FSS2019-0078ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT CHARLES F BROWN FIRE
PROTECTION DESIGN
21386 LILIUM COURT MORENO
VALLEY
CA 92557 CHUCK92234@AOL.CO
M
CONTRACTOR CHARLES F BROWN FIRE
PROTECTION DESIGN
21386 LILIUM COURT MORENO
VALLEY
CA 92557 CHUCK92234@AOL.CO
M
OWNER LA PALOMA HOMES INC P O BOX 10179 PALM DESERT CA 92255
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
E-MAIL KOHL HETRICK 3/4/2020 3/4/2020
RECEIVED EMAIL FROM CONTRACTOR WITH THE REVISED 2-
HEAD CALC. NOW SHOWING THE MINIMUM DEMAND FOR
THE VK496 MODEL. APPROVED AND RETURNED VIA EMAIL.
OKAY TO SCHEDULE FINAL INSPECTION.
CONDITIONS
Description: BROWN / BRES2018-0415 / FIRE SPRINKLERS
Type: FIRE SPRINKLER Subtype: RESIDENTIAL - CUSTOM
HOMES
Status: FINALED Applied: 6/21/2019 AMA
Parcel No: 774263006 Site Address: 54620 AVENIDA JUAREZ LA QUINTA,CA 92253 Approved: 7/9/2019 EGO
Subdivision: SANTA CARMELITA VALE LA QUINTA
UNIT 25
Block: 271 Lot: 19 Issued: 7/12/2019 AHI
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 3/31/2020 KHET
Valuation: $0.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
Printed: Friday, February 03, 2023 12:54:04 PM 1 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2019-0078
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE FAILED OR
ADDITIONAL RE-
INSPECTION
101-0000-42421 0 $161.00 $161.00 3/3/20 WEB4635 CREDIT CHARLES F BROWN
FIRE PROTECTIO ECON
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $160.00 $160.00 6/21/19 R50605 5088 CHECK CHARLES F BROWN
FIRE PROTECTIO AMA
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED PC
101-0000-42420 0 $240.00 $240.00 6/21/19 R50605 5088 CHECK CHARLES F BROWN
FIRE PROTECTIO AMA
Total Paid for FIRE FEES: $561.00 $561.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 6/21/19 R50605 5088 CHECK CHARLES F BROWN
FIRE PROTECTIO AMA
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 6/21/19 R50605 5088 CHECK CHARLES F BROWN
FIRE PROTECTIO AMA
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$576.00 $576.00
Printed: Friday, February 03, 2023 12:54:04 PM 2 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2019-0078
OVERHEAD ROUGH
PIPING KHET 11/25/2019 11/25/2019 DISAPPROVE
D
Overhead Rough and Hydro revealed items
requiring correction.
1) VK496 has been installed throughout the
whole house at 200-degrees. This model is
K3.0 and was not any of the 3 shown on the
plans.
2) Rooms shown with single head protection
exceed maximum spacing both for K4.9 and
K3.0 heads.
Change out heads to approved plan details,
including spacing - or provide resubmittal
with calculations prior to Reinspection.
*A Reinspection fee will be assessed.
OVERHEAD HYRO KHET 11/25/2019 11/25/2019 APPROVED
OVERHEAD ROUGH
PIPING KHET 12/4/2019 12/4/2019 APPROVED
All heads have been changed to approved
plans with the exception Vk496 K3.0
installed in place of Vk488. The Vk496 has a
greater spk demand. Spacing is per plan and
adequate. As-builts are required with
calculations prior to final inspection.
FIRE FINAL**KHET 3/4/2020 3/4/2020 DISAPPROVE
D
Observed 85-feet of UG supply from water
meter to BOR. Max 32-feet per plans and
calls.
Riser residual test was not satisfactory,
observed psi go down to 0-5.
FIRE FINAL**KHET 3/31/2020 3/31/2020 APPROVED 78 psi static / 45 psi residual main drain test.
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
PARENT PROJECTS
Printed: Friday, February 03, 2023 12:54:04 PM 3 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2019-0078
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 7/12/2019 AARON HICKSON FIRE JOB CARD FIRE JOB CARD.doc
DOC 7/9/2019 EDGAR GONZALEZ
FSS2019-0078 - JUAREZ
RESIDENCE - 54-620
AVENIDA JUAREZ - FIRE
SPRINKER (COA).docx
FSS2019-0078 - JUAREZ
RESIDENCE - 54-620
AVENIDA JUAREZ - FIRE
SPRINKER (COA).docx
1
DOC 11/25/2019 KOHL HETRICK FSS2019-0078
Corrections.pdf
FSS2019-0078
Corrections.pdf 1
BOND INFORMATION
1ST FIRE (2 WK)EDGAR
GONZALEZ 6/21/2019 7/5/2019 7/9/2019 APPROVED-
CONDITIONS SEE ATTACHED CONDITIONS LETTER.
1ST PERMIT TECH (1
DAY)JACK LIMA 6/24/2019 6/24/2019 6/24/2019 COMPLETE
1ST FIRE (1 DAY)KOHL
HETRICK 3/4/2020 3/5/2020 3/4/2020 APPROVED REVISED 2HD CALC
VK496
NO CHARGE
CONTRACTOR PROVIDED A REVISED 2-HEAD CALC
FOR THE REPLACEMENT VK496 HEADS THAT
WERE INSTALLED AND MORE DEMANDING THAN
THE ORIGINALLY PROPOSED VK488.
Printed: Friday, February 03, 2023 12:54:04 PM 4 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2019-0078
78-495 Calle Tampico, La Quinta CA 92253
Main: 760-777-7000 Direct: 760-777-7074
PAGE _____ OF _____
PERMIT/CASE#: NOTICE NO:
FACILITY NAME: DATE:
FACILITY ADDRESS: CONTACT:
The items below are in violation of or shall meet additional requirements of one or more of the following:
CALIFORNIA FIRE CODE __________________ NFPA STD. ______________
CALIFORNIA BUILDING CODE _____________ CCR TITLE ______________
LA QUINTA MUNICIPAL CODE _____________ OTHER ________________
The listed violations/requirements shall be corrected immediately.
A re-inspection will be conducted on or after ______________________________ 20____.
FAILURE TO COMPLY MAY RESULT IN LEGAL ACTION AND/OR SIGNIFICANT DELAYS FOR APPROVAL.
Received By: __________________________________ Signature: _______________________________________
Fire Inspector: _________________________________ Radio I.D.: _______________________________________
IF YOU HAVE ANY QUESTIONS OR NEED ADDITIONAL INFORMATION, PLEASE CALL 760-777-7074.
79485 Calle Tampico La Quinta, CA 92253 Main Number (760) 777-7158 Inspection Number (760)777-7131
CITY OF LA QUINTA FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 54620 AVENIDA JUAREZ PERMIT# : FSS2019-0078 DATE
ISSUED:
DESCRIPTION: BROWN / BRES2018-0415 / FIRE
SPRINKLERS CONTRACTOR: CHARLES F BROWN FIRE PROTECTION DESIGN
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
79485 Calle Tampico La Quinta, CA 92253 Main Number (760) 777-7158 Inspection Number (760)777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration.
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may
cause the affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number
available when scheduling inspections. The inspection hotline for the City of La Quinta is (760)777-7131
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT
commence without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be
required to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the
responsible party not on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be
entered into the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire
Clearance has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building
Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS
MUST BE AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED
WITHIN 180 DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE
RESTRICTIVE REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.