FA2019-0008ADDITIONAL SITES
CHRONOLOGY
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
NOTE ARMANDO MAGALLON 8/30/2019 8/30/2019 REVISION 1 HAS BEEN APPROVED AND ISSUED
NOTE KAYLI ALFORD 7/30/2019 7/30/2019
SPOKE TO KOHL REGARDING THE RESTRICTION FOR THE
SCOPE OF WORK. HE ADVISED OK TO ISSUE PERMIT AND
MAY REQUIRE REVISIONS UPON INSPECTION.
NOTE KAYLI ALFORD 7/30/2019 7/30/2019
JONATHAN PASTION CAME TO THE COUNTER TO PICK UP
PLANS AND JOB CARD. INFORMED HIM THAT WHILE THE
PERMIT WAS APPROVED WITH CONDITIONS, THERE IS A
RESTRICTION DUE TO THE SCOPE OF WORK BEING CHANGED.
HE STATED HE WOULD BE CONTACTING FIRE SAFETY
SPECIALIST KOHL AND PERMIT WAS NOT ISSUED.
Description: GRUNDER / BCOM2019-0030 / FIRE ALARM SYSTEM
Type: FIRE ALARM Subtype: COMMERCIAL - FIRE
ALARM SYSTEM
Status: FINALED Applied: 7/16/2019 JLIM
Parcel No: 770020023 Site Address: 78140 CALLE TAMPICO LA QUINTA,CA 92253 Approved: 7/30/2019 KAL
Subdivision: PM 27109 Block: Lot: 1 Issued: 7/30/2019 KAL
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 9/5/2019 crw
Valuation: $0.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details: FIRE ALARM SYSTEM FOR TENANT IMPROVEMENT
ADDING 5 HORNS TO 1ST LEVEL TI SPACES.
Printed: Wednesday, January 25, 2023 3:40:54 PM 1 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FA2019-0008
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT PASTION INDUSTRIES 45-450 TOWNE STREET INDIO CA 92201 (760)345-7088 JASON@PASTIONINDU
STRIES.COM
BILL TO PASTION INDUSTRIES 45-450 TOWNE STREET INDIO CA 92201 (760)345-7088
CONTRACTOR PASTION INDUSTRIES 45-450 TOWNE STREET INDIO CA 92201 (760)345-7088
OWNER PIERCE GROUP CALLE TAMPICO, LLC.78140 CALLE TAMPICO LA QUINTA CA 92253 (760)345-7088
CONDITION
TYPE CONTACT DATE
ADDED
DATE
REQUIRED
DATE
SATISFIED STATUS REMARKS NOTES
READY TO ISSUE
CHECKLIST JACK LIMA 7/16/2019 7/17/2019 7/17/2019 COMPLETE
1. PERMIT FEES OF $1056.00 NEED TO BE PAID.
2. CONTRACTOR BUSINESS LICENSE NEEDS TO BE
RENEWED.
ALL ABOVE ITEMS HAVE BEEN COMPLETED.
PUBLIC COUNTER VISIT JACK LIMA 7/16/2019 7/16/2019
PLANS SUBMITTED BY JASON PASTION. APPLICANT
SUBMITTED INCORRECT PERMIT AND FEES SUBMITTED.
UNPAID CHECK #3589 FOR $415.00 FROM PASTION
INDUSTRIES, INC. AND PLACED UNDER HUB COUNTER # 3.
ALSO, APPLICANT NEEDS TO RETURN CONTRACTOR BUSIENSS
LICENSE APPLICATION.
PUBLIC COUNTER VISIT JACK LIMA 7/17/2019 7/17/2019
BUSINESS LICENSE IS RENEWED AND I RETURNED INCORRECT
PAYMENT CHECK #3589 FOR $415.00 FROM PASTION
INDUSTRIES, INC. TO JASON PASTION AT THE COUNTER.
