FS2019-0002ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT MAJESTIC FIRE INC DBA KORD FIRE
PROTECTI
5160 VAN NUYS BLVD
#257
SHERMAN OAKS CA 91403 (818)501-4989 MARTHA@KORDFILE.C
OM
BILL TO MAJESTIC FIRE INC DBA KORD FIRE
PROTECTI
5160 VAN NUYS BLVD
#257
SHERMAN OAKS CA 91403 (818)501-4989 MARTHA@KORDFILE.C
OM
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
NOTE KAYLI ALFORD 6/30/2020 6/30/2020 PERMIT EXPIRED 4/25/20. OK TO EXTEND PERMIT PER KOHL,
NO FEE ASSESSED.
PLAN CHECK PICKED UP ARMANDO MAGALLON 10/28/2019 10/28/2019 PLANS ISSUED TO LILIANA RUEDA WITH KORD FIRE
PLAN CHECK PICKED UP STEPHANIE SWANSTROM 3/20/2019 3/20/2019 ROJAS
CONDITIONS
Description: MY THAI / FIRE SUPRESSION KITCHEN HOOD
Type: FIRE SUPRESSION Subtype: HOOD & DUCT Status: FINALED Applied: 2/21/2019 JLIM
Parcel No: 643020060 Site Address: 46520 WASHINGTON ST STE 3 LA QUINTA,CA 92253 Approved: 10/1/2019 KHET
Subdivision: PM 32683-3 AMEND Block: Lot: 3 Issued: 10/28/2019 AMA
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 7/1/2020 crw
Valuation: $0.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details: SCOPE OF WORK: 1) x1 Drop added for existing fire suppression system. 2) Drop added over deep fryer
Printed: Thursday, January 26, 2023 10:39:39 AM 1 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FS2019-0002
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
CONTRACTOR MAJESTIC FIRE INC DBA KORD FIRE
PROTECTI
5160 VAN NUYS BLVD
#257
SHERMAN OAKS CA 91403 (818)501-4989
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
Credit Card Fee 101-0000-43505 0 $7.47 $7.47 2/21/19 R45294 0001 CREDIT
CARD
KORD FIRE
PROTECTION DBA
MAJES
JLIM
Total Paid for Credit Card Fee: $7.47 $7.47
FIRE COMMERCIAL
COOKING HOOD AND
DUCT SYSTEMS
101-0000-42421 0 $160.00 $160.00 2/21/19 R45294 0001 CREDIT
CARD
KORD FIRE
PROTECTION DBA
MAJES
JLIM
FIRE COMMERCIAL
COOKING HOOD AND
DUCT SYSTEMS PC
101-0000-42420 0 $240.00 $240.00 2/21/19 R45294 0001 CREDIT
CARD
KORD FIRE
PROTECTION DBA
MAJES
JLIM
Total Paid for FIRE FEES: $400.00 $400.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 2/21/19 R45294 0001 CREDIT
CARD
KORD FIRE
PROTECTION DBA
MAJES
JLIM
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 2/21/19 R45294 0001 CREDIT
CARD
KORD FIRE
PROTECTION DBA
MAJES
JLIM
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$422.47 $422.47
Printed: Thursday, January 26, 2023 10:39:39 AM 2 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FS2019-0002
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 3/12/2019 EDGAR GONZALEZ
FS2019-0002 - KING
KITCHEN - 46-520
WASHINGTON ST STE 3 -
FIRE HOOD
SUPPRESSION
(CORRECTIONS).docx
FS2019-0002 - KING
KITCHEN - 46-520
WASHINGTON ST STE 3 -
FIRE HOOD
SUPPRESSION
(CORRECTIONS).docx
1
DOC 11/4/2021 JOSE DELGADO Fire Review
Application.pdf
Fire Review
Application.pdf 0
DOC 11/5/2021 JOSE DELGADO Approved My Thai
Plans.pdf
Approved My Thai
Plans.pdf 0
DOC 10/1/2019 KOHL HETRICK MY THAI REVISED.pdf MY THAI REVISED.pdf 1
DOC 10/1/2019 KOHL HETRICK
FS2019-0002 - MY THAI -
KITCH SUPPR ALTERED -
APPROVED.docx
FS2019-0002 - MY THAI -
KITCH SUPPR ALTERED -
APPROVED.docx
1
BOND INFORMATION
FIRE FINAL**KHET 7/1/2020 7/1/2020 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST FIRE (2 WK)EDGAR
GONZALEZ
3/1/2019 3/7/2019 3/12/2019 REVISIONS REQUIRED SEE ATTACHED CORRECTION LIST.
