP. 3" PVC
WATER LINE
FIRE RISER
10+75.60 EC
CLUBHOUSE
FF 22.97
REVISIONS
A REVISED SURFACE FEATURES & STORM DRAIN
0+56.06
SD BOP 20.10
FIRE TOP 18.89
1 1 +23.1 1 EC
PROP. 3" PVC
EE HEET 5
r SEE DETAIL
10+27.27
10+27.84
10+40.92
WR TOP 14.13
90.45 C
WATER LINE FIRE RISER
SEE DETAIL D
PROP. 6" PV\
SEWER LINE
PROP. S/W
APPR. DATE
SCALE 1"=20'
DESIGNED BY
MP
DRAWN BY
CC
CHECKED BY
MTC
BLDG 6
FF 22.57
© Copyright 2022
MSA Consulting, Inc.
All Ri • hts Reserved
PROP. 6" PVC
SEWER LINE
BLDG 4
FF 22.17
FIRE RISER
1 1 +69.04
SD BOP 19.30
FIRE TOP 17.60
1 1 +61.32
SD BOP 17.T-71
FIRE TOP 16.71 ia
0
1 1 +40.88 hw '
0
3
PVC
1 1 +23.02
PROP. 3"
ATER SERVICE
PROP.-8-
WTR
BOP 18.5
FIRE TOP 17.52
L WATER MAN
PROP. 6" PVC
SEWER LINE
ONIOSVH3 A3
MSA CONSULTING, INC
Civil Engineering • Land Surveying • Landscape Architecture
Planning • Environmental Services • Dry Utility Coordination • GIS
+99.46 FC
34200 Bob Hope Drive Rancho Mirage, CA 92270 1760.320.98111 MSAConsultinginc.com
PREPARED UNDER THE DIRECT SUPERVISION OF:
08/02/2022
EDON, R.C.E. NO. 75478 DATE
PROP. 6" PVC
SEWER LINE
©10+04.29
WTR BOP 19.39
FIRE TOP 18.53
10+12.29
PROP. 3" PVC
WATER SERVICE
PROP. S/W
THIS SHEET SUPERSEDES THE
PREVIOUSLY APPROVED SHEET 1
APPROVED 10/26/2020 AND IS
IDENTICAL EXCEPT FOR THOSE
REVISIONS "CLOUDED" AND LABELED
WITH REVISION TRIANGLES.
R.C.E. C75478
CASE # - APPROVAL:
RIVERSIDE COUNTY FIRE DEPARTMENT
LA QUINTA OFFICE OF THE FIRE MARSHAL
THE FIRE DEPT. APPROVAL IS VALID FOR
ONE YEAR -SUBJECT TO COMPLIANCE WITH
APPLICABLE CODES
T. CELEDN
EXP 6-30-24
10+30.57
10+34.57
PROP. S/W
DETAIL D
SCALE 1"=5'
10+00.00
EX. 8" CVWD
BACKFLOW DEICE
IN VAULT
10+38. 7
EX. 12" I
WATER AII\
INSTALLING CONTRACTOR ACCEPTANCE
BUSINESS NAME:
ADDRESS:
RESPONSIBLE
MANAGING OFFICER:
SIGNATURE: DATE:
EXP DATE:
IN THE CITY OF LA QUINTA, CALIFORNIA
SILVERROCK RESORT - LQ RESORT CONDOMINIUMS
TRACT MAP NO. 37930
PRIVATE FIRE SERVICE PLAN
PLAN VIEW
PORTIONS OF THE SW 1 /4 OF SEC. 5, AND NW, NE, AND SE
1/4 OF SEC. 8, T.6S., R.7E., S.B.M.
SHEET
4
OF
8
SHEETS
LINE DATA
NO.
LENGTH
BEARING
L1
2.00'
S22' 23' 05.58"W
L2
2.00'
S22' 23' 05.58"W
L3
4.00'
S22' 23' 05.58"W
L4
4.00'
S22' 23' 05.58"W
L5
3.59'
S67' 23' 05.58"W
L6
96.65'
589' 53' 05.58"W
L7
23.72'
S41' 05' 05.01"W
L8
4.00'
N67' 36' 54.42"W
L9
2.00'
S22' 23' 05.58"W
L10
4.00'
S22' 23' 05.58"W
L11
4.00'
522' 23' 05.58"W
L12
2.37'
S67' 23' 05.58"W
L13
106.22'
589' 53' 05.58"W
L14
32.90'
N48' 54' 54.99"W
L15
20.55'
S89' 53' 05.58"W
L16
11.08'
N48' 54' 54.99"W
L17
25.79'
S89' 53' 05.58"W
L18
4.00'
S67° 36' 54.42"E
L19
2.00'
S22' 36' 54.42"E
L20
4.00'
S22' 36' 54.42"E
L21
10.46'
S22' 36' 54.42"E
L22
15.72'
S 1 1 ° 47' 27.03"W
CURVE DATA
NO.
