FSS2018-0165ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT J D MECHANICAL FIRE INC 82579 FLEMING WAY
SUITE D
INDIO CA 92201 KATHY@JDMECHANIC
AL.CO
BILL TO J D MECHANICAL FIRE INC 82579 FLEMING WAY
SUITE D
INDIO CA 92201 KATHY@JDMECHANIC
AL.CO
CONTRACTOR J D MECHANICAL FIRE INC 82579 FLEMING WAY
SUITE D
INDIO CA 92201 KATHY@JDMECHANIC
AL.CO
OWNER LMLQ PROP 78100 MAIN ST STE 203 LA QUINTA CA 92253
CONDITION
TYPE CONTACT DATE
ADDED
DATE
REQUIRED
DATE
SATISFIED STATUS REMARKS NOTES
READY TO ISSUE
CHECKLIST
ARMANDO
MAGALLON 10/30/2018 11/15/2018 COMPLETE APPLICANT NEEDS TO SIGN APPLICATION AND
PAY THE REMAINDING $10.
CONDITIONS
Description: ACUITY EYE GROUP / FIRE SPRINKLER / BCOM2018-0029
Type: FIRE SPRINKLER Subtype: TENANT IMPROVEMENT Status: ISSUED Applied: 10/30/2018 AMA
Parcel No: 643200005 Site Address: 47474 WASHINGTON ST LA QUINTA,CA 92253 Approved: 11/14/2018 EGO
Subdivision: PM 27892 Block: Lot: 5 Issued: 11/15/2018 AMA
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled:
Valuation: $0.00 Occupancy Type: Construction Type: Expired: 5/14/2019 AMA
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
Printed: Friday, January 20, 2023 10:29:08 AM 1 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0165
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD ROUGH
PIPING EGO 12/13/2018 12/13/2018
APPROVED
W/EXCEPTIO
N
APPROVED WITH THE FOLLOWING
CONDITIONS:
PAINT PIV AND FDC FOR CORROSION
RESISTANCE
5 YEAR FIRE SPRINKLER CERTIFICATION
SPARE WRENCHES AND HEADS UTILIZED ON
JOB IN HEAD BOX
AS BUILT DRAWINGS SUBMITTED AND
APPROVED ON OR BEFORE FINAL
INSPECTION
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPRINKLER
SYSTEMS - TENANT
IMPROVEMENT OVER
10 HEADS
101-0000-42420 0 $160.00 $160.00 10/30/18 R40737 1409 CHECK JD MECHANICAL FIRE
INC AMA
FIRE SPRINKLER
SYSTEMS - TENANT
IMPROVEMENT OVER
10 HEADS PC
101-0000-42420 0 $240.00 $240.00 10/30/18 R40737 1409 CHECK JD MECHANICAL FIRE
INC AMA
Total Paid for FIRE FEES: $400.00 $400.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 11/15/18 R41342 1417 CHECK J D MECHANICAL FIRE
INC AMA
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 10/30/18 R40737 1409 CHECK JD MECHANICAL FIRE
INC AMA
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$415.00 $415.00
Printed: Friday, January 20, 2023 10:29:08 AM 2 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0165
OVERHEAD HYRO EGO 12/13/2018 12/13/2018
APPROVED
W/EXCEPTIO
N
HYDRO AT STANDARD OPERATING
PRESSURE DUE TO WORK LESS THAN 20
HEADS.
FIRE FINAL**EGO 2/11/2019 2/13/2019 PARTIALLY
APPROVED
PENDING HYDRAULIC CALC PLATE AND 5
YEAR CERTIFICATION.
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
ARMANDO
MAGALLON 10/30/2018 10/31/2018 10/30/2018 READY FOR APPROVAL
- CONDS
APPLICANT NEEDS TO PAY REMAINDING FEE AND
SIGN APPLICATION.
11/14/2018
Kathy Sloan
JD Mechanical
82-579 Fleming Wy.
