FSS2018-0181ADDITIONAL SITES
CHRONOLOGY
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
NOTE ARMANDO MAGALLON 6/6/2019 6/6/2019 APPLICANT PIKCKED UP AS-BUILT PLANS
NOTE KAYLI ALFORD 8/9/2019 8/9/2019
H2O PROTECTION CALLED TO SCHEDULE A FINAL
INSPECTION. I INFORMED THEM THAT THE HYDRO WAS NOT
IN OUR SYSTEM AS BEING APPROVED AND HE STATED THAT
FSS EDGAR HAD WAIVED THAT INSPECTION - SEE JOB CARD
ON SITE TO CONFIRM.
PLAN CHECK PICKED UP JACK LIMA 11/29/2018 11/29/2018 APPROVED SPRINKLER PLANS PICKED UP BY MR. PAUL
HARRIS FROM H2O FIRE PROTECTION, INC.
RESUBMITTAL JACK LIMA 5/29/2019 5/29/2019
REVISION 1 RESUBMITTED BY ARIAS MARCEL. PERMIT
SHOWED THAT IT HAD EXPIRED. I CHANGED THE DATE 180
DAYS OUT SINCE THE APPLICANT HAD AN INSPECTION DONE
ON 3/25/2019. PER THE BUILDING OFFICIAL ANY INSPECTION
PERFORMED WHEATHER APPROVED OR NOT GRANTS AN
EXTENSION OF 180 DAYS.
Description: MARVYN'S MAGIC CABARE / BCOM2018-0045 / FIRE SPINKLER SYSTEM
Type: FIRE SPRINKLER Subtype:
COMMERCIAL/INDUSTRIAL
Status: FINALED Applied: 11/27/2018 JLIM
Parcel No: 643020062 Site Address: 46630 WASHINGTON ST STE 1 LA QUINTA,CA 92253 Approved: 11/28/2018 EGO
Subdivision: PM 32683-3 AMEND Block: Lot: 5 Issued: 11/29/2018 JLIM
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 9/23/2019 crw
Valuation: $0.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
Printed: Friday, February 03, 2023 11:18:48 AM 1 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0181
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT H 2 O FIRE PROTECTION INC - PAUL
FERRIS
417-B WEST FOOTHILLS
BLVD #282
GLENDORA CA 91741 (909)394-7979 PF@H20FP.COM
BILL TO H 2 O FIRE PROTECTION INC - PAUL
FERRIS
417-B WEST FOOTHILLS
BLVD #282
GLENDORA CA 91741 (909)394-7979 PF@H20FP.COM
CONTRACTOR H 2 O FIRE PROTECTION INC 417-B WEST FOOTHILLS
BLVD #282
GLENDORA CA 91741 (909)394-7979 PF@H20FP.COM
OWNER WASHINGTON 111 LTD 80618 DECLARATION
AVE
INDIO CA 92253 (909)394-7979
CONDITIONS
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPRINKLER
SYSTEMS
COMMERCIAL/INDUSTR
IAL
101-0000-42421 0 $234.00 $234.00 11/29/18 R41790 8148 CHECK H 2 O FIRE
PROTECTION INC - PA JLIM
FIRE SPRINKLER
SYSTEMS
COMMERCIAL/INDUSTR
IAL PC
101-0000-42420 0 $390.00 $390.00 11/29/18 R41790 8148 CHECK H 2 O FIRE
PROTECTION INC - PA JLIM
Total Paid for FIRE FEES: $624.00 $624.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 11/29/18 R41790 8148 CHECK H 2 O FIRE
PROTECTION INC - PA JLIM
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 11/29/18 R41790 8148 CHECK H 2 O FIRE
PROTECTION INC - PA JLIM
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$639.00 $639.00
Printed: Friday, February 03, 2023 11:18:48 AM 2 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0181
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD ROUGH
PIPING
EGO 2/25/2019 2/25/2019 NOT READY
OVERHEAD ROUGH
PIPING EGO 3/21/2019 3/25/2019 PARTIALLY
APPROVED
HARDLID AREAS ONLY. SEE FIELD PLANS
AND ISSUED INSPECTION LOG.
OVERHEAD HYRO EGO 3/21/2019 3/25/2019 NOT READY
OVERHEAD ROUGH
PIPING
EGO 6/3/2019 6/3/2019 APPROVED
FIRE FINAL**KHET 8/13/2019 8/13/2019 DISAPPROVE
D
CONTRACTOR STATES EDGAR WAIVED
HYDRO INSPECTION - SEE JOB CARD ON SITE
TO CONFIRM.