DELTA
RADIUS
LENGTH
TANGENT
C1
8'59'19"
200.00'
31.38'
15.72'
CONSTRUCTION NOTES
FURNISH AND INSTALL 8" C-900, CLASS 200 PVC
(42" TYPICAL COVER UNLESS NOTED ON PLAN)
DELETED
DELETED
FURNISH
FURNISH
FURNISH
FURNISH
FURNISH
AND
AND
AND
AND
AND
BLDG 1
FF 24.27
PROP. S/W
FIRE RISER
12+12.90
PROP. 6" PVC
SEWER LINE
SD BOP 21.43
FIRE TOP 20.43
SD BOP 21.89
FIRE TOP 20.43
n11+87.11
FIRE BOP 21.39
WTR TOP 20.39
PROP. 3" PVC
WATER LINE
INSTALL 8" X 22 1/7 DI BEND W/ THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
INSTALL 8" X 45' DI BEND W/ THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
INSTALL 8" X 90' DI BEND W/ THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
INSTALL 8" DI TEE W/THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
INSTALL 8" DI CROSS W/THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
CONSTRUCT POST INDICATOR VALVE AND FIRE DEPARTMENT CONNECTION PER DETAIL ON SHEET 2
CONTRACTOR TO CONNECT 8" PVC C-900 PIPE TO BUILDING SPRINKLER SYSTEM, IF BUILDING
SPRINKLER SYSTEM IS UNAVAILABLE INSTALL 8" DI BLIND FLANGE AND MARKER POST MARKED "F"
CONTRACTOR TO CONNECT TO BOTTOM ELBOW OF ABOVE GROUND DOUBLE CHECK DETECTOR
ASSEMBLY (DCDA INSTALLED BY PUBLIC WATER CONTRACTOR) AND INSTALL 8" DI REDUCER
FURNISH AND INSTALL RAISED BLUE REFLECTIVE PAVEMENT MARKERS
PER RIVERSIDE COUNTY FIRE DEPARTMENT STANDARD NO. 06-11
DIG ALERT
DigSafely
DIAL TOLL FREE
1-800-227-2600
AT LEAST TWO DAYS BEFORE YOU DIG
UNDERGROUND SERVICE ALERT
OF SOUTHERN CALIFORNIA
BENCHMARK BM #430
ELEVATION 5.467' (NAVD88)
PROJECT ELEVATION
AT BM *430 3.903'
LOCATION
CITY OF LA QUINTA BM #430: 1-1/2" COPPERWELD MONUMENT,
STAMPED "LS-98", FLUSH AT THE CENTERLINE INTERSECTION OF
AVENUE 54 AND JEFFERSON STREET.
ELEVATION = 5.467' (NAVD88)
PROJECT ELEVATION AT BM #430 = ELEV. 3.903'
TO OBTAIN PROJECT ELEVATIONS IN NAVD88 DATUM,
ADD 1.564' TO ELEVATIONS SHOWN.
CVWD
EASEMENT
(*ram
NO/
i w
PARKING/
EVCHARGING
EVCHARGING
TR BOP 21.6
FIRE TOP 20.68
/ram 1 1 +22.59
FIRE BOP 20.58
SWR TOP 19.57
SD BOP 21.96
FIRE TOP 21.05
11+35.96
FIRE RISER
BASIS OF BEARINGS
EASTERLY LINE OF SECTION 8, TOWNSHIP 6 SOUTH, RANGE 7
EAST, S.B.M., AS SHOWN ON PARCEL MAP 37207, ON FILE IN
BOOK 242, AT PAGES 72-87, OF PARCEL MAPS, O.R. TAKEN
AS: N 0212'49" W
BLDG 2
FF 25.07
FIRE BOP 20.14
SWR TOP_ 18.36
'JNINtiVd
FIRE e0
SWR TO 18.21
FIRE Bs20 55
SWR *P\18.34
11+00
11+00
0
11+12.24®
/PAVING AMMR
PROP. 6" PVC
SEWER LINE
MATCHLINE
SEE SHEET 4
DATE
D7/28/22
REVISIONS
/ ' \ REVISED SURFACE FEATURES & STORM DRAIN
APPR. DATE
GARAGE 1
'Jream A3
'Jream A3
- EX. 12" DI
WATER MAIN
PROP. ALT
_L-
DESIGNED BY
MP
DRAWN BY
CC
CHECKED BY
MTC
LL.
