FSS2019-0009ADDITIONAL SITES
CHRONOLOGY
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
E-MAIL KOHL HETRICK 11/1/2019 11/1/2019 Received PDF of As-Built Plans as requested. See
attachments.
NOTE ARMANDO MAGALLON 2/19/2019 2/19/2019 APPLICANT WANTED PLANS SENT BACK TO THEM VIA FEDEX.
APPROVED PLANS WILL BE MAILED BACK.
NOTE JACK LIMA 2/7/2019 3/5/2019
APPLICANT SUBMITTED TO US VIA FEDEX. CHECK WAS SHORT
$10.00 AS THE APPLICANT HAD SUBMITTED AN OLD
APPLICATION. I REACHED OUT THE APPLICANT AND THEY
WILL SEND THE ADDITIONAL PAYMENT TO ME BY MONDAY
2/11/2019. ALSO, APPLICANT INCLUDED A RETURN SHIPPING
LABEL.
NOTE JACK LIMA 2/12/2019 2/12/2019 ALL FEES HAVE BEEN PAID PER PREVIOUS NOTES.
Description: CHAPMAN / FIRE SPRINKLER SYSTEM BRES2018-0267
Type: FIRE SPRINKLER Subtype: RESIDENTIAL - CUSTOM
HOMES
Status: FINALED Applied: 2/7/2019 JLIM
Parcel No: 777210026 Site Address: 80129 VIA PESSARO LA QUINTA,CA 92253 Approved: 2/14/2019 EGO
Subdivision: TR 29894-2 Block: Lot: 212 Issued: 2/19/2019 AMA
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 10/21/2019 crw
Valuation: $0.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details: 4/3/19 - FSS E GONZALEZ - "Submit revisions identifying the riser location change and overhead piping changes to most remote
calculated area."
Printed: Thursday, January 19, 2023 11:42:28 AM 1 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2019-0009
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT RESIDENTIAL FIRE SYSTEMS INC -
RUBI GUTIERREZ
8085 E CRYSTAL DRIVE ANAHEIM CA 92807 (714)666-8450 ENGINEERING@RESFIR
E.COM
BILL TO RESIDENTIAL FIRE SYSTEMS INC 8085 E CRYSTAL DRIVE ANAHEIM CA 92807 (714)666-8450 ENGINEERING@RESFIR
E.COM
CONTRACTOR RESIDENTIAL FIRE SYSTEMS INC 8085 E CRYSTAL DRIVE ANAHEIM CA 92807 (714)666-8450 ENGINEERING@RESFIR
E.COM
OWNER GREGORY & KRISTIN CHAPMAN 80129 VIA PESSARO LA QUINTA CA 0 (714)666-8450
NOTE KAYLI ALFORD 10/14/2019 10/14/2019
RECEIVED FINAL INSPECTION REQUEST. PERMIT HAS EXPIRED,
INFORMED CONTRACTOR THAT A $40 EXTENSION FEE &
EXTENSION REQUEST LETTER WILL BE NEEDED IN ORDER TO
SCHEDULE THE INSPECTION.
CONDITIONS
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $160.00 $160.00 2/7/19 R44569 107487 CHECK RESIDENTIAL FIRE
SYSTEMS INC -JLIM
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED PC
101-0000-42420 0 $240.00 $240.00 2/7/19 R44569 107487 CHECK RESIDENTIAL FIRE
SYSTEMS INC -JLIM
FIRE STAFF - PER HOUR 101-0000-42420 0.25 $40.00 $40.00 10/17/19 R54997 1738 CHECK MICHAEL JEHA
CONSTRUCTION, LLC AMA
Total Paid for FIRE FEES: $440.00 $440.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 2/12/19 R44733 107510 CHECK RESIDENTIAL FIRE
SYSTEMS INC -JLIM
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
Printed: Thursday, January 19, 2023 11:42:28 AM 2 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2019-0009
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD ROUGH
PIPING EGO 3/18/2019 3/20/2019 PARTIALLY
APPROVED
ONLY A PARTIAL ROUGH/PIPING
INSPECTION WAS APPROVED. SEE
APPROVED FIELD PLANS FOR FURTHER
DETAILS.
OVERHEAD ROUGH
PIPING EGO 4/3/2019 4/10/2019 APPROVED
SEE CORRECTIONS IN PEMRIT FILE.
REVISIONS ARE TO BE SUMBITTED FOR
REVIEW AND APPROVAL ALONG WITH
ORIGINAL FIELD SET MARKED BY FIELD
INSPECTOR (FSS GONZALEZ)
FIRE FINAL**KHET 10/21/2019 10/21/2019 APPROVED AS BUILTS AND BUCKET
TEST REQUIRED
Bucket test passed with 15 gpm from each
head observed while flowing 5 gpm
domestic. 70 psi static observed at riser.
