FNCUW2021-0004ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT JAMES A SHIRLEY CONSTRUCTION
INC
59160 MESA DRIVE YUCCA VALLEY CA 92284137
3
(760)228-0447 OFFICE@JASHIRLEYINC.
COM
BILL TO JAMES A. SHIRLEY CONSTRUCTION,
INC
P.O. BOX 555 WEWOKA OK 74884 (760)228-0447 BILLING@JASHIRLEYIN
C.COM
CONTRACTOR JAMES A SHIRLEY CONSTRUCTION
INC
59160 Mesa Dr.Yucca Valley CA 92284137
3
(760)228-0447 greg@jashirleyinc.com
OWNER SUNRISE LQ, LLC 300 EAGLE DANCE CIR PALM DESERT CA 92211 (760)228-0447
CONDITIONS
Description: TM 37790 LOT 42 SALES AND DESIGN CENTER/ PRIVATE FIRE LINE
Type: FIRE NEW COMMERCIAL
UNDERGROUND WATER (WEB)
Subtype: Status: FINALED Applied: 10/27/2021 ECON
Parcel No: 764200071 Site Address: 59140 MARBELLA LA QUINTA,CA 92253 Approved: 11/6/2021 KHET
Subdivision: TR 37790 Block: Lot: 42 Issued:
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 3/23/2022 KHET
Valuation: $10,000.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
FINANCIAL INFORMATION
Printed: Friday, February 24, 2023 2:25:22 PM 1 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FNCUW2021-0004
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
THRUST BLOCK PRE-POUR KHET 1/4/2022 1/4/2022 APPROVED
UG HYDRO KHET 1/5/2022 1/5/2022 APPROVED
UG ROUGH PIPING KHET 1/5/2022 1/5/2022 APPROVED NEED TO CHECK TORQUE
FLUSH KHET 1/5/2022 1/5/2022 APPROVED
FIRE FINAL**KHET 1/5/2022 1/5/2022 NOT READY SEE NOTES
*No Fees for reinspection
(1) Need FDC and Address Signage.
(2) Caps for FDC
(3) Completed and signed Contractor's
Material and Test Certificate. (Now Provided
- See Attachments)
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE NEW
COMMERCIAL -
UNDERGROUND
WATER
101-0000-42421 0 $500.00 $500.00 11/10/21 WEB9845 633538257
97 CREDIT 710357 ECON
FIRE NEW
COMMERCIAL -
UNDERGROUND
WATER PC
101-0000-42420 0 $417.00 $417.00 11/10/21 WEB9845 633538257
97 CREDIT 710357 ECON
Total Paid for FIRE FEES: $917.00 $917.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $11.00 $11.00 11/10/21 WEB9845 633538257
97 CREDIT 710357 ECON
Total Paid for RECORDS MANAGEMENT FEE: $11.00 $11.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 11/10/21 WEB9845 633538257
97 CREDIT 710357 ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$933.00 $933.00
Printed: Friday, February 24, 2023 2:25:22 PM 2 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FNCUW2021-0004
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 10/27/2021 Etrakit Contractor 1ST SUBMITTAL PLAN
21-0689 ANDALUSIA
SALES and DESIGN FIRE
SERVICE.pdf
1
DOC 11/6/2021 KOHL HETRICK FNCUW2021-0004 -
APPROVED PLANS.pdf
FNCUW2021-0004 -
APPROVED PLANS.pdf 1
DOC 11/6/2021 KOHL HETRICK FNCUW2021-0004 - COA
AND JOB CARD.pdf
FNCUW2021-0004 - COA
AND JOB CARD.pdf 1
DOC 1/10/2022 KOHL HETRICK
FNCUW2021-0004 -
CONTRACTOR CERT -
SIGNED.pdf
FNCUW2021-0004 -
CONTRACTOR CERT -
SIGNED.pdf
1
BOND INFORMATION
FIRE FINAL**LIN 3/8/2022 3/8/2022 NOT READY
FIRE FINAL**KHET 3/23/2022 3/23/2022 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
PERMIT TECH
BUCKET
10/27/2021 10/28/2021 10/27/2021 COMPLETE
1ST FIRE (2 WK)KOHL
HETRICK
10/27/2021 11/10/2021 11/6/2021 APPROVED SEE ATTACHMENTS
PARENT PROJECTS
Printed: Friday, February 24, 2023 2:25:22 PM 3 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FNCUW2021-0004
++VANACCESSIBLE ROUTEHCHCHC
EXISTING PARKING LOT 40 SPACES TOTAL(3) EXISTING ACCESSIBLE SPACES(1) VAN ACCESSIBLE 24A1.411111NOTE: PATH IS A GENERALCIRCULATION PATH ALLOWEDBY 11B-206.2.1 EXCEPTION 3FOR GENERAL MAINTENANCEAND EQUIPMENT MONITORING(FIRE RISER CLOSET) 11-203.524" MIN24" MIN7 -0"60 X 60 PAD12A1.0A15'-0"RECESSED ENTRYRECESSEDENTRYACCESSIBLE ROUTE4 -0 4 -0 7'-0 "LIMIT OF EXISTING SIDEWALKNEW SIDEWALK9'-0" 9'-0" 9'-0"5'-0"8 -0"4'-0"18'-0"EXISTING ACCESSIBLEPARKING, RESTRIPE PERATTACHED DIAGRAM, TYPICALEXISTING ACCESSIBLE SIGN TO REMAIN, TYP.LOT 42LOT 41LOT 40LOT 39LOT 43LOT 44EXISTING CURB20'-0"20'-0"20'-0"40'-0"19'-5"START PTFOR FOUNDATION12'-6 15/32"23'-8"60'-0"60'-0"59'-2"4'-0"4'-0"8'-0"FS 441.50EXISTINGFS 442.36FS 442.68FS 443.50FS 443.50442.38FFE 443.50FFE 443.50FFE 443.50FS 443.50FFE 443.502.3%2.3%2.3%1.0%3.5%3.5%4" C-900 CL-305 DR 14 UGD57'-0
