CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
PUBLIC COUNTER VISIT AARON HICKSON 6/28/2018 6/28/2018
MONTE SORENSEN PICKED UP PLANS FOR REVISIONS
PRINTED CORRECTIONS FOR HIM.FOLDER ON REVISION
REQUESTED SHELF WHEN RETURNED
RESUBMITTAL AARON HICKSON 6/29/2018 6/29/2018 MONTE SORENSEN FROM COMTRON RESUBMITTED
CORRECTIONS
CONDITIONS
Description: PGA WEST MULTI PURPOSE / COMMERCIAL SPRINKLER MONITORING
Type: FIRE ALARM Subtype: COMMERCIAL -
SPRINKLER MONITORING
Status: FINALED Applied: 6/15/2018 RCA
Parcel No: 775220027 Site Address: 55965 PGA BLVD LA QUINTA,CA 92253 Approved: 11/9/2018 EGO
Subdivision: PM 24995 Block: Lot: 4 Issued:
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 11/9/2018 EGO
Valuation: $0.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
Printed: Wednesday, January 18, 2023 4:31:27 PM 1 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FA2018-0005
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
CONTRACTOR COMTRON SYSTEMS P O BOX 13470 PALM DESERT CA 92255 JOHN@COMTRON1.CO
M
OWNER LQR GOLF 1 BUSH ST STE 1100 SAN FRANCISCO CA 94104
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
FUNCTION TEST EGO APPROVED
SPRINKLER MONITORING EGO APPROVED
FIRE FINAL**EGO APPROVED
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPRINKLER
SYSTEMS SUPERVISION
AND ALARMS
101-0000-42421 0 $156.00 $156.00 6/15/18 R36637 16432 CHECK COMTRON SYSTEMS AMA
FIRE SPRINKLER
SYSTEMS SUPERVISION
AND ALARMS PC
101-0000-42420 0 $234.00 $234.00 6/15/18 R36637 16432 CHECK COMTRON SYSTEMS AMA
Total Paid for FIRE FEES: $390.00 $390.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 6/15/18 R36637 16432 CHECK COMTRON SYSTEMS AMA
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 6/15/18 R36637 16432 CHECK COMTRON SYSTEMS AMA
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$405.00 $405.00
Printed: Wednesday, January 18, 2023 4:31:27 PM 2 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FA2018-0005
SPRINKLER MONITORING EGO 7/10/2018 7/10/2018 PARTIALLY
APPROVED
FIRE ALARM ROUGH WIRE INSPECTIONS
APPROVED.
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
REYNA
CAMARENA 6/15/2018 6/15/2018 6/15/2018 COMPLETE
1ST FIRE (2 WK)EDGAR
GONZALEZ 6/15/2018 6/29/2018 6/28/2018 REVISIONS REQUIRED
FIRE ALARM - WATERFLOW MONITORING
SYSTEM - PLAN REVIEWYour plans have been
reviewed by the Riverside County Fire Dept. and
require the following corrections listed below
before approval.1.) Please correct address on
plan. Actual site address on building plan is listed
as 55-965 PGA BLVD.2.) List control valve on
symbol legend or remove if it is not being
installed.3.) Correct node point 5 and 4 on plan.
Node point 5 is listed as a PIV tamper switch on
site yet node point 4 has listed information for
outside wiring on wire schedule. Please correct or
clarify. 4.) List node point 5 on wire schedule. 5.)
Show wire runs on plan. It should still be shown
on the "exploded view."6.) List battery(ies) that
will be utilized on install on FACP schematic. 7.)
Show fire alarm annunciator on FACP's exploded
view or remove and provide clarification on why
it is not being installed.
2ND FIRE (2 WK)EDGAR
GONZALEZ 6/29/2018 7/6/2018 7/3/2018 APPROVED-
CONDITIONS CORRECTIONS SUBMITTED BY COMTRON
PARENT PROJECTS
Printed: Wednesday, January 18, 2023 4:31:27 PM 3 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FA2018-0005
ATTACHMENTS
BOND INFORMATION
2ND FIRE (2 WK)EDGAR
GONZALEZ 6/29/2018 7/6/2018 7/3/2018 APPROVED-
CONDITIONS
FIRE ALARM/WATERFLOW MONITORING - PLAN
REVEIW - APPROVAL
The fire alarm plans you submitted for the above
referenced project have been reviewed by
Riverside County Fire Department - Office of the
Fire Marshal personnel and are approved with
the following conditions.
1.) A rough-wire inspections shall be conducted
before concealment of structural members for
wire verification.
2.) A function test is required on all installed
equipment is required to be witnessed by Fire
Department. All signals shall be verified before
final approval is granted.
3.) A document box is to be installed at FACP
panel with approved plan and equipment keys.
4.) Plan did not indicate communication method.
Fire alarm equipment is required to be monitored
by 2 phone lines or approved cell communicator.
If cell communicator is to be utilized, an as built
drawing shall be submitted before final for
review.
5.) All j-boxes and electric boxes serving fire
alarm system shall be red in color or labeled.
6.) Compartment/room containing fire alarm
equipment shall be labeled "FACP" on exterior
side.
7.) NFPA 72 Record of Completion shall be
provided at Final Inspection.