FA2019-0005ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT DESERT ALARM INC 73168 HWY 111 #204 PALM DESERT CA 92260 MANNY@DESERTALAR
M.COM
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
NOTE AARON HICKSON 4/15/2019 4/15/2019 INFORMED CONTRACTOR OF CONDITIONS AND AS BUILTS
NEEDED BEFORE FINAL
PLAN CHECK PICKED UP AARON HICKSON 4/1/2019 4/1/2019 MANUEL PUGA PICKED UP CORRECTIONS
PUBLIC COUNTER VISIT AARON HICKSON 4/10/2019 4/10/2019 ADDED CONTRACTORS EMAIL AND DID A TEST TO MAKE
SURE HE WAS GETTING UPDATES
RESUBMITTAL STEPHANIE SWANSTROM 4/9/2019 4/9/2019 ROUTED TO FIRE
CONDITIONS
Description: SPECTRUM / FIRE ALARM FOR TI BCOM2018-0047
Type: FIRE ALARM Subtype: COMMERCIAL - FIRE
ALARM SYSTEM
Status: FINALED Applied: 3/7/2019 JLIM
Parcel No: 600440006 Site Address: 79785 HIGHWAY 111 STE 103 LA QUINTA,CA 92253 Approved: 4/15/2019 EGO
Subdivision: PM 036269 Block: Lot: 6 Issued: 4/15/2019 AHI
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 7/15/2021 KHET
Valuation: $0.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
Printed: Wednesday, January 18, 2023 3:03:24 PM 1 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FA2019-0005
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
CONTRACTOR DESERT ALARM INC 73168 HWY 111 #204 PALM DESERT CA 92260 MANNY@DESERTALAR
M.COM
OWNER P6K PORTFOLIO KDP 2301 ROSECRANS STE
2110
EL SEGUNDO CA 92253
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
ROUGH-WIRE INSPECTION EGO 4/16/2019 5/10/2019 APPROVED
FUNCTION TEST EGO 4/16/2019 5/10/2019 APPROVED
ROUGH-WIRE INSPECTION EGO 4/17/2019 5/10/2019 APPROVED
FUNCTION TEST EGO 4/17/2019 5/10/2019 APPROVED
FIRE FINAL**EGO 4/18/2019 7/15/2021 APPROVED PER CALENDAR NOTES
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE ALARM SYSTEMS 101-0000-42421 0 $480.00 $480.00 3/7/19 MR686 33918 CHECK DESERT ALARM INC JLIM
FIRE ALARM SYSTEMS
PC 101-0000-42420 0 $560.00 $560.00 3/7/19 MR686 33918 CHECK DESERT ALARM INC JLIM
Total Paid for FIRE FEES: $1,040.00 $1,040.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 3/7/19 MR686 33918 CHECK DESERT ALARM INC JLIM
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 3/7/19 MR686 33918 CHECK DESERT ALARM INC JLIM
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$1,055.00 $1,055.00
Printed: Wednesday, January 18, 2023 3:03:24 PM 2 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FA2019-0005
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 3/26/2019 EDGAR GONZALEZ
FA2019-0005 -
SPECTRUM - 79-785
HWY 111 - FIRE ALARM
(CORRECTIONS).docx
FA2019-0005 -
SPECTRUM - 79-785
HWY 111 - FIRE ALARM
(CORRECTIONS).docx
1
DOC 4/15/2019 EDGAR GONZALEZ
FA2019-0005 -
SPECTRUM - 79-785
HWY 111 103 - FIRE
ALARM (COA).docx
FA2019-0005 -
SPECTRUM - 79-785
HWY 111 103 - FIRE
ALARM (COA).docx
1
BOND INFORMATION
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
JACK LIMA 3/7/2019 3/7/2019 3/7/2019
1ST FIRE (2 WK)EDGAR
GONZALEZ
3/7/2019 3/21/2019 3/26/2019 REVISIONS REQUIRED SEE CORRECTIONS LETTER.
2ND FIRE (2 WK)EDGAR
GONZALEZ 4/9/2019 4/23/2019 4/15/2019 APPROVED-
CONDITIONS
SEE CONDITIONS LETTER. AS BUILTS DUE BY
FINAL.
