FSS2018-0097ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT CHARLES F BROWN FIRE
PROTECTION DESIGN
21386 LILIUM COURT MORENO
VALLEY
CA 92557 (951)712-4959 CHUCK92234@AOL.CO
M
BILL TO CHARLES F BROWN FIRE
PROTECTION DESIGN
21386 LILIUM COURT MORENO
VALLEY
CA 92557 (951)712-4959 CHUCK92234@AOL.CO
M
CONTRACTOR CHARLES F BROWN FIRE
PROTECTION DESIGN
21386 LILIUM COURT MORENO
VALLEY
CA 92557 (951)712-4959 CHUCK92234@AOL.CO
M
CONDITIONS
Description: CORONEL / SFD SPRINKLER
Type: FIRE SPRINKLER Subtype: RESIDENTIAL - CUSTOM
HOMES
Status: FINALED Applied: 6/6/2018 SSW
Parcel No: 773233007 Site Address: 52140 AVENIDA MENDOZA LA QUINTA,CA 92253 Approved: 7/12/2018 RCA
Subdivision: SANTA CARMELITA VALE LA QUINTA
UNIT 11
Block: 94 Lot: 16 Issued: 7/16/2018 SSW
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 10/11/2018 EGO
Valuation: $0.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details: 1.) Show underground detail with water meter size and node points on plan.
2.) Show scaled dimensions of pipe lengths on plan.
3.) Add fire sprinkler protection in FAU Room. Fire sprinkler head to be intermediate temperature.
4.) Show hanger location on plan. Several pipe areas on plans are lacking hangers.
5.) Provide water meter cut sheet for review.
6.) Show 10% safety margin on hydraulic calculations.
PLANS WERE APPROVED PER EG ON 7/12/18. I CHANGED STATUS TO APPROVED AND ADJUSTED DATE TO MATCH.
Printed: Friday, January 27, 2023 9:51:37 AM 1 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0097
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
OWNER DARIO SANCHEZ 417 VIA MALAGA REDONDO
BEACH
CA 0 (951)712-4959
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD HYRO EGO 7/16/2018 7/16/2018 APPROVED
OVERHEAD ROUGH
PIPING
EGO 7/16/2018 7/16/2018 APPROVED
FIRE FINAL**EGO 9/27/2018 9/27/2018 NOT READY
FIRE FINAL**EGO 10/11/2018 10/11/2018 APPROVED
PARENT PROJECTS
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $156.00 $156.00 6/6/18 R36215 4665 CHECK CHARLES F BROWN
FIRE PROTECTIO SSW
Total Paid for FIRE FEES: $156.00 $156.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 6/6/18 R36215 4665 CHECK CHARLES F BROWN
FIRE PROTECTIO SSW
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 6/6/18 R36215 4665 CHECK CHARLES F BROWN
FIRE PROTECTIO SSW
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$171.00 $171.00
Printed: Friday, January 27, 2023 9:51:37 AM 2 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0097
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
STEPHANIE
SWANSTROM 6/6/2018 6/7/2018 6/13/2018 COMPLETE
1ST FIRE (2 WK)EDGAR
GONZALEZ 6/13/2018 6/18/2018 6/19/2018 REVISIONS REQUIRED
1.) Show underground detail with water meter
size and node points on plan.
2.) Show scaled dimensions of pipe lengths on
plan.
3.) Add fire sprinkler protection in FAU Room. Fire
sprinkler head to be intermediate temperature.
4.) Show hanger location on plan. Several pipe
areas on plans are lacking hangers.
5.) Provide water meter cut sheet for review.
6.) Show 10% safety margin on hydraulic
calculations.
2ND FIRE (2 WK)EDGAR
GONZALEZ 6/28/2018 7/12/2018 7/12/2018 APPROVED-
CONDITIONS
The sprinkler plans you submitted for the above
referenced project have been reviewed by
Riverside County Fire Department - Office of the
Fire Marshal personnel and are approved with
the following conditions.
Permanently marked identification signs shall be
attached to all control valves.
The following inspections/tests are required to be
witnessed by Office of the Fire Marshal Staff:
(a) Overhead Rough and Hydro static test: All
piping shall be visible and pumped at normal
operating pressure. *No jacketed electrical and
data wiring shall be in contact with, nor have the
potential to contact CPVC piping once insulation
is installed.
(b) Final inspection
The Fire Department approved plans and
conditions letter must be at the job site.
Printed: Friday, January 27, 2023 9:51:37 AM 3 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0097
ATTACHMENTS
BOND INFORMATION
Applicant/installer shall be responsible to contact
the Fire Department to schedule inspections.
Requests for inspections are to be made at least
72 hours in advance and may be arranged by
calling (760)777-7000.
SUBJECT TO FIELD INSPECTION - Nothing in our
review shall be construed as encompassing
structural integrity. Review of this plan does not
authorize or approve any omission or deviation
from all applicable regulations. Final approval is
subject to field inspection.
All questions regarding the meaning of these
conditions should be referred to the Office of the
Fire Marshal staff at (760)777-7074.
Edgar Gonzalez - Fire Safety Specialist