Description: MONTAGE CONFERENCE CENTER/SHARED SERVICES PRIVATE FIRE MAIN
Type: FIRE NEW COMMERCIAL
UNDERGROUND WATER (WEB)
Subtype: Status: ISSUED Applied: 12/22/2021 ECON
Parcel No: 777490011 Site Address: 52049 SILVERROCK WY LA QUINTA,CA 92253 Approved: 1/26/2022 KHET
Subdivision: Block: Lot: Issued: 2/11/2022 JAG
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled:
Valuation: $30,000.00 Occupancy Type: Construction Type: Expired: 3/15/2023 KHET
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
FINANCIAL INFORMATION
Printed: Friday, February 24, 2023 2:30:47 PM 1 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FNCUW2021-0005
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
THRUST BLOCK PRE-POUR LIN 2/16/2022 2/16/2022 APPROVED SEE NOTES
021622- Paper plans on site indicated
ORANGE area of today's inspection. I
attached a photo of the plans and clouded
three revised areas. Changes are shown on
revised plans emailed to me and uploaded
into the file. Inspection approved for Rough
and PrePour.
UG HYDRO LIN 2/22/2022 2/22/2022 APPROVED
UG ROUGH PIPING LIN 2/22/2022 2/22/2022 APPROVED FNCUW permits use the Fire Sprinkler UG
inspection types. Voided and re-entered.
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE NEW
COMMERCIAL -
UNDERGROUND
WATER
101-0000-42421 0 $500.00 $500.00 2/11/22 WEB10699 635342221
99 CREDIT 953845 ECON
FIRE NEW
COMMERCIAL -
UNDERGROUND
WATER PC
101-0000-42420 0 $417.00 $417.00 2/11/22 WEB10699 635342221
99 CREDIT 953845 ECON
FIRE STAFF - PER HOUR 101-0000-42420 0.5 $83.50 $0.00
Total Paid for FIRE FEES: $1,000.50 $917.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $11.00 $11.00 2/11/22 WEB10699 635342221
99 CREDIT 953845 ECON
Total Paid for RECORDS MANAGEMENT FEE: $11.00 $11.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 2/11/22 WEB10699 635342221
99 CREDIT 953845 ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$1,016.50 $933.00
Printed: Friday, February 24, 2023 2:30:47 PM 2 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FNCUW2021-0005
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 12/22/2021 Etrakit Contractor 1ST SUBMITTAL PLANS
CALCS AND SPECS
2021.07.20 SW2019-
0002 PA 2 Private
Utilities 210609
Permited Plans R3
Contractor Permit
Submittal.pdf
1
DOC 1/26/2022 KOHL HETRICK
FNCUW2021-0005 - 1ST
SUBMITTAL - MATERIAL
SPECIFICATIONS.pdf
FNCUW2021-0005 - 1ST
SUBMITTAL - MATERIAL
SPECIFICATIONS.pdf
1
DOC 1/26/2022 KOHL HETRICK
FNCUW2021-0005 -
APPROVED - PLANS AND
CALCULATIONS.pdf
FNCUW2021-0005 -
APPROVED - PLANS AND
CALCULATIONS.pdf
1
DOC 1/26/2022 KOHL HETRICK
FNCUW2021-0005 -
PLANS FOR
INSPECTIONS.pdf
FNCUW2021-0005 -
PLANS FOR
INSPECTIONS.pdf
0
DOC 1/26/2022 KOHL HETRICK FNCUW2021-0005 - COA
AND JOB CARD.pdf
FNCUW2021-0005 - COA
AND JOB CARD.pdf 1
DOC 9/19/2022 KOHL HETRICK
2022.09.16 RDOC Letter
to COLQ for Permit
Extension.pdf
2022.09.16 RDOC Letter
to COLQ for Permit
Extension.pdf
1
BOND INFORMATION
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
PERMIT TECH
BUCKET
12/22/2021 12/27/2021 12/27/2021 COMPLETE
1ST FIRE (2 WK)KOHL
HETRICK 12/22/2021 1/11/2022 1/26/2022 APPROVED COA IN
ATTACHMENTS
PARENT PROJECTS
Printed: Friday, February 24, 2023 2:30:47 PM 3 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FNCUW2021-0005
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 2/16/2022 LUCERO INIGUEZ
FNCUW2021-0005
MONTAGE
CONFERENCE - UG
INSPECTION REDLINED
PLANS 021622.pdf
FNCUW2021-0005
MONTAGE
CONFERENCE - UG
INSPECTION REDLINED
PLANS 021622.pdf
0
DOC 2/16/2022 LUCERO INIGUEZ
Sewer Delta -
APPROVED MYLAR -
REVISED SW2019-
0002.pdf
Sewer Delta -
APPROVED MYLAR -
REVISED SW2019-
0002.pdf
1
Printed: Friday, February 24, 2023 2:30:47 PM 4 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FNCUW2021-0005
Installing Contractor:APPROVEDRiverside County Fire DepartmentLa Quinta Office of the Fire MarshalBy:FIRE SAFETY SPECIALIST01/26/2022 8:09:02 AMThe approval of plans and specifications does notpermit the violation, deletion, omission or faultyinstallation of any requirements of Title 24 or anyLocal Ordinances. Construction shall remainaccessible and exposed for inspection purposesuntil approved by the Fire Department.PERMIT # -FNCUW2021-0005PRIVATE FIRE MAIN - FOR INSTALLATIONKohl HetrickReason: I am approving this documentContact Info: 760-409-5109
P-187P-186P-185P-184P-183P-182P-180P-174P-173P-171P-168P-167P-163P-162P-160P-159P-158P-157P-156P-155P-153P-152P-149P -1 48P-147P-146P-145P-144P-143P-142P-140P-138P-137P-136P-135P-133P-131P-130P -1 2 9
P-128P-126P-124P-123P-122P -121P-119P-118P-114P-113P-112P-111P-110P-109P-108P-107P-105P -1 0 4 P-103P-101P-100P-99P-98P-97P-96P -95P-92P-84P-83P-82P-80P -79 P-78P-77P-76P-75P-74P-73P-72P-71P-70P-69P-68P-67P-64P-63P-62P-58P-57P-55P-54P-53P-15P-14P -1 2 P-11P-6P-3P-2P -2 4
P -2 3
P -2 2 P-5P-4P-8P-7P -9
P -1 0
P-49P -4 6
P-45P-44P-43P-42P-39P-34P-33P-29P-25P-21P -2 0 P-18P-17P-16J-5J-233J-4J-3J-121J-74J-231J-73J-230J-72J-71J-70J-133J-69J-68J-147J-145J-144J-67J-66J-143J-65J-132J-140J-148J-129J-137J-146J-126J-64J-63J-62J-125J-142J-61J-141J-131J-60J-139J-59J-138J-58J-136J-57J-135J-56J-134J-55J-PH2J-53J-124J-52J-130J-51J-122J-50J-128J-49J-127J-H2J-PH1J-SSJ-45J-44J-43J-123J-42J-41J-117J-39J-121J-114J-38J-113J-37J-120J-36J-119J-35J-118J-245J-97J-34J-116J-115J-105J-33J-112J-111J-110J-32J-247J-109J-31J-108J-107J-106J-30J-102J-29J-244J-234J-104J-243J-98J-28J-27J-89J-HSJ-95J-103J-94J-246J-101J-100J-99J-25J-24J-23 J-22J-21J-96J-20J-19J-18J-17J-16J-15J-14J-93J-232J-92J-91J-13J-90J-1J-88J-12J-87J-11J-86J-10J-85J-79J-84J-H1J-77J-82J-9J-CHJ-81J-8J-75J-80J-6J-14985 psi76 psi76 psi76 psi86 psi86 psi86 psi84 psi79 psi79 psi80 psi85 psi81 psi81 psi85 psi85 psi85 psi84 psi84 psi87 psi85 psi84 psi85 psi86 psi84 psi85 psi85 psi85 psi81 psi81 psi81 psi83 psi85 psi85 psi85 psi85 psi85 psi85 psi77 psi86 psi77 psi85 psi76 psi86 psi79 