PARENT PROJECTS
Printed: Wednesday, January 18, 2023 3:03:24 PM 3 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FA2019-0005
Office of the Fire Marshal
City of La Quinta
78-495 Calle Tampico, La Quinta CA 92253
• Phone (760)777-7000 •Direct (760)777-7074
3/25/2019
Manny Puga
Desert Alarm
73-168 Hwy 111 Suite 104
Palm Desert, CA
Re: Spectrum
FA2019-0005
79-785 Highway 111
La Quinta, CA 92253
The Fire Alarm plans you submitted for the above referenced project have been reviewed by the
Riverside County Fire Department and are require revisions. Please review the corrections below
and re-submit your plans providing a response/clarifying/correcting the listed items:
1.) The structure does indeed have an existing fire sprinkler system. Please correct on plan.
2.) The structure already contains an existing fire alarm control panel. That existing panel may
either be upgraded to meet all tenant improvement needs or will have to be tied into existing
panel by a relay module or power supply unit for new notification appliance circuits.
3.) NAC wiring shall be properly accounted for on voltage drop calculations. Shows 14 AWG
while 16 AGW is noted on floor plan and other portion of plan. Please correct or clarify.
4.) Provide ceiling heights on floor plan.
All questions regarding the meaning of these corrections should be referred to the Office of the
Fire Marshal staff at (760)777-7074.
Edgar Gonzalez
Fire Safety Specialist
Office of the Fire Marshal
City of La Quinta
78-495 Calle Tampico, La Quinta CA 92253
• Phone (760)777-7000 •Direct (760)777-7074
4/15/2019
Manny Puga
Desert Alarm Inc.
73-168 Hwy 111 #204
Palm Desert, CA 92253
Re: Fire Alarm System Plan Review – Spectrum
FA2019-0005
79-785 Hwy 111 - 103
La Quinta, CA 92253
The alarm plans you submitted for the above referenced project have been reviewed by the Riverside
County Fire Department and are approved with the following conditions:
1. For Central Station monitoring service, provide written documentation, at the time of acceptance testing, that
there is a contract to provide the runner and maintenance services as required per NFPA 72.
2. The Office of the Fire Marshal staff shall witness the following inspections/tests:
a) Rough-Wire Inspection – all wire not in conduit is exposed for inspection.
b) Function Test / Start 24-hour Battery - The alarm installer shall provide all needed testing equipment to
complete the final alarm inspection. All fire alarm notification and initiating appliances shall be tested in
accordance with NFPA 72.
c) 5-Minute Ring-out / Final Acceptance Testing and Certification
3. Provide a completed NFPA 72 Record of Completion that the system has been installed in accordance with the
approved plans and specifications as required.
4. Operating, testing, and maintenance instructions, record drawings (“as builds”), site-specific software and
equipment specifications shall be provided in a documentation cabinet in compliance with NFPA 72 Section
7.7.2
5. A zone map indicating location of all initiating devices shall be installed at an approved location.
6. All equipment keys shall be provided for placement in building’s KNOX box systems for Fire
Department access.
7. All j-boxes and electric boxes serving fire alarm system shall be red in color or labeled.
8. Compartment/room containing fire alarm equipment that is capable of system operation shall be
labeled "FACP" on exterior side.
9. All electrical breaker circuit switches controlling fire alarm power source shall be locked in the ON position for
the life of the system by an approved lock-out assembly.
10. All signals witnesses at function testing shall be verified before final approval is granted.
Office of the Fire Marshal
City of La Quinta
78-495 Calle Tampico, La Quinta CA 92253
• Phone (760)777-7000 •Direct (760)777-7074
The Fire Department approved plans, job card and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 72 hours in advance and may be arranged by calling (760)863-8886.
SUBJECT TO FIELD INSPECTION - Nothing in our review shall be construed as encompassing structural
integrity. Review of this plan does not authorize or approve any omission or deviation from all applicable
regulations. Final approval is subject to field inspection.
AS BUILT DRAWINGS SHALL BE SUBMITTED BEFORE FIANL IS GRANTED!
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Edgar Gonzalez
Fire Safety Specialist