2ND FIRE (2 WK)KOHL
HETRICK
9/16/2019 9/30/2019 10/1/2019 APPROVED SEE ATTACHMENTS
PARENT PROJECTS
Printed: Thursday, January 26, 2023 10:39:39 AM 3 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FS2019-0002
GENERAL NOTES1. 2 x PCL460 PYRO CHEM (Wet Chemical) Fire Suppression System (UL300).2. Remote Pull Station As Shown near exit3. Quantity 6 Fusible Link Detectors As Shown (450 F).4. 2 " Mechanical Gas Valve Shut-off As Shown.5. Nozzle Count: TYPE FLOW POINTS QTY. TOTAL 2D 2 2 4 1H 1 10 10 2L 2 1 2 2H 2 1 2 SYSTEM TOTAL 30 FLOW POINTS AVAILABLE 12 DISCHARGE NOZZLES AS SHOWN - USES 16 FLOW POINTS OF 20 FLOW POINTS.A, 2D (Quantity 2, 2 Flow Point Per Nozzle) in Ducts, 2 x 2 = 4B. 1H (Quantity 1, 1 Flow Point Per Nozzle) in 6 b Range , 1 x 1 = 1C. 2L (Quantity 1, 2 Flow Point Per Nozzle) in 6 b Range , 1 x 2 = 2D. 1H (Quantity 2, 1 Flow Point Per Nozzle) in 2 Plenum , 2 x 1 = 2E. 2H (Quantity 1, 2 Flow Point Per Nozzle) in Fryer , 1 x 2 = 2F. 1H (Quantity 6, 1 Flow Point Per Nozzle) in 6 Woks , 6 x 1 = 6G. 1H (Quantity 1, 1Flow Point Per Nozzle) in Charboiler 1 x 1 = 16. All Pipes Are 38 " Sch. 40 Black Steel As Shown On Plan.7. System Must Be Test-Fired For Local Authorities Upon Completion.8. Provide Two "K" Class Fire Extinguisher Near Kitchen Hood System.9. All Equipment Under Hood To Shut Down Upon Activation.10. Extinguishing System Is To Be Connected To Existing Alarm System ( if available ) .11. Designed To Comply With Pyrochem (UL300).12. Exhaust System Must Remain On Upon System Activation.FManual pull stationNozzle Aiming upNozzle Aiming DownNozzle Aiming RightNozzle Aiming LeftCorner pullyMCH3Tee pullyPYROCHEM control headAll units are inchPCL 460 15 FPPCL 460 15 FPFMechanical gasshut off valveon the roofCopper tubing54.036.02L1H1H1H1H1H1H1H1H FRYER 24'' to 48 '' Nozzle Height27.036.02H 6 BURNER RANGE40'' to 50 '' Nozzle Height1H2D2D1HCharboiler24'' to 48 '' Nozzle HeightPlenum : Up to 20 FT max protected by 2 x 1HnozzleDuct : Duct Up to 100" Perimeter protectedby 1 x 2D nozzleHood : 240 x 486 Woks24'' to 48 '' Nozzle HeightMy ThaiJessica Zhuang (760) 564 - 842446520 Washington St #3, La Quinta, CAKord Fire Protection1105 N Gene Autry Trail #1,Palm Springs, CA 92262Not scaled Sheet 1 of 1PCL 460 15 FPPCL 460 15 FPFMechanical gasshut off valveon the roofCopper tubing27.018.02L1H1H1H1H1H1H1H1H FRYER 24'' to 48 '' Nozzle Height13.518.02H 6 BURNER RANGE40'' to 50 '' Nozzle Height1H2D2D1HCharboiler24'' to 48 '' Nozzle HeightPlenum : Up to 20 FT max protected by 2 x 1H nozzleDuct : Duct Up to 100" Perimeter protected by 1 x 2D nozzleHood : 240 x 486 Woks24'' to 48 '' Nozzle Height450 FUSIBLE LINK450 FUSIBLE LINK450 FUSIBLE LINK450 FUSIBLE LINK450 FUSIBLE LINK450 FUSIBLE LINKProportion areaEXITDining area(KORD FIRE SCOPE OF WORK)1- 1 DROP ADDED FOR EXISTING FIRE SUPPRESSION SYSTEM2- DROP ADDED OVER DEEP DRYER.DROP ADDED ABOVE