FA2018-0029ADDITIONAL SITES
CHRONOLOGY
CONDITION
TYPE CONTACT DATE
ADDED
DATE
REQUIRED
DATE
SATISFIED STATUS REMARKS NOTES
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
NOTE ARMANDO MAGALLON 11/29/2018 11/29/2018
FEES FROM FEE SCHEDULE DO NOT MATCH. FINAL FEE WAS 1
DOLLAR OFF. CASHOVER WAS CREATED N ORDER TO TAKE IN
PAYMENT.
PLAN CHECK PICKED UP JACK LIMA 12/14/2018 12/14/2018 FIRE ALARM CORRECTIONS PICKED UP BY KEVIN SHEEHAN
FROM J CHASE BUILDERS.
PLAN CHECK SUBMITTAL
RECEIVED STEPHANIE SWANSTROM 1/24/2019 1/24/2019 1ST AS BUILT
RESUBMITTAL JACK LIMA 1/8/2019 1/8/2019 PLANS HAVE BEEN RESUBMITTED BY JASON MADRIGAL.
PLANS ARE LOCATED IN FIRE SHELVING UNIT.
CONDITIONS
Description: PLANET FITENES / BCOM2018-0035 / FIRE ALARM
Type: FIRE ALARM Subtype: COMMERCIAL - FIRE
ALARM SYSTEM
Status: FINALED Applied: 11/28/2018 AMA
Parcel No: 643020050 Site Address: 78987 HIGHWAY 111 LA QUINTA,CA 92253 Approved: 1/23/2019 EGO
Subdivision: PM 32683-1 Block: Lot: 6 Issued: 1/23/2019 AHI
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 1/31/2019 EGO
Valuation: $0.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details: FIRE ALARM FUNCTION TEST SCHEDULED FOR 1/28 AT 10:30. FIRE ALARM FINAL SCHEDULED FOR 1/29 AT 11:30.
Printed: Wednesday, January 18, 2023 4:45:25 PM 1 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FA2018-0029
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT MFS 491 HERNDON AVENUE
#2230
CLOVIS CA 93612 JASON@MFSALARM.C
OM
BILL TO MFS 491 HERNDON AVENUE
#2230
CLOVIS CA 93612
CONTRACTOR MFS 491 HERNDON AVENUE
#2230
CLOVIS CA 93612
OWNER OD LA QUINTA 80618 DECLARATION
AVE
INDIO CA 92253
READY TO ISSUE
CHECKLIST JACK LIMA 12/14/2018 PENDING
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
CASH OVER 101-0000-42300 0 $1.00 $1.00 11/28/18 R41753 5156 CHECK LORAYNE ANN
MADRIGAL AMA
Total Paid for CASH OVER: $1.00 $1.00
FIRE ALARM SYSTEMS 101-0000-42421 0 $480.00 $480.00 11/28/18 R41753 5156 CHECK LORAYNE ANN
MADRIGAL AMA
FIRE ALARM SYSTEMS
PC 101-0000-42420 0 $560.00 $560.00 11/28/18 R41753 5156 CHECK LORAYNE ANN
MADRIGAL AMA
Total Paid for FIRE FEES: $1,040.00 $1,040.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 11/28/18 R41753 5156 CHECK LORAYNE ANN
MADRIGAL AMA
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 11/28/18 R41753 5156 CHECK LORAYNE ANN
MADRIGAL AMA
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$1,056.00 $1,056.00
Printed: Wednesday, January 18, 2023 4:45:25 PM 2 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FA2018-0029
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
ROUGH-WIRE INSPECTION EGO 1/28/2019 1/28/2019 APPROVED
FUNCTION TEST EGO 1/28/2019 1/28/2019 DISAPPROVE
D
DUCT
DETECTORS/VELOCITY EGO 1/28/2019 1/28/2019 DISAPPROVE
D
24 HR. BATTERY TEST EGO 1/28/2019 1/28/2019 DISAPPROVE
D
SPRINKLER MONITORING EGO 1/28/2019 1/28/2019 DISAPPROVE
D
FIRE FINAL**EGO 1/29/2019 1/31/2019 APPROVED
FUNCTION TEST EGO 1/29/2019 1/31/2019 APPROVED
DUCT
DETECTORS/VELOCITY
EGO 1/29/2019 1/31/2019 APPROVED
24 HR. BATTERY TEST EGO 1/29/2019 1/31/2019 APPROVED
SPRINKLER MONITORING EGO 1/29/2019 1/31/2019 APPROVED
FIRE FINAL**EGO 1/29/2019 1/31/2019 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
ARMANDO
MAGALLON 11/28/2018 11/29/2018 11/29/2018 COMPLETE
1ST FIRE (2 WK)EDGAR
GONZALEZ 11/28/2018 12/12/2018 12/12/2018 REVISIONS REQUIRED SEE ATTACHED CORRECTIONS LETTER.
