FNCUW2022-0004ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT CONSTRUCT AND MAINTAIN CORP 27075 CABOT RD STE
#114
LAGUNA HILLS CA 92653 (949)305-8888 PBRAY@CMCORP.CO
BILL TO CONSTRUCT & MAINTAIN CORP 27075 CABOT ROAD,
#114
LAGUNA HILLS CA 92653 (949)305-8888 PBRAY@CMCORP.CO
CONTRACTOR CONSTRUCT AND MAINTAIN CORP 27075 CABOT RD STE
#114
LAGUNA HILLS CA (949)305-8888 PBRAY@CMCORP.CO
OWNER PANERA LLC 3630 S. GEYER RD,
SUITE 100
SUNSET HILLS MO 63127 (949)305-8888 JAVIER.MARTINEZ2@P
ANERABREAD.COM
CONDITIONS
Description: PANERA BREAD #1254 UNDERGROUND FIRE SERVICE PLAN
Type: FIRE NEW COMMERCIAL
UNDERGROUND WATER (WEB)
Subtype: Status: FINALED Applied: 11/9/2022 ECON
Parcel No: 643080051 Site Address: 78902 HIGHWAY 111 LA QUINTA,CA 92253 Approved: 12/8/2022 AHI
Subdivision: PM 25865 Block: Lot: 12 Issued: ONLINE
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 5/11/2023 LRO
Valuation: $70,000.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
FINANCIAL INFORMATION
Printed: Wednesday, September 27, 2023 11:33:35 AM 1 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FNCUW2022-0004
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
UG ROUGH PIPING KHET 1/4/2023 1/4/2023 DISAPPROVE
D SEE NOTES
Bell restraints not installed. Tried for thrust
blocks but were undersized. Opted fir install
of bell restraints, will reinspect.
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
2.5 CREDIT CARD
PROCESSING FEE 101-0000-43505 0 $4.37 $4.37 5/10/23 R75826 09040g CREDIT
CARD
CONSTRUCT AND
MAINTAIN CORP AHI
Total Paid for 2.5 CREDIT CARD PROCESSING FEE: $4.37 $4.37
FIRE FAILED OR
ADDITIONAL FIELD
INSPECTIONS
(EXCESSIVE) EACH
101-0000-42421 0 $175.00 $175.00 5/10/23 R75826 09040g CREDIT
CARD
CONSTRUCT AND
MAINTAIN CORP AHI
FIRE NEW
COMMERCIAL -
UNDERGROUND
WATER
101-0000-42421 0 $500.00 $500.00 12/29/22 WEB13937 778840749 CREDIT 817124 ECON
FIRE NEW
COMMERCIAL -
UNDERGROUND
WATER PC
101-0000-42420 0 $417.00 $417.00 12/29/22 WEB13937 778840749 CREDIT 817124 ECON
Total Paid for FIRE FEES: $1,092.00 $1,092.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $11.00 $11.00 12/29/22 WEB13937 778840749 CREDIT 817124 ECON
Total Paid for RECORDS MANAGEMENT FEE: $11.00 $11.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $8.00 $8.00 12/29/22 WEB13937 778840749 CREDIT 817124 ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $8.00 $8.00
TOTALS:$1,115.37 $1,115.37
Printed: Wednesday, September 27, 2023 11:33:35 AM 2 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FNCUW2022-0004
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 11/10/2022 Etrakit Contractor 1ST SUBMITTAL PLAN
LA QUINTA PANERA
BREAD UDERGROUND
FIRE SERVICE PLAN.pdf
1
DOC 12/8/2022 KOHL HETRICK FNCUW2022-0004 -
APPROVED PLANS.pdf
FNCUW2022-0004 -
APPROVED PLANS.pdf 1
DOC 12/8/2022 KOHL HETRICK FNCUW2022-0004 - COA
AND JOB CARD.pdf
FNCUW2022-0004 - COA
AND JOB CARD.pdf 1
DOC 1/4/2023 KOHL HETRICK
La Quinta Panera Bread
U.G. Fire Service Plan
REVISED.pdf
La Quinta Panera Bread
U.G. Fire Service Plan
REVISED.pdf
1
DOC 5/11/2023 KOHL HETRICK Panera UG CERT.pdf Panera UG CERT.pdf 1
BOND INFORMATION
UG ROUGH PIPING KHET 1/9/2023 1/9/2023 APPROVED Observed bell restraints installed and
wrapped correctly.
UG HYDRO KHET 1/9/2023 1/9/2023 APPROVED Observed 200 psi/2 hrs
FLUSH LRO 2/24/2023 2/24/2023 APPROVED
FIRE FINAL**KHET 5/11/2023 5/11/2023 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
AARON
HICKSON
11/9/2022 11/10/2022 11/10/2022 COMPLETE
1ST FIRE (2 WK)KOHL
HETRICK
11/9/2022 11/28/2022 12/8/2022 APPROVED SEE ATTACHMENTS
PARENT PROJECTS
Printed: Wednesday, September 27, 2023 11:33:35 AM 3 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FNCUW2022-0004
6" STUB-UP RISER DETAILR-2FIRE DEPARTMENT CONNECTION ASSEMBLYUNDERGROUND FIRE SERVICE DETAILR-1
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
December 8, 2022
Unlimited Engineering, INC. (A-995902)
510 E Stuart Ave.
Redlands, CA 92374
Re: Private Fire Main Plan Review – PANERA BREAD
FNCUW2022-0004 / 78902 HIGHWAY 111, LA QUINTA, CA 92253
The private fire main plans you submitted for the above referenced project have been reviewed by Riverside
County Fire Department - Office of the Fire Marshal personnel and are approved with the following
conditions.
The following inspections and tests must be observed:
1) Rough Piping
a. Confirm pipe material, bury depth and backfill requirements
b. Mechanical Restraints: Confirm break-aways cleared and mastic applied
2) Hydrostatic Test
a. Minimum 200 psi for two (2) hours or at 50 psi in excess of the maximum static pressure when it is in
excess of 150 psi.
3) Underground Flush & Final -
a. Flush of the underground supply line until clear of all debris and to the satisfaction of the
inspector.
b. The underground flush shall be done through a pipe or hose equal in size to the sprinkler underground
supply pipe, prior to connection to the above ground sprinkler piping.
c. Appropriate valve and connection signage is provided
d. Private fire hydrants are painted red and provided with OSFM tag.
e. Provide the completed Contractor’s Material and Test Certificate for Underground Pipe
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Kohl Hetrick - Fire Safety Specialist
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
RIVERSIDE COUNTY FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 78902 HIGHWAY 111 PERMIT#: FNCUW2022-0004 DATE
ISSUED: 12/8/2022
DESCRIPTION: PANERA BREAD CONTRACTOR: UNLIMITED ENGINEERING INC
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F Access & Address verification
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
**WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE**
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler
Systems)
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the
affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when
scheduling inspections. For City of La Quinta inspections call: (760) 777-7131.
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence
without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required
to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not
on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into
the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance
has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE
AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180
DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE
REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.