CONDITIONS
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE ALARM SYSTEMS 101-0000-42421 0 $481.00 $481.00 7/17/19 R51586 3591 CHECK JASON PASTION -
PASTION INDUST JLIM
Printed: Wednesday, January 25, 2023 3:40:54 PM 2 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FA2019-0008
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
ROUGH-WIRE INSPECTION KHET 8/16/2019 8/16/2019 APPROVED
FUNCTION TEST KHET 9/4/2019 9/4/2019 APPROVED
24 HR. BATTERY TEST KHET 9/5/2019 9/5/2019 APPROVED
FIRE FINAL**KHET 9/5/2019 9/5/2019 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
1ST FIRE (2 WK)KOHL
HETRICK 7/15/2019 7/29/2019 7/29/2019 APPROVED-
CONDITIONS
LETTER OF CONDITIONS IN ATTACHMENTS
LETTER OF CONDITIONS IN ATTACHMENTS
1ST PERMIT TECH (1
DAY)
PERMIT TECH
BUCKET 7/16/2019 7/17/2019 7/16/2019 COMPLETE COMPLETE
FEE MODIFIED TO REFLECT THE EXTRA $1.00 PER
FEE SCHEDULE. TOTAL PERMIT FEE IS $1056.00
AND NOT $1055.00 AS ORIGINALLY INDICATED.
PARENT PROJECTS
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE ALARM SYSTEMS
PC 101-0000-42420 0 $560.00 $560.00 7/17/19 R51586 3591 CHECK JASON PASTION -
PASTION INDUST JLIM
Total Paid for FIRE FEES: $1,041.00 $1,041.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 7/17/19 R51586 3591 CHECK JASON PASTION -
PASTION INDUST JLIM
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 7/17/19 R51586 3591 CHECK JASON PASTION -
PASTION INDUST JLIM
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$1,056.00 $1,056.00
Printed: Wednesday, January 25, 2023 3:40:54 PM 3 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FA2019-0008
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 7/29/2019 KOHL HETRICK
FA2019-0008 -
GRUNDER TI - FIRE
ALARM TI -
APPROVED.docx
FA2019-0008 -
GRUNDER TI - FIRE
ALARM TI -
APPROVED.docx
1
IMAGE 8/16/2019 KOHL HETRICK Spliced wire needs to be
in box.JPG
Spliced wire needs to be
in box.JPG 0
BOND INFORMATION
1ST PERMIT TECH (1
DAY)
PERMIT TECH
BUCKET 7/16/2019 7/17/2019 7/16/2019 COMPLETE COMPLETE APPLICANT PAID CORRECT FEE AND RENEWED
BUSINESS LICENSE.
1ST FIRE (1 WK)KOHL
HETRICK 8/20/2019 8/27/2019 8/28/2019 APPROVED
THIS REVIEW WAS INITIALLY CREATED IN PERMIT
NUMBER FSS2019-0077 BUT KOHL NOTICED THAT
IT WAS NOT A REVISION TO THE FIRE SPRINKLER
BUT THE FIRE ALARM. I VOIDED THE OTHER
REVIEW AND ADDED THIS ONE.
Printed: Wednesday, January 25, 2023 3:40:54 PM 4 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FA2019-0008
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
July 29, 2019
Pastion Industries, INC.
45-450 Towne St
Indio, CA 92201
Re: FA2019-0008 – GRUNDER DEVELOPMENT TI – FIRE ALARM TI
The Fire Alarm plans that you have submitted have been reviewed and approved with the following
conditions:
1. For Central Station monitoring service, provide written documentation, at the time of acceptance testing,
that there is a contract to provide the runner and maintenance services as required per NFPA 72.
2. The Office of the Fire Marshal staff shall witness the following inspections/tests:
a) Rough-Wire Inspection – all wire not in conduit is exposed for inspection.
b) Function Test / Start 24-hour Battery - The alarm installer shall provide all needed testing equipment to
complete the final alarm inspection.
c) 5-Minute Ring-out / Final Acceptance Testing and Certification
3. Provide a completed NFPA 72 Record of Completion that the system has been installed in accordance with the
approved plans and specifications as required.
4. Operating, testing, and maintenance instructions, record drawings (“as builds”), site-specific software and
equipment specifications shall be provided in a documentation cabinet in compliance with NFPA 72 Section 7.7.2
*Be advised, it was recently verbally stated that the scope of the Tenant Improvement has been reduced to no
longer include suites 101 and 103. Resubmittal of FA plans would be necessary upon confirmation/clarification
from the General Contractor.
The Fire Department approved plans, job card and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
Questions should be directed to the Riverside County Fire Department, Office of the Fire
Marshal, La Quinta Office at 78495 Calle Tampico, La Quinta, CA 92253.
Kohl Hetrick - Fire Safety Specialist