psi85 psi79 psi76 psi77 psi82 psi78 psi85 psi77 psi86 psi78 psi84 psi79 psi85 psi79 psi76 psi79 psi80 psi81 psi85 psi83 psi85 psi85 psi86 psi80 psi85 psi87 psi84 psi87 psi84 psi76 psi77 psi76 psi76 psi84 psi81 psi85 psi76 psi85 psi86 psi86 psi79 psi85 psi85 psi86 psi82 psi81 psi87 psi79 psi85 psi88 psi88 psi82 psi83 psi79 psi85 psi84 psi85 psi83 psi86 psi82 psi79 psi72 psi75 psi84 psi84 psi76 psi85 psi83 psi83 psi84 psi76 psi77 psi76 psi76 psi82 psi84 psi76 psi76 psi76 psi77 psi76 psi76 psi75 psi74 psi87 psi72 psi72 psi79 psi72 psi85 psi73 psi78 psi74 psi78 psi77 psi78 psi78 psi77 psi75 psi76 psi76 psi76 psi77 psi84 psi76 psi77 psi86 psi77 psi78 psi85 psiColor Coding LegendPipe: Diameter (in)<= 2.0<= 4.0<= 6.0<= 8.0<= 10.0<= 12.0<= 18.0OtherColor Coding LegendJunction: Pressure (psi)<= 20<= 30OtherSCENARIO 3:Shared Services-Fire flow of 2,750GPM split between 2 hydrantsFH 1 @J-125FH 1 @J-243
Label Diameter
(in)
Velocity
(ft/s) Length (ft)
Start
Node Stop Node
Hazen-
Williams C
Flow
(gpm)
Headloss
Gradient
(ft/ft)
P-73 2 7.61 11 J-61 GPV-25 130 74 0.127
P-74 2 7.61 12 GPV-25 J-64 130 74 0.127
P-182 2 7.53 11 J-244 GPV-36 130 74 0.125
P-183 2 7.53 12 GPV-36 J-245 130 74 0.125
P-75 2 7.52 11 J-60 GPV-26 130 74 0.125
P-76 2 7.52 13 GPV-26 J-63 130 74 0.125
P-185 2 7.52 12 J-246 GPV-37 130 74 0.125
P-186 2 7.52 12 GPV-37 J-247 130 74 0.125
P-77 2 7.51 11 J-41 GPV-27 130 74 0.124
P-78 2 7.51 12 GPV-27 J-62 130 74 0.124
P-33 2 7.44 27 J-29 GPV-21 130 -73 0.122
P-34 2 7.44 23 GPV-21 J-30 130 -73 0.122
P-42 2 7.42 30 J-33 GPV-23 130 -73 0.122
P-43 2 7.42 23 GPV-23 J-28 130 -73 0.122
P-29 2 7.42 23 J-21 GPV-20 130 73 0.122
P-30 2 7.42 27 GPV-20 J-27 130 73 0.122
P-38 2 7.39 27 J-31 GPV-22 130 -72 0.121
P-39 2 7.39 25 GPV-22 J-32 130 -72 0.121
P-52 12 4.72 194 J-40 J-37 130 1,666 0.007
P-178 2 4.59 13 J-233 GPV-31 130 45 0.05
P-179 2 4.59 12 GPV-31 J-234 130 45 0.05
P-85 2 4.58 12 J-65 GPV-28 130 45 0.05
P-86 2 4.58 14 GPV-28 J-66 130 45 0.05
P-87 2 4.57 13 J-42 GPV-29 130 45 0.05
P-88 2 4.57 13 GPV-29 J-67 130 45 0.05
P-155 6 4.19 105 J-64 J-70 130 369 0.012
P-100 2 3.98 14 J-74 GPV-30 130 39 0.038
P-101 2 3.98 15 GPV-30 J-121 130 39 0.038
P-152 12 3.9 175 J-123 J-125 130 1,375 0.005
P-150 12 3.9 31 J-122 J-133 130 1,375 0.005
P-151 12 3.9 214 J-133 J-123 130 1,375 0.005
P-181 12 3.9 132 J-243 J-37 130 -1,375 0.005
P-154 4 3.43 218 J-66 J-44 130 135 0.013
P-79 6 3.34 17 J-64 J-63 130 -295 0.008
P-14 6 3.3 132 J-12 J-6 130 -291 0.008
P-15 6 3.3 77 J-6 J-13 130 -291 0.008
P-40 6 3.3 17 J-1 J-28 130 291 0.008
P-104 6 3.3 108 J-33 J-13 130 291 0.008
P-57 4 3.29 130 J-49 J-50 130 129 0.012
P-58 4 3.29 124 J-50 J-51 130 129 0.012
P-72 4 3.29 144 J-70 J-49 130 129 0.012
P-2 4 3.02 118 J-121 J-3 130 -118 0.01
P-3 4 3.02 107 J-3 J-4 130 -118 0.01
P-6 4 3.02 76 J-8 J-9 130 -118 0.01
P-9 4 3.02 51 J-77 J-79 130 118 0.01
Scenario 3: Shared Services Pipe Table
P-7 4 3.02 67 J-9 J-80 130 -118 0.01
P-8 4 3.02 77 J-80 J-79 130 -118 0.01
P-4 4 3.02 98 J-4 J-81 130 -118 0.01
P-5 4 3.02 136 J-81 J-8 130 -118 0.01
P-115 4 3.02 31 J-91 J-92 130 -118 0.01
P-116 4 3.02 112 J-92 J-93 130 -118 0.01
P-117 4 3.02 201 J-93 J-94 130 -118 0.01
P-118 4 3.02 42 J-94 J-121 130 -118 0.01
P-59 4 2.91 138 J-52 J-53 130 114 0.01
P-92 4 2.91 186 J-70 J-71 130 114 0.01
P-93 4 2.91 87 J-71 J-72 130 114 0.01
P-94 4 2.91 63 J-72 J-52 130 114 0.01
P-62 4 2.91 94 J-PH1 J-57 130 -114 0.01
P-63 4 2.91 101 J-57 J-51 130 -114 0.01
P-66 4 2.91 58 J-53 J-59 130 114 0.01
P-67 4 2.91 193 J-59 J-PH2 130 114 0.01
P-16 4 2.8 91 J-15 J-14 130 -110 0.009
P-17 4 2.8 18 J-22 J-14 130 110 0.009
P-18 4 2.8 27 J-23 J-22 130 110 0.009
P-19 4 2.8 262 J-24 J-23 130 110 0.009
P-25 4 2.8 116 J-16 J-15 130 -110 0.009
P-47 4 2.8 83 J-36 J-24 130 110 0.009
P-110 4 2.8 133 J-16 J-87 130 110 0.009
P-111 4 2.8 95 J-87 J-88 130 110 0.009
P-112 4 2.8 157 J-88 J-89 130 110 0.009
P-113 4 2.8 59 J-89 J-90 130 110 0.009
P-114 4 2.8 77 J-90 J-91 130 110 0.009
P-80 6 2.51 14 J-63 J-62 130 -221 0.005
P-37 6 2.47 27 J-32 J-28 130 -218 0.004
P-41 6 2.47 25 J-33 J-31 130 -218 0.004
P-109 4 2.46 211 J-77 J-36 130 96 0.007
P-11 6 2.44 134 J-5 J-10 130 -215 0.004
P-12 6 2.44 64 J-10 J-11 130 -215 0.004
P-13 6 2.44 122 J-11 J-12 130 -215 0.004
P-10 6 2.44 19 J-77 J-5 130 -215 0.004
P-81 18 2.42 547 J-40 J-122 130 1,918 0.001
P-55 4 2.32 440 J-44 J-45 130 91 0.006
P-56 4 2.32 74 J-45 J-SS 130 91 0.006
P-105 4 1.94 114 J-12 J-82 130 76 0.005
P-106 4 1.94 54 J-82 J-H1 130 76 0.005
P-184 6 1.67 12 J-245 J-62 130 147 0.002
P-35 6 1.65 29 J-31 J-29 130 -146 0.002
P-36 6 1.65 29 J-30 J-32 130 -146 0.002
P-107 4 1.62 260 J-H1 J-84 130 63 0.003
P-108 4 1.62 67 J-84 J-HS 130 63 0.003
P-44 4 1.49 134 J-34 J-35 130 58 0.003
P-45 4 1.49 62 J-35 J-18 130 58 0.003
P-26 4 1.49 40 J-HS J-119 130 58 0.003
P-27 4 1.49 92 J-119 J-120 130 58 0.003
P-28 4 1.49 26 J-120 J-20 130 58 0.003
P-149 4 1.49 31 J-20 J-34 130 58 0.003
P-84 6 1.02 14 J-66 J-67 130 -90 0.001
P-102 4 1 346 J-121 J-147 130 39 0.001
P-103 4 1 215 J-147 J-CH 130 39 0.001
P-187 6 0.84 12 J-247 J-245 130 74 0.001
P-49 12 0.82 117 J-38 J-37 130 -291 0
P-89 12 0.82 210 J-38 J-68 130 291 0
P-90 12 0.82 176 J-68 J-69 130 291 0
P-91 12 0.82 377 J-69 J-39 130 291 0
P-50 12 0.82 9 J-1 J-95 130 -291 0
P-51 12 0.82 172 J-95 J-39 130 -291 0
P-31 6 0.82 30 J-29 J-27 130 -73 0.001
P-32 6 0.82 30 J-30 J-21 130 73 0.001
P-176 46 0.69 30 R-5 PMP-3 130 3,583 0
P-177 46 0.69 40 PMP-3 J-40 130 3,583 0
P-82 18 0.68 12 J-122 J-65 130 543 0
P-83 18 0.63 12 J-65 J-42 130 498 0
P-53 18 0.57 11 J-42 J-233 130 453 0
P-69 18 0.51 332 J-43 J-126 130 408 0
P-54 18 0.51 196 J-233 J-43 130 408 0
P-70 18 0.51 9 J-126 J-61 130 408 0
P-180 6 0.51 10 J-234 J-67 130 45 0
P-71 18 0.42 16 J-61 J-60 130 334 0
P-60 4 0.38 124 J-51 J-56 130 15 0
P-61 4 0.38 368 J-56 J-H2 130 15 0
P-20 4 0.34 49 J-19 J-25 130 13 0