1/23/2019
PARENT PROJECTS
Printed: Wednesday, January 18, 2023 4:45:25 PM 3 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FA2018-0029
Jason Madrisal
MFS
491 Herndon #230
Clovis, CA 93612
Re: Planet Fitness – Fire Alarm Tenant
Improvement
FA2018-0029
78-987 Highway 111
La Quinta, CA 92253
The alarm plans you submitted for the above
referenced project have been reviewed by the
Riverside County Fire Department and are
approved with the following conditions:
1. For Central Station monitoring service, provide
written documentation, at the time of acceptance
testing, that there is a contract to provide the
runner and maintenance services as required per
NFPA 72.
2. The Office of the Fire Marshal staff shall
witness the following inspections/tests:
a) Rough-Wire Inspection – all wire not in conduit
is exposed for inspection.
b) Function Test / Start 24-hour Battery - The
alarm installer shall provide all needed testing
equipment to complete the final alarm
inspection. All fire alarm notification and
initiating appliances shall be tested in accordance
with NFPA 72.
c) 5-Minute Ring-out / Final Acceptance Testing
and Certification
3. Provide a completed NFPA 72 Record of
Completion that the system has been installed in
accordance with the approved plans and
specifications as required.
Printed: Wednesday, January 18, 2023 4:45:25 PM 4 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FA2018-0029
2ND FIRE (2 WK)EDGAR
GONZALEZ 1/8/2019 1/22/2019 1/23/2019 APPROVED-
CONDITIONS
4. Operating, testing, and maintenance
instructions, record drawings (“as builds”), site-
specific software and equipment specifications
shall be provided in a documentation cabinet in
compliance with NFPA 72 Section 7.7.2
5. A zone map indicating location of all initiating
devices shall be installed at an approved location.
6. All equipment keys shall be provided for
placement in building’s KNOX box systems for Fire
Department access.
7. All j-boxes and electric boxes serving fire alarm
system shall be red in color or labeled.
8. Compartment/room containing fire alarm
equipment that is capable of system operation
shall be labeled "FACP" on exterior side.
9. All electrical breaker circuit switches controlling
fire alarm power source shall be locked in the ON
position for the life of the system by an approved
lock-out assembly.
10. All signals witnesses at function testing shall
be verified before final approval is granted.
The Fire Department approved plans, job card
and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact
the Fire Department to schedule inspections.
Requests for inspections are to be made at least
72 hours in advance and may be arranged by
calling (760)863-8886.
Printed: Wednesday, January 18, 2023 4:45:25 PM 5 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FA2018-0029
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 12/12/2018 EDGAR GONZALEZ
FA2018-0029 - PLANET
FITNESS - 78-987 HWY
111 - FIRE ALARM
(CORRECTIONS).docx
FA2018-0029 - PLANET
FITNESS - 78-987 HWY
111 - FIRE ALARM
(CORRECTIONS).docx
1
DOC 1/23/2019 EDGAR GONZALEZ
FA2018-0029 - PLANET
FITNESS - 78-987 HWY
111 - FIRE ALARM
(COA).docx
FA2018-0029 - PLANET
FITNESS - 78-987 HWY
111 - FIRE ALARM
(COA).docx
0
BOND INFORMATION
SUBJECT TO FIELD INSPECTION - Nothing in our
review shall be construed as encompassing
structural integrity. Review of this plan does not
authorize or approve any omission or deviation
from all applicable regulations. Final approval is
subject to field inspection.
