FSS2018-0110ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT J C FIRE PROTECTION 81705 DE ORO AVENUE INDIO CA 92201 (760)819-5476 JCFIREPROTECTION@V
ERIZON.NET
BILL TO J C FIRE PROTECTION 81705 DE ORO AVENUE INDIO CA 92201 (760)819-5476 JCFIREPROTECTION@V
ERIZON.NET
CONTRACTOR J C FIRE PROTECTION 81705 DE ORO AVENUE INDIO CA 92201 (760)819-5476 JCFIREPROTECTION@V
ERIZON.NET
OWNER BRIAN STEMMER 52940 AVENIDA
VELASCO
LA QUINTA CA 92253 (760)819-5476
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
PLAN CHECK PICKED UP AARON HICKSON 8/10/2018 8/10/2018 BRIAN STEMMER PICKED UP PLAN CHECK
CONDITIONS
Description: STEMMER / VELASCO FIRE SPRINKLER
Type: FIRE SPRINKLER Subtype: RESIDENTIAL - CUSTOM
HOMES
Status: FINALED Applied: 7/2/2018 AHI
Parcel No: 774054025 Site Address: 53095 AVENIDA VELASCO LA QUINTA,CA 92253 Approved: 7/20/2018 EGO
Subdivision: SANTA CARMELITA VALE LA QUINTA
UNIT 21
Block: 217 Lot: 5 Issued: 9/17/2018 AHI
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 1/9/2019 EGO
Valuation: $0.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
Printed: Tuesday, January 31, 2023 12:02:40 PM 1 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0110
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD ROUGH
PIPING
EGO 10/30/2018 10/30/2018 APPROVED
OVERHEAD HYRO EGO 10/30/2018 10/30/2018 APPROVED
FIRE FINAL**EGO 1/9/2019 1/9/2019 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
PARENT PROJECTS
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $156.00 $156.00 7/2/18 R37135 1447 CHECK J C FIRE PROTECTION AHI
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED PC
101-0000-42420 0 $234.00 $234.00 7/2/18 R37135 1447 CHECK J C FIRE PROTECTION AHI
Total Paid for FIRE FEES: $390.00 $390.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 7/2/18 R37135 1447 CHECK J C FIRE PROTECTION AHI
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 7/2/18 R37135 1447 CHECK J C FIRE PROTECTION AHI
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$405.00 $405.00
Printed: Tuesday, January 31, 2023 12:02:40 PM 2 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0110
1ST PERMIT TECH (1
DAY)
AARON
HICKSON 7/2/2018 7/3/2018 7/3/2018 COMPLETE
1ST FIRE (2 WK)EDGAR
GONZALEZ 7/2/2018 7/16/2018 7/20/2018 APPROVED-
CONDITIONS
The Riverside County Fire Department has
reviewed the Residential Fire Sprinkler plans and
they are approved with the following conditions
in accordance with NPFA 13D 2016:
General Requirements
1. Installation of sprinkler system shall only be
performed by people knowledgeable and trained
in such systems. Provide proof of training. NFPA
13D Sec. 4.6
2. Contractors Test and Material Certificate shall
be submitted upon final inspection. (NFPA 13 Sec.
24.1)
3. An owner’s manual for the fire sprinkler system
shall be provided to the owner.
4. A sign or valve tag shall be installed at the main
shutoff valve(s) to the water distribution system
stating:
“Warning, the water system in this home supplies
fire sprinklers that require certain flows and
pressures to fight a fire. Devices that restrict the
flow or decrease the pressure automatically shut
off the water to the fire sprinkler system, such as
water softeners filtration systems and automatic
shutoff valves, shall not be added to the system
without a review of the fire sprinkler system by a
fire protection specialist. Do not remove this
sign.”
5. Local water flow alarms shall be provided on all
sprinkler systems in homes not equipped with
smoke detectors. (NFPA 13D Sec. 7.6)
Printed: Tuesday, January 31, 2023 12:02:40 PM 3 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0110
ATTACHMENTS
BOND INFORMATION
Inspection Requirements
1. Rough and Hydro: All piping must be visible
and hydrostatically tested for leakage at
normal system operating pressure OR
manufacturer’s prescribed pressure, PRIOR TO
CONCEALMENT.
2. Final Inspection.
The Fire Department job card, approved plans
and conditions letter must be at the job site
always.
Approval of this plan is subject to field inspection.
Should there be need for further information
and/or clarification, please contact the
undersigned. Thank you for your continuing
cooperation in advance.
Edgar Gonzalez
Fire Safety Specialist
Printed: Tuesday, January 31, 2023 12:02:40 PM 4 of 4