FA2018-0008ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT MAJESTIC FIRE INC DBA KORD FIRE
PROTECTI
5160 VAN NUYS BLVD
#257
SHERMAN OAKS CA 91403
BILL TO MAJESTIC FIRE INC DBA KORD FIRE
PROTECTI
5160 VAN NUYS BLVD
#257
SHERMAN OAKS CA 91403
CONTRACTOR MAJESTIC FIRE INC DBA KORD FIRE
PROTECTI
5160 VAN NUYS BLVD
#257
SHERMAN OAKS CA 91403
OWNER IMPERIAL IRRIGATION DIST P O BOX 987 IMPERIAL CA 92253
CONDITIONS
Description: IID / FIRE SPRINKLER MONITORING
Type: FIRE ALARM Subtype: COMMERCIAL -
SPRINKLER MONITORING
Status: FINALED Applied: 11/13/2018 AHI
Parcel No: 764010012 Site Address: 81600 AVENUE 58 LA QUINTA,CA 92253 Approved: 11/28/2018 EGO
Subdivision: Block: Lot: Issued: 12/4/2018 AHI
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 7/15/2021 KHET
Valuation: $0.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
FINANCIAL INFORMATION
Printed: Tuesday, January 24, 2023 10:48:38 AM 1 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FA2018-0008
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
FUNCTION TEST EGO 12/6/2018 12/6/2018 APPROVED
SPRINKLER MONITORING EGO 12/6/2018 12/6/2018 APPROVED
FIRE FINAL**EGO 12/6/2018 7/15/2021 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
PERMIT TECH
BUCKET 11/13/2018 11/14/2018 11/14/2018 COMPLETE
PARENT PROJECTS
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPRINKLER
SYSTEMS SUPERVISION
AND ALARMS
101-0000-42421 0 $160.00 $160.00 11/13/18 R41215 1074 CHECK KORD FIRE
PROTECTION AHI
FIRE SPRINKLER
SYSTEMS SUPERVISION
AND ALARMS PC
101-0000-42420 0 $240.00 $240.00 11/13/18 R41215 1074 CHECK KORD FIRE
PROTECTION AHI
FIRE STAFF - PER HOUR 101-0000-42420 0.25 $40.00 $40.00 2/27/19 R45635 060074 DEBIT JOSEPH MARTINEZ AMA
Total Paid for FIRE FEES: $440.00 $440.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 11/13/18 R41215 1074 CHECK KORD FIRE
PROTECTION AHI
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 11/13/18 R41215 1074 CHECK KORD FIRE
PROTECTION AHI
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$455.00 $455.00
Printed: Tuesday, January 24, 2023 10:48:38 AM 2 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FA2018-0008
11/28/2018
Martha Felix
1105N. Gene Autry
Palm Springs CA, 92262
Re: Fire Alarm System Plan Review – Imperial
Irrigation District
FA2018-0008
81-600 58th Ave.
La Quinta CA, 92253
The alarm plans you submitted for the above
referenced project have been reviewed by the
Riverside County Fire Department and are
approved with the following conditions:
1. For Central Station monitoring service, provide
written documentation, at the time of acceptance
testing, that there is a contract to provide the
runner and maintenance services as required per
NFPA 72.
2. The Office of the Fire Marshal staff shall
witness the following inspections/tests:
a) Rough-Wire Inspection – all wire not in conduit
is exposed for inspection.
b) Function Test / Start 24-hour Battery - The
alarm installer shall provide all needed testing
equipment to complete the final alarm
inspection. All fire alarm notification and
initiating appliances shall be tested in accordance
with NFPA 72.
c) 5-Minute Ring-out / Final Acceptance Testing
and Certification
3. Provide a completed NFPA 72 Record of
Printed: Tuesday, January 24, 2023 10:48:38 AM 3 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FA2018-0008
1ST FIRE (2 WK)EDGAR
GONZALEZ 11/13/2018 11/27/2018 11/28/2018 APPROVED-
CONDITIONS
Completion that the system has been installed in
accordance with the approved plans and
specifications as required.
4. Operating, testing, and maintenance
instructions, record drawings (“as builds”), site-
specific software and equipment specifications
shall be provided in a documentation cabinet in
compliance with NFPA 72 Section 7.7.2
5. A zone map indicating location of all initiating
devices shall be installed at an approved location.
6. All equipment keys shall be provided for
placement in building’s KNOX box systems for Fire
Department access.
7. All j-boxes and electric boxes serving fire alarm
system shall be red in color or labeled.
8. Compartment/room containing fire alarm
equipment that is capable of system operation
shall be labeled "FACP" on exterior side.
9. All signals witnesses at function testing shall be
verified before final approval is granted.
The Fire Department approved plans, job card
and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact
the Fire Department to schedule inspections.
Requests for inspections are to be made at least
72 hours in advance and may be arranged by
calling (760)777-7131.
SUBJECT TO FIELD INSPECTION - Nothing in our
review shall be construed as encompassing
Printed: Tuesday, January 24, 2023 10:48:38 AM 4 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FA2018-0008
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 11/28/2018 EDGAR GONZALEZ
FA2018-0008 - IID - 81-
600 58TH AVE - FIRE
ALARM (COA).docx
FA2018-0008 - IID - 81-
600 58TH AVE - FIRE
ALARM (COA).docx
1
DOC 1/5/2022 JULIA AGGREH
Fire Alarm System Plan
Review_Imperial
Irrigation District.pdf
Fire Alarm System Plan
Review_Imperial
Irrigation District.pdf
0
DOC 1/5/2022 JULIA AGGREH
Fire Review
Application_Paid 2 27
2019.pdf
Fire Review
Application_Paid 2 27
2019.pdf
0
DOC 1/5/2022 JULIA AGGREH
Fire Review
Application_Paid 11 13
2018.pdf
Fire Review
Application_Paid 11 13
2018.pdf
0
DOC 1/5/2022 JULIA AGGREH Specifications-Alarm
Products.pdf
Specifications-Alarm
Products.pdf 0
BOND INFORMATION
structural integrity. Review of this plan does not
authorize or approve any omission or deviation
from all applicable regulations. Final approval is
subject to field inspection.
All questions regarding the meaning of these
conditions should be referred to the Office of the
Fire Marshal staff at (760)777-7074.
Edgar Gonzalez
Fire Safety Specialist
1ST FIRE (1 WK)EDGAR
GONZALEZ 2/19/2019 2/26/2019 2/20/2019 APPROVED-
CONDITIONS CONDITIONS TO REMAIN.
Printed: Tuesday, January 24, 2023 10:48:38 AM 5 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FA2018-0008
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 1/5/2022 JULIA AGGREH
FA2018-0008 PLAN Copy
slight difference pg
2.pdf
FA2018-0008 PLAN Copy
slight difference pg
2.pdf
0
DOC 1/5/2022 JULIA AGGREH FA2018-0008 PLAN.pdf FA2018-0008 PLAN.pdf 0
Printed: Tuesday, January 24, 2023 10:48:38 AM 6 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FA2018-0008