P-21 4 0.34 216 J-18 J-19 130 13 0
P-46 4 0.34 33 J-25 J-36 130 13 0
P-68 18 0.33 14 J-60 J-41 130 260 0
P-95 18 0.23 12 J-41 J-244 130 186 0
P-96 18 0.14 11 J-244 J-246 130 113 0
P-97 18 0.05 352 J-246 J-73 130 39 0
P-98 18 0.05 10 J-73 J-74 130 39 0
P-146 12 0 321 J-116 J-117 130 1 0
P-145 12 0 116 J-148 J-116 130 1 0
P-142 12 0 127 J-113 J-114 130 1 0
P-143 12 0 398 J-114 J-115 130 1 0
P-144 12 0 45 J-115 J-148 130 1 0
P-148 12 0 101 J-117 J-98 130 1 0
P-122 12 0 179 J-98 J-99 130 1 0
P-123 12 0 251 J-99 J-100 130 1 0
P-124 12 0 60 J-100 J-101 130 1 0
P-125 12 0 24 J-101 J-102 130 1 0
P-129 12 0 300 J-104 J-105 130 1 0
P-130 12 0 101 J-105 J-106 130 1 0
P-131 12 0 72 J-106 J-107 130 1 0
P-127 12 0 59 J-102 J-230 130 1 0
P-128 12 0 265 J-230 J-104 130 1 0
P-138 12 0 189 J-110 J-111 130 1 0
P-135 12 0 160 J-107 J-231 130 1 0
P-136 12 0 218 J-231 J-232 130 1 0
P-137 12 0 70 J-232 J-110 130 1 0
P-140 12 0 258 J-111 J-149 130 1 0
P-141 12 0 306 J-149 J-113 130 1 0
P-168 12 0 34 J-75 J-138 130 0 0
P-170 12 0 251 J-144 J-139 130 0 0
P-169 12 0 162 J-138 J-144 130 0 0
P-171 12 0 64 J-139 J-140 130 0 0
P-65 4 0 69 J-58 J-55 130 0 0
P-64 4 0 140 J-53 J-58 130 0 0
P-172 12 0 83 J-140 J-141 130 0 0
P-174 12 0 323 J-142 J-143 130 0 0
P-173 12 0 187 J-141 J-142 130 0 0
P-175 12 0 352 J-143 J-113 130 0 0
P-147 8 0 53 J-117 J-118 130 0 0
P-156 12 0 22 J-126 J-134 130 0 0
P-99 18 0 8 J-74 J-75 130 0 0
P-157 12 0 110 J-134 J-127 130 0 0
P-132 8 0 161 J-107 J-108 130 0 0
P-126 8 0 48 J-102 J-103 130 0 0
P-121 12 0 204 J-97 J-98 130 0 0
P-167 12 0 108 J-136 J-137 130 0 0
P-134 8 0 62 J-109 J-7 130 0 0
P-133 8 0 141 J-108 J-109 130 0 0
P-139 8 0 175 J-111 J-112 130 0 0
P-166 12 0 231 J-146 J-136 130 0 0
P-162 12 0 195 J-131 J-132 130 0 0
P-158 12 0 421 J-127 J-128 130 0 0
P-161 12 0 495 J-130 J-131 130 0 0
P-153 12 0 337 J-125 J-124 130 0 0
P-164 12 0 126 J-135 J-145 130 0 0
P-160 12 0 45 J-127 J-130 130 0 0
P-165 12 0 104 J-145 J-146 130 0 0
P-163 12 0 23 J-73 J-135 130 0 0
P-159 12 0 152 J-128 J-129 130 0 0
P-120 12 0 116 J-96 J-97 130 0 0
P-22 4 0 65 J-18 J-85 130 0 0
P-23 4 0 100 J-85 J-86 130 0 0
P-24 4 0 94 J-86 J-17 130 0 0
P-119 12 0 67 J-95 J-96 130 0 0
Label Pressure
(psi)
Demand
(gpm)
Elevation
(ft)
Hydraulic
Grade (ft)
J-90 72 0 26.5 191.87
J-91 72 228 25 191.19
J-92 72 0 25 191.51
J-89 72 0 25 192.4
J-88 73 0 24.5 193.81
J-93 74 0 22 192.66
J-87 74 0 23.47 194.66
J-84 75 0 30 202.51
J-HS 75 5 29.33 202.29
J-14 75 0 23.4 197.69
J-15 76 0 22.35 196.88
J-119 76 0 27.65 202.18
J-57 76 0 28.9 203.57
J-94 76 0 19.9 194.72
J-121 76 0 20 195.16
J-PH1 76 114 27.47 202.66
J-81 76 0 23.2 198.47
J-22 76 0 22.5 197.85
J-PH2 76 114 27 202.37
J-3 76 0 20.94 196.36
J-19 76 0 25.66 201.18
J-4 76 0 21.65 197.47
J-16 76 0 20 195.84
J-120 76 0 26.06 201.92
J-77 76 0 26.6 202.65
J-23 76 0 21.85 198.1
J-18 76 45 24.9 201.22
J-25 76 0 24.83 201.18
J-35 76 0 24.83 201.39
J-34 76 0 25.2 201.77
J-82 76 0 27 203.59
J-20 76 0 25.15 201.85
J-5 76 0 26 202.73
J-H1 76 13 26.6 203.35
J-8 77 0 22.65 199.87
J-86 77 0 23.92 201.22
J-36 77 0 23.86 201.17
J-79 77 0 24.5 202.13
J-9 77 0 22.9 200.65
J-58 77 0 27 204.78
J-51 77 0 26.7 204.53
J-59 77 0 26 204.22
J-80 77 0 23 201.34
J-17 77 0 22.83 201.22
Scenario 3: Shared Service Junction Table
J-24 77 0 21.83 200.43
J-53 77 0 26 204.78
J-85 78 0 22 201.22
J-52 78 0 26 206.1
J-11 78 0 23 203.58
J-50 78 0 25.43 206.03
J-10 78 0 22.5 203.31
J-6 78 0 24 205.1
J-12 78 0 23 204.1
J-33 79 0 25 206.48
J-13 79 0 24.17 205.67
J-31 79 0 25 206.59
J-29 79 0 25 206.65
J-27 79 0 25 206.67
J-72 79 0 25 206.71
J-49 79 0 25.68 207.59
J-H2 79 15 22.5 204.42
J-56 79 0 22.5 204.51
J-71 79 0 25.4 207.54
J-55 79 0 22.5 204.78
J-SS 79 91 29.47 213.05
J-70 80 126 25.24 209.32
J-45 80 0 29 213.52
J-39 80 0 35 220.67
J-64 81 0 24 210.55
J-63 81 0 24 210.67
J-62 81 0 24 210.74
J-245 81 0 24 210.76
J-247 81 0 24 210.77
J-44 81 44 28.8 216.28
J-69 81 0 33 220.76
J-68 81 0 33 220.81
J-124 82 0 29.47 219.6
J-21 82 0 30 220.29
J-30 82 0 30 220.31
J-32 82 0 30 220.37
J-28 82 0 30 220.49
J-125 83 1,375 28.8 219.6
J-100 83 0 30 221.48
J-123 83 0 28.8 220.4
J-243 83 1,375 28 220.29
J-101 83 0 29 221.48
J-102 83 0 28.88 221.48
J-37 84 0 27.52 220.89
J-128 84 0 28 221.48
J-129 84 0 27.47 221.48
J-103 84 0 27.45 221.48
J-96 84 0 27 221.48
J-230 84 0 27 221.48
J-132 84 0 27 221.48
J-CH 84 39 25 219.84
J-38 84 0 26 220.86
J-99 84 0 26.6 221.48
J-118 84 0 26.5 221.48
J-66 84 0 24 219.12
J-67 84 0 24 219.13
J-234 84 0 24 219.13
J-95 84 0 25.39 220.62
J-112 85 0 26 221.48
J-131 85 0 26 221.48
J-1 85 0 25 220.62
J-147 85 0 24 220.12
J-127 85 0 25.24 221.48
J-111 85 0 25.2 221.48
J-142 85 0 25 221.48
J-149 85 0 25 221.48
J-137 85 0 25 221.48
J-130 85 0 25 221.48
J-134 85 0 25 221.48
J-104 85 0 24.85 221.48
J-108 85 0 24.5 221.48
J-97 85 0 24.17 221.48
J-133 85 0 24 221.38
J-116 85 0 24 221.48
J-136 85 0 24 221.48
J-139 85 0 24 221.48
J-140 85 0 24 221.48
J-141 85 0 24 221.48
J-144 85 0 24 221.48
J-145 85 0 24 221.48
J-146 85 0 24 221.48
J-246 85 0 24 221.48
J-244 85 0 24 221.48
J-41 85 0 24 221.48
J-60 85 0 24 221.48
J-61 85 0 24 221.48
J-126 85 0 24 221.48
J-43 85 0 24 221.5
J-233 85 0 24 221.51
J-42 85 0 24 221.51
J-65 85 0 24 221.51
J-121 85 0 23 220.57
J-122 86 0 23.71 221.52
J-117 86 0 23.5 221.48
J-98 86 0 23 221.48
J-138 86 0 23 221.48
J-231 86 0 23 221.48
J-135 86 0 23 221.48
J-148 86 0 22.9 221.48
J-115 86 0 22.54 221.48
J-110 86 0 22.45 221.48
J-74 86 0 22.4 221.48
J-75 86 0 22.4 221.48
J-73 86 0 22.4 221.48
J-105 86 0 22.12 221.48
J-232 87 0 21.5 221.48
J-40 87 0 22 222.16
J-114 87 0 21 221.48
J-109 87 0 20 221.48
J-143 87 0 20 221.48
J-113 87 0 19.9 221.48
J-7 88 0 19 221.48
J-107 88 0 17.99 221.48
J-106 88 0 17.15 221.48
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
January 26, 2022
R D Olson Construction Inc.
400 Spectrum Center Drive #1200
Irvine, CA 92618
R-3 Contractors Inc.
