FSS2018-0096ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT CHARLES F BROWN FIRE
PROTECTION DESIGN
21386 LILIUM COURT MORENO
VALLEY
CA 92557 CHUCK92234@AOL.CO
M
BILL TO CHARLES F BROWN FIRE
PROTECTION DESIGN
21386 LILIUM COURT MORENO
VALLEY
CA 92557 CHUCK92234@AOL.CO
M
CONTRACTOR CHARLES F BROWN FIRE
PROTECTION DESIGN
21386 LILIUM COURT MORENO
VALLEY
CA 92557 CHUCK92234@AOL.CO
M
OWNER SEAN PATTERSON 123 J AVE CORONADO CA 0
CONDITIONS
Description: CORONEL / BRES2017-0248 / SFD SPRINKLER
Type: FIRE SPRINKLER Subtype: RESIDENTIAL - CUSTOM
HOMES
Status: ISSUED Applied: 6/6/2018 SSW
Parcel No: 774282001 Site Address: 54510 AVENIDA VALLEJO LA QUINTA,CA 92253 Approved: 6/19/2018 RCA
Subdivision: SANTA CARMELITA AT VALE LA QUINTA
UNIT 28
Block: 305 Lot: 24 Issued: 5/2/2019 KPI
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled:
Valuation: $0.00 Occupancy Type: Construction Type: Expired: 10/29/2019 KPI
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details: Changed status to approved per Edgar's approval which is indicated below.
FINANCIAL INFORMATION
Printed: Friday, January 13, 2023 8:51:48 AM 1 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0096
INSPECTIONS
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
ARMANDO
MAGALLON 6/7/2018 6/8/2018 6/7/2018 COMPLETE
PARENT PROJECTS
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $156.00 $156.00 6/6/18 R36215 4665 CHECK CHARLES F BROWN
FIRE PROTECTIO SSW
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED PC
101-0000-42420 0 $234.00 $234.00 6/6/18 R36215 4665 CHECK CHARLES F BROWN
FIRE PROTECTIO SSW
Total Paid for FIRE FEES: $390.00 $390.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 6/6/18 R36215 4665 CHECK CHARLES F BROWN
FIRE PROTECTIO SSW
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 6/6/18 R36215 4665 CHECK CHARLES F BROWN
FIRE PROTECTIO SSW
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$405.00 $405.00
Printed: Friday, January 13, 2023 8:51:48 AM 2 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0096
1ST FIRE (2 WK)EDGAR
GONZALEZ 6/13/2018 6/20/2018 6/19/2018 APPROVED-
CONDITIONS
The sprinkler plans you submitted for the above
referenced project have been reviewed by
Riverside County Fire Department - Office of the
Fire Marshal personnel and are approved with
the following conditions.
Permanently marked identification signs shall be
attached to all control valves.
The following inspections/tests are required to be
witnessed by Office of the Fire Marshal Staff:
(a) Overhead Rough and Hydro static test: All
piping shall be visible and pumped at normal
operating pressure. *No jacketed electrical and
data wiring shall be in contact with, nor have the
potential to contact CPVC piping once insulation
is installed.
(b) Final inspection
The Fire Department approved plans and
conditions letter must be at the job site.
Applicant/installer shall be responsible to contact
the Fire Department to schedule inspections.
Requests for inspections are to be made at least
72 hours in advance and may be arranged by
calling (760)863-8886.
SUBJECT TO FIELD INSPECTION - Nothing in our
review shall be construed as encompassing
structural integrity. Review of this plan does not
authorize or approve any omission or deviation
from all applicable regulations. Final approval is
subject to field inspection.
All questions regarding the meaning of these
conditions should be referred to the Office of the
Fire Marshal staff at (760)895-9006.
Printed: Friday, January 13, 2023 8:51:48 AM 3 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0096
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 12/21/2021 JOSE DELGADO
CVWD - Residential
Connection Charge
Estimate.pdf
CVWD - Residential
Connection Charge
Estimate.pdf
0
DOC 12/21/2021 JOSE DELGADO Fire Review
Application.pdf
Fire Review
Application.pdf 0
DOC 12/21/2021 JOSE DELGADO
Model F1 Residential
Sprinkler for Design
Density.pdf
Model F1 Residential
Sprinkler for Design
Density.pdf
0
DOC 12/21/2021 JOSE DELGADO Hydraulic Calculations
FP -1.1 Kitchen.pdf
Hydraulic Calculations
FP -1.1 Kitchen.pdf 0
DOC 12/21/2021 JOSE DELGADO
Hydraulic Calculations
FP-1.1 Kitchen and
Dining.pdf
Hydraulic Calculations
FP-1.1 Kitchen &
Dining.pdf
0
DOC 12/21/2021 JOSE DELGADO FSS2018-0096.pdf FSS2018-0096.pdf 0
BOND INFORMATION
Printed: Friday, January 13, 2023 8:51:48 AM 4 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0096