FSS2018-0122ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT C J SUPPRESSION INC 205 LEWIS COURT CORONA CA 92882 estimating@cjsuppress
ion.com
CONTRACTOR C J SUPPRESSION INC 205 LEWIS COURT CORONA CA 92882 estimating@cjsuppress
ion.com
OWNER P6K PORTFOLIO KDP 2301 ROSECRANS STE
2110
EL SEGUNDO CA 92253
CONDITIONS
Description: STARBUCKS / FIRE SPRINKLER
Type: FIRE SPRINKLER Subtype: TENANT IMPROVEMENT Status: FINALED Applied: 7/25/2018 AHI
Parcel No: 600440008 Site Address: 79845 HIGHWAY 111 STE 104 LA QUINTA,CA 92253 Approved: 8/7/2018 EGO
Subdivision: PM 036269 Block: Lot: 8 Issued:
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 9/25/2018 EGO
Valuation: $0.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details: I SPOKE WITH JORDAN OF CJ SUPPRESSION REGARDING HAVING THE JOB CARD ON SITE AT TIME OF INSPECTION. I DIDN'T SEE A
PICK UP DATE BUT HE SAID THAT IT WAS PICKED UP. HE WILL DOUBLE CHECK.
FINANCIAL INFORMATION
Printed: Tuesday, January 31, 2023 12:21:22 PM 1 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0122
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD ROUGH
PIPING EGO 9/6/2018 9/10/2018 PARTIALLY
APPROVED
ONLY CERTAIN AREAS WERE READY FOR
INSPECTION. SEE APPROVED PLANS FOR
FURTHER DETAILS.
FIRE FINAL**EGO 9/17/2018 9/17/2018 DISAPPROVE
D
FIRE FINAL**EGO 9/25/2018 9/25/2018 APPROVED
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
Credit Card Fee 101-0000-43505 0 $7.29 $7.29 7/25/18 R37891 0001 CREDIT
CARD C J SUPPRESSION INC AHI
Total Paid for Credit Card Fee: $7.29 $7.29
FIRE SPRINKLER
SYSTEMS - TENANT
IMPROVEMENT OVER
10 HEADS
101-0000-42420 0 $156.00 $156.00 7/25/18 R37891 0001 CREDIT
CARD C J SUPPRESSION INC AHI
FIRE SPRINKLER
SYSTEMS - TENANT
IMPROVEMENT OVER
10 HEADS PC
101-0000-42420 0 $234.00 $234.00 7/25/18 R37891 0001 CREDIT
CARD C J SUPPRESSION INC AHI
Total Paid for FIRE FEES: $390.00 $390.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 7/25/18 R37891 0001 CREDIT
CARD C J SUPPRESSION INC AHI
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 7/25/18 R37891 0001 CREDIT
CARD C J SUPPRESSION INC AHI
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$412.29 $412.29
Printed: Tuesday, January 31, 2023 12:21:22 PM 2 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0122
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
AARON
HICKSON 7/25/2018 7/26/2018 7/31/2018 COMPLETE
1ST FIRE (2 WK)FIRE BUCKET 7/25/2018 8/8/2018 8/7/2018 APPROVED-
CONDITIONS
8/7/2018
Jordan Lundberg
CJ Suppression
205 Lewis Ct.
Corona, CA 92882
Re: Starbucks
FSS2018-0122 – Fire Sprinkler TI
79-845 Hwy 111 – 104
La Quinta, CA 92253
The Fire Sprinkler TI plans you submitted for the
above referenced project have been reviewed by
the Riverside County Fire Department and are
approved with the following conditions:
1.) Provide spare sprinkler head of each type
installed at fire sprinkler riser’s spare head box (at
least 1.)
2.) Existing fire sprinkler system shall have a
current 5 year inspection/certification. Proof
shall be provided on or before final is granted.
3.) Fire Sprinkler system tenant improvements
with 20 or more heads augmented/affected shall
be hydrostatically tested at 200 psi or 50 above
static pressure, whichever is greater.
4.) Approval of this plan is subject on the
following field inspections:
PARENT PROJECTS
Printed: Tuesday, January 31, 2023 12:21:22 PM 3 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0122
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 8/7/2018 EDGAR GONZALEZ
FSS2018-0122 -
STARBUCKS - 79-845
HWY 111 - 104 - FIRE
SPRINKLER TI -
(COA).docx
FSS2018-0122 -
STARBUCKS - 79-845
HWY 111 - 104 - FIRE
SPRINKLER TI -
(COA).docx
0
BOND INFORMATION
• Overhead Rough/Piping Inspection
• Final Inspection
The Fire Department approved plans and
conditions letter must be at the job site.
Applicant/installer shall be responsible to contact
the Fire Department to schedule inspections.
Requests for inspections are to be made at least
72 hours in advance and may be arranged by
calling (760)777-7000.
SUBJECT TO FIELD INSPECTION - Nothing in our
review shall be construed as encompassing
structural integrity. Review of this plan does not
authorize or approve any omission or deviation
from all applicable regulations. Final approval is
subject to field inspection.
All questions regarding the meaning of these
conditions should be referred to the Office of the
Fire Marshal staff at (760)777-7074.
Edgar Gonzalez - Fire Safety Specialist
Printed: Tuesday, January 31, 2023 12:21:22 PM 4 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0122