L_L_L
L_L_L
L_L-I,
PROP. 3" PVC
WATER LINE
n 10+51.83
PROP. 2" PVC
WATER LINE
CVWD
EASEMENT
SD BOP 20.89
FIRE TOP 19.88
10+67.55
FIRE RISER
BLDG 3
FF 24.07
SCALE 1 "=20'
PROP. 6" PVC
SEWER LINE
PROP. S/W
PROP. CURB
© Copyright 2022
MSA Consulting, Inc.
All Ri • hts Reserved
MSA CONSULTING, INC.
Civil Engineering • Land Surveying • Landscape Architecture
Planning • Environmental Services • Dry Utility Coordination • GIS
34200 Bob Hope Drive Rancho Mirage, CA 922701760.320.98111 MSAConsultinginc.com
PREPARED UNDER THE DIRECT SUPERVISION OF:
08/02/2022
EDON, R.C.E. NO. 75478 DATE
PROP. C&G
EX. 8" PVC
SEWER MAIN
PROP. CURB
EX. HYDRANT
CVWD EASEMENT
10+04.00
10+06.00
+ 14.00
@10+16.37
10+00.00
10+04.00
10+12.00®
10+15.59®
PROP. 3" PVC
WATER LINE
DETAIL E
SCALE 1 "=5'
THIS SHEET SUPERSEDES THE
PREVIOUSLY APPROVED SHEET 1
APPROVED 10/26/2020 AND IS
IDENTICAL EXCEPT FOR THOSE
REVISIONS "CLOUDED" AND LABELED
WITH REVISION TRIANGLES.
R.C.E. C75478
CASE # - APPROVAL:
RIVERSIDE COUNTY FIRE DEPARTMENT
LA QUINTA OFFICE OF THE FIRE MARSHAL
DATE
THE FIRE DEPT. APPROVAL IS VALID FOR
ONE YEAR -SUBJECT TO COMPLIANCE WITH
APPLICABLE CODES
T. CELEDeN
EXP 6-30-24
EX. 12" DI
WATER MAIN
EX. 8" CVWD
BACKFLOW DEVICE
IN VAULT
10+02.00 (N&S) =
10+00.00 (W&E)
EMENT
PROP. S/W
10+20.46®
WTR BOP 20.57
FIRE TOP 19.86
INSTALLING CONTRACTOR ACCEPTANCE
BUSINESS NAME:
ADDRESS:
RESPONSIBLE
MANAGING OFFICER:
SIGNATURE: DATE:
LIC #:
EXP DATE:
(SEAL)
IN THE CITY OF LA QUINTA, CALIFORNIA
SILVERROCK RESORT - LQ RESORT CONDOMINIUMS
TRACT MAP NO. 37930
PRIVATE FIRE SERVICE PLAN
PLAN VIEW
PORTIONS OF THE SW 1/4 OF SEC. 5, AND NW, NE, AND SE
1/4 OF SEC. 8, T.6S., R.7E., S.B.M.
SHEET
5
OF
8
SHEETS
R:\2502\ACAD\Improvement Plansorivate Fire-endry Residences\2502 Private Fire 05.dwg, 7/28/2022 10:59:19 AM, mpompa, MSA Consulting, Inc.
DIG ALERT
DigSafely
DIAL TOLL FREE
1-800-227-2600
AT LEAST TWO DAYS BEFORE YOU DIG
UNDERGROUND SERVICE ALERT
OF SOUTHERN CALIFORNIA
BENCHMARK BM #430
ELEVATION 5.467' (NAVD88)
PROJECT ELEVATION
AT BM *430 3.903'
LOCATION
CITY OF LA QUINTA BM #430: 1-1/2" COPPERWELD MONUMENT,
STAMPED "LS-98", FLUSH AT THE CENTERLINE INTERSECTION OF
AVENUE 54 AND JEFFERSON STREET.
ELEVATION = 5.467' (NAVD88)
PROJECT ELEVATION AT BM #430 = ELEV. 3.903'
TO OBTAIN PROJECT ELEVATIONS IN NAVD88 DATUM,
ADD 1.564' TO ELEVATIONS SHOWN.
