FSS2018-0136ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT A & D FIRE SPRINKLERS INC 7130 CONVOY CT SAN DIEGO CA 92111 JC@ADFIRESPRINKLERS
.COM
BILL TO A & D FIRE SPRINKLERS INC 7130 CONVOY CT SAN DIEGO CA 92111 JC@ADFIRESPRINKLERS
.COM
CONTRACTOR A & D FIRE SPRINKLERS INC 7130 CONVOY CT SAN DIEGO CA 92111 JC@ADFIRESPRINKLERS
.COM
OWNER TARGET CORP 1000 NICOLLET MALL
TPN 12
MINNEAPOLIS MN 92253
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
PUBLIC COUNTER VISIT AARON HICKSON 10/23/2018 10/23/2018 CARLOS CORTEZ PICKED UP APPROVED PLANS
CONDITIONS
Description: TARGET / SPRINKLERS
Type: FIRE SPRINKLER Subtype: TENANT IMPROVEMENT Status: FINALED Applied: 8/27/2018 SSW
Parcel No: 643020029 Site Address: 78935 HIGHWAY 111 LA QUINTA,CA 92253 Approved: 9/10/2018 EGO
Subdivision: PM 30903 Block: Lot: 5 Issued: 10/23/2018 AHI
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 10/30/2018 EGO
Valuation: $0.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
Printed: Thursday, January 19, 2023 12:32:08 PM 1 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0136
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD ROUGH
PIPING EGO 10/25/2018 10/25/2018 DISAPPROVE
D
OVERHEAD ROUGH
PIPING
EGO 10/30/2018 10/30/2018 APPROVED
FIRE FINAL**EGO 10/30/2018 10/30/2018 APPROVED
REVIEWS
PARENT PROJECTS
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPRINKLER
SYSTEMS - TENANT
IMPROVEMENT OVER
10 HEADS
101-0000-42420 0 $156.00 $156.00 8/27/18 MR611 2899 CHECK A & D FIRE
SPRINKLERS INC SSW
FIRE SPRINKLER
SYSTEMS - TENANT
IMPROVEMENT OVER
10 HEADS PC
101-0000-42420 0 $234.00 $234.00 8/27/18 MR611 2899 CHECK A & D FIRE
SPRINKLERS INC SSW
Total Paid for FIRE FEES: $390.00 $390.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 8/27/18 MR611 2899 CHECK A & D FIRE
SPRINKLERS INC SSW
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 8/27/18 MR611 2899 CHECK A & D FIRE
SPRINKLERS INC SSW
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$405.00 $405.00
Printed: Thursday, January 19, 2023 12:32:08 PM 2 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0136
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
PERMIT TECH
BUCKET 8/27/2018 8/28/2018 8/27/2018 COMPLETE
1ST FIRE (2 WK)EDGAR
GONZALEZ 8/27/2018 9/10/2018 9/10/2018 APPROVED-
CONDITIONS
9/10/2018
A and D Fire Protection
7130 Convoy Ct.
San Diego CA, 92111
Re: Target #1867
Fire Sprinkler TI – FSS2018-0136
78-935 Hwy 111
La Quinta CA, 92253
The Fire Sprinkler TI plans you submitted for the
above referenced project have been reviewed by
the Riverside County Fire Department and are
approved with the following conditions:
1.) Provide spare sprinkler head of each type
installed at fire sprinkler riser’s spare head box (at
least 1.)
2.) Existing fire sprinkler system shall have a
current 5 year inspection/certification. Proof
shall be provided on or before final is granted.
3.) Fire Sprinkler system tenant improvements
with 20 or more heads augmented/affected shall
be hydrostatically tested at 200 psi or 50 above
static pressure, whichever is greater.
4.) Approval of this plan is subject on the
following field inspections:
• Overhead Rough/Piping Inspection
• Final Inspection
The Fire Department approved plans and
conditions letter must be at the job site.
Printed: Thursday, January 19, 2023 12:32:08 PM 3 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0136
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 9/10/2018 EDGAR GONZALEZ
FSS2018-0136 - TARGET
- 78935 HWY 111 - FIRE
SPRINKLER TI
(COA).docx
FSS2018-0136 - TARGET
- 78935 HWY 111 - FIRE
SPRINKLER TI
(COA).docx
1
BOND INFORMATION
Applicant/installer shall be responsible to contact
the Fire Department to schedule inspections.
Requests for inspections are to be made at least
72 hours in advance and may be arranged by
calling (760)777-7131.
SUBJECT TO FIELD INSPECTION - Nothing in our
review shall be construed as encompassing
structural integrity. Review of this plan does not
authorize or approve any omission or deviation
from all applicable regulations. Final approval is
subject to field inspection.
All questions regarding the meaning of these
conditions should be referred to the Office of the
Fire Marshal staff at (760)777-7074.
Edgar Gonzalez - Fire Safety Specialist
Printed: Thursday, January 19, 2023 12:32:08 PM 4 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0136
Office of the Fire Marshal
City of La Quinta
78-495 Calle Tampico, La Quinta CA 92253
• Phone (760)777-7000 •Direct (760)777-7074
9/10/2018
A and D Fire Protection
7130 Convoy Ct.
San Diego CA, 92111
Re: Target #1867
Fire Sprinkler TI – FSS2018-0136
78-935 Hwy 111
La Quinta CA, 92253
The Fire Sprinkler TI plans you submitted for the above referenced project have been reviewed by the
Riverside County Fire Department and are approved with the following conditions:
1.) Provide spare sprinkler head of each type installed at fire sprinkler riser’s spare head box (at least 1.)
2.) Existing fire sprinkler system shall have a current 5 year inspection/certification. Proof shall be
provided on or before final is granted.
3.) Fire Sprinkler system tenant improvements with 20 or more heads augmented/affected shall be
hydrostatically tested at 200 psi or 50 above static pressure, whichever is greater.
4.) Approval of this plan is subject on the following field inspections:
• Overhead Rough/Piping Inspection
• Final Inspection
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests
for inspections are to be made at least 72 hours in advance and may be arranged by calling (760)777-
7131.
SUBJECT TO FIELD INSPECTION - Nothing in our review shall be construed as encompassing
structural integrity. Review of this plan does not authorize or approve any omission or deviation from
all applicable regulations. Final approval is subject to field inspection.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire
Marshal staff at (760)777-7074.
Edgar Gonzalez - Fire Safety Specialist