800 E Orangefair Lane
Anaheim, CA 92801
Re: Private Fire Main Plan Review – TALUS – SHARED SERVICES BUILDINGS
FNCUW2021-0005 / 52049 TALUS WAY, LA QUINTA, CA 92253
The private fire main plans you submitted for the above referenced project have been reviewed by Riverside
County Fire Department - Office of the Fire Marshal personnel and are approved with the following
conditions.
The following inspections and tests must be observed:
1) Pre-Pour Thrust Block cutout inspection
2) Rough Piping / Hydrostatic Test
a. Confirm pipe material, bury depth and backfill requirements
b. Minimum 200 psi for two (2) hours or at 50 psi in excess of the maximum static pressure when it is in
excess of 150 psi.
3) Underground Flush & Final -
a. Flush of the underground supply line until clear of all debris and to the satisfaction of the
inspector.
b. The underground flush shall be done through a pipe or hose equal in size to the sprinkler underground
supply pipe, prior to connection to the above ground sprinkler piping.
c. Appropriate valve and connection signage is provided
d. Private fire hydrants are painted red and provided with OSFM tag.
e. Provide the completed Contractor’s Material and Test Certificate for Underground Pipe
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Kohl Hetrick - Fire Safety Specialist
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
RIVERSIDE COUNTY FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 52049 Talus Way PERMIT#: FNCUW2021-0005 DATE
ISSUED: 1/26/2022
DESCRIPTION: PVT FIRE MAIN – SHARED SERVICES CONTRACTOR: R-3 CONTRACTORS INC.
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F Access & Address verification
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
**WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE**
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler
Systems)
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the
affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when
scheduling inspections. For City of La Quinta inspections call: (760) 777-7131.
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence
without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required
to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not
on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into
the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance
has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE
AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180
DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE
REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.
General Contractor
Construction Management
400 S PECTRUM C ENTER D RIVE, S UITE 1200, I RVINE, C ALIFORNIA 92618 T EL: 949-474-2001 WWW.RDOLSON.COM
Sent via email:aortega@laquinta.gov
September 16, 2022
AJ Ortega
Building Official – Design and Development Department
CITY OF LA QUINTA
78-495 Calle Tampico
La Quinta, California 92253
Re: Montage Hotel & Spa / Conference Center / Golf Clubhouse
REQUEST FOR PERMIT EXTENSION
Dear AJ,
R.D. Olson is requesting an extension of the following existing active permits due to the recent work
stoppage due to a lack of funding. We expect to be back on site working next week.
If you have any questions or need anything further, please reach out to Samantha Sheinberg at 714-920-
7537 or ssheinberg@rdolson.com and she can assist.
Respectfully,
R.D. OLSON CONSTRUCTION, INC.
John A. Ramirez
Senior Vice President of Operations
Cc: Jerry Bloom, Lang Naefke, Patrick Ready, Armando Alarcon, John Staff, Gary Hoskins, Jeremy
Dunn, Keith Freeman, Eduardo Paz
Specification Name:Utilites CSI Code:33 00 00 -002
Detail Description:Domestic Water & Fire Water, (OCC) Product Data/Sp Status:For Approval
Category:Product Data/Specifications Submittal Pkg. #:034
Date:11/19/2021 Due Date:11/26/2021
REVIEWED AND FORWARDED FOR APPROVAL
REVIEWED WITH EXCEPTIONS NOTED
NONCONFORMING, REVISED & RESUBMITTED
The Submittals have been reviewed for general conformation to the design
intent of the contract documents with regard to type and quality and not quantity
and/or dimensions, which are the responsibility of the subcontractor and/or
supplier making the submittal. The subcontractor and/or supplier is responsible
for coordination of their work with other trades. Review of submittals and/or
shop drawings does not relieve the subcontractor's and/or supplier's
responsibility for any errors, omissions and/or changes for the requirements of
the contract documents, nor for errors and/or omissions made by subcontractor
and/or supplier in bad submittals and/or shop drawings.
R.D. OLSON CONSTRUCTION
BY:Keith Freeman DATE:11/19/2021
JOB:Montage Conference Center, Meeting
Center and Shared Services Building
(210500)
SPEC:33 00 00 -002
Project Name:Montage Conference Center, Meeting Center and Shared Services Building Project Number: 210500
Comment:
330000-002.0 Domestic Water & Fire Water, (OCC) Product Data/Specifications
Submittal Transmittal
400 SPECTRUM CENTER DRIVE, SUITE 1200 IRVINE, CALIFORNIA 92618 TEL: 949-474-2001 WEBSITE: WWW.RDOLSON.COM
Page 1 of 1
11/23/21 (APPROVED)
161178
Rich Vaughn
X
SUBMITTAL REVIEW
NO EXCEPTIONS TAKEN.
MAKE CORRECTIONS AS NOTED. Resubmittal not required unless
Contractor cannot comply with corrections noted.
REVISE AS NOTED AND RESUBMIT.
RESUBMIT PROPERLY. Submittal not reviewed for reasons noted.
NOT REVIEWED. Submittal not required by Contract Documents.
RECEIVED FOR CLIENT’S RECORD ONLY. Submittal not reviewed.
Gensler has reviewed this Submittal, but only for the purpose of checking
for conformance with the design intent expressed in the Contract
Documents. Gensler’s action on a specific item does not indicate approval
of an assembly of which the item is a component, nor of an item as
delivered and installed if it does not conform to the Contract Documents.
