FSS2018-0102ADDITIONAL SITES
CHRONOLOGY
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
NOTE KAYLI ALFORD 10/14/2019 10/14/2019
RECEIVED A FINAL INSPECTION REQUEST FROM CONTRACTOR
FOR THIS PERMIT. THERE WAS NO ISSUE DATE, SO I ISSUED
THE PERMIT AS OF THE DATE OF APPROVAL, 7/2/18. THERE
WERE SEVERAL INSPECTIONS ALREADY ENTERED AND
APPROVED, AND ARMANDO CONFIRMED THE DATE OF THE
OH ROUGH/HYDRO AS 10/11/18. CHANGED EXPIRATION
DATE TO 6 MOS FROM DATE OF LAST INSPECTION - 4/11/19.
NOTE KAYLI ALFORD 10/14/2019 10/14/2019
RECEIVED FINAL INSPECTION REQUEST. PERMIT HAS EXPIRED,
INFORMED CONTRACTOR THAT A $40 EXTENSION FEE &
EXTENSION REQUEST LETTER WILL BE NEEDED IN ORDER TO
SCHEDULE THE INSPECTION.
CONDITIONS
Description: MACDONALD / FIRE SPRINKLER SYSTEM
Type: FIRE SPRINKLER Subtype: RESIDENTIAL - CUSTOM
HOMES
Status: FINALED Applied: 6/19/2018 AHI
Parcel No: 777140012 Site Address: 80875 VIA PORTOFINO LA QUINTA,CA 92253 Approved: 7/2/2018 RCA
Subdivision: TR 29894-2 Block: Lot: 152 Issued: 7/2/2018 KAL
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 10/23/2019 crw
Valuation: $0.00 Occupancy Type: Construction Type: Expired: 4/20/2020 KHET
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details: PER EDGAR G. PLANS WERE APPROVED 7/2/18 AND STATUS HAS BEEN CHANGED 8/28/18
Printed: Thursday, January 19, 2023 11:20:05 AM 1 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0102
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT ALEXIS RAMIREZ / RESIDENTIAL FIRE
SYSTEMS
8085 E CRYSTAL DRIVE ANAHEIM CA 92807 ENGINEERING@RESFIR
E.COM
CONTRACTOR RESIDENTIAL FIRE SYSTEMS INC 8085 E CRYSTAL DRIVE ANAHEIM CA 92807
OWNER JOHN AND LINDA MACDONALD LA QUINTA CA 92253
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED COMPLETED RESULT REMARKS NOTES
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE FAILED OR
ADDITIONAL RE-
INSPECTION
101-0000-42421 0 $161.00 $0.00
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $156.00 $156.00 6/19/18 R36678 1317 CHECK MICHAEL JEHA
CONSTRUCTION AHI
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED PC
101-0000-42420 0 $234.00 $234.00 6/19/18 R36678 1317 CHECK MICHAEL JEHA
CONSTRUCTION AHI
FIRE STAFF - PER HOUR 101-0000-42420 0.25 $40.00 $40.00 10/17/19 R54997 1738 CHECK MICHAEL JEHA
CONSTRUCTION, LLC AMA
Total Paid for FIRE FEES: $591.00 $430.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 6/19/18 R36678 1317 CHECK MICHAEL JEHA
CONSTRUCTION AHI
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 6/19/18 R36678 1317 CHECK MICHAEL JEHA
CONSTRUCTION AHI
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$606.00 $445.00
Printed: Thursday, January 19, 2023 11:20:05 AM 2 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0102
DATE DATE
OVERHEAD HYRO EGO PARTIALLY
APPROVED
2 ACCESSORY STRUCTURES ONLY. NOT
MAIN RESIDENCE.
OVERHEAD ROUGH
PIPING EGO 8/30/2018 8/30/2018 PARTIALLY
APPROVED
ACCESSORY STRUCTURES ONLY. NOT MAIN
RESIDENCE
OVERHEAD ROUGH
PIPING EGO 10/11/2018 10/11/2018 APPROVED
OVERHEAD HYRO EGO 10/11/2018 10/11/2018 APPROVED
FIRE FINAL**KHET 10/23/2019 10/23/2019 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
PERMIT TECH
BUCKET 6/19/2018 6/20/2018 6/19/2018 COMPLETE
FIRE SPRINKLER - PLAN REVIEW - APPROVED
WITH CONDITIONS:
The Riverside County Fire Department has
reviewed the Residential Fire Sprinkler plans and
they are approved with the following conditions
in accordance with NPFA 13D 2016:
General Requirements
1. Installation of sprinkler system shall only be
performed by people knowledgeable and trained
in such systems. Provide proof of training. NFPA
13D Sec. 4.6
2. Contractors Test and Material Certificate shall
be submitted upon final inspection. (NFPA 13 Sec.
24.1)
PARENT PROJECTS
Printed: Thursday, January 19, 2023 11:20:05 AM 3 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0102
1ST FIRE (2 WK)EDGAR
GONZALEZ 6/19/2018 7/3/2018 7/2/2018 APPROVED-
CONDITIONS
3. An owner’s manual for the fire sprinkler system
shall be provided to the owner.
4. A sign or valve tag shall be installed at the main
shutoff valve(s) to the water distribution system
stating:
“Warning, the water system in this home supplies
fire sprinklers that require certain flows and
pressures to fight a fire. Devices that restrict the
flow or decrease the pressure automatically shut
off the water to the fire sprinkler system, such as
water softeners filtration systems and automatic
shutoff valves, shall not be added to the system
without a review of the fire sprinkler system by a
fire protection specialist. Do not remove this
sign.”
5. Local water flow alarms shall be provided on all
sprinkler systems in homes not equipped with
smoke detectors. (NFPA 13D Sec. 7.6)
Inspection Requirements
1. Rough and Hydro: All piping must be visible
and hydrostatically tested for leakage at
normal system operating pressure OR
manufacturer’s prescribed pressure, PRIOR TO
CONCEALMENT.
2. Final Inspection.
The Fire Department job card, approved plans
and conditions letter must be at the job site
always.
Approval of this plan is subject to field inspection.
Should there be need for further information
Printed: Thursday, January 19, 2023 11:20:05 AM 4 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0102
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 7/26/2018 AARON HICKSON FIRE JOB CARD FIRE JOB CARD.doc
IMAGE 10/23/2019 KOHL HETRICK Stock unpainted trim
plates.JPG
Stock unpainted trim
plates.JPG 0
BOND INFORMATION
and/or clarification, please contact the
undersigned. Thank you for your continuing
cooperation in advance.
Printed: Thursday, January 19, 2023 11:20:05 AM 5 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0102
79485 Calle Tampico La Quinta, CA 92253 Main Number (760) 777-7158 Inspection Number (760)777-7131
CITY OF LA QUINTA FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 80875 VIA PORTOFINO PERMIT# : FSS2018-0102 DATE
ISSUED:
DESCRIPTION: MACDONALD / FIRE SPRINKLER SYSTEM CONTRACTOR:
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
79485 Calle Tampico La Quinta, CA 92253 Main Number (760) 777-7158 Inspection Number (760)777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration.
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may
cause the affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number
available when scheduling inspections. The inspection hotline for the City of La Quinta is (760)777-7131
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT
commence without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be
required to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the
responsible party not on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be
entered into the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire
Clearance has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building
Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS
MUST BE AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED
WITHIN 180 DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE
RESTRICTIVE REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.