BASIS OF BEARINGS
EASTERLY LINE OF SECTION 8, TOWNSHIP 6 SOUTH, RANGE 7
EAST, S.B.M., AS SHOWN ON PARCEL MAP 37207, ON FILE IN
BOOK 242, AT PAGES 72-87, OF PARCEL MAPS, O.R. TAKEN
AS: N 0212'49" W
SCALE 1 "=30'
CONSTRUCTION NOTES
0
0
0
0
0
0
0
0
0
10
11
FURNISH AND
(42" TYPICAL
DELETED
DELETED
FURNISH AND INSTALL
FURNISH AND INSTALL
FURNISH AND INSTALL
FURNISH AND INSTALL
FURNISH AND INSTALL
INSTALL 8" C-900, CLASS 200 PVC PIPE
COVER UNLESS NOTED ON PLAN)
8" X 22 1/2' DI BEND W/ THRUST BLOCK OR RESTRAINED JOINTS
8" X 45' DI BEND W/ THRUST BLOCK OR RESTRAINED JOINTS PER
8" X 90' DI BEND W/ THRUST BLOCK OR RESTRAINED JOINTS PER
PER DETAIL ON SHEET 3
DETAIL ON SHEET 3
DETAIL ON SHEET 3
8" DI TEE W/THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
8" DI CROSS W/THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
CONSTRUCT POST INDICATOR VALVE AND FIRE DEPARTMENT CONNECTION PER DETAIL ON SHEET 2
CONTRACTOR TO CONNECT 8" PVC C-900 PIPE TO BUILDING SPRINKLER SYSTEM, IF BUILDING
SPRINKLER SYSTEM IS UNAVAILABLE INSTALL 8" DI BLIND FLANGE AND MARKER POST MARKED "F"
CONTRACTOR TO CONNECT TO BOTTOM ELBOW OF ABOVE GROUND DOUBLE CHECK DETECTOR
ASSEMBLY (DCDA INSTALLED BY PUBLIC WATER CONTRACTOR) AND INSTALL 8" DI REDUCER
FURNISH AND INSTALL RAISED BLUE REFLECTIVE PAVEMENT MARKERS
PER RIVERSIDE COUNTY FIRE DEPARTMENT STANDARD NO. 06-11
DATE
)7/28/22
REVISIONS
A REVISED SURFACE FEATURES
APPR. DATE
DESIGNED BY
MP
DRAWN BY
CC
CHECKED BY
MTC
© Copyright 2022
MSA Consulting, Inc.
All Ri • hts Reserved
MSA CONSULTING, INC
Civil Engineering • Land Surveying • Landscape Architecture
Planning • Environmental Services • Dry Utility Coordination • GIS
34200 Bob Hope Drive Rancho Mirage, CA 922701760.320.98111 MSAConsultinginc.com
PREPARED UNDER THE DIRECT SUPERVISION OF:
08/02/2022
EDO , R.C.E. NO. 75478 DATE
LEGEND
ONO PARKING - FIRE LANE - CVC 22500.1
CONTRACTOR TO PAINT CURB WITH OSHA SAFETY RED SEMI GLOSS.
CONTRACTOR TO PAINT "NO PARKING FIRE LANE CVC 22500.1" AT
30' INTERVALS. ALL LETTERS AND NUMBERS SHALL BE A MINIMUM
OF 3" ON TOP OF CURB OR INSTALL 12" X 18" NO PARKING/FIRE
LANE SIGN AT 30—FOOT INTERVALS, PER DETAILS ON THIS SHEET
AND RIVERSIDE COUNTY FIRE DEPARTMENT FIRE LANE REQUIREMENTS
IVO PARKING - FIRE LANE - CVC 22500.1
CONTRACTOR TO PAINT "NO PARKING FIRE LANE CVC 22500.1" AT
30' INTERVALS WITH OSHA SAFETY RED SEMI GLOSS. DO NOT PAINT
CURB, STENCIL ONLY. ALL LETTERS AND NUMBERS SHALL BE A MINIMUM
OF 3" ON TOP OF CURB OR INSTALL 12" X 18" NO PARKING/FIRE
LANE SIGN AT 30—FOOT INTERVALS, PER DETAILS ON THIS SHEET
AND RIVERSIDE COUNTY FIRE DEPARTMENT FIRE LANE REQUIREMENTS
NO
PARKING
FIRE
LANE
CVC 22500.1 ,
NO PARKING/FIRE LANE SIGN, 12"X18" SEE NO PARKING POST DETAIL
FOR POST AND FOOTING INFORMATION SPACING: EVERY 30—FEET
PROPOSED 8" FIRE MAIN
PROPOSED 8" FIRE SERVICE MAIN
PROPOSED HYDRANTS
PROPOSED FDC
PROPOSED PIV
PROPOSED FIRE HYDRANT BLUE REFLECTIVE MARKER
INSTALL 14.5' FROM CURB FACE, PERPENDICULAR TO HYDRANT
EMERGENCY FIRE ACCESS LANE
ATTACH/FASTEN "NO
PARKING/FIRE LANE" SIGN
WITH VANDAL PROOF
HARDWARE.
