FSS2018-0108ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT MARK TRELAK /DESERT FIRE
EXTINGUISHER CO INC
P O BOX 1607 PALM SPRINGS CA 92263 (760)322-0995 MARK@DESERT-
FIRE.COM
BILL TO DESERT FIRE EXTINGUISHER CO INC P O BOX 1607 PALM SPRINGS CA 92263 (760)322-0995 MARK@DESERT-
FIRE.COM
CONTRACTOR DESERT FIRE EXTINGUISHER CO INC P O BOX 1607 PALM SPRINGS CA 92263 (760)322-0995 MARK@DESERT-
FIRE.COM
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
NOTE ARMANDO MAGALLON 7/17/2018 7/17/2018 PERMIT AND JOB CARD ISSUED
PLAN CHECK PICKED UP ARMANDO MAGALLON 7/5/2018 7/5/2018 APPLICANT PICKED UP 3 SETS OF PLANS AND CUTSHEETS
RESUBMITTAL STEPHANIE SWANSTROM 7/11/2018 7/11/2018
CONDITIONS
Description: PGA / MULTI USE BUILDING
Type: FIRE SPRINKLER Subtype:
COMMERCIAL/INDUSTRIAL
Status: FINALED Applied: 6/29/2018 AHI
Parcel No: 775220027 Site Address: 55955 PGA BLVD LA QUINTA,CA 92253 Approved: 7/16/2018 EGO
Subdivision: PM 24995 Block: Lot: 4 Issued: 7/17/2018 AMA
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 11/9/2018 EGO
Valuation: $0.00 Occupancy Type: Construction Type: Expired: 5/8/2019 EGO
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
Printed: Wednesday, January 18, 2023 4:40:14 PM 1 of 8
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0108
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
FIRE FINAL**EGO APPROVED
OVERHEAD ROUGH
PIPING EGO 7/23/2018 7/24/2018
APPROVED
W/EXCEPTIO
N
AS BUILT DRAWINGS TO BE SUBMITTED
BEFORE FINAL.
OVERHEAD HYRO EGO 7/23/2018 7/23/2018
APPROVED
W/EXCEPTIO
N
AS BUILT DRAWINGS TO BE SUBMITTED
BEFORE FINAL INSPECTION.
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPRINKLER
SYSTEMS
COMMERCIAL/INDUSTR
IAL
101-0000-42421 0 $234.00 $234.00 6/29/18 R37044 354 CHECK DESRT FIRE
EXTINGUISHER AHI
FIRE SPRINKLER
SYSTEMS
COMMERCIAL/INDUSTR
IAL PC
101-0000-42420 0 $390.00 $390.00 6/29/18 R37044 354 CHECK DESRT FIRE
EXTINGUISHER AHI
Total Paid for FIRE FEES: $624.00 $624.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 6/29/18 R37044 354 CHECK DESRT FIRE
EXTINGUISHER AHI
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 6/29/18 R37044 354 CHECK DESRT FIRE
EXTINGUISHER AHI
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$639.00 $639.00
Printed: Wednesday, January 18, 2023 4:40:14 PM 2 of 8
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0108
UG HYDRO EGO 10/25/2018 10/25/2018
APPROVED
W/EXCEPTIO
N
FLUSH EGO 10/25/2018 10/25/2018
APPROVED
W/EXCEPTIO
N
CORRECTIONS WRITTEN AND ISSUED TO
CONTRACTOR.
FIRE FINAL**EGO 11/9/2018 11/9/2018 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
1ST FIRE (2 WK)EDGAR
GONZALEZ 6/18/2018 7/2/2018 7/2/2018 REVISIONS REQUIRED
PERMIT WAS APPLIED FOR ON 6/18/2018 AND
NOT PROCESSED BY TECH APPLICANT CAME IN TO
CHECK STATUS AND DISCOVERED MISTAKE.
INFORMED APPLICANT WILL LET REVIEWER
KNOW OF MISTAKE AND TRY TO EXPIDITE
PARENT PROJECTS
Printed: Wednesday, January 18, 2023 4:40:14 PM 3 of 8
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0108
1ST FIRE (2 WK)EDGAR
GONZALEZ 6/18/2018 7/2/2018 7/2/2018 REVISIONS REQUIRED
FIRE SPRINKLER - PLAN REVIEW - REVISIONS
REQUESTED.The Riverside County Fire
Department – City of La Quinta Fire Marshal’s
Office has reviewed your submitted plans and the
following corrections addressed before approval
is granted:1.) Provide elevation plan for
building.2.) Pipe lengths are not shown on floor
plan. Please show pipe lengths in order to verify
hydraulic calculations.3.) Note of building's
details is not shown on plan. Provide building
construction classification and square footage
and occupancy classification for reference.4.)
System's remote calculated area is not identified
on plan. Please provide for reference on floor
plan.5.) Fire flow test is not within a year's date.
Only fire flow tests that were conducted within a
year from current date will be taken. Please
provide an updated fire flow report with a map
locating fire hydrants that were utilized for
testing for reference. 6.) Show fire sprinkler head
spacing on plan.7.) Identify pipe diameter size
from node point TR to 55. (Hydraulic calculations
show 4'') 8.) Upright fire sprinklers for concealed
spaces show 155 degree temperature heads.