1. Remove Paint protection tape from
upright sprinklers where affected.2. ITM 5-
year or annual service tag is missing from
the riser. Provide documentation of current
service report.
FIRE FINAL**KHET 9/5/2019 9/5/2019 DISAPPROVE
D
1) Uprights that had paint protection
removed revealed existing painted heads -
Replace 3+.2) Pendant heads in hard-lid
require 1-inch clearance below ceiling.
FIRE FINAL**KHET 9/23/2019 9/23/2019 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
PERMIT TECH
BUCKET 11/27/2018 11/28/2018 11/27/2018 COMPLETE
11/28/2018
PARENT PROJECTS
Printed: Friday, February 03, 2023 11:18:48 AM 3 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0181
1ST FIRE (2 WK)EDGAR
GONZALEZ 11/27/2018 12/11/2018 11/28/2018 APPROVED-
CONDITIONS
Paul Serah
H2O Fire Protection Inc.
449 W. Foothill Blvd. Ste #282
Glendora CA, 91741
Re: Marvin’s Magic – Fire Sprinkler TI Plan
Review
FSS2018-0181
46-630 Washington St.
La Quinta CA, 92553
The Fire Sprinkler TI plans you submitted for the
above referenced project have been reviewed by
the Riverside County Fire Department and are
approved with the following conditions:
1.) Provide spare sprinkler head of each type
installed at fire sprinkler riser’s spare head box (at
least 1.)
2.) Existing fire sprinkler system shall have a
current 5 year inspection/certification. Proof
shall be provided on or before final is granted.
3.) Fire Sprinkler system tenant improvements
with 20 or more heads augmented/affected shall
be hydrostatically tested at 200 psi or 50 above
static pressure, whichever is greater.
4.) Approval of this plan is subject on the
following field inspections:
• Overhead Rough/Piping Inspection
• Final Inspection
The Fire Department approved plans and
conditions letter must be at the job site.
Applicant/installer shall be responsible to contact
the Fire Department to schedule inspections.
Requests for inspections are to be made at least
Printed: Friday, February 03, 2023 11:18:48 AM 4 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0181
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 11/28/2018 EDGAR GONZALEZ
FSS2018-0181 -
MARVINS MAGIC - 46-
630 WASHINGTON ST. -
FIRE SPRINKLER TI
(COA).docx
FSS2018-0181 -
MARVINS MAGIC - 46-
630 WASHINGTON ST. -
FIRE SPRINKLER TI
(COA).docx
1
DOC 11/27/2018 JACK LIMA
TYCO TY-FRB QRUpr and
QRRecPend
TFP171_10_2013 (2).pdf
TYCO TY-FRB QRUpr and
QRRecPend
TFP171_10_2013 (2).pdf
0
DOC 12/21/2021 JOSE DELGADO Fire Review Application
Revision 1 - Asbuilts.pdf
Fire Review Application
Revision 1 - As builts.pdf 0
DOC 12/21/2021 JOSE DELGADO Fire Review
Application.pdf
Fire Review
Application.pdf 0
BOND INFORMATION
72 hours in advance and may be arranged by
calling (760)777-7131.
SUBJECT TO FIELD INSPECTION - Nothing in our
review shall be construed as encompassing
structural integrity. Review of this plan does not
authorize or approve any omission or deviation
from all applicable regulations. Final approval is
subject to field inspection.
All questions regarding the meaning of these
conditions should be referred to the Office of the
Fire Marshal staff at (760)777-7074.
Edgar Gonzalez - Fire Safety Specialist
1ST FIRE (1 WK)EDGAR
GONZALEZ 5/29/2019 6/5/2019 6/3/2019 APPROVED REVISION - 1 CONDITIONS TO REMAIN. READY FOR FINAL
INSPECTION.
Printed: Friday, February 03, 2023 11:18:48 AM 5 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0181
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 12/21/2021 JOSE DELGADO FSS2018-0181 Revision
1 - Asbuilts.pdf
FSS2018-0181
Asbuilts.pdf 0
DOC 12/21/2021 JOSE DELGADO FSS2018-0181.pdf FSS2018-0181.pdf 0
IMAGE 8/13/2019 KOHL HETRICK 08132019_115652_AM.J
PG
08132019_115652_AM.J
PG 0
IMAGE 8/13/2019 KOHL HETRICK 08132019_115637_AM.J
PG
08132019_115637_AM.J
PG 0
Printed: Friday, February 03, 2023 11:18:48 AM 6 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2018-0181