FS2018-0006ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT UNITED FIRE SERVICES INC P O BOX 9007 CANOGA PARK CA 91309
BILL TO UNITED FIRE SERVICES INC P O BOX 9007 CANOGA PARK CA 91309
CONTRACTOR UNITED FIRE SERVICES INC P O BOX 9007 CANOGA PARK CA 91309
OWNER LQ INV 17165 NEWHOPE ST FOUNTAIN
VALLEY
CA 92253
CONDITIONS
Description: LQ INV / HOOD AND DUCT
Type: FIRE SUPRESSION Subtype: HOOD & DUCT Status: FINALED Applied: 8/29/2018 RCA
Parcel No: 770020017 Site Address: 50855 WASHINGTON ST STE 2I LA QUINTA,CA 92253 Approved: 9/12/2018 RCA
Subdivision: PM 27984 Block: Lot: 3 Issued: 9/26/2018 AHI
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 10/31/2018 EGO
Valuation: $0.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
FINANCIAL INFORMATION
Printed: Thursday, January 19, 2023 11:11:07 AM 1 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FS2018-0006
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
DETECTION SYSTEM EGO 10/31/2018 10/31/2018 APPROVED
FUNCTION TEST EGO 10/31/2018 10/31/2018 APPROVED
GAS/ELECTRICAL SHUT-
OFF
EGO 10/31/2018 10/31/2018 APPROVED
NOZZLE
MODEL/REPLACEMENT
EGO 10/31/2018 10/31/2018 APPROVED
FIRE FINAL**EGO 10/31/2018 10/31/2018 APPROVED
REVIEWS
RETURNED
PARENT PROJECTS
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE COMMERCIAL
COOKING HOOD AND
DUCT SYSTEMS
101-0000-42421 0 $156.00 $156.00 8/30/18 R39037 10493 CHECK UNITED FIRE SERVICES
INC AMA
FIRE COMMERCIAL
COOKING HOOD AND
DUCT SYSTEMS PC
101-0000-42420 0 $234.00 $234.00 8/30/18 R39037 10493 CHECK UNITED FIRE SERVICES
INC AMA
Total Paid for FIRE FEES: $390.00 $390.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 8/30/18 R39037 10493 CHECK UNITED FIRE SERVICES
INC AMA
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 8/30/18 R39037 10493 CHECK UNITED FIRE SERVICES
INC AMA
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$405.00 $405.00
Printed: Thursday, January 19, 2023 11:11:07 AM 2 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FS2018-0006
REVIEW TYPE REVIEWER SENT DATE DUE DATE DATE STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
REYNA
CAMARENA 8/29/2018 8/29/2018 8/29/2018 COMPLETE
**APPLICANT NEEDS A BUSINESS LICENSE BEFORE
ISSUANCE**
/12/2018
Aviva Shetrit
United Fire Services
PO Box 9007
Canoga Park CA, 91309
Re: LQ Investments
FS2018-0006 – Fire Hood
Suppression System
50-855 Washington St.
La Quinta CA, 92253
The hood/duct plans you submitted for the above
referenced project have been reviewed by
Riverside County Fire Department and are
approved with the following conditions:
Printed: Thursday, January 19, 2023 11:11:07 AM 3 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FS2018-0006
1ST FIRE (2 WK)EDGAR
GONZALEZ 8/29/2018 9/12/2018 9/12/2018 APPROVED-
CONDITIONS
· Operation instructions must be posted
in a visible location.
· The Alternative Automatic Fire-
Extinguishing System must be monitored by the
fire alarm system if building is currently
monitored.
The following inspections/tests shall be
witnessed by the Fire Department:
· System operation checkout and final
test to be performed by the installer. Shall be in
compliance with CFC 904 and NFPA 2010 Chapter
8 requirements.
Alarm company representative must also be
present at the time of acceptance
testing/inspection.
The Fire Department approved plans and
conditions letter must be at the job site.
Applicant/installer shall be responsible to contact
the Fire Department to schedule inspections.
Requests for inspections are to be made at least
72 hours in advance and may be arranged by
Printed: Thursday, January 19, 2023 11:11:07 AM 4 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FS2018-0006
ATTACHMENTS
BOND INFORMATION
calling (760)863-8886.
SUBJECT TO FIELD INSPECTION - Nothing in our
review shall be construed as encompassing
structural integrity. Review of this plan does not
authorize or approve any omission or deviation
from all applicable regulations. Final approval is
subject to field inspection.
All questions regarding the meaning of these
conditions should be referred to the Office of the
Fire Marshal staff at (760)777-7074.
Edgar Gonzalez
Fire Safety Specialist
Printed: Thursday, January 19, 2023 11:11:07 AM 5 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FS2018-0006