CONDITIONS
Description: ADD WIRELESS COMMUNICATOR TO EXISTING FIRE SYSTEM
Type: FIRE ALARM (WEB)Subtype: COMMERCIAL - FIRE
ALARM SYSTEM
Status: FINALED Applied: 2/12/2021 ECON
Parcel No: 604521009 Site Address: 44025 JEFFERSON ST LA QUINTA,CA 92253 Approved: 3/2/2021 KHET
Subdivision: Block: Lot: Issued: 3/2/2021 ONLINE
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 3/29/2021 KHET
Valuation: $300.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details: WATERFLOW MONITORING SYSTEM
FINANCIAL INFORMATION
Printed: Thursday, February 23, 2023 3:27:54 PM 1 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FA2021-0002
BOND INFORMATION
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
FUNCTION TEST KHET 3/29/2021 3/29/2021 APPROVED
FIRE FINAL**KHET 3/29/2021 3/29/2021 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST FIRE (2 WK)KOHL
HETRICK
2/12/2021 3/1/2021 3/2/2021 APPROVED SEE ATTACHMENTS
1ST PERMIT TECH (1
DAY)
PERMIT TECH
BUCKET
2/12/2021 2/16/2021 2/16/2021 COMPLETE
PARENT PROJECTS
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE STAFF - PER HOUR 101-0000-42420 1 $161.00 $161.00 3/2/21 WEB7523 002014 CREDIT STRATEX SOLUTIONS
INC ECON
Total Paid for FIRE FEES: $161.00 $161.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 3/2/21 WEB7523 002014 CREDIT STRATEX SOLUTIONS
INC ECON
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 3/2/21 WEB7523 002014 CREDIT STRATEX SOLUTIONS
INC ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$176.00 $176.00
Printed: Thursday, February 23, 2023 3:27:54 PM 2 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FA2021-0002
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 2/12/2021 EtrakitContractor
1ST SUBMITTAL FIRE
ALARM / SPRINKLER
MONITORING
JEFFERSON SQUARE
SHOP 3.pdf 1
DOC 2/12/2021 EtrakitContractor 1ST SUBMITTAL ALL CUT
SHEETS/ SFM LISTINGS Bldg. 3 Cut Sheets.pdf 1
DOC 3/2/2021 KOHL HETRICK FA2021-0002 - COA AND
JOB CARD.pdf
FA2021-0002 - COA AND
JOB CARD.pdf 1
DOC 3/2/2021 KOHL HETRICK FA2021-0002 -
APPROVED PLANS.pdf
FA2021-0002 -
APPROVED PLANS.pdf 1
DOC 3/2/2021 KOHL HETRICK Permit Details Permit Details.pdf 0
Printed: Thursday, February 23, 2023 3:27:54 PM 3 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FA2021-0002
SYSTEM ZONESMATERIAL LIST / LEGEND GENERAL NOTESBUILDING INFORMATIONPOINT TO POINT WIRING DIAGRAMRESET INSTRUCTIONFA1.0ST049-08NONERSP12-16-08P.O. #3469RSPCENTRAL STATION SERVICEFIRE ALARM SYSTEMS FORPROJECT NAME:LA QUINTA, CA 9225344025 JEFFERSON STREETJEFFERSON SQUARE1938 N Batavia St Unit ECALIFORNIA CONTRACTORS Orange CA 92865Tel. No. 714-456-9191 LICENSE#874378 (C-10)RAOUL STANDT(CONTACT PERSON)SHOPS -3 (SHELL BUILDING)1-800-662-1711WARNINGSAMPLE PLACARD (5" X 5")NATIONAL MONITORING CENTERSEQUENCE OF OPERATIONS-MATRIXTO110 VACJ1-+-+TB1TB2JP2J8J9J4J5TB5TB6TB7TB3MDF-300MMF-300Power Supply(SLE-ULPS-R)YellowTroubleLEDGreen ACON LED+ BAT –RED BLK6723451Black ( - )Red (+)Single 12V/7AhRechargeableBackup Battery0.5AFuse(wire tie)(wire tie)16.5VACClass 2IN1+ 12V -AC INNote: Maintainminimum 1/4"separation ofbattery leads fromall other wiring.J2Chassis Mounted 16.5VAC / 20VA TransformerBLKRelay contactsrated max30VDC, 1A12VDC output ispower limitedSLE-LTEVI-CFB-PSPC BoardAll connections are power limited exceptAC Mains, Telco and battery terminalsNote: Maintain minimum 1/4"separation of all wiring in this compartment from the yellowwires of the transformer.