FSS2018-0129ADDITIONAL SITES
CHRONOLOGY
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
TELEPHONE CALL AARON HICKSON 8/17/2018 8/17/2018 JOHN PAULUS CALLED AND ASKED ABOUT STAMPED PLANS.
FOR THIS PERMIT AND ASKED ABOUT REFUND.
TELEPHONE CALL EDGAR GONZALEZ 8/14/2018 8/16/2018
SHASTA IS ADDING 1 SPRINKLER HEAD, THEY ARE
QUESTIONING THE FEE AS IT'S THE SAME AS A NEW HOUSE
OR RISER AND SYSTEM,,,, CAN YOU PLEASE GIVE JOHN
PAULUS (951)242-1621.
EDGAR, STEPHANIE SENT THIS TO ME TO FOLLOW UP WITH
BUT I AM NOT FAMILIAR WITH THE FIRE FEES, I KNOW WITH
OUR BUILDING FEES WE BASE THEM ON GETTING OUT THERE
TO DO THE WORK, SO WHETHER IT IS ONE RECEPTACLE OR
20, IT TAKES ABOUT THE SAME AMOUNT OF TIME, AND
THEIR ISN'T A DISCOUNT OF DOING JUST ONE.
I SPOKE WITH REYNA AND BUILDING PERMITS TECHINICIANS
IN REGARDS TO THIS MATTER. THEY WILL NEED TO PAY FOR
THE FULL $405.00 FEE FOR PLAN CHECK AND INSPECTIONS.
Description: WALMART / BCOM2018-0016 / FIRE SPRINKLERS
Type: FIRE SPRINKLER (WEB)Subtype:
COMMERCIAL/INDUSTRIAL
Status: FINALED Applied: 8/8/2018 EPRS
Parcel No: 600340027 Site Address: 79295 HIGHWAY 111 LA QUINTA,CA 92253 Approved: 8/16/2018 EGO
Subdivision: PM 30420 Block: Lot: 1 Issued: 8/16/2018 AMA
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 10/1/2018 EGO
Valuation: $4,500.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
Printed: Friday, February 10, 2023 10:56:58 AM 1 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0129
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT John Paulus 72120 Northshore St.
Ste. "C"
Thousand Palms CA 92276 (760)404-1350 jpaulus@shastafire.co
m
BILL TO SHASTA FIRE PROTECTION INC 72120 NORTHSHORE ST
#C
THOUSAND
PALMS
CA 92276 (760)404-1350 JSTAHL@SHASTAFIRE.C
OM
CONTRACTOR SHASTA FIRE PROTECTION INC 72120 NORTHSHORE ST
#C
THOUSAND
PALMS
CA 92276 (760)404-1350 JSTAHL@SHASTAFIRE.C
OM
OWNER WAL MART REAL ESTATE BUSINES 72120 Northshore St.
Ste. "C"
Thousand Palms CA 92276 (760)404-1350 jpaulus@shastafire.co
m
CONDITIONS
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
Credit Card Fee 101-0000-43505 0 $11.50 $11.50 8/8/18 WEB2804 CREDIT John Paulus EPRS
Total Paid for Credit Card Fee: $11.50 $11.50
FIRE SPRINKLER
SYSTEMS
COMMERCIAL/INDUSTR
IAL
101-0000-42421 0 $234.00 $234.00 8/8/18 WEB2804 CREDIT John Paulus EPRS
FIRE SPRINKLER
SYSTEMS
COMMERCIAL/INDUSTR
IAL PC
101-0000-42420 0 $390.00 $390.00 8/8/18 WEB2804 CREDIT John Paulus EPRS
Total Paid for FIRE FEES: $624.00 $624.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 8/8/18 WEB2804 CREDIT John Paulus EPRS
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
Printed: Friday, February 10, 2023 10:56:58 AM 2 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0129
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD ROUGH
PIPING EGO 8/29/2018 8/29/2018
APPROVED
W/EXCEPTIO
N
CONTRACTOR TO CALL BACK FOR FINAL
INSPECTION. DID NOT HAVE A SPARE
SPRINKLER HEAD TO PROVIDE AT HEAD BOX.
FIRE FINAL**EGO 10/1/2018 10/1/2018 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
PERMIT TECH
BUCKET 8/8/2018 8/9/2018 8/9/2018 COMPLETE
8/16/2018
Shasta Fire Protection
72120 Northshore St.
Thousand Palms CA
Re: Fire Sprinkler TI (Fire Sprinkler TI)
Wal-Mart
79-295 Hwy 111
La Quinta CA
The Fire Sprinkler TI plans you submitted for the
PARENT PROJECTS
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 8/8/18 WEB2804 CREDIT John Paulus EPRS
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$650.50 $650.50
Printed: Friday, February 10, 2023 10:56:58 AM 3 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0129
1ST FIRE (2 WK)EDGAR
GONZALEZ 8/8/2018 8/22/2018 8/16/2018 APPROVED-
CONDITIONS
above referenced project have been reviewed by
the Riverside County Fire Department and are
approved with the following conditions:
1.) Provide spare sprinkler head of each type
installed at fire sprinkler riser’s spare head box (at
least 1.)
2.) Existing fire sprinkler system shall have a
current 5 year inspection/certification. Proof
shall be provided on or before final is granted.
3.) Fire Sprinkler system tenant improvements
with 20 or more heads augmented/affected shall
be hydrostatically tested at 200 psi or 50 above
static pressure, whichever is greater.
4.) Approval of this plan is subject on the
following field inspections:
• Overhead Rough/Piping Inspection
• Final Inspection
The Fire Department approved plans and
conditions letter must be at the job site.
Applicant/installer shall be responsible to contact
the Fire Department to schedule inspections.
Requests for inspections are to be made at least
72 hours in advance and may be arranged by
calling (760)777-7000.
SUBJECT TO FIELD INSPECTION - Nothing in our
review shall be construed as encompassing
structural integrity. Review of this plan does not
authorize or approve any omission or deviation
from all applicable regulations. Final approval is
subject to field inspection.
All questions regarding the meaning of these
conditions should be referred to the Office of the
Fire Marshal staff at (760)777-7074.
Printed: Friday, February 10, 2023 10:56:58 AM 4 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0129
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 8/8/2018 EtrakitPublicReg SITE PLAN 18-050 WALMART LA
QUINTA T.I. 8-8-18.pdf 1
DOC 8/8/2018 EtrakitPublicReg SPRINKLER
SPECIFICATIONS
TYCO TY 5251 ELO
SSP.pdf 1
BOND INFORMATION
Edgar Gonzalez - Fire Safety Specialist
Printed: Friday, February 10, 2023 10:56:58 AM 5 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0129