Please revise with an intermediate temperature
fire sprinkler head or clarify.9.) Please note that
underground fire service main plans/permit have
not been submitted/approved. If underground
fire main plans differ from the floor plan that was
submitted, a resubmittal to this plan shall be
provided upon field inspection.
1ST PERMIT TECH (1
DAY)
PERMIT TECH
BUCKET 6/29/2018 7/2/2018 7/2/2018
FIRE SPRINKLER SYSTEM - CONDITIONS OF
APPROVAL.
Printed: Wednesday, January 18, 2023 4:40:14 PM 4 of 8
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0108
The sprinkler plans you submitted for the above
referenced project have been reviewed by
Riverside County Fire Department – Office of the
Fire Marshal personnel and are approved with
the following conditions:
Underground Fire Service Main Conditions:
The following inspections and tests must be
observed:
1) Pre-Pour Thrust Block cutout inspection
2) Rough Piping – Confirm pipe material, bury
depth and backfill requirements
3) Hydrostatic Test –
a. Minimum 200 psi for two (2) hours or at 50 psi
in excess of the maximum static pressure when it
is in excess of 150 psi.
4) Underground Flush & Final -
a. Flush of the underground supply line until clear
of all debris and to the satisfaction of the
inspector.
b. The underground flush shall be done through a
pipe or hose equal in size to the sprinkler
underground supply pipe, prior to connection to
the above ground sprinkler piping.
c. Appropriate valve and connection signage is
provided
Printed: Wednesday, January 18, 2023 4:40:14 PM 5 of 8
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0108
2ND FIRE (2 WK)EDGAR
GONZALEZ 7/11/2018 7/25/2018 7/16/2018 APPROVED-
CONDITIONS
d. Private fire hydrants are painted red and
provided with OSFM tag.
e. Provide the completed Contractor’s Material
and Test Certificate for Underground Pipe
Fire Sprinkler System Conditions:
1) Approval of these plans does not include the
piping of the underground system. Installing
contractor shall provide separate underground
plans for review and approval prior to
installation.
2) The completed Contractor’s Material and Test
Certificate for Aboveground Piping shall be
provided to the fire inspector prior to a final
inspection.
3) Permanently marked identification signs shall
be attached to all control valves.
4) A sign shall be located adjacent to the alarm
bell worded as follows:
a) SPRINKLER FIRE ALARM - WHEN BELL RINGS
CALL 911
5) Provide for 24 hour monitoring of the sprinkler
alarm system.
6) The following inspections/tests are required to
be witnessed by Office of the Fire Marshal staff:
Printed: Wednesday, January 18, 2023 4:40:14 PM 6 of 8
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0108
a) Overhead Rough: All installed/relocated piping
must be visible.
b) Overhead Hydro: Entire system shall be
hydrostatically tested at a minimum of 200 psi for
2 hours.
c) Underground Supply Flush: Flush of the
underground supply line until clear of all debris
and to the satisfaction of the inspector.
d) Final inspection: Water-flow signal test as
performed from the inspector test valve. As-Built
plans required to be maintained on site as
approved by the inspector. General Information
sign and Hydraulic Calculation plate(s) affixed to
riser and engraved with information in a
permanent fashion. Title 19 “New” system tag
affixed to riser.
NOTE: The underground flush shall be done
through a pipe or hose equal in size to the
sprinkler underground supply pipe, prior to
connection to the above ground sprinkler piping.
The Fire Department approved plans, job card
and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact
the Fire Department to schedule inspections.
Requests for inspections are to be made at least
72 hours in advance and may be arranged by
calling (760)777-7000.
Printed: Wednesday, January 18, 2023 4:40:14 PM 7 of 8
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0108
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 11/15/2018 EDGAR GONZALEZ
FSS2018-0108 PGA FIRE
SPRINKLER UG HOLD
HARMLESS.pdf
FSS2018-0108 PGA FIRE
SPRINKLER UG HOLD
HARMLESS.pdf
1
DOC 11/15/2018 EDGAR GONZALEZ
FSS2018-0108 PGA West
Mutiuse Bldg Orr Hold
Harmless - County
Riverside ....pdf
FSS2018-0108 PGA West
Mutiuse Bldg Orr Hold
Harmless - County
Riverside ....pdf
1
DOC 11/15/2018 EDGAR GONZALEZ
FSS2018-0108 PGA West
Underground piping
test certificate .pdf
FSS2018-0108 PGA West
Underground piping
test certificate .pdf
1
BOND INFORMATION
SUBJECT TO FIELD INSPECTION - Nothing in our
review shall be construed as encompassing
structural integrity. Review of this plan does not
authorize or approve any omission or deviation
from all applicable regulations. Final approval is
subject to field inspection.
All questions regarding the meaning of these
conditions should be referred to the Office of the
Fire Marshal staff at (760)777-7074.
Printed: Wednesday, January 18, 2023 4:40:14 PM 8 of 8
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0108