FS2020-0004ADDITIONAL SITES
CHRONOLOGY
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
E-MAIL KAYLI ALFORD 6/16/2020 6/16/2020
PER AJ: Fine for issuance (and now inspection) of the FS2020-
0004 Fire Permit with Building, but restaurant does need a
City Business License.
E-MAIL KOHL HETRICK 4/6/2020 4/6/2020
COMMUNICATED WITH BUILDING DEPARTMENT ABOUT
CONCERNS FOR NEEDING A "TENANT IMPROVEMENT -
CONSTRUCTION" PERMIT.
PER AJ ORTEGA: I think it’d be important to verify if the
equipment and hood types comply with each other, and then
I think more building related is the fuel demand changing to
where we need to assess the system… We could issue him a
special inspection to verify all this if needed, have him reach
out to Jake and I to discuss. Jake is in the office Monday and
Tuesday (760-777-7081) and I am in the office Wednesday
and Thursday (760-777-7018).
CONDITIONS
Description: TORAKICHI RAMEN / HOOD & DUCT / BCOM2020-?
Type: FIRE SUPRESSION (WEB)Subtype: HOOD & DUCT Status: FINALED Applied: 3/19/2020 JLIM
Parcel No: 600440005 Site Address: 79775 HIGHWAY 111 105 LA QUINTA,CA 92253 Approved: 4/6/2020 KHET
Subdivision: PM 036269 Block: Lot: 5 Issued: 4/6/2020 KHET
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 6/18/2020 KHET
Valuation: $0.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
Printed: Thursday, February 16, 2023 3:26:06 PM 1 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FS2020-0004
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT FRANK GORTZ / FIRELINE INC 37921 PORTER DRIVE CATHEDRAL
CITY
CA 92234 gortz3@msn.com
CONTRACTOR FIRELINE INC 37921 PORTER DRIVE CATHEDRAL
CITY
CA 92234 gortz3@msn.com
OWNER P6K PORTFOLIO KDP 2301 ROSECRANS STE
2110
EL SEGUNDO CA 92253
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
FIRE FINAL**KHET 6/18/2020 6/18/2020 APPROVED
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE COMMERCIAL
COOKING HOOD AND
DUCT SYSTEMS
101-0000-42421 0 $161.00 $161.00 3/19/20 WEB4717 CREDIT FIRELINE INC ECON
FIRE COMMERCIAL
COOKING HOOD AND
DUCT SYSTEMS PC
101-0000-42420 0 $242.00 $242.00 3/19/20 WEB4717 CREDIT FIRELINE INC ECON
Total Paid for FIRE FEES: $403.00 $403.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 3/19/20 WEB4717 CREDIT FIRELINE INC ECON
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 3/19/20 WEB4717 CREDIT FIRELINE INC ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$418.00 $418.00
Printed: Thursday, February 16, 2023 3:26:06 PM 2 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FS2020-0004
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 4/6/2020 KOHL HETRICK
1ST SUBMITTAL - HOOD
and DUCT TI -
APPROVED PLANS.pdf
1ST SUBMITTAL - HOOD
and DUCT TI -
APPROVED PLANS.pdf
1
DOC 4/6/2020 KOHL HETRICK
FS2020-0004 -
TORAKICHI RAMEN -
HOOD SUPP ADJUST -
COA AND JOB CARD.pdf
FS2020-0004 -
TORAKICHI RAMEN -
HOOD SUPP ADJUST -
COA AND JOB CARD.pdf
1
BOND INFORMATION
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
JACK LIMA 3/19/2020 3/20/2020 3/20/2020 COMPLETE
1ST FIRE (2 WK)KOHL
HETRICK 3/19/2020 4/2/2020 4/6/2020 APPROVED SEE ATTACHMENTS NO TENANT IMPROVEMENT PLANS FOUND FOR
THIS PROJECT.
PARENT PROJECTS
Printed: Thursday, February 16, 2023 3:26:06 PM 3 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FS2020-0004
FS2020-0004
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
April 6, 2020
Fireline Inc
37921 Porter Drive
Cathedral City, CA 92234
Re: Kitchen Suppression System – Adjustment - Plan Review – Torakichi Ramen
FS2020-0004 / 79775 HIGHWAY 111 #105, LA QUINTA, CA 92253
The plans you submitted for the above referenced project have been reviewed by Riverside County Fire Department
and are approved with the following conditions:
The following inspections/tests shall be witnessed by the Fire Department:
o Final inspection required to ensure nozzles are installed correctly. A full acceptance test is not required by the Fire
Department. Reference 2016 California Fire Code (CFC) Section 106.2
o The system shall have a current service inspection. Ref. CFC 904.5.1
o Ensure there is a sign next to the K class fire extinguisher indicating the suppression system shall be activated
before the use of the fire extinguisher. Ref. NFPA 17A Section 4.4.3.6
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Kohl Hetrick - Fire Safety Specialist
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
RIVERSIDE COUNTY FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 79775 HIGHWAY 111 #105 PERMIT#: FS2020-0004 DATE
ISSUED: 4/6/2020
DESCRIPTION: HOOD SUPPRESSION ADJUSTMENT CONTRACTOR: FIRELINE INC.
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F Access & Address verification
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
**WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE**
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler
Systems)
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the
affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when
scheduling inspections. For City of La Quinta inspections call: (760) 777-7131.
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence
without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required
to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not
on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into
the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance
has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE
AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180
DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE
REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.