FSS2018-0164ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT DAART ENGINEERING COMPANY INC 1598 NORTH H STREET SAN
BERNARDINO
CA 92405 (909)888-8696 SUSAN@DAARTENG.C
OM
BILL TO DAART ENGINEERING COMPANY INC 1598 NORTH H STREET SAN
BERNARDINO
CA 92405 (909)888-8696 BYRON@DARTENG.CO
M
CONTRACTOR DAART ENGINEERING COMPANY INC 1598 NORTH H STREET SAN
BERNARDINO
CA 92405 (909)888-8696 BYRON@DARTENG.CO
M
OWNER STATER BROS MARKETS 21700 BARTON RD COLTON CA 92253 (909)888-8696
CONDITIONS
Description: STATER BROS. # 128 - TENANT IMPROVEMENT
Type: FIRE SPRINKLER Subtype: TENANT IMPROVEMENT Status: FINALED Applied: 10/25/2018 JLIM
Parcel No: 604050031 Site Address: 78630 HIGHWAY 111 LA QUINTA,CA 92253 Approved: 11/13/2018 EGO
Subdivision: PM 25865 Block: Lot: 2 Issued: 11/16/2018 AMA
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 4/10/2019 EGO
Valuation: $0.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
FINANCIAL INFORMATION
Printed: Friday, January 27, 2023 10:23:54 AM 1 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0164
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD ROUGH
PIPING EGO 12/3/2018 12/3/2018 PARTIALLY
APPROVED
OVERHEAD ROUGH
PIPING EGO 2/19/2019 2/21/2019 PARTIALLY
APPROVED
SEE APPROVED PLANS ON SITE FOR
FURTHER DETAILS.
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
Credit Card Fee 101-0000-43505 0 $4.32 $4.32 11/16/18 R41377 807244 CREDIT
CARD
DAART ENGINEERING
CO AMA
Total Paid for Credit Card Fee: $4.32 $4.32
FIRE SPRINKLER
SYSTEMS - TENANT
IMPROVEMENT OVER
10 HEADS
101-0000-42420 0 $160.00 $160.00 10/25/18 R40613 13876 CHECK DAART ENGINEERING
COMPANY INC JLIM
FIRE SPRINKLER
SYSTEMS - TENANT
IMPROVEMENT OVER
10 HEADS PC
101-0000-42420 0 $240.00 $240.00 11/16/18 R41377 807244 CREDIT
CARD
DAART ENGINEERING
CO AMA
FIRE SPRINKLER
SYSTEMS - TENANT
IMPROVEMENT OVER
10 HEADS PC
101-0000-42420 0 $240.00 $240.00 10/25/18 R40613 13876 CHECK DAART ENGINEERING
COMPANY INC JLIM
Total Paid for FIRE FEES: $640.00 $640.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 10/25/18 R40613 13876 CHECK DAART ENGINEERING
COMPANY INC JLIM
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 10/25/18 R40613 13876 CHECK DAART ENGINEERING
COMPANY INC JLIM
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$659.32 $659.32
Printed: Friday, January 27, 2023 10:23:54 AM 2 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0164
OVERHEAD HYRO EGO 2/19/2019 2/21/2019 DISAPPROVE
D
OVERHEAD ROUGH
PIPING EGO 3/25/2019 3/26/2019 ALL AREAS IN PERMIT INSPECTED.
APPROVED AND READY FOR FINAL.
OVERHEAD HYRO EGO 3/25/2019 3/26/2019 CANCELED NOT REQURIED.
FIRE FINAL**EGO 4/10/2019 4/10/2019 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
PERMIT TECH
BUCKET 10/25/2018 10/26/2018 10/25/2018 COMPLETE
11/13/2018
Daart Engineering
1598 N. H St.
San Bernardino, CA 92405
Re: Stater Bros #128 - Fire Sprinkler TI - ¬FSS2018
-0164
78-630 Hwy 111
La Quinta, CA 92553
The Fire Sprinkler TI plans you submitted for the
above referenced project have been reviewed by
the Riverside County Fire Department and are
approved with the following conditions:
1.) Provide spare sprinkler head of each type
installed at fire sprinkler riser’s spare head box (at
least 1.)
2.) Existing fire sprinkler system shall have a
PARENT PROJECTS
Printed: Friday, January 27, 2023 10:23:54 AM 3 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0164
BOND INFORMATION
1ST FIRE (2 WK)EDGAR
GONZALEZ 10/25/2018 11/8/2018 11/13/2018 APPROVED
current 5 year inspection/certification. Proof
shall be provided on or before final is granted.
3.) Fire Sprinkler system tenant improvements
with 20 or more heads augmented/affected shall
be hydrostatically tested at 200 psi or 50 above
static pressure, whichever is greater.
4.) Approval of this plan is subject on the
following field inspections:
• Overhead Rough/Piping Inspection
• Final Inspection
The Fire Department approved plans and
conditions letter must be at the job site.
Applicant/installer shall be responsible to contact
the Fire Department to schedule inspections.
Requests for inspections are to be made at least
72 hours in advance and may be arranged by
calling (760)777-7131.
SUBJECT TO FIELD INSPECTION - Nothing in our
review shall be construed as encompassing
structural integrity. Review of this plan does not
authorize or approve any omission or deviation
from all applicable regulations. Final approval is
subject to field inspection.
All questions regarding the meaning of these
conditions should be referred to the Office of the
Fire Marshal staff at (760)777-7074.
Edgar Gonzalez
Fire Safety Specialist
Printed: Friday, January 27, 2023 10:23:54 AM 4 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0164
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 11/15/2018 EDGAR GONZALEZ
FSS2018-0164 - STATER
BROS - 78-630 HWY 111
- FIRE SPRINKLER TI
(LOC).docx
FSS2018-0164 - STATER
BROS - 78-630 HWY 111
- FIRE SPRINKLER TI
(LOC).docx
1
Printed: Friday, January 27, 2023 10:23:54 AM 5 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0164