"NO PARKING/FIRE LANE"
"CVC 22500.1" SIGN,
REFLECTORIZED 12"X18"
WITH 3" RED LETTERING
SIMILAR TO CA—MUTCD R26F
NOTE:
PLACE SIGN 2' MIN.
FROM CURB OR 5'
MIN. FROM EDGE OF
PAVEMENT WHERE
CURB DOES NOT
OCCUR, AT 30—FOOT
INTERVALS.
2"X2" SQUARE QWIK
PUNCH POST
VANDAL PROOF
HARDWARE
SLEEVE
ALL SIGN POSTS
TO BE INSTALLED
IN 560—C-3250
CONCRETE
NO PARKING POST DETAIL
THIS SHEET SUPERSEDES THE
PREVIOUSLY APPROVED SHEET 1
APPROVED 10/26/2020 AND IS
IDENTICAL EXCEPT FOR THOSE
REVISIONS "CLOUDED" AND LABELED
WITH REVISION TRIANGLES.
�R•
R.C.E. C75478
T. CELED•N
EXP 6-30-24
1
CASE # — APPROVAL:
RIVERSIDE COUNTY FIRE DEPARTMENT
LA QUINTA OFFICE OF THE FIRE MARSHAL
DATE
THE FIRE DEPT. APPROVAL IS VALID FOR
ONE YEAR —SUBJECT TO COMPLIANCE WITH
APPLICABLE CODES
INSTALLING CONTRACTOR ACCEPTANCE
BUSINESS NAME:
ADDRESS:
RESPONSIBLE
MANAGING OFFICER:
SIGNATURE: DATE:
LIC #:
EXP DATE:
(SEAL)
IN THE CITY OF LA QUINTA, CALIFORNIA
SILVERROCK RESORT - LQ RESORT CONDOMINIUMS
TRACT MAP NO. 37930
PRIVATE FIRE SERVICE PLAN
SIGNAGE AND STRIPING PLAN
PORTIONS OF THE SW 1 /4 OF SEC. 5, AND NW, NE, AND SE
1 /4 OF SEC. 8, T.6S., R.7E., S.B.M.
SHEET
6
OF
8
SHEETS
R:\2502\ACAD\Improvement Plansorivate Fire-endry Residences\2502 Private Fire 06.dwg, 7/28/2022 11:00:16 AM, mpompa, MSA Consulting, Inc.
DIG ALERT
DigSafely
DIAL TOLL FREE
1-800-227-2600
AT LEAST TWO DAYS BEFORE YOU DIG
UNDERGROUND SERVICE ALERT
OF SOUTHERN CALIFORNIA
BLDG 1
BENCHMARK BM #430
BLDG 2
BLDG 5
CLUBHOUSE
PROJECT ELEVATION
ELEVATION 5.467' (NAVD88) AT BM *430 3.903'
LOCATION
CITY OF LA QUINTA BM #430: 1-1/2" COPPERWELD MONUMENT,
STAMPED "LS-98", FLUSH AT THE CENTERLINE INTERSECTION OF
AVENUE 54 AND JEFFERSON STREET.
ELEVATION = 5.467' (NAVD88)
PROJECT ELEVATION AT BM #430 = ELEV. 3.903'
TO OBTAIN PROJECT ELEVATIONS IN NAVD88 DATUM,
ADD 1.564' TO ELEVATIONS SHOWN.
GARAGE 1
°WWI> ONicunn
LL
LL . L_
L_
LL L_
LL i L_
L_L_LL_L_L_
LL LL
BLDG 6
BASIS OF BEARINGS
EASTERLY LINE OF SECTION 8, TOWNSHIP 6 SOUTH, RANGE 7
EAST, S.B.M., AS SHOWN ON PARCEL MAP 37207, ON FILE IN
BOOK 242, AT PAGES 72-87, OF PARCEL MAPS, O.R. TAKEN
AS: N 0212'49" W
BLDG 3
BLDG 4
)7/28/22
REVISIONS
n REVISED SURFACE FEATURES
GARAGE 2
GARAGE 3
BLDG 7
APPR. DATE
DESIGNED BY
MP
DRAWN BY
CC
CHECKED BY
MTC
GARAGE 6
GARAGE 5
SCALE 1 "=30'
© Copyright 2022
MSA Consulting, Inc.