48'-10½72'-0½46'-10½15'-957'-3110'-0½28'-5½4970sfSTATE APPROVEDCOMMERCIALMODULARMARBELLAEX. 8" PVC CVWD MAIN4" GATE VALVEAMES C500 4" BACKFLOW W/ FDCHYDRANTEX.(POINT OF FLOW TEST)(POINT OF CONNECTION 6"-12" ABOVE SLAB)4" FIRE RISERN12342-WAY FDC 4x2½x2½ w/ BRASS FACE PLATE4" WAFER CHECK VALVE4" D.I.EL: -194" AMES C500 RPDA4" C-900 PVCTO BLDG.4" D.I.PER NFPA (2 IN.)NFPA 24 & WT-014" C-900 PVCFROM CITY12" MIN
TAMPER DEVICES ON CONTROL VALVES CONSTANTLY MONITOREDCLEARANCE THRUST BLOCKS PER434" PVC C9004" STAINLESS STEELFROM ON-SITE U.G.4" STAINLESS STEELPOINT OF CONNECTION AT 6" FROM FINISHED FLOOR8" PVC CVWD MAIN2" ANNULAR CLEARANCETO BUILDINGEXTERIOR6'X6' AMES STAINLESS STEEL IN-BUILDING RISER 4" GROOVE X CAST IRON PIPE SIZE4" PVC C900THRUST BLOCKS PER NFPA 2436" MINFIRE HYDRANTTHRUST BLOCK (BY OTHERS)LEGENDVICINITY MAPFLOW TESTUNDERGROUND PIPING GENERAL NOTESFIRE SERVICE PLANSCALE: 1" = 20' 0"THE RECIPIENT OF THESE PLANS HEREBY ACKNOWLEDGES THAT ALL PLANS, DETAILS, SPECIFICATIONS AND/OR METHODS OF INSTALLATION CONTAINED IN THIS SET OF DRAWINGS IS THE SOLE PROPERTY OF SYMONS FIRE PROTECTION, INC., AND THAT ANY USE OF THIS SET OF DRAWINGS IS PROHIBITED AND IS A VIOLATION OF COPYRIGHT LAWS WITHOUT FIRST RECEIVING PERMISSION FROM SYMONSDATE-REVISIONSAS NOTEDMARKPHONE-MARBELLA LOT 42 & 43LA QUINTA, CACONTRACT WITH:FS1AUTHORITY HAVING JURISDICTIONDESCRIPTIONDRAWN BY: DEREK POWELLSCALE :PROJECT:ANDALUSIA SALES AND DESIGN CENTER(760) 564-2122-SHEET-21-0689JOBDATEDRAWING TITLE:LA QUINTA FIRE DEPARTMENT10-13-2021FIRE SERVICEBYSUNRISE LQ, LLCN1.Installation shall conform to N.F.P.A. 24 (2016 EDITION.) and the City Of LaQuinta regulations.2.Minimum depth of bury for underground piping to be 2'-6" in pedestrianareas. All piping under traffic areas to have a minimum bury of 3'-0" measuredfrom top of pipe.3.All underground piping, fittings, valves & equipment to be UL listed or FMapproved. Piping from 5'-0" outside the building foot print to be PVC C900.Piping within 5'-0" of building foot print to be Ames in-building riser.4.Excavation to proper depth for installation and backfill with native soils.compaction to 90% M.P.M. unless noted otherwise.5.Underground system to be flushed and hydrostatically tested at 200 psi or50 psi higher than the maximum system pressure for 2 hours per N.F.P.A. 24(10.10.2.2.1) before connection to sprinkler system. By installing contractor.6.Contractors material & test certification to be delivered upon inspection byinstalling contractor 7.Dimensions are approximate. Field verify all dimensions, and coordinate allinstallation with other trades and utilities.8.Thrust blocking shall be required at all changes of direction, restraining pipeadapters listed as a restraining adapter can be utilized in lieu of thrust blocks. 9.Pipe shall be installed with sand surrounding the pipe zone. see trenchdetails.10.All ferrous pipe and fittings below grade to be wrapped and coated. perN.F.P.A. 24 10.1.611.All fitting on PVC to be M.J. fittings with ductile iron gland, gasket, t-boltsand nuts or equal. Fittings attached to valves and transitions between PVC& ferrous piping are to be flange with mechanical joint adapters. 12.Underground piping to be C900 DR14 PVC. Exposed piping to be DuctileIron 52 pipe 13.All penetrations through slabs for in building feeding fire sprinkler risersshall require 2" annular clearance around the pipe. By installing contractor.14.Chain and lock and a tamper switch to be provided on backflow devicesby installing contractor at the time of installation. 