FSS2018-0098ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT CHARLES F BROWN FIRE
PROTECTION DESIGN
21386 LILIUM COURT MORENO
VALLEY
CA 92557 (951)712-4959 CHUCK92234@AOL.CO
M
BILL TO CHARLES F BROWN FIRE
PROTECTION DESIGN
21386 LILIUM COURT MORENO
VALLEY
CA 92557 (951)712-4959 CHUCK92234@AOL.CO
M
CONTRACTOR CHARLES F BROWN FIRE
PROTECTION DESIGN
21386 LILIUM COURT MORENO
VALLEY
CA 92557 (951)712-4959 CHUCK92234@AOL.CO
M
OWNER DARIO SANCHEZ 417 VIA MALAGA REDONDO
BEACH
CA 0 (951)712-4959
CONDITIONS
Description: CORONEL / BRES2017-0249 / SFD SPRINKLER
Type: FIRE SPRINKLER Subtype: RESIDENTIAL - CUSTOM
HOMES
Status: FINALED Applied: 6/6/2018 SSW
Parcel No: 770165015 Site Address: 51325 CALLE JACUMBA LA QUINTA,CA 92253 Approved: 7/12/2018 RCA
Subdivision: DESERT CLUB TR UNIT 2 Block: 3 Lot: 4 Issued: 7/16/2018 SSW
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 9/27/2018 EGO
Valuation: $0.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
FINANCIAL INFORMATION
Printed: Friday, January 20, 2023 10:34:45 AM 1 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0098
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD ROUGH
PIPING
EGO 7/16/2018 7/16/2018 APPROVED
OVERHEAD HYRO EGO 7/16/2018 7/16/2018 APPROVED
FIRE FINAL**EGO 9/27/2018 9/27/2018 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
PERMIT TECH
BUCKET 6/6/2018 6/7/2018 6/13/2018 COMPLETE
PARENT PROJECTS
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $156.00 $156.00 6/6/18 R36215 4665 CHECK CHARLES F BROWN
FIRE PROTECTIO SSW
Total Paid for FIRE FEES: $156.00 $156.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 6/6/18 R36215 4665 CHECK CHARLES F BROWN
FIRE PROTECTIO SSW
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 6/6/18 R36215 4665 CHECK CHARLES F BROWN
FIRE PROTECTIO SSW
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$171.00 $171.00
Printed: Friday, January 20, 2023 10:34:45 AM 2 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0098
1ST FIRE (2 WK)EDGAR
GONZALEZ 6/13/2018 6/20/2018 6/20/2018 REVISIONS REQUIRED
FIRE SPRINKLER PLAN REVIEW - CORRECTIONS
1.) Provide water flow test for project. To be
conducted by local water district.
2.) Plan is missing hanger/strap location marks
indicating their installation location on plans.
3.) No pipe lengths are indicated on plans.
Please indicate pipe lengths in order to verify
hydraulic calculations.
4.) Provide appropriate architectural/engineer's
scale for reference.
5.) Provide underground detail with water meter
shown.
6.) Add MTR1 and MTR2 node points on
hydraulic calculations indicating friction loss
caused by water meter.
7.) Change fire sprinkler head legend in indicate
whether heads on floor plan are 3.0 or 4.9 K
Factor.
The sprinkler plans you submitted for the above
referenced project have been reviewed by
Riverside County Fire Department - Office of the
Fire Marshal personnel and are approved with
the following conditions.
Permanently marked identification signs shall be
attached to all control valves.
The following inspections/tests are required to be
witnessed by Office of the Fire Marshal Staff:
(a) Overhead Rough and Hydro static test: All
piping shall be visible and pumped at normal
operating pressure. *No jacketed electrical and
data wiring shall be in contact with, nor have the
potential to contact CPVC piping once insulation
is installed.
(b) Final inspection
Printed: Friday, January 20, 2023 10:34:45 AM 3 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0098
ATTACHMENTS
BOND INFORMATION
2ND FIRE (2 WK)EDGAR
GONZALEZ
6/28/2018 7/12/2018 7/12/2018 APPROVED-
CONDITIONS
The Fire Department approved plans and
conditions letter must be at the job site.
Applicant/installer shall be responsible to contact
the Fire Department to schedule inspections.
Requests for inspections are to be made at least
72 hours in advance and may be arranged by
calling (760)777-7000.
SUBJECT TO FIELD INSPECTION - Nothing in our
review shall be construed as encompassing
structural integrity. Review of this plan does not
authorize or approve any omission or deviation
from all applicable regulations. Final approval is
subject to field inspection.
All questions regarding the meaning of these
conditions should be referred to the Office of the
Fire Marshal staff at (760)777-7074.
Edgar Gonzalez - Fire Safety Specialist
Printed: Friday, January 20, 2023 10:34:45 AM 4 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0098