All Ri • hts Reserved
CONSTRUCTION NOTES
10
11
12
FURNISH AND INSTALL 8" C-900, CLASS 200 PVC PIPE
(42" TYPICAL COVER UNLESS NOTED ON PLAN)
DELETED
DELETED
FURNISH
FURNISH
FURNISH
FURNISH
FURNISH
AND INSTALL
AND INSTALL
AND INSTALL
AND INSTALL
AND INSTALL
8" X 22 1/2' DI BEND W/ THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
8" X 45' DI BEND W/ THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
8" X 90' DI BEND W/ THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
8" DI TEE W/THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
8" DI CROSS W/THRUST BLOCK OR RESTRAINED JOINTS PER DETAIL ON SHEET 3
CONSTRUCT POST INDICATOR VALVE AND FIRE DEPARTMENT CONNECTION PER DETAIL ON SHEET 2
CONTRACTOR TO CONNECT 8" PVC C-900 PIPE TO BUILDING SPRINKLER SYSTEM, IF BUILDING
SPRINKLER SYSTEM IS UNAVAILABLE INSTALL 8" DI BLIND FLANGE AND MARKER POST MARKED "F"
CONTRACTOR TO CONNECT TO BOTTOM ELBOW OF ABOVE GROUND DOUBLE CHECK DETECTOR
ASSEMBLY (DCDA INSTALLED BY PUBLIC WATER CONTRACTOR) AND INSTALL 8" DI REDUCER
FURNISH AND INSTALL RAISED BLUE REFLECTIVE PAVEMENT MARKERS
PER RIVERSIDE COUNTY FIRE DEPARTMENT STANDARD NO. 06-11
MSA CONSULTING, 'NIL
Civil Engineering • Land Surveying • Landscape Architecture
Planning • Environmental Services • Dry Utility Coordination • GIS
34200 Bob Hope Drive Rancho Mirage, CA 922701760.320.98111 MSAConsultinginc.com
PREPARED UNDER THE DIRECT SUPERVISION OF:
08/02/2022
EDON, R.C.E. NO. 75478 DATE
CASE # — APPROVAL:
RIVERSIDE COUNTY FIRE DEPARTMENT
LA QUINTA OFFICE OF THE FIRE MARSHAL
THE FIRE DEPT. APPROVAL IS VALID FOR
ONE YEAR —SUBJECT TO COMPLIANCE WITH
APPLICABLE CODES
LEGEND
ONO PARKING - FIRE LANE - CVC 22500.11
CONTRACTOR TO PAINT CURB WITH OSHA SAFETY RED SEMI GLOSS.
CONTRACTOR TO PAINT "NO PARKING FIRE LANE CVC 22500.1" AT
30' INTERVALS. ALL LETTERS AND NUMBERS SHALL BE A MINIMUM
OF 3" ON TOP OF CURB OR INSTALL 12" X 18" NO PARKING/FIRE
LANE SIGN AT 30—FOOT INTERVALS, PER DETAILS ON THIS SHEET
AND RIVERSIDE COUNTY FIRE DEPARTMENT FIRE LANE REQUIREMENTS
NO PARKING - FIRE LANE - CVC 22500.1 3"
CONTRACTOR TO PAINT "NO PARKING FIRE LANE CVC 22500.1" AT '
30' INTERVALS WITH OSHA SAFETY RED SEMI GLOSS. DO NOT PAINT
CURB, STENCIL ONLY. ALL LETTERS AND NUMBERS SHALL BE A MINIMUM
OF 3" ON TOP OF CURB OR INSTALL 12" X 18" NO PARKING/FIRE
LANE SIGN AT 30—FOOT INTERVALS, PER DETAILS ON THIS SHEET
AND RIVERSIDE COUNTY FIRE DEPARTMENT FIRE LANE REQUIREMENTS
NO
PARKING
FIRE
LANE
CVC 22500.1 ,
NO PARKING/FIRE LANE SIGN, 12"X18" SEE NO PARKING POST DETAIL
FOR POST AND FOOTING INFORMATION SPACING: EVERY 30—FEET
PROPOSED 8" FIRE MAIN
FS PROPOSED 8" FIRE SERVICE MAIN
o� PROPOSED HYDRANTS
PROPOSED FDC
PROPOSED PIV
PROPOSED FIRE HYDRANT BLUE REFLECTIVE MARKER
INSTALL 14.5' FROM CURB FACE, PERPENDICULAR TO HYDRANT
EMERGENCY FIRE ACCESS LANE
ATTACH/FASTEN "NO
PARKING/FIRE LANE" SIGN
WITH VANDAL PROOF
HARDWARE.
"NO PARKING/FIRE LANE"
"CVC 22500.1" SIGN,
REFLECTORIZED 1 2"X1 8"
WITH 3" RED LETTERING
SIMILAR TO CA—MUTCD R26F
NOTE:
PLACE SIGN 2' MIN.