Bucket test passed with 15 gpm from each
head observed while flowing 5 gpm
domestic. 70 psi static observed at riser.
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)JACK LIMA 2/7/2019 2/8/2019 3/5/2019 COMPLETE
PARENT PROJECTS
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 2/7/19 R44569 107487 CHECK RESIDENTIAL FIRE
SYSTEMS INC -JLIM
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$455.00 $455.00
Printed: Thursday, January 19, 2023 11:42:28 AM 3 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2019-0009
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 2/14/2019 EDGAR GONZALEZ
FSS2019-0009 -
CHAPMAN RESIDENCE -
80-129 VIA PESSARO -
FIRE SPRINKLER
(COA).docx
FSS2019-0009 -
CHAPMAN RESIDENCE -
80-129 VIA PESSARO -
FIRE SPRINKLER
(COA).docx
1
DOC 11/1/2019 KOHL HETRICK FSS2019-0009 AS-
BUILTS.pdf
FSS2019-0009 AS-
BUILTS.pdf 1
BOND INFORMATION
1ST FIRE (2 WK)EDGAR
GONZALEZ 2/7/2019 2/21/2019 2/14/2019 APPROVED SEE CONDITIONS LETTER.
Printed: Thursday, January 19, 2023 11:42:28 AM 4 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2019-0009
RESIDENTIALfire systems inc.
09.09.16
NOT TO SCALE
TEK TYPE SCREWS TYP.
OFFSET HANGER TYP.
3/4" THRU 2" PIPE
3/4" THRU 3" PIPE
DOUBLE
FASTNER STRAP TYP.
SIDE MOUNTED
DOUBLE FASTENER STRAP TYP.
3/4" THRU 2" PIPE
***MOUNTING POSITION - TOP & BOTTOM
SEE BELOW.
PIPE SIZE
* MOUNTING POSITION - TOP, BOTTOM OR SIDE U.N.O.
* 1/4" TEK TYPE SCEWS PROVIDED.
INSTALLATION
08.18.16
11.29.17
08.18.16
08.18.16
2"x_WOOD BLOCK TYP.
1/2" OR 3/8" GYP.
BOARD TYP.
FIRE
SPRINKLERBRANCH LINE TYP.
6" MAX.
TYP.
PIPE
HANGER TYP.
SCREW
W/ BACKING NUT
MAIN LINE TYP.
JOIST FLOOR FRAMING
SCREW
TJI JOIST
TJI FLOOR FRAMING
08.18.16
·
·
·
·
·
·
·
08.18.16
6" MIN.12"
M
I
N
.
12"
M
I
N
.6" MIN.12" MIN.12" MIN.
BATT INSULATION (TYP.)
CEILING
SPRINKLER
PIPE ON BOT. CHORD OF ROOF TRUSS UNDER
BATT INSULATION W/IN ATTIC TYP. (BY OTHERS)
3/8" GYP. BOARD
OR 1/2" PLYWOOD
ATTIC
INTERIOR
SPACE3/8" GYP. BOARD
OR 1/2" PLYWOOD
CEILING
SPRINKLER BELOW
PIPE TYP.
PIPE ON BOT. CHORD OF
ROOF TRUSS UNDER BATT INSULATION
W/IN ATTIC TYP. (BY OTHERS)
BATT
INSULATION (TYP.)
(BY OTHERS)
08.09.17
PROJECT
SITE
08.18.16VAN BUREN STCALHOUN STJACKSON STMONROE STAVENUE 52
JEFFERSON STAVENUE 54
HIDEW
A
Y
C
L
U
B
D
R
VIA
PESSARO
10.04.16
TOLCO
2" MAX. FIRE SPRINKLER PIPE
CPVC, COPPER, OR STEEL (SEE PLANS)
RING HANGER
1/2" MAX.
GST20 SAMMY SCREW
(PRE-DRILL @ MID. OF BM.)
NOTE: GST20 SAMMY SCREW MUST EXTEND
MINIMUM 3/16" ABV. TOP OF BOT. FLANGE
MAXIMUM HANGER
SPACING PER
NFPA 13 (SEE PLANS)3/16" MIN.3/8" ALL THREAD ROD
2x_
WOOD JOIST
TJIEQ.EQ.2" MIN.08.18.16
09.28.16
·
·
TYPICAL - 11.29.17
FIRE CAULK ALL JOIST
BAY PENETRATIONS, EQUAL TO RATED WALL
GARAGE/DWELLING
COMMON WALL TYP.
