FSS2018-0105ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT J C FIRE PROTECTION 81705 DE ORO AVENUE INDIO CA 92201 JCFIREPROTECTION@V
ERIZON.NET
BILL TO J C FIRE PROTECTION 81705 DE ORO AVENUE INDIO CA 92201 JCFIREPROTECTION@V
ERIZON.NET
CONTRACTOR J C FIRE PROTECTION 81705 DE ORO AVENUE INDIO CA 92201 JCFIREPROTECTION@V
ERIZON.NET
OWNER RICHARD LOTT 41534 NAVARRE CT PALM DESERT CA 0
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
PLAN CHECK PICKED UP MARY FASANO 7/5/2018 7/5/2018
CONDITIONS
Description: STEMMER / BRES2018-0160 / FIRE SPRINKLER
Type: FIRE SPRINKLER Subtype: RESIDENTIAL - CUSTOM
HOMES
Status: ISSUED Applied: 6/19/2018 RCA
Parcel No: 773154017 Site Address: 51855 AVENIDA JUAREZ LA QUINTA,CA 92253 Approved: 7/26/2018 EGO
Subdivision: SANTA CARMELITA VALE LA QUINTA
UNIT 2
Block: 31 Lot: 5 Issued: 7/27/2018 AMA
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled:
Valuation: $0.00 Occupancy Type: Construction Type: Expired: 2/25/2019 EGO
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
FINANCIAL INFORMATION
Printed: Friday, January 20, 2023 10:32:23 AM 1 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0105
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD ROUGH
PIPING
EGO 8/23/2018 8/23/2018 APPROVED
OVERHEAD HYRO EGO 8/23/2018 8/23/2018 APPROVED
FIRE FINAL**EGO 12/6/2018 12/6/2018 DISAPPROVE
D
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
PARENT PROJECTS
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $156.00 $156.00 6/19/18 R36699 1437 CHECK J C FIRE PROTECTION AMA
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED PC
101-0000-42420 0 $234.00 $234.00 6/19/18 R36699 1437 CHECK J C FIRE PROTECTION AMA
Total Paid for FIRE FEES: $390.00 $390.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 6/19/18 R36699 1437 CHECK J C FIRE PROTECTION AMA
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 6/19/18 R36699 1437 CHECK J C FIRE PROTECTION AMA
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$405.00 $405.00
Printed: Friday, January 20, 2023 10:32:23 AM 2 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0105
1ST PERMIT TECH (1
DAY)
REYNA
CAMARENA 6/19/2018 6/19/2018 6/19/2018 COMPLETE
1ST FIRE (2 WK)EDGAR
GONZALEZ 6/19/2018 7/4/2018 7/3/2018 REVISIONS REQUIRED
FIRE SPRINKLER - PLAN REVIEW - REVSIONS
REQUIRED:
The Riverside County Fire Department – City of La
Quinta Fire Marshal’s Office has reviewed your
submitted plans and the following corrections
addressed before approval is granted:
1.) Provide hanger/strap location on plans.
2.) Hydraulic calculations for 2 head calc. (for
concealed VK488 heads with 3.0 k factor at a
14X14 spacing) indicate that only 10gpm is
available at most remote, while cut sheets
submitted indicate that a minimum of 13gpm is
required for proper operation. Please correct
hydraulic calculations or clarify.
FIRE SPRINKLER SYSTEM - PLAN REVIEW
CONDITIONS OF APPROVAL:
7/26/2018
JC Fire Protection
81-705 De Oro Ave.
Indio CA, 92201
Re: Residential Fire Sprinkler Plan Review –
Stemmer – Juarez Residence
FSS2018-0105
51-855 Avenida Juarez
La Quinta CA, 92253
The sprinkler plans you submitted for the above
referenced project have been reviewed by
Riverside County Fire Department - Office of the
Printed: Friday, January 20, 2023 10:32:23 AM 3 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0105
2ND FIRE (2 WK)EDGAR
GONZALEZ 7/10/2018 7/24/2018 7/26/2018 APPROVED-
CONDITIONS
Fire Marshal personnel and are approved with
the following conditions.
Permanently marked identification signs shall be
attached to all control valves.
The following inspections/tests are required to be
witnessed by Office of the Fire Marshal Staff:
(a) Overhead Rough and Hydro static test: All
piping shall be visible and pumped at normal
operating pressure. *No jacketed electrical and
data wiring shall be in contact with, nor have the
potential to contact CPVC piping once insulation
is installed.
(b) Final inspection
The Fire Department approved plans and
conditions letter must be at the job site.
Applicant/installer shall be responsible to contact
the Fire Department to schedule inspections.
Requests for inspections are to be made at least
72 hours in advance and may be arranged by
calling (760)863-8886.
SUBJECT TO FIELD INSPECTION - Nothing in our
review shall be construed as encompassing
structural integrity. Review of this plan does not
authorize or approve any omission or deviation
from all applicable regulations. Final approval is
subject to field inspection.
All questions regarding the meaning of these
conditions should be referred to the Office of the
Fire Marshal staff at (760)895-9006.
Edgar Gonzalez
Printed: Friday, January 20, 2023 10:32:23 AM 4 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0105
ATTACHMENTS
BOND INFORMATION
Fire Safety Specialist
Printed: Friday, January 20, 2023 10:32:23 AM 5 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0105