Description: TIFFANY'S SWEET SPOT / ANSUL HOOD SYSTEM
Type: FIRE SUPRESSION (WEB)Subtype: HOOD & DUCT Status: FINALED Applied: 1/21/2021 ECON
Parcel No: 604050037 Site Address: 78590 HIGHWAY 111 LA QUINTA,CA 92253 Approved: 2/4/2021 KHET
Subdivision: Block: Lot: Issued: 4/1/2021 ONLINE
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 4/7/2021 KHET
Valuation: $4,000.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
FINANCIAL INFORMATION
Printed: Friday, February 24, 2023 3:14:03 PM 1 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FS2021-0001
BOND INFORMATION
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
FIRE FINAL**KHET 4/7/2021 4/7/2021 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST FIRE (2 WK)KOHL
HETRICK
1/21/2021 2/4/2021 2/4/2021 APPROVED SEE ATTACHMENTS
1ST PERMIT TECH (1
DAY)
ARMANDO
MAGALLON
1/21/2021 1/22/2021 2/24/2021 COMPLETE
PARENT PROJECTS
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE COMMERCIAL
COOKING HOOD AND
DUCT SYSTEMS
101-0000-42421 0 $161.00 $161.00 4/1/21 WEB7796 075424 CREDIT DESERT FIRE
EXTINGUISHER CO INC ECON
FIRE COMMERCIAL
COOKING HOOD AND
DUCT SYSTEMS PC
101-0000-42420 0 $242.00 $242.00 4/1/21 WEB7796 075424 CREDIT DESERT FIRE
EXTINGUISHER CO INC ECON
Total Paid for FIRE FEES: $403.00 $403.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 4/1/21 WEB7796 075424 CREDIT DESERT FIRE
EXTINGUISHER CO INC ECON
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 4/1/21 WEB7796 075424 CREDIT DESERT FIRE
EXTINGUISHER CO INC ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$418.00 $418.00
Printed: Friday, February 24, 2023 3:14:03 PM 2 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FS2021-0001
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 1/21/2021 EtrakitContractor 1ST SUBMITTAL - CUT
SHEETS Cut sheets.pdf 1
DOC 1/21/2021 EtrakitContractor APPLICATION Fire App.pdf 1
DOC 1/21/2021 EtrakitContractor 1ST SUBMITTAL - PLAN
SET
TIFFANYS SWEET SPOT
PLANS.pdf 1
DOC 2/4/2021 KOHL HETRICK FS2021-0001 - COA AND
JOB CARD.pdf
FS2021-0001 - COA AND
JOB CARD.pdf 1
Printed: Friday, February 24, 2023 3:14:03 PM 3 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FS2021-0001
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
February 4, 2021
Desert Fire Extinguisher
PO Box 1607
Palm Springs, CA 92263
Re: Kitchen Suppression System Plan Review – TIFFANY’S SWEET SPOT
FS2021-0001 / 78590 HIGHWAY 111, LA QUINTA, CA 92253
The plans you submitted for the above referenced project have been reviewed by Riverside County Fire Department
and are approved with the following conditions:
o Operation instructions must be posted in a visible location.
o The hood/duct system must be monitored by the fire alarm system if building is currently monitored.
o In a pre-engineered system, only listed components from a single manufacturer shall be used.
o When hood/duct system is activated, the gas supply, electric supply, and make up air must automatically shut
off. The hood exhaust fan shall remain on after system activation.
o A “K” rated extinguisher must be mounted in the kitchen area. The “K” rated extinguisher shall not substitute
for the required conventional dry chemical extinguishers in the kitchen.
The following inspections/tests shall be witnessed by the Fire Department:
o System operation checkout and final test to be performed by the installer. Alarm company representative must
also be present at the time of hood/duct inspection.
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Kohl Hetrick - Fire Safety Specialist
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
RIVERSIDE COUNTY FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 78590 HIGHWAY 111 PERMIT#: FS2021-0001 DATE
ISSUED: 2/4/2021
DESCRIPTION: TIFFANY’S SWEET SPOT CONTRACTOR: DESERT FIRE
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F Access & Address verification
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
**WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE**
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler
Systems)
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the
affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when
scheduling inspections. For City of La Quinta inspections call: (760) 777-7131.
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence
without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required
to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not
on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into
the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance
has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE
AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180
DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE
REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.