(Earth Ground)123PWR(-)45678(-)PGM3(+)IN1IN2(-)(+)IN3(-)(+)TELEPHONESECPRIM(RJ-45) (RJ-45)910IN4(-)(+)IN5(-)(+)EGND11 12 13ETHERNETOUT1C19 20 21(+)TO LOCALNETWORKN/CN/OOUT2C22 23 24N/C N/OEOLRJP1FACP8910N/CCOMN/OSpecial Requirements:Any failure of the communication path shall be annunciated at the central station within 60 minutes.Incomplete, corrupted, or other signal errors will be recorded and displayed at the central station.Communicator will resend message of receipt is not acknowledged by receiver at central station. "FaultData" will announce at central station if proper data is not received.The record and display rate of subsequent alarms will not be less than one every 10 seconds.Compatible with control panels that communicate using Contact ID format.Can use local or remote antennaInstalled in seperate enclosure connected to main alarm panel; has its own back-up batteriesSYSTEM INPUTSMISC.NOTIFICATIONCONTROL UNIT ANNUNCIATIONKJIHGFEDCBA321KJIHGFEDCBALL5MM694321564SYSTEM OUTPUTS1178911781010FIRE NOTES:FIRE ALARM CONTROL UNIT (FACU) STANDBY BATTERYCALCULATIONFACU EXTERNAL LOADEQUIPMENT MODELCIRCUIT# N1 CIRCUIT# N2 - -QTY. AMPS QTY. AMPS QTY. AMPS QTY. AMPSSCRL VISUAL 15cd (CEILING MOUNT)10.0410.041 1 0.041 0 0.000 0 0.000 0 0.000SCRL VISUAL 75cd (CEILING MOUNT)10.1110.111 1 0.111 0 0.000 0 0.000 0 0.000PC2RL HORN/VISUAL 75cd (CEILING MOUNT)10.1430.143 1 0.143 0 0.000 0 0.000 0 0.00030.295 A DISTANCE (FEET)70 FT 0 FT 0 FT 0 FT WIRE SIZE (AWG)14 AWG 14 AWG 14 AWG 14 AWG WIRE RESISTANCE (OHMS/1000 FT)3.07 3.07 3.07 3.07 TOTAL RESISTANCE (OHMS)0.4298 0 0 0 TOTAL CURRENT (mA)0.295 A 0.000 A 0.000 A 0.000 A VOLTAGE DROP (VOLTS)0.127 V 0 V 0 V 0 V % VOLTAGE DROP0.622% 0% 0% 0% OPERATING VOLTAGE (OPERATING VOLTAGE OF DEVICE IS 16 - 33 VDC)20.27 V 20.4 V 20.4 V 20.4 VTOTAL RESISTANCE = (2 x DISTANCE x WIRE RESISTANCE) / 1000VOLTAGE DROP = TOTAL CURRENT x TOTAL RESISTANCESTANDBY TIME24 HRS.ALARM TIME 5 MIN. = 0.083 HRS.TOTAL EXTERNAL LOAD (mA)0 0.295 A(1) CONTROL PANEL/DISPLAY0.12 A 0.2 A(1) MDF-300 ADDRESSABLE DUAL MONITOR MODULE0.00075 A 0 A(1) MMF-300 ADDRESSABLE MONITOR MODULE0.0004 A 0 A(1) SD355 ADDRESSABLE SMOKE DETECTOR0.0003 A 0 A(2) BG-12LX MANUAL PULL STATION (2 X 0.0003)0.0006 A 0 A(1) MMF-301 ADDRESSABLE MINI MONITOR MODULE0.0004 A 0 AALL ADDRESSABLE DEVICES (MAXIMUM)0 A 0.4 ATOTAL LOAD (AMPS)0.122 A 0.895 ACURRENT UNDER ALARM CONDITIONSBATTERIES REQUIRED FOR 24 HRS. IN SUPERVISION5 MIN. IN ALARMAH = (STANDBY TIME * SUPERVISORY CURRENT) + (ALARM TIME * ALARM TIME)(2) 12 VDC, 7 A.H. (24 VDC, 7 A.H. TOTAL) PROVIDEDDERATE BATTERY BY 20% (7 A.H. X 80% = 5.6 A.H.)BATTERY SPARE CAPACITY 5.6 A.H. - 3.002 A.H. = 2.598 A.H.WIRELESS FIRE ALARM COMMUNICATOR PANEL (WCP) STANDBY BATTERYBATTERY CALCULATIONS SLE-LTEVI-CFB-PS WIRELESS COMM. PANELEQUIPMENT MODEL QUANTITYSTANDBY CURRENT ALARM CURRENTUNITTOTALUNITTOTAL1 0.12500 0.125 0.12500 0.125SUB TOTAL 0.125 A SUB TOTAL 0.125 ASTANDBY 3.000000 AH STANDBY 24 HRS. ALARM 0.083 HRS.ALARM 0.013075 AH3.013075 AHREQUIRED (1) 12VDC, 7A.H. (12VDC, 7 A.H, TOTAL) PROVIDED DERATE BATTERY BY 20% (7 A.H. X 80% = 5.6 A.H.)BATTERY SPARE CAPACITY 5.6 A.H. - 3.013075 A.H. = 22.586925 A.H.