FNCUW2022-0003ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT VERTICAL INTEGRITY INC 917 GLENNEYRE ST STE
A
LAGUNA BEACH CA 92651 (949)279-2418 dk@verticalintegrity.n
et
CONTRACTOR TBU INC 244 MAPLE AVENUE
SUITE T
BEAUMONT CA 92223 (949)279-2418 KAITLYN@TBUINC.NET
OWNER ADAMS OWNER, LP 18565 JAMBOREE RD
#200
IRVINE CA 99261 (949)279-2418
CONDITIONS
Description: SOLTERRA RECREATION BLDG - PRIVATE FIRE MAIN
Type: FIRE NEW COMMERCIAL
UNDERGROUND WATER (WEB)
Subtype: Status: FINALED Applied: 10/8/2022 ECON
Parcel No: 600340048 Site Address: 47470 ALOE WY LA QUINTA,CA 92253 Approved: 11/8/2022 KHET
Subdivision: Block: Lot: REC Issued: 7/1/2023 ONLINE
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 7/19/2023 KHET
Valuation: $25,000.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
FINANCIAL INFORMATION
Printed: Friday, September 22, 2023 4:29:51 PM 1 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FNCUW2022-0003
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
THRUST BLOCK PRE-POUR KHET APPROVED RISER SWEEP - COURTESY
SCHEDULED FOR 10/26/2022 @ 0700
Through multiple reinspections to get the
thrust block cutout correct - approval was
granted on 10/31/2022
THRUST BLOCK PRE-POUR KHET 12/29/2022 12/29/2022 APPROVED All cutouts were increased in dimension to
comply with approved plans.
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE FAILED OR
ADDITIONAL FIELD
INSPECTIONS
(EXCESSIVE) EACH
101-0000-42421 0 $175.00 $175.00 7/1/23 WEB15595 111180786
1 CREDIT 1057032 ECON
FIRE NEW
COMMERCIAL -
UNDERGROUND
WATER
101-0000-42421 0 $500.00 $500.00 11/15/22 WEB13615 753648804 CREDIT 1057032 ECON
FIRE NEW
COMMERCIAL -
UNDERGROUND
WATER PC
101-0000-42420 0 $417.00 $417.00 11/15/22 WEB13615 753648804 CREDIT 1057032 ECON
Total Paid for FIRE FEES: $1,092.00 $1,092.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $11.00 $11.00 11/15/22 WEB13615 753648804 CREDIT 1057032 ECON
Total Paid for RECORDS MANAGEMENT FEE: $11.00 $11.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $8.00 $8.00 11/15/22 WEB13615 753648804 CREDIT 1057032 ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $8.00 $8.00
TOTALS:$1,111.00 $1,111.00
Printed: Friday, September 22, 2023 4:29:51 PM 2 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FNCUW2022-0003
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 10/8/2022 Etrakit Contractor
1ST SUBMITTAL - FIRE
WATER PLAN TRACT
37359
Private Fire Water Plan
2022-10-06.pdf 1
DOC 11/8/2022 KOHL HETRICK FNCUW2022-0003 -
APPROVED PLANS.pdf
FNCUW2022-0003 -
APPROVED PLANS.pdf 1
BOND INFORMATION
UG ROUGH PIPING KHET 12/29/2022 1/3/2023 APPROVED SEE NOTES
Area impacted by gas and domestic water
lines requires a 90-degree changed out to (2)
45s to avoid impacting the utilities.
UG HYDRO KHET 1/10/2023 1/10/2023 APPROVED maintained 200 psi
FLUSH KHET 1/17/2023 1/17/2023 NOT READY
Was not connected to the CVWD Backflow
prevention device. Reinspection required.
No Fee.
FLUSH KHET 6/7/2023 6/7/2023 NOT READY
Did not have all required equipment
installed and ready for test/inspection.
Reschedule. Fees apply.
FLUSH KHET 6/8/2023 6/8/2023 APPROVED See Notes
Flush approved, will need following
documents for Final: Contractor Material &
Test Certificate and FDC Signage.
FIRE FINAL**KHET 7/19/2023 7/19/2023 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
PERMIT TECH
BUCKET
10/8/2022 10/10/2022 10/10/2022 COMPLETE
1ST FIRE (2 WK)KOHL
HETRICK
10/8/2022 10/21/2022 11/8/2022 APPROVED SEE ATTACHMENTS
PARENT PROJECTS
Printed: Friday, September 22, 2023 4:29:51 PM 3 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FNCUW2022-0003
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 11/8/2022 KOHL HETRICK FNCUW2022-0003 - COA
AND JOB CARD.pdf
FNCUW2022-0003 - COA
AND JOB CARD.pdf 1
DOC 7/19/2023 KOHL HETRICK 7-19-2023 - UG Cont
Cert..pdf
7-19-2023 - UG Cont
Cert..pdf 1
Printed: Friday, September 22, 2023 4:29:51 PM 4 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FNCUW2022-0003
C I T Y O F L A Q U I N T ATECHEI
C O N S U L T I N G
w w w . h e i t e c i n c . c o m
Suite 309
777 East Tahquitz Canyon Way
Palm Springs, California 92262
Phone: 760.340.9060
"SOLTERRA" - TRACT NO. 37359
FIRE WATER PLAN
2
2PLAN AND DETAILS
CONSTRUCTION NOTESIRIS WAYRISER IN BUILDING DETAIL
TYPICAL PIPE TRENCH BACKFILL DETAIL
P.I.V. & F.D.C. DETAIL
4" STAINLESS STEEL SWEEP12" MIN.La Quinta OFM - Inspector =
78495 Calle Tampico, La Quinta, CA 92253
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
November 8, 2022
TBU, INC.
244 Maple Ave #T
Beaumont, CA 92223
Re: Private Fire Main Plan Review – SOLTERRA – RECREATION BUILDING
FNCUW2022-0003 / 47470 ALOE WAY, LA QUINTA, CA 92253
The private fire main plans you submitted for the above referenced project have been reviewed by Riverside
County Fire Department - Office of the Fire Marshal personnel and are approved with the following
conditions.
The following inspections and tests must be observed:
1) Pre-Pour Thrust Block cutout inspection / Rough Piping
a. Confirm dimensions of Thrust Block cutouts prior to pouring, if present
b. Confirm pipe material, bury depth and backfill requirements
c. Mechanical Restraints: Confirm break-aways cleared and mastic applied
2) Hydrostatic Test
a. Minimum 200 psi for two (2) hours or at 50 psi in excess of the maximum static pressure when it is in
excess of 150 psi.
3) Underground Flush & Final -
a. Flush of the underground supply line until clear of all debris and to the satisfaction of the
inspector.
b. The underground flush shall be done through a pipe or hose equal in size to the sprinkler underground
supply pipe, prior to connection to the above ground sprinkler piping.
c. Appropriate valve and connection signage is provided
d. Private fire hydrants are painted red and provided with OSFM tag.
e. Provide the completed Contractor’s Material and Test Certificate for Underground Pipe
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Kohl Hetrick - Fire Safety Specialist
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
RIVERSIDE COUNTY FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 47470 ALOE WAY PERMIT#: FNCUW2022-0003 DATE
ISSUED: 11/8/2022
DESCRIPTION: SOLTERRA REC BLDG – SPK UG CONTRACTOR: TBU INC
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F Access & Address verification
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
**WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE**
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler
Systems)
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the
affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when
scheduling inspections. For City of La Quinta inspections call: (760) 777-7131.
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence
without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required
to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not
on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into
the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance
has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE
AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180
DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE
REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.