FROM CURB OR 5'
MIN. FROM EDGE OF
PAVEMENT WHERE
CURB DOES NOT
OCCUR, AT 30—FOOT
INTERVALS.
2"X2" SQUARE QWIK
PUNCH POST
VANDAL PROOF
HARDWARE
SLEEVE
ALL SIGN POSTS
TO BE INSTALLED
IN 560—C-3250
CONCRETE
NO PARKING POST DETAIL
THIS SHEET SUPERSEDES THE
PREVIOUSLY APPROVED SHEET 1
APPROVED 10/26/2020 AND IS
IDENTICAL EXCEPT FOR THOSE
REVISIONS "CLOUDED" AND LABELED
WITH REVISION TRIANGLES. / \
R.C.E. C75478
T. CELEDON
EXP 6-30-24
INSTALLING CONTRACTOR ACCEPTANCE
BUSINESS NAME:
ADDRESS:
RESPONSIBLE
MANAGING OFFICER:
SIGNATURE: DATE:
EXP DATE:
IN THE CITY OF LA QUINTA, CALIFORNIA
SILVERROCK RESORT - LQ RESORT CONDOMINIUMS
TRACT MAP NO. 37930
PRIVATE FIRE SERVICE PLAN
SIGNAGE AND STRIPING PLAN
PORTIONS OF THE SW 1 /4 OF SEC. 5, AND NW, NE, AND SE
1 /4 OF SEC. 8, T.6S., R.7E., S.B.M.
SHEET
7
OF
8
SHEETS
2 AM, mpompa, MSA Consulting, Inc.
0
0
92
I)
0
0_
N
0
u)
i)
U
c
1)
D
c
N
1)
0
•
`
c
0
:\2502\ACAD\Improvemen
DIG ALERT
DigSafely
DIAL TOLL FREE
1-800-227-2600
AT LEAST TWO DAYS BEFORE YOU DIG
UNDERGROUND SERVICE ALERT
OF SOUTHERN CALIFORNIA
BENCHMARK BM #430
ELEVATION 5.467' (NAVD88)
PROJECT ELEVATION
AT BM *430 3.903'
LOCATION
CITY OF LA QUINTA BM #430: 1-1/2" COPPERWELD MONUMENT,
STAMPED "LS-98", FLUSH AT THE CENTERLINE INTERSECTION OF
AVENUE 54 AND JEFFERSON STREET.
ELEVATION = 5.467' (NAVD88)
PROJECT ELEVATION AT BM #430 = ELEV. 3.903'
TO OBTAIN PROJECT ELEVATIONS IN NAVD88 DATUM,
ADD 1.564' TO ELEVATIONS SHOWN.
24-20 INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIRAPPURTENANCES
Contractor's Material and Test Certificate for Underground Piping
PROCEDURE
Upon completion of work, inspection and tests shall be made by the contractor's representative and witnessed by an owner's
representative. All defects shall be corrected and system left in service before contractor's personnel finally leave the job.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners, and
contractor. It is understood the owner's representative's signature in no way prejudices any claim against contractor for faulty material, poor
workmanship, or failure to comply with approving authority's requirements or local ordinances.
Property name
Date
Property address
Plans
Accepted by approving authorities (names)
Address
Installation conforms to accepted plans ❑ Yes ❑ No
Equipment used is approved ❑ Yes D No
If no, state deviations
Instructions
Has person in charge of fire equipment been instructed as to location of ❑ Yes ❑ No
control valves and care and maintenance of this new equipment?
If no, explain
Have copies of appropriate instructions and care and maintenance ❑ Yes D No
charts been left on premises?
If no, explain
Location
Supplies buildings
Underground
pipes and joints
Pipe types and class
Type joint
Pipe conforms to standard
❑ Yes ❑ No
❑ Yes ❑ No
Fittings conform to standard
If no, explain
Joints needing anchorage clamped, strapped, or blocked in
accordance with standard
❑ Yes ❑ No
If no, explain
Test
description
Flushing: Flow the required rate until water is clear as indicated by
no collection of foreign material in burlap bags at outlets such as
in 10.10.2.1.3.
working pressure shall be hydrostatically tested at 200 psi
whichever is greater, and shall maintain that pressure ±5 psi
the system to maintain the test pressures required by 10.10.2.2.1,
of the following equation (for metric equation, see 10.10.2.2.6):
water), in gallons per hour (Ipm)
feet (m)
pipe, in inches (mm)
during the hydrostatic test, in pounds per square inch (gauge) (bar)
hydrants and blow -offs. Flush at one of the flow rates as specified
Hydrostatic: All piping and attached appurtenances subjected to system
(13.8 bar) or 50 psi (3.4 bar) in excess of the system working pressure,
(0.34 bar) for 2 hours.