GYP. BOARD LINED
JOIST BAY, EQUAL
TO RATED WALL
GYP. BOARD BTWN.
FURRED WALL
24"DRAIN LINE TO EXT. OR DRAIN
(IF APPLICABLE: W/ RELIEF VALVE)
14-1/2"
(FIRE CAULKING NOT REQ'D)
07.19.17
14-1/2"
GARAGE/DWELLING
COMMON WALL TYP.
14-1/2"
FIRE SPRINKLER RISER
W/ INTERIOR ACCESS
PANEL (14-1/2"x24") TYP.
FIRE SPRINKLER RISER
W/ INTERIOR ACCESS
PANEL (14-1/2"x24") TYP.
GYP. BOARD LINED
JOIST BAY, EQUAL TO RATED WALL
08.18.16
08.10.17
08.18.16
2x6
DWELL'G GARAGE2x4
DWELL'G GARAGEROOF TRU
S
S
O
R
R
A
F
T
E
R
HANGER
BRANCH LINE
MAIN LINE
UPRIGHT
SPRIG-UP
1/2" OR 3/8" GYP. BOARD TYP.
WOOD TRUSS
UPRIGHT, PARALLEL
W/ ROOF (IF APPLICABLE)
6" MAX.
OR JOIST
FIRE SPRINKLER
SEE NOTES
08.18.16
1-1/2" COP
P
E
R
K
2" PVC 2" COPPER L24'-9"
72'-2"
+10
-2
-4
+2+2
-2
-4
1" COPPER L
1" WATER METER ( FIELD VERIFICATION
NEEDED AT ROUGH INSTALLATION )
PVC TO COPPER ADAPTER
MAIN SHUT OFF VALVE
(IF REQUIRED)
DOMESTIC SHUT OFF VALVE
(IF REQUIRED)
TO DOMESTIC WATER SUPPLY
TO IRRIGATION
(W/ IN-LINE CHECK VALVE)
TO FIRE SPRINKLER
SYSTEM, SEE PLANS
POINT OF CONNECTION FOR
RESIDENTIAL FIRE SYSTEMS, INC.
1" CPVC RUBBER FACED CHECK VALVE
300 PSI PRESSURE GAUGE
TO 1/2" BALL VALVE / DRAIN LINE
FIRE SPRINKLER RISER
W/ INTERIOR ACCESS
PANEL (14-1/2"x24") TYP.
1" CPVC
(PER RCC
E
)
1" CPVC
FROM FIRE SPRINKLER SYSTEM
2'-0" MIN.FIN. FLR.
AUXILIARY DRAIN SIGN
1/2" KEYLESS HOSE BIB
08.18.16
INSP. TESTRESIDENTIALfire systems inc.
09.09.16
08.18.16
UP10'x1"UP10'x1"UP10'UP10'x1"UP5'UP10'x1"INSP. TESTUP4'x1"UP10'X1"UP10'X1"UP10'X1"UP10'RESIDENTIALfire systems inc.09.09.16OBSTRUCTIONDABOBSTRUCTIONCLG.BABCLG.WALLABA08.18.1608.10.17FIRE SPRINKLER PLAN (NFPA 13D) NOTES:- ALL COMPARTMENTS WITH 1 RESIDENTIAL HEAD TO BE SPACED @ MAX. ALL COMPARTMENTS WITH 2 OR MORE RESIDENTIAL HEADS TO BE SPACED @ MAX.- ONE UPRIGHT TO BE INSTALLED IN ATTIC AT F.A.U.- ALL PIPING TO BE CPVC PIPE U.N.O.- ALL DROPS TO HEADS TO BE CPVC PIPE3/4"3/4"20'x20'16'x16'
DN10'X1"DN10'X1"DN10'DN10'x1"DN5'DN10'X1"DN10'X1"DN10'X1"DN10'DN10'RESIDENTIALfire systems inc.09.09.16OBSTRUCTIONDABOBSTRUCTIONCLG.BABCLG.WALLABA08.18.1608.10.17FIRE SPRINKLER PLAN (NFPA 13D) NOTES:- ALL COMPARTMENTS WITH 1 RESIDENTIAL HEAD TO BE SPACED @ MAX. ALL COMPARTMENTS WITH 2 OR MORE RESIDENTIAL HEADS TO BE SPACED @ MAX.- ONE UPRIGHT TO BE INSTALLED IN ATTIC AT F.A.U.- ALL PIPING TO BE CPVC PIPE U.N.O.- ALL DROPS TO HEADS TO BE CPVC PIPE3/4"3/4"20'x20'16'x16'