Contractor is responsible for checking for deviations between this
Submittal and differing information or conditions in the Contract
Documents and field conditions; for determining or substantiating
the accuracy and completeness of other details such as dimensions and
quantities; for substantiating instructions for installation or performance
of equipment or systems designed by Contractor; for construction means,
methods, techniques, schedules, sequences, procedures, and fabrication
processes; for errors and omissions in Submittals; for coordination of the
Work of the trades, safety precautions and performing the Work in a safe
and satisfactory manner and in conformance with the Contract
Documents.
If more than one submittal review stamp appears on this Submittal, the
most stringent action and notations thereon apply. Signature of a
submittal review stamp by Gensler or a consultant does not imply that it
has reviewed work not within its professional discipline or scope of
services. v1 3/2012
By: Date:
Project No:
Submittal:
Seth Briskman Sun Dec 19, 2021
055.7598.000
330000-002.0 DomWtr&FireWa-MBI - Copy
/C/Users/92527/AppData/Local/Temp/Bluebeam Temp/
Together, Building the Future
A general engineering contractor specializing in
Underground Utilities, Drainage and Sump Pump Systems.
SUBMITTAL NO. 1
SEWER, WATER, FIRE, & STORM MATERIAL
SUBMITTAL
6/18/21
Re: 79179 AHMANSON LN.
LA QUINTA, CA 92253
www R3co.com
SEWER, WATER, FIRE, & STORM MATERIAL
SUBMITTAL
SEWER
• 10” ANSI/AWWA C900; VINYLTECH PVC PIPE, IPEX, JM
EAGLE, DIAMOND PLASTICS, NORTH AMERICAN PIPE
CORPORATION
• 4” & 6” ASTM D3034 SDR35/PS 46 PVC SEWER PIPE;
VINYLTECH PIPE, DIAMOND PLASTICS, JM EAGLE,
NORTH AMERICAN PIPE CORPORATION
• SDR35 D-3034/PS46 F-679 SEWER FITTINGS; GPK
PRODUCTS, INC.
• 10” VALVE BOX SERIES; EISEL EBTERPRISES INC.
WATER
• 4” ANSI/AWWA C900; VINYLTECH, IPEX, JM EAGLE,
DIAMOND PLASTICS, NORTH AMERICAN PIPE
CORPORATION
• 2” & 3” SCHEDULE 40 PVC PRESSURE PIPE; UNI BELL
PVC PIPE ASSOCIATION
• 4” A-2362 RW GATE VALVE FLG x FLG; MUELLER
COMPANY
• 6” A-2362 RW GATE VALVE FLG x FLG; MUELLER
COMPANY
• HEX BOLTS A307 GRADE A; WESTERN WATER WORKS
• TEADIT NA 1082SAN NSF61 APPROVED NON ASBESTOS
GASKET; ITP
• MARK VTB VALVE BOX SERIES; BINGHAM & TAYLOR
• PVC SCH 40 FITTINGS; LASCO FITTING, INC.
• 4” IMPORT DUCTILE IRON PUSH-ON COMPACT FITTINGS;
STAR PIPE PRODUCTS, SIP INDUSTRIES, SIGMA, TYLER
UNION
FIRE
• 1-1/2” SCHEDULE 40 PVC PRESSURE PIPE; UNI-BELL PVC
PIPE ASSOCIATION
• 6”, 8”, & 12” ANSI/AWWA C900; VINYLTECH PVC PIPE,
IPEX, JM EAGLE, DIAMOND PLASTICS, NORTH AMERICAN
PIPE CORPORATION
• HEX BOLTS A307 GRADE A; WESTERN WATER WORKS
• TEADIT NA 1082SAN NSF61 APPROVED NON ASBESTOS
GASKET; IPT
• 6” A-2362 RW GATE VALVE FLG X FLG; MUELLER
COMPANY
• 8” A-2362 RW GATE VALVE FLG X FLG; MUELLER
COMPANY
• 10” A-2362 RW GATE VALVE FLG X FLG; MUELLER
COMPANY
• 6” & 12” IMPORT DUCTILE IRON FLANGED FITTINGS;
STAR PIPE PRODUCTS, SIP INDUSTRIES, SIGMA, TYLER
UNION
• 4” IN-BUILDING RISER; AMES FIRE & WATER WORKS,
ZURN WILKINS
• J-4000 TRITON SERIES DUCTILE IRON HYDRANTS;
MUELLER COMPANY, JONES
• 6” CLOW LBI 400A BREAK-OFF CHECK VALVE; CLOW
VALVE
• 6” x 42” PUSH-ON HYDRANT BURYS; WESTERN WATER
WORKS
• 6” & 12” PRESSURE CLASS 350 TYTON-JOINT PIPE; US
PIPE
• 6”, 8”, & 12” IMPORT DUCTILE IRON PUSH-ON COMPACT
FITTINGS; STAR PIPE PRODUCTS, SIP INDUSTRIES,
SIGMA, TYLER UNION
• FIELD LOK 350 GASKETS; US PIPE
• HEX BOLTS GRADE 5 & 8; WESTERN WATER WORKS
• 6”, 8”, & 12” ANSI/AWWA C900; VINYLTECH PVC PIPE,
IPEX, JM EAGLE, DIAMOND PLASTICS, NORTH AMERICAN
PIPE CORPORATION
• MARK VTB VALVE BOX SERIES; BINGHAM & TAYLOR
STORM
• 18” CATCH BASIN GRATE SERIES; NDS
• 18” CATCH BASIN FRAME; NDS
• 9” CATCH BASIN; NDS
• BRASS & CHROME GRATES; NDS
• SPEE-D BASINS; NDS
• 4”, 6”, & 12” HDPE PIPE; PRINSCO, ADS
• 4”, 6”, & 12” HDPE FITTINGS; PRINSCO, ADS
• HARCO DRAIN BASIN STANDARD DETAIL; THE
HARRINGTON CORPORATION
FIRE
Smooth Running Jobs
PVC Pipe
SCHEDULE 40 PVC PRESSURE PIPE
General Information:
Product Standard: ASTM D1785, ASTM D2665
Pipe Compound: ASTM D1784 Cell Class 12454
Certification: ANSI/NSF 61, ANSI/NSF 14* Uniform Plumbing Code*
Pipe End Finish: Bell End*, Plain End Nominal Laying Length: 10/20 feet
(Laying length tolerances are in accordance
with ASTM standards)
Installation: Manufacturers Solvent Weld Installation Guide
Water pressure rating measured at 23°C (73°F)
Manning Coefficient (n) = 0.009
Hazen-Williams Coefficient (c) = 150
Available Size: 1/2"- 4"
Product Standard: ASTM D1785 Certification: ANSI/NSF 61
Pipe End Finish: Bell End
PVC PRESSURE PIPE
ANSI/AWWA C900
UL 1285
FM 1612**
*See Certification Letter for full explanation and list of exceptions.
**FM 1612 calculates pressure ratings differently than AWWA for
4"-12" only with DR 18 as 185 psi and DR 14 as 250 psi.
‡See Installation Guide for more information.
Pipe Standard:AWWA C900-16
Diameter Std.:Cast Iron Outside Diameter (CIOD)
Nominal Sizes:4", 6", 8", 10", 12", 14", 16",
18", 20", 24", 30", 36"
Dimension Ratios
& Pressure
Ratings:
DR 51 – 80 psi
DR 41 – 100 psi
DR 32.5 – 125 psi
DR 25 – 165 psi
DR 21 – 200 psi
DR 18 – 235 psi
(185 psi)**
DR 14 – 305 psi
(250 psi)**
Lay Length:20' [6.1m]
Pipe Compound:ASTM D1784 Cell Class 12454
Pipe Joint Std.:ASTM D3139
Max. Angular
Joint Deflection:‡1°
Gasket Standard:ASTM F477, UL 157
Gasket Material
Offerings:
Standard – SBR
Optional – NBR or EPDM
Installation Std.:AWWA C605
Color:Blue Green Purple
Certifications:*
NSF 14
NSF 61
CSA B137.3 CSA B137.3 CSA B137.3
Applications
Potable
Water
Waste-
water
Reclaimed
Water
Only products
bearing the NSF
Mark are Certified
Short Form Specification MARKING
The pipe shall be marked in accordance with AWWA C900.
QUALITY CONTROL
Each length of the pipe including the bell shall be hydrostatically
tested in accordance with AWWA C900. The pipe shall meet all
additional test requirements as described in AWWA C900.
Manufacturers full-time quality assurance staff continually
administers a rigid program of tests to maintain the production
of the best pipe products available.