15.Piping must be 1'-0" min. below the footing per NFPA 24(A.10.4.3.1.2)16. All required traffic control to be provided by installing contractor as wellas any traffic control plans.17.Point of connection and wet tap shown for reference only see additionaldetailed on civiL plan18.Fire sprinkler point of connection shall be 6"-12" max above slab.19.All onsite water and sewer facilities shown on this drawing are privateand shall be designed to meet requirements of the California uniformplumbing code and shall be reviewed as part of the building permit plancheckPRIVATE FIRE LINE CONTRACTORPRIVATE FIRE LINE CONTRACTORN.T.S.N.T.S.Cp=0.7APPROVEDRiverside County Fire DepartmentLa Quinta Office of the Fire MarshalBy:FIRE SAFETY SPECIALIST11/06/2021 6:04:31 AMThe approval of plans and specifications does notpermit the violation, deletion, omission or faultyinstallation of any requirements of Title 24 or anyLocal Ordinances. Construction shall remainaccessible and exposed for inspection purposesuntil approved by the Fire Department.PERMIT # -FNCUW2021-0004Kohl HetrickReason: I am approving this documentContact Info: 760-409-5109
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
November 6, 2021
James A Shirley Construction Inc.
59160 Mesa Drive
Yucca Valley, CA 92284
Re: Private Fire Main Plan Review – ANDALUSIA SALES CENTER
FNCUW2021-0004 / 59140 MARBELLA, LA QUINTA, CA 92253
The private fire main plans you submitted for the above referenced project have been reviewed by Riverside
County Fire Department - Office of the Fire Marshal personnel and are approved with the following
conditions.
The following inspections and tests must be observed:
1) Pre-Pour Thrust Block cutout inspection
2) Rough Piping / Hydrostatic Test
a. Confirm pipe material, bury depth and backfill requirements
b. Minimum 200 psi for two (2) hours or at 50 psi in excess of the maximum static pressure when it is in
excess of 150 psi.
3) Underground Flush & Final -
a. Flush of the underground supply line until clear of all debris and to the satisfaction of the
inspector.
b. The underground flush shall be done through a pipe or hose equal in size to the sprinkler underground
supply pipe, prior to connection to the above ground sprinkler piping.
c. Appropriate valve and connection signage is provided
d. Private fire hydrants are painted red and provided with OSFM tag.
e. Provide the completed Contractor’s Material and Test Certificate for Underground Pipe
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Kohl Hetrick - Fire Safety Specialist
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
RIVERSIDE COUNTY FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: PERMIT#: DATE
ISSUED:
DESCRIPTION: CONTRACTOR:
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F Access & Address verification
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
**WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE**
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler
Systems)
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the
affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when
scheduling inspections. For City of La Quinta inspections call: (760) 777-7131.
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence
without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required
to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not
on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into
the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance
has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE
AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180
DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE
REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.