(0.083 HRS. = 5 MIN)DRAWING INDEX03/31/2022CONDUIT FILL212222225341 COMMERCENTRE DR.LAKE FOREST, CA 92630NATIONAL MONITORING CENTERTel. No. 1-800-662-1711222BG-12LXMS-9050UDFIRE ALARM CONTROL PANELFIRE-LITE(24 VDC, 7 A.H. TOTAL)NOTE: (2) BATTERIESBATTERY(12VDC,7 AH)BATTERY(12VDC,7 AH)APPROVEDRiverside County Fire DepartmentLa Quinta Office of the Fire MarshalBy:FIRE SAFETY SPECIALIST03/02/2021 11:12:14 AMThe approval of plans and specifications does notpermit the violation, deletion, omission or faultyinstallation of any requirements of Title 24 or anyLocal Ordinances. Construction shall remainaccessible and exposed for inspection purposesuntil approved by the Fire Department.PERMIT # -FA2021-0002Kohl HetrickReason: I am approving this documentContact Info: 760-777-7074Date: 2021.03.02 11:12:52-08'00'
OPENINSTALLATION DETAILSFA2.0ST049-08AS NOTEDRSP12-16-08P.O. #3469RSPCENTRAL STATION SERVICE
FIRE ALARM SYSTEMS FOR1938 N Batavia St Unit ECALIFORNIA CONTRACTORS Orange CA 92865Tel. No. 714-456-9191 LICENSE#874378 (C-10)RAOUL STANDT(CONTACT PERSON)DRAWING LEGENDWIRE SCHEDULEINITIATING ZONE CALL-OUT LEGENDs c a l e : 1/18" = 1'-0"BUILDING FLOOR PLANNORTHFACPFIRE-LITELA QUINTA, CA 92253
44025 JEFFERSON STREET
JEFFERSON SQUARE
SHOPS -3 (SHELL BUILDING)11(MS9050UD)DRAWING LEGENDWCPNAPCO12
1
PROJECT NAME:25341 COMMERCENTRE DR.LAKE FOREST, CA 92630NATIONAL MONITORING CENTER
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
March 2, 2021
Stratex
1938 N Batabia St #E
Orange, CA 92865
Re: Monitoring Fire Alarm System Plan Review (Communicator Upgrade) – JEFFERSON SQUARE
SHOPS - 3
FA2021-0002 / 44025 JEFFERSON STREET, LA QUINTA, CA 92253
The fire alarm system plans you submitted for the above referenced project have been reviewed by
Riverside County Fire Department - Office of the Fire Marshal personnel and are approved with the
following conditions.
1. The Office of the Fire Marshal staff shall witness the following inspections/tests:
a) Function Test / Final Acceptance Testing and Certification
2. Provide a completed NFPA 72 Record of Completion that the system has been installed in accordance with the
approved plans and specifications as required.
3. Operating, testing, and maintenance instructions, record drawings (“as builds”), site-specific software and
equipment specifications shall be provided in a documentation cabinet in compliance with NFPA 72 Section
7.7.2
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Kohl Hetrick - Fire Safety Specialist
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
RIVERSIDE COUNTY FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 44025 JEFFERSON STREET PERMIT#: FA2021-0002 DATE
ISSUED: 3/2/2021
DESCRIPTION: COMMUNICATOR UPGRADE CONTRACTOR: STRATEX
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F Access & Address verification
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
**WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE**
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler
Systems)
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the
affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when
scheduling inspections. For City of La Quinta inspections call: (760) 777-7131.
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence
without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required
to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not
on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into
the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance
has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE
AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180
DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE
REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.