INSTALLATION
Instruction procedures are outlined in AWWA C605,
Underground Installation of Polyvinyl Chloride (PVC) Pressure
Pipe and Fittings for Water. The AWWA Manual M23, PVC Pipe
Design and Installation, is also an invaluable resource guide for
design and installation.
TAPPING
The consistent success of tapping PVC pressure pipe is
contingent upon the use of proper procedures and equipment.
Strict compliance with the requirements as specified in AWWA
C605.
ASSEMBLING THE PIPE
Assembly of PVC water pipe is easily accomplished. A depth of
entry mark is on each spigot end to serve as a visual check for
rapid, accurate joint inspection. Do not over insert.
Smooth Running Jobs
BOLTS & NUTS
Smooth Running Jobs
HEX BOLTS A307 GRADE A
SUBMITTAL SPECIFICATIONS
ABSTRACT OF ASTM A307 GRADE A
GRADE: Low Carbon Steel 60,000 PSI
CHEMICAL REQUIREMENTS
Chemical analysis shall be performed in accordance with ASTM A751
CARBON
MAX
MANGANESE
MAX
PHOPHOROUS
MAX
SULFER
MAX
0.29 1.20 0.04 0.15
MECHANICAL REQUIREMENTS
HARDNESS
BRINEL
MIN MAX
HARDNESS
ROCKWELL
MIN MAX
TENSILE STRENGTH
(KSI)
MIN MAX
ELONGATION
IN 2 IN (50MM)
MIN
121 241 69 100 60 - 18
Hex Nuts ASTM A563 (ASME B18.2.2) Heavy Hex Nuts ASTM A563 (ASME B18.2.2)
Washers ASTM F844-04 (ASME B18.22.1)
FINISH
Plain Zinc Plated per
ASTM B633
Hot Dip Galvanized
Per ASTM A153
Cadmium Plated
DIMENSIONAL DATA: Unless otherwise specified in the purchase order, parts shall be the coarse
threaded series as specified in the latest issue of ANSI / ASME B1.1, page A-26. Having a 2A tolerance.
Grade A Bolts shall have Hex Bolt Dimensions as given in the latest issue of ANSI / ASME B 18.2.1,
Page C1. Unless otherwise specified Grade A Bolts should be used with Hex Nuts.
ADDITINOAL INFORMATION: Additional information can be found in ASTM A307A-07B,,
ASTM A563-04A
FLANGE GASKETS
TEADIT NA 1082SAN NSF61 APPROVED
NON ASBESTOS GASKET
Smooth Running Jobs
SUBMITTAL SPECIFICATIONS
GASKETS MEET THE PRESSURE RATINGS, DRILLING AND DIMENSIONS OF ANSI/ASME B16.21
AND AWWA C111 NSF 61 CERTIFIED FOR CHLORINATED POTABLE WATER
TECHNICAL DATA
MANUFACTURES STYLE COLOR BINDER TEMP
MAX
HARDNESS
SHORE A
TENSILE
STRENGTH
ASTM F-
152
ELONGATION APPLICATION CERTIFICATION MATERIAL
Teadit. NA1082SAN Blue Proprietary 752 N/A 1885 N/A Potable Water
Systems
NSF 61 Non
Asbestos
Full Face Ring 1/16” 1/8”
GENERAL DESCRIPTION: Teadit style NA1002SAN is specifically formulated to pass criteria established
in NSF-61 for sealing materials, as well as providing excellent resistance to conductivity.
** Domestically manufactured in the USA**
GATE VALVES
2"-12" A-2362 RW GATE VALVES FLG X FLG
This information is based on the best data available at the date printed above. Please check with www.muellercompany.com for any updates or changes.
6" FLG x FLG RW
GATE VALVE OPEN
LEFT NDZ STEM T316
SS HARDWARE
Smooth Running Jobs
SPECIFICATIONS:
Meets or exceeds all applicable requirements of ANSI/AWWA C509 and C515, UL
Listed, FM Approved, and certified to ANSI/NSF 61 & 372.
Standard Flanged Ends (2” thru 12”) with flange drilling complying to ANSI B16.1
Class 125
Ductile Iron body with nominal 10 mils MUELLER® Pro-Gard® Fusion Epoxy
Coated interior and exterior surfaces
Epoxy coating meets or exceeds all applicable requirements of ANSI/AWWA
C550 Standard and is certified to ANSI/NSF Standard 61 & 372†
Ductile Iron wedge, symmetrical & fully encapsulated with molded *EPDM Rubber;
no exposed iron
Stem non-rising (NRS) Manganese **Bronze, ASTM B138 Alloy C67600
Triple O-ring seal stuffing box (2 upper & 1 lower O-rings) with fourth o-ring serving
as dirt seal *EPDM Rubber
2" square wrench nut-open left
*Bolts & Nuts for stuffing box and bonnet Type 316 Stainless Steel
350 psig (2400 kPa/24 barg) maximum working pressure,
700 psig (4800 kPa/48 barg) static test pressure
UL Listed, FM Approved: 350 psig (2400 kPa/24 barg)
Mueller valves are designed for potable water application
**Bronze components meet current lead-free requirements
A-2362-6 *E381
MANUFACTURED IN
THE U.S.A.
Shown with optional hand wheel
† Approved for backflow prevention devices by USC (for 4” - 10” sizes)
GATE VALVES
2"-12" A-2362 RW GATE VALVES FLG X FLG
This information is based on the best data available at the date printed above. Please check with www.muellercompany.com for any updates or changes.
8" FLG x FLG RW
GATE VALVE OPEN
LEFT NDZ STEM T316
SS HARDWARE
Smooth Running Jobs
SPECIFICATIONS:
Meets or exceeds all applicable requirements of ANSI/AWWA C509 and C515, UL
Listed, FM Approved, and certified to ANSI/NSF 61 & 372.
Standard Flanged Ends (2” thru 12”) with flange drilling complying to ANSI B16.1
Class 125
Ductile Iron body with nominal 10 mils MUELLER® Pro-Gard® Fusion Epoxy
Coated interior and exterior surfaces
Epoxy coating meets or exceeds all applicable requirements of ANSI/AWWA
C550 Standard and is certified to ANSI/NSF Standard 61 & 372†
Ductile Iron wedge, symmetrical & fully encapsulated with molded *EPDM Rubber;
no exposed iron
Stem non-rising (NRS) Manganese **Bronze, ASTM B138 Alloy C67600
Triple O-ring seal stuffing box (2 upper & 1 lower O-rings) with fourth o-ring serving
as dirt seal *EPDM Rubber
2" square wrench nut-open left
*Bolts & Nuts for stuffing box and bonnet Type 316 Stainless Steel
350 psig (2400 kPa/24 barg) maximum working pressure,
700 psig (4800 kPa/48 barg) static test pressure
UL Listed, FM Approved: 350 psig (2400 kPa/24 barg)
Mueller valves are designed for potable water application
**Bronze components meet current lead-free requirements
A-2362-6 *E381
MANUFACTURED IN
THE U.S.A.
Shown with optional hand wheel
† Approved for backflow prevention devices by USC (for 4” - 10” sizes)
GATE VALVES
2"-12" A-2362 RW GATE VALVES FLG X FLG
This information is based on the best data available at the date printed above. Please check with www.muellercompany.com for any updates or changes.
10" FLG x FLG RW
GATE VALVE OPEN
LEFT NDZ STEM T316
SS HARDWARE
Smooth Running Jobs
SPECIFICATIONS:
Meets or exceeds all applicable requirements of ANSI/AWWA C509 and C515, UL
Listed, FM Approved, and certified to ANSI/NSF 61 & 372.
Standard Flanged Ends (2” thru 12”) with flange drilling complying to ANSI B16.1
Class 125
Ductile Iron body with nominal 10 mils MUELLER® Pro-Gard® Fusion Epoxy
Coated interior and exterior surfaces
Epoxy coating meets or exceeds all applicable requirements of ANSI/AWWA
C550 Standard and is certified to ANSI/NSF Standard 61 & 372†
Ductile Iron wedge, symmetrical & fully encapsulated with molded *EPDM Rubber;
no exposed iron
Stem non-rising (NRS) Manganese **Bronze, ASTM B138 Alloy C67600
Triple O-ring seal stuffing box (2 upper & 1 lower O-rings) with fourth o-ring serving
as dirt seal *EPDM Rubber
2" square wrench nut-open left
*Bolts & Nuts for stuffing box and bonnet Type 316 Stainless Steel
350 psig (2400 kPa/24 barg) maximum working pressure,
700 psig (4800 kPa/48 barg) static test pressure
UL Listed, FM Approved: 350 psig (2400 kPa/24 barg)
Mueller valves are designed for potable water application
**Bronze components meet current lead-free requirements
A-2362-6 *E381
MANUFACTURED IN
THE U.S.A.