Hydrostatic Testing Allowance: Where additional water is added to
the amount of water shall be measured and shall not exceed the limits
SDI L = testing allowance (makeup
L S = length of pipe tested, in
-
148,000 D = nominal diameter of the
P = average test pressure
Flushing
tests
© 2012 National Fire
New underground piping flushed according to
standard by (company)
❑ Yes D No
If no, explain
How flushing flow was obtained
❑ Public water ❑ Tank or reservoir ❑ Fire pump
Through what type opening
❑ Hydrant butt ❑ Open pipe
Lead-ins flushed according to standard by
(company) ❑ Yes ❑ No
If no, explain
How flushing flow was obtained
❑ Public water ❑ Tank or reservoir ❑ Fire pump
Protection Association
Through what type opening
❑ Y connection to flange ❑ Open pipe
and spigot
NFPA 24 (p. 1 of 2)
FIGURE 10.10.1 Sample of Contractor's Material and Test Certificate for Underground Piping.
2016 Edition
BASIS OF BEARINGS
EASTERLY LINE OF SECTION 8, TOWNSHIP 6 SOUTH, RANGE 7
EAST, S.B.M., AS SHOWN ON PARCEL MAP 37207, ON FILE IN
BOOK 242, AT PAGES 72-87, OF PARCEL MAPS, O.R. TAKEN
AS: N 0212'49" W
DATE
REVISIONS
APPR. DATE
D7/28/22
/ ' \ NO REVISIONS
DESIGNED BY
MP
DRAWN BY
CC
CHECKED BY
MTC
UNDERGROUND REQUIREMENTS
24-21
Hydrostatic
test
All new underground piping hydrostatically tested at
psi (bar) for hours
Joints covered
❑ Yes
❑ No
Leakage
test
Total amount of leakage measured
gallons (liters) hours
Allowable leakage
gallons (liters) hours
Forward flow
test of backflow
preventer
Foward flow test performed in accordance with 10.10.2.5.2:
❑ Yes
❑ No
Hydrants
Number installed
Type and make
All operate satisfactorily
❑ Yes
D No
Control
valves
Water control valves left wide open
If no, state reason
Hose threads of fire department connections and hydrants interchangeable with
those of fire department answering alarm
❑ Yes
❑ Yes
❑ No
❑ No
Remarks
Date left in service
Signatures
Name of Installing contractor
Tests witnessed by
For property owner (signed) Title
Date
For installing contractor (signed) Title
Date
Additional explanation and notes
© 2012 National Fire Protection Association
NFPA 24 (p. 2 of 2)
FIGURE 10.10.1 Continued
© Copyright 2022
MSA Consulting, Inc.
All Ri • hts Reserved
MSA CONSULTING, INC
Civil Engineering • Land Surveying • Landscape Architecture
Planning • Environmental Services • Dry Utility Coordination • GIS
34200 Bob Hope Drive Rancho Mirage, CA 92270 1760.320.9811MSAConsultinginc.com
PREPARED UNDER THE DIRECT SUPERVISION OF:
1i
08/02/2022
EDON, R.C.E. NO. 75478 DATE
2016 Edition
THIS SHEET SUPERSEDES THE
PREVIOUSLY APPROVED SHEET 1
APPROVED 10/26/2020 AND IS
IDENTICAL EXCEPT FOR THOSE
REVISIONS "CLOUDED" AND LABELED
WITH REVISION TRIANGLES.
T.
R.C.E. C75478
CASE # — APPROVAL:
RIVERSIDE COUNTY FIRE DEPARTMENT
LA QUINTA OFFICE OF THE FIRE MARSHAL
DATE
THE FIRE DEPT. APPROVAL IS VALID FOR
ONE YEAR —SUBJECT TO COMPLIANCE WITH
APPLICABLE CODES
INSTALLING CONTRACTOR ACCEPTANCE
BUSINESS NAME:
ADDRESS:
RESPONSIBLE
MANAGING OFFICER:
SIGNATURE: DATE:
LIC #:
EXP DATE:
(SEAL)
IN THE CITY OF LA QUINTA, CALIFORNIA
SILVERROCK RESORT - LQ RESORT CONDOMINIUMS
TRACT MAP NO. 37930
PRIVATE FIRE SERVICE PLAN
UNDERGROUND REQUIREMENTS
PORTIONS OF THE SW 1/4 OF SEC. 5, AND NW, NE, AND SE
1/4 OF SEC. 8, T.6S., R.7E., S.B.M.
SHEET
8
OF
8
SHEETS
CL
:\2502\ACAD\Improvemen