FA2020-0002ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT INTERFACE SYSTEMS 3750 SHAUFELE AVE
STE 200
LONG BEACH CA 90808 (562)353-4680 Kelley.SantaCruz@inte
rfacesys.com
CONTRACTOR INTERFACE SYSTEMS 3750 SHAUFELE AVE
STE 200
LONG BEACH CA 90808 (562)353-4680 Kelley.SantaCruz@inte
rfacesys.com
OWNER CMR CONSTRUCTION 23603 VIA PRIMERO VALENCIA CA 92253 (562)353-4680
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
NOTE KAYLI ALFORD 2/11/2020 2/11/2020 ISSUED PER JOB CARD ATTACHED BY KOHL - 2/7/20
CONDITIONS
Description: LA QUINTA MEDICAL - STE 140
Type: FIRE ALARM (WEB)Subtype: COMMERCIAL - FIRE
ALARM SYSTEM
Status: FINALED Applied: 1/16/2020 ECON
Parcel No: 643200004 Site Address: 47647 CALEO BAY #140 LA QUINTA,CA 92253 Approved: 2/7/2020 KHET
Subdivision: PM 27892 Block: Lot: 4 Issued: 2/7/2020 KAL
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 2/25/2020 crw
Valuation: $2,500.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
FINANCIAL INFORMATION
Printed: Wednesday, February 15, 2023 12:50:24 PM 1 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FA2020-0002
BOND INFORMATION
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
ROUGH-WIRE INSPECTION KHET 2/18/2020 2/18/2020 APPROVED
FIRE FINAL**KHET 2/25/2020 2/25/2020 APPROVED CONTRACTOR STATES FUNCTION & BATTERY
WERE SIGNED OFF AT ROUGH.
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
PERMIT TECH
BUCKET
1/16/2020 1/17/2020 1/17/2020 COMPLETE
1ST FIRE (2 WK)KOHL
HETRICK
1/16/2020 1/30/2020 2/7/2020 APPROVED SEE ATTACHMENTS
PARENT PROJECTS
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE ALARM SYSTEMS 101-0000-42421 0 $483.00 $483.00 1/16/20 WEB4488 CREDIT INTERFACE SYSTEMS ECON
FIRE ALARM SYSTEMS
PC 101-0000-42420 0 $564.00 $564.00 1/16/20 WEB4488 CREDIT INTERFACE SYSTEMS ECON
Total Paid for FIRE FEES: $1,047.00 $1,047.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 1/16/20 WEB4488 CREDIT INTERFACE SYSTEMS ECON
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 1/16/20 WEB4488 CREDIT INTERFACE SYSTEMS ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$1,062.00 $1,062.00
Printed: Wednesday, February 15, 2023 12:50:24 PM 2 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FA2020-0002
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 2/7/2020 KOHL HETRICK
FA2020-0002 - STE 140
TI - APPROVED
SPECS.pdf
FA2020-0002 - STE 140
TI - APPROVED
SPECS.pdf
1
DOC 2/7/2020 KOHL HETRICK
FA2020-0002 - STE 140
TI - APPROVED
PLANS.pdf
FA2020-0002 - STE 140
TI - APPROVED
PLANS.pdf
1
DOC 2/7/2020 KOHL HETRICK
FA2020-0002 - LQ MED
CTR 140 - FA TI - COA
and JOB CARD.pdf
FA2020-0002 - LQ MED
CTR 140 - FA TI -
APPROVED.pdf
1
Printed: Wednesday, February 15, 2023 12:50:24 PM 3 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FA2020-0002
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
February 7, 2020
Interface
3750 Schaufele #200
Long Beach, CA 90808
Re: Fire Alarm System Plan Review – La Quinta Medical – Ste 140 TI
FA2020-0002 / 47647 CALEO BAY, CA 92253
The fire alarm system plans you submitted for the above referenced project have been reviewed by
Riverside County Fire Department - Office of the Fire Marshal personnel and are approved with the
following conditions.
1. For Central Station monitoring service, provide written documentation, at the time of acceptance
testing, that there is a contract to provide the runner and maintenance services as required per NFPA 72.
2. The Office of the Fire Marshal staff shall witness the following inspections/tests:
a) Rough-Wire Inspection – all wire not in conduit is exposed for inspection.
b) Function Test / Start 24-hour Battery - The alarm installer shall provide all needed testing equipment to
complete the final alarm inspection.
c) 5-Minute Ring-out / Final Acceptance Testing and Certification
3. Provide a completed NFPA 72 Record of Completion that the system has been installed in accordance with the
approved plans and specifications as required.
4. Operating, testing, and maintenance instructions, record drawings (“as builds”), site-specific software and
equipment specifications shall be provided in a documentation cabinet in compliance with NFPA 72 Section
7.7.2
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Kohl Hetrick - Fire Safety Specialist
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
RIVERSIDE COUNTY FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 47647 CALEO BAY #140 PERMIT#: FA2020-0002 DATE
ISSUED: 2/7/2020
DESCRIPTION: FIRE ALARM TI CONTRACTOR: INTERFACE CSLB: 469046
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F Access & Address verification
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
**WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE**
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler
Systems)
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the
affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when
scheduling inspections. For City of La Quinta inspections call: (760) 777-7131.
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence
without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required
to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not
on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into
the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance
has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE
AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180
DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE
REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.