Shown with optional hand wheel
† Approved for backflow prevention devices by USC (for 4” - 10” sizes)
IMPORT DUCTILE IRON FLANGED FITTINGS
ANSI / AWWA C110 / A21.10 Class 125
Smooth Running Jobs
APPROVED
MEMBER
GENERAL SPECIFICATIONS
MATERIAL:
PRESSURE:
TESTING:
LAYING LENGTH:
WEIGHTS:
DRILLING:
CEMENT LINING:
COATING:
APPROVALS:
DIMENSIONS:
INSTALLATION:
Ductile iron per ASTM A536
*Flanged fittings *2” – 48” rated at 250 psi. 54” – 64” rated at 150psi.
*Note: With rubber annular ring flange gasket, 2” – 24” flanged fittings can be rated at 350 psi.
In accordance with ANSI/AWWA C110/A21.10, UL and FM requirements
2" - 48" sizes in accordance with ANSI/AWWA C110/A21.10 and ANSI B16.1 and 54" - 64" sizes in accordance with ANSI/AWWA C153/
A21.53
(fittings not listed in ANSI/AWWA have dimensions per design as noted in the catalog)
Are in pounds, unless noted otherwise and do not include accessories, cement lining and coatings
In accordance with ANSI/AWWA C110/A21.10, ANSI/AWWA C153/A21.53 and ANSI B16.1 Class 125 Flanges
In accordance with ANSI/AWWA C104/A21.4 and UL/NSF-61 -- sizes 1"- 3" single thickness and sizes 4"- 64" double thickness
Zinc coating will follow ISO 8179-2 (Zinc Primer) standards. Top Coat Asphaltic seal coat per ANSI/AWWA C104/A21.4
2" - 12" Underwriters Laboratories and ULC Listed and Factory Mutual approved for 300 PSI rating. Please consult factory for detail listing
and approvals.. 2" and greater are UL/NSF-61.
All dimensions are in inches unless noted otherwise.
Per ANSI/AWWA C110 and C111
Smooth Running Jobs
In-Building Riser
LEAD-FREE*
In-Building Risers are used to connect the main fire supply to the building
overhead fire system. The fitting passes under the foundation without joints and
ex-tends up through the floor. Provided with installation tabs, the unit has a
CIPS (Cast Iron Pipe Size) coupler for easy connection to the underground
supply (AWWA C900 PVC and Ductile Iron Pipe) and industry standard
grooved-end connection IPS (AWWA C606) on the building side for easy
connection to the overhead fire sprinkler system. The In-Building Riser features
Lead Free* construction to comply with Lead Free* installation requirements.
$SSUoYDOs
0DteUiDOs
)eDtXUes
00 PSI
40-
End Connections
OUTLET:
Includes Coupling & 1" Tap with Plug
: PVC or Ductile Iron pipe AWWA C900
6'x6' standard length
(custom lengths from 3' – 20'available)
Transition Risers
Application
J-4000 Triton® Series Ductile Iron Hydrants
Refer to our catalog or visit us on the web at Joneswaterproducts.com for the full selection of Wet Barrel Fire Hydrants.
•Furnished with cast iron hose caps with 1-1/8",
1-1/2" or 1-3/4" operating nuts.
•Non-kinking chains.
•Low-zinc silicon bronze stem.
•Two O-ring seals on stem insert.
•Field-replaceable nozzles.
•Removable outlet threads for easy access to
disc holder and stem.
•Clean aesthetic lines
The number of options and combinations provides just about any configuration of ductile iron wet
barrel fire hydrant needed.
•UL listed and FM approved wet barrel
hydrant.
•Lead-Free ASTM B584 Alloy C89833,
C87600 & C89836
•Meets requirements of AWWA C503.
•Cast, manufactured, and assembled inAlbertville, AL, U.S.A.
•
•
Contemporary design features a contouredhead and fluted spool.
Produced by Mueller Co. at its Albertville,Alabama plant which assures customers thatstandard orders are filled more rapidly.
•Operating pressure up to 350psig/24barg
(HP models)
TRITON J-4040 TRITON J-4048 TRITON J-4060
Part Number Description Size
J-4060 Hydrant Complete - 6 Hole .75 on 9.38 BC - CI Caps 1-1/8 Pent 4" x 2-1/2" x 2-1/2"
Note: 4-1/2" Nozzle Option is available for all stated 4" iron outlets. Please make a note on the order if this is
required. All Iron Hydrants are regularly furnished with Cast Iron Caps (CI)
hydrant general
components
§
Outlet Nozzle
Nozzle Cap
Inlet Flange
Nozzle Cap
Cap Op Nut
Op Nut on Stem
Stem Insert
Hydrant Body
J4000 Sieries Ductile Iron Hydrant
Refer to www.clowvalve.com for more information
Part Number Description Size
LBI 400A Break-Off Check Valve 8-Hole x 6-Hole W/Blue Coated Hex Nuts Low Lead 6"
Smooth Running Jobs
Clow LBI 400A Break-Off Check Valve
The Clow LBI 400A is an efficient means for
preventing the loss of water when a hydrant has been
knocked off its mounting.
A double-groove extension riser controls the break
point enabling the bury to be protected during impact.
As the break occurs, upward movement of a secured
threaded stainless steel rod automatically releases a
spring-loaded bronze valve flapper into the waterway.
In static operation the valve flapper is housed in a
recessed area out of the waterway.ea
The Clow LBI 400A can easily be installed with any
wet barrel fire hydrant regardless of model or
manufacturer. Any bolt-hole pattern may be ordered
upon request. All Clow LBI 400A are made standard
with protective fusion epoxy lining.
Conservation sensitive areas will also recognize the
opportunity to reduce water losses by specifying the
Clow LBI 400A . A hydrant broken from a 6” line
under normal operating pressures can quickly result in
large and highly visible water losses as indicated by the
flow table below.
TYPICAL FLOW RATES FOR A 6” LINE
Part Number Description Size
POB642-8 D.I. 8-Hole PO Hydrant Bury C/L with Gasket 6" x 42"
Smooth Running Jobs
Fire Hydrant Burys & Extension Spools
Short Form Specification:
Casting : As per ANSI/AWWA C153/A21.53Material : Ductile Iron per ASTM A536Cement Lining : As per ANSI/AWWA C104/A21.4, 1/8" thickness minimum Coating : Standard NSF-61 approved asphaltic coating inside-out Pressure Rating : 350 PSI hydrostatic pressure
PUSH-ON HYDRANT BURYS
Smooth Running Jobs
Ductile Iron Pipe
PRESSURE CLASS 350 TYTON-JOINT® PIPE
ANSI/AWWA STANDARDS:ANSI/AWWA C151/A21.5, Ductile Iron Pipe, Centrifugally Cast for Water. Ductile Iron Tyton Joint Pipe is centrifugally cast in metal molds in accordance with ANSI/AWWA C151/A21.5.
The asphaltic outside coating is in accordance with ANSI/AWWA C151/A21.51.
ANSI/AWWA C111/A21.11 Standard for Rubber-Gasket Joints for Ductile Iron Pressure Pipe.The standard rubber compound is SBR –
Styrene Butadiene Rubber. This material has a maximum service temperature rating of 150°F and is used as the predominant gasket material for
Drinking Water, Sea Water, Sanitary Sewer, Reclaimed Water, Raw Water, & Storm Water.
ANSI/AWWA C104/A21.4, Cement-Mortar Lining for Ductile-Iron Pipe and Fittings for Water.
The cement-mortar lining and inside coating are in accordance with ANSI/AWWA C104/ A21.4. Special linings and/or coatings can be furnished
for specific conditions.
ANSI/AWWA C111/A21.11, Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and Fittings.
Tyton Gaskets are furnished in accordance with ANSI/AWWA C111/A21.11.
ANSI/AWWA C105/A21.5, Polyethylene Encasement for Ductile
Iron Pipe Systems.
If specifiers and users believe that corrosive soils will be encountered where our products are to be installed, please refer to ANSI/AWWA C105/
A21.5, for proper external protection procedures.
ASTM A536 "Standard Specification for Ductile Iron Castings."
Tyton joint pipe is NSF/ANSI 61 Certified for drinking water system components.
MADE IN U.S.A.
