CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
PUBLIC COUNTER VISIT JACK LIMA 1/8/2019 1/8/2019
APPLICANT CAME FROM OUT OF TOWN AND HAD AN OVER
THE COUNTER PLAN REVIEW APPOINTMENT WITH EDGAR
GONZALES IN FIRE. I CREATED A RECORD AND PROCESSED
ALL APPLICABLE FEES. WHEN I WAS FINISHED I DIRECTED
APPLICANT TO FIRE FOR HIS REVIEW.
PUBLIC COUNTER VISIT JACK LIMA 1/8/2019 1/8/2019 PLANS HAVE BEEN APPROVED BY EDGER GONZALES AND
ISSUED TO APPLICANT EMANUEL SOLT.
CONDITIONS
Description: COSTCO / FIRE SPRINKLER TI FOR HEARING AID CENTER
Type: FIRE SPRINKLER Subtype: TENANT IMPROVEMENT Status: FINALED Applied: 1/8/2019 JLIM
Parcel No: 600440010 Site Address: 79795 HIGHWAY 111 LA QUINTA,CA 92253 Approved: 1/8/2019 EGO
Subdivision: PM 33960 Block: Lot: 1 Issued: 1/8/2019 JLIM
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 2/13/2019 EGO
Valuation: $0.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details: TI ADDITION OF (3) SPRINKERS FOR THE COSTCO HEARING AID CENTER
Printed: Friday, February 03, 2023 11:34:30 AM 1 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2019-0001
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
CONTRACTOR UNI FIRE PROTECTION INC 22046 CELES ST WOODLAND
HILLS
CA 91364
OWNER COSTCO WHOLESALE CORP 999 LAKE DR ISSAQUAH WA 92253
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD ROUGH
PIPING EGO 2/11/2019 2/13/2019 APPROVED
FIRE FINAL**EGO 2/11/2019 2/13/2019 APPROVED
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPRINKLER
SYSTEMS - TENANT
IMPROVEMENT OVER
10 HEADS
101-0000-42420 0 $160.00 $160.00 1/8/19 R42758 11006 CHECK UNI FIRE PROTECTION
INC - EMAN JLIM
FIRE SPRINKLER
SYSTEMS - TENANT
IMPROVEMENT OVER
10 HEADS PC
101-0000-42420 0 $240.00 $240.00 1/8/19 R42758 11006 CHECK UNI FIRE PROTECTION
INC - EMAN JLIM
Total Paid for FIRE FEES: $400.00 $400.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 1/8/19 R42758 11006 CHECK UNI FIRE PROTECTION
INC - EMAN JLIM
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 1/8/19 R42758 11006 CHECK UNI FIRE PROTECTION
INC - EMAN JLIM
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$415.00 $415.00
Printed: Friday, February 03, 2023 11:34:30 AM 2 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2019-0001
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
PERMIT TECH
BUCKET 1/8/2019 1/8/2019 1/8/2019 COMPLETE
1ST FIRE (2 WK)EDGAR
GONZALEZ 1/8/2019 1/22/2019 1/8/2019 APPROVED-
CONDITIONS
1/8/2019
Emanuel Solt
Uni Fire Protection
22-046 Cece St.
Woodland Hills, CA 91364
Re: Costco #638
Fire Sprinkler TI – FSS2019-0001
79-795 Highway 111
La Quinta CA, 92253
The Fire Sprinkler TI plans you submitted for the
above referenced project have been reviewed by
the Riverside County Fire Department and are
approved with the following conditions:
1.) Provide spare sprinkler head of each type
installed at fire sprinkler riser’s spare head box (at
least 1.)
2.) Existing fire sprinkler system shall have a
current 5 year inspection/certification. Proof
shall be provided on or before final is granted.
3.) Fire Sprinkler system tenant improvements
with 20 or more heads augmented/affected shall
be hydrostatically tested at 200 psi or 50 above
static pressure, whichever is greater.
4.) Approval of this plan is subject on the
PARENT PROJECTS
Printed: Friday, February 03, 2023 11:34:30 AM 3 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2019-0001
ATTACHMENTS
BOND INFORMATION
following field inspections:
• Overhead Rough/Piping Inspection
• Final Inspection
The Fire Department approved plans and
conditions letter must be at the job site.
Applicant/installer shall be responsible to contact
the Fire Department to schedule inspections.
Requests for inspections are to be made at least
72 hours in advance and may be arranged by
calling (760)777-7131.
SUBJECT TO FIELD INSPECTION - Nothing in our
review shall be construed as encompassing
structural integrity. Review of this plan does not
authorize or approve any omission or deviation
from all applicable regulations. Final approval is
subject to field inspection.
All questions regarding the meaning of these
conditions should be referred to the Office of the
Fire Marshal staff at (760)777-7074.
Edgar Gonzalez
Fire Safety Specialist
Printed: Friday, February 03, 2023 11:34:30 AM 4 of 4