Indio, CA 92253
Re: Acuity Eye Group – Fire Sprinkler TI
FSS2018-0165
47474 Washington St.
La Quinta, CA 92253
The Fire Sprinkler TI plans you submitted for the
above referenced project have been reviewed by
the Riverside County Fire Department and are
approved with the following conditions:
1.) Provide spare sprinkler head of each type
installed at fire sprinkler riser’s spare head box (at
least 1.)
2.) Existing fire sprinkler system shall have a
current 5 year inspection/certification. Proof
PARENT PROJECTS
Printed: Friday, January 20, 2023 10:29:08 AM 3 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0165
BOND INFORMATION
1ST FIRE (2 WK)EDGAR
GONZALEZ 10/30/2018 11/13/2018 11/14/2018 APPROVED-
CONDITIONS
shall be provided on or before final is granted.
3.) Fire Sprinkler system tenant improvements
with 20 or more heads augmented/affected shall
be hydrostatically tested at 200 psi or 50 above
static pressure, whichever is greater.
4.) Approval of this plan is subject on the
following field inspections:
• Overhead Rough/Piping Inspection
• Final Inspection
The Fire Department approved plans and
conditions letter must be at the job site.
Applicant/installer shall be responsible to contact
the Fire Department to schedule inspections.
Requests for inspections are to be made at least
72 hours in advance and may be arranged by
calling (760)777-7131.
SUBJECT TO FIELD INSPECTION - Nothing in our
review shall be construed as encompassing
structural integrity. Review of this plan does not
authorize or approve any omission or deviation
from all applicable regulations. Final approval is
subject to field inspection.
All questions regarding the meaning of these
conditions should be referred to the Office of the
Fire Marshal staff at (760)777-7074.
Edgar Gonzalez
Fire Safety Specialist
Printed: Friday, January 20, 2023 10:29:08 AM 4 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0165
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 11/14/2018 EDGAR GONZALEZ
FSS2018-0165 - ACUITY
EYE GROUP - 47474
WASHINGTON ST - FIRE
SPRINKLER TI -
(COA).docx
FSS2018-0165 - ACUITY
EYE GROUP - 47474
WASHINGTON ST - FIRE
SPRINKLER TI -
(COA).docx
1
Printed: Friday, January 20, 2023 10:29:08 AM 5 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0165
Office of the Fire Marshal
City of La Quinta
78-495 Calle Tampico, La Quinta CA 92253
• Phone (760)777-7000 •Direct (760)777-7074
11/14/2018
Kathy Sloan
JD Mechanical
82-579 Fleming Wy.
Indio, CA 92253
Re: Acuity Eye Group – Fire Sprinkler TI
FSS2018-0165
47474 Washington St.
La Quinta, CA 92253
The Fire Sprinkler TI plans you submitted for the above referenced project have been reviewed by the
Riverside County Fire Department and are approved with the following conditions:
1.) Provide spare sprinkler head of each type installed at fire sprinkler riser’s spare head box (at least 1.)
2.) Existing fire sprinkler system shall have a current 5 year inspection/certification. Proof shall be
provided on or before final is granted.
3.) Fire Sprinkler system tenant improvements with 20 or more heads augmented/affected shall be
hydrostatically tested at 200 psi or 50 above static pressure, whichever is greater.
4.) Approval of this plan is subject on the following field inspections:
• Overhead Rough/Piping Inspection
• Final Inspection
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests
for inspections are to be made at least 72 hours in advance and may be arranged by calling (760)777-
7131.
SUBJECT TO FIELD INSPECTION - Nothing in our review shall be construed as encompassing
structural integrity. Review of this plan does not authorize or approve any omission or deviation from
all applicable regulations. Final approval is subject to field inspection.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire
Marshal staff at (760)777-7074.
Edgar Gonzalez
Fire Safety Specialist
Office of the Fire Marshal
City of La Quinta
78-495 Calle Tampico, La Quinta CA 92253
• Phone (760)777-7000 •Direct (760)777-7074