INCHES PSI INCHES POUNDS
SIZE PRESSURE
CLASS THICKNESS OUTSIDE DIAMETER a BARREL WEIGHT
PER FOOT WEIGHT PER LAYING LENGTH b
18-FOOT 20-FOOT
3 — —————
4 350 0.25 4.80 10.9 205 230
6 350 0.25 6.90 16.0 305 335
8 350 0.25 9.05 21.1 400 445
10 350 0.26 11.10 27.1 515 570
12 350 0.28 13.20 34.8 660 730
14 350 0.31 15.30 44.7 860 945
16 350 0.34 17.40 55.8 1065 1175
IMPORT DUCTILE IRON PUSH-ON COMPACT FITTINGS
ANSI/AWWA C153/A21.53
Ductile Iron per ASTM A536.
350 psi Rating for 4”-24". Pressure rating applies to fittings only and not to retaining lugs
In accordance with ANSI/AWWA C153/A21.53 and UL Requirement.
In accordance with ANSI/AWWA C153/A21.53. Fittings not listed in ANSI/AWWA have
dimensions per as noted in Catalog.
Are in pounds, unless noted otherwise and do not include Accessories, Cement Lining
and Coatings.
Flanged ends on Fittings match ANSI/AWWA C115/A21.15 and ANSI B16.1 CLASS
125 Flanges.
In accordance with ANSI/AWWA C104/A21.4.
Asphaltic Seal Coat inside and out in accordance with ANSI/AWWA C104/A21.4
Dual Hardness SBR in accordance with ANSI/AWWA C 111/A21.11.
All dimensions are in inches unless noted otherwide..
4”- 12” UL/ULC Listed - 4" AND GREATER UL/ANSI/NSF 61 and 372 - 4"-12" FM
Approved. Please consult factory for details.
MATERIAL :
PRESSURE :
TESTING :
LAYING LENGTH :
WEIGHTS :
FLANGES :
CEMENT LINING :
COATING :
GASKETS :
DIMENSIONS :
APPROVALS :
GENERAL SPECIFICATIONS
Smooth Running Jobs
APPROVEDMEMBER
INSTALLATION :Per ANSI/AWWA C600 and C111 using DIP conforming to C150/C151 and PVC pipe
conforming to C900/C905
90 Bend Shown
RESTRAINTS
FIELD LOK 350® Gaskets
Product Features
•The gold standard for push-on joint restraint. U.S. Pipe's FIELD LOK 350® Gasket is
an extremely successful, trouble-free means of joint restraint in 4" - 24" sizes for well
over one million Ductile Iron pipe and fitting joint assemblies across North America.
•No pipe surface preparation or grooving is required for field cut pipe other than the cut end needing to be
beveled as required for any push-on joint spigot end.
•Joints are restrained without thrust blocks, bolts, grooves, rods, clamps or retainer glands, resulting in savings
of labor, material and time.
•Available in 4" - 24" sizes (350 psi)
• Providing a boltless, integral restraining system, and shall be rated for 350 psi in accordance with the
requirements of ANSI/AWWA C111/A21.11.
•Underwriters Laboratories lists the 4"–24" sizes for 350 psi. Factory Mutual, utilizing a safety factor of 4,
approves the 4"–16" sizes for 250 psi and the 18"–24" sizes for 200 psi service.
Smooth Running Jobs
Part Number Description Size
6000000108 Field Lok 350 Gasket for DI Pipe 12"
Visit: www.uspipe.com for more information
FIELD LOK ®, FIELD LOK 350 ®, TYTON ®, TYTON JOINT ® and TR FLEX ® are Registered Trademarks
of U.S. Pipe and Foundry Company.
FOR WATER & WASTEWATER, FIRE PROTECTION & INDUSTRIAL APPLICATIONS
BOLTS & NUTS
Smooth Running Jobs
HEX BOLTS GRADE 5 AND 8
SUBMITTAL SPECIFICATIONS
Abstract of SAE J429 CHEMICAL REQUIREMENTS Chemical analysis shall be performed in accordance with SAE J429
CARBON
MIN MAX
PHOPHOROUS
MIN MAX
SULFER
MIN MAX
GRADE 5 0.28 0.55 - 0.05 - 0.06
GRADE 8 0.28 0.55 - 0.04 - 0.05
MECHANICAL REQUIREMENTS
HARDNESS
ROCKWELL
MIN MAX
TENSILE
STRENGTH
(KSI)
MIN MAX
PROOF LOAD
(KSI)
MIN MAX
ELONGATION
GRADE 5 C19 C34 105 120 75 85 14
GRADE 8 C33 C39 150 - 120 - 12
GRADE: CARBON STEEL GRADES 1 THOUGH 8
Hex Nuts ASTM A563 Hex Nuts Grade 5 SAE J995 Hex Nuts Grade 8 SAE J995
Washers ASTM F844-00 (ASME B18.22.1)
FINISH
Plain Zinc Plated Hot Dip Galvanized Blue Xylan
DIMENSIONAL DATA: Unless otherwise specified, threads shall be the coarse threaded series as
specified in the latest issue of ANSI / ASME B1.1, page A-26. Having a class 2A tolerance. Bolts shall
have Hex Heads with Dimensions as given in the latest issue of ANSI / ASME B 18.2.1, page C1.
ADDITIONAL INFORMATION: Additional information can be found in SAE J429, SAE J995, and ASTM
A563.
PVC PRESSURE PIPE
ANSI/AWWA C900
UL 1285
FM 1612**
*See Certification Letter for full explanation and list of exceptions.
**FM 1612 calculates pressure ratings differently than AWWA for
4"-12" only with DR 18 as 185 psi and DR 14 as 250 psi.
‡See Installation Guide for more information.
Pipe Standard:AWWA C900-16
Diameter Std.:Cast Iron Outside Diameter (CIOD)
Nominal Sizes:4", 6", 8", 10", 12", 14", 16",
18", 20", 24", 30", 36"
Dimension Ratios
& Pressure
Ratings:
DR 51 – 80 psi
DR 41 – 100 psi
DR 32.5 – 125 psi
DR 25 – 165 psi
DR 21 – 200 psi
DR 18 – 235 psi
(185 psi)**
DR 14 – 305 psi
(250 psi)**
Lay Length:20' [6.1m]
Pipe Compound:ASTM D1784 Cell Class 12454
Pipe Joint Std.:ASTM D3139
Max. Angular
Joint Deflection:‡1°
Gasket Standard:ASTM F477, UL 157
Gasket Material
Offerings:
Standard – SBR
Optional – NBR or EPDM
Installation Std.:AWWA C605
Color:Blue Green Purple
Certifications:*
NSF 14
NSF 61
CSA B137.3 CSA B137.3 CSA B137.3
Applications
Potable
Water
Waste-
water
Reclaimed
Water
Only products
bearing the NSF
Mark are Certified
Short Form Specification MARKING
The pipe shall be marked in accordance with AWWA C900.
QUALITY CONTROL
Each length of the pipe including the bell shall be hydrostatically
tested in accordance with AWWA C900. The pipe shall meet all
additional test requirements as described in AWWA C900.
Manufacturers full-time quality assurance staff continually
administers a rigid program of tests to maintain the production
of the best pipe products available.
INSTALLATION
Instruction procedures are outlined in AWWA C605,
Underground Installation of Polyvinyl Chloride (PVC) Pressure
Pipe and Fittings for Water. The AWWA Manual M23, PVC Pipe
Design and Installation, is also an invaluable resource guide for
design and installation.
TAPPING
The consistent success of tapping PVC pressure pipe is
contingent upon the use of proper procedures and equipment.
Strict compliance with the requirements as specified in AWWA
C605.
ASSEMBLING THE PIPE
Assembly of PVC water pipe is easily accomplished. A depth of
entry mark is on each spigot end to serve as a visual check for
rapid, accurate joint inspection. Do not over insert.
Smooth Running Jobs
CLEANOUT & VALVE BOXES
GRE10RTF
Visit binghamandtaylor.com for more information
BINGHAM & TAYLOR MARK VTB VALVE BOX SERIES
10 BINGHAM HEAVY MARK VTB
TRI CAST IRON VALVE BOX RIM
WITH FLANGE
GENERAL INFORMATION:
Smooth Running Jobs
CLEANOUT & VALVE BOXES
CUL10LTCVWD-W-Y
Visit binghamandtaylor.com for more information
BINGHAM & TAYLOR MARK VTB VALVE BOX SERIES
10 BINGHAM MARK VTB CAST IRON
TRIANGULAR COVER
MARKED "CVWD WATER" YELLOW
GENERAL INFORMATION:
Smooth Running Jobs