All questions regarding the meaning of these
conditions should be referred to the Office of the
Fire Marshal staff at (760)777-7074.
Edgar Gonzalez
Fire Safety Specialist
1ST FIRE (2 WK)EDGAR
GONZALEZ 1/24/2019 2/7/2019 1/31/2019 APPROVED 1ST: AS BUILT AS BUILTS APPROVED. CONDITIONS TO REMAIN.
Printed: Wednesday, January 18, 2023 4:45:25 PM 6 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FA2018-0029
Office of the Fire Marshal
City of La Quinta
78-495 Calle Tampico, La Quinta CA 92253
• Phone (760)777-7000 •Direct (760)777-7074
1/23/2019
Jason Madrisal
MFS
491 Herndon #230
Clovis, CA 93612
Re: Planet Fitness – Fire Alarm Tenant Improvement
FA2018-0029
78-987 Highway 111
La Quinta, CA 92253
The alarm plans you submitted for the above referenced project have been reviewed by the Riverside
County Fire Department and are approved with the following conditions:
1. For Central Station monitoring service, provide written documentation, at the time of acceptance testing, that
there is a contract to provide the runner and maintenance services as required per NFPA 72.
2. The Office of the Fire Marshal staff shall witness the following inspections/tests:
a) Rough-Wire Inspection – all wire not in conduit is exposed for inspection.
b) Function Test / Start 24-hour Battery - The alarm installer shall provide all needed testing equipment to
complete the final alarm inspection. All fire alarm notification and initiating appliances shall be tested in
accordance with NFPA 72.
c) 5-Minute Ring-out / Final Acceptance Testing and Certification
3. Provide a completed NFPA 72 Record of Completion that the system has been installed in accordance with the
approved plans and specifications as required.
4. Operating, testing, and maintenance instructions, record drawings (“as builds”), site-specific software and
equipment specifications shall be provided in a documentation cabinet in compliance with NFPA 72 Section
7.7.2
5. A zone map indicating location of all initiating devices shall be installed at an approved location.
6. All equipment keys shall be provided for placement in building’s KNOX box systems for Fire
Department access.
7. All j-boxes and electric boxes serving fire alarm system shall be red in color or labeled.
8. Compartment/room containing fire alarm equipment that is capable of system operation shall be
labeled "FACP" on exterior side.
9. All electrical breaker circuit switches controlling fire alarm power source shall be locked in the ON position for
the life of the system by an approved lock-out assembly.
10. All signals witnesses at function testing shall be verified before final approval is granted.
Office of the Fire Marshal
City of La Quinta
78-495 Calle Tampico, La Quinta CA 92253
• Phone (760)777-7000 •Direct (760)777-7074
The Fire Department approved plans, job card and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 72 hours in advance and may be arranged by calling (760)863-8886.
SUBJECT TO FIELD INSPECTION - Nothing in our review shall be construed as encompassing structural
integrity. Review of this plan does not authorize or approve any omission or deviation from all applicable
regulations. Final approval is subject to field inspection.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Edgar Gonzalez
Fire Safety Specialist
Office of the Fire Marshal
City of La Quinta
78-495 Calle Tampico, La Quinta CA 92253
• Phone (760)777-7000 •Direct (760)777-7074
12/12/2018
Jason Madrisal
MFS
491 Herndon #230
Clovis, CA 93612
Re: Planet Fitness – Fire Alarm Tenant Improvement
FA2018-0029
78-987 Highway 111
La Quinta, CA 92253
The Fire Alarm plans you submitted for the above referenced project have been reviewed by the
Riverside County Fire Department and are require revisions. Please review the corrections below
and re-submit your plans providing a response/clarifying/correcting the listed items:
1.) Floor plan (FA-2) is faint and not visible. Please adjust and resubmit with visible floor plan to
determine adequate fire alarm appliance location and coverage.
2.) Please adjust NAC 1’s circuit configuration and voltage drop calculation by adding one
additional 75 candela horn/strobe or clarify.
3.) A documentation cabinet is required per NFPA 72. Please make note on plan stating that one
will be installed.
All questions regarding the meaning of these corrections should be referred to the Office of the
Fire Marshal staff at (760)777-7074.
Edgar Gonzalez
Fire Safety Specialist