FSS2019-0144ADDITIONAL SITES
CHRONOLOGY
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
NOTE JACK LIMA 12/5/2019 12/5/2019
REMOVED FIRE FEE OF $161.00 PER KAYLI ALFORD'S
REQUEST. REINSPECTION FEE HAD ALREADY BEEN ENTERED
AND PAID ON 11/13/2019.
NOTE KAYLI ALFORD 11/4/2019 11/4/2019 APPROVED PER KOHL 11/4/19
NOTE KAYLI ALFORD 11/5/2019 11/5/2019 JOB CARD ISSUED TO ERIC FRANCO
NOTE KAYLI ALFORD 11/13/2019 11/13/2019 REVISED PLAN SUBMITTAL TAKEN IN BY PERMIT TECH JLIMA
11/13/19 - ADDED 2 WK REVIEW FOR REVISION 1
TELEPHONE CALL KOHL HETRICK 11/27/2019 11/27/2019
Spoke with Javier and his Designer. Need them to swap out
plans with ones that provide a 3-head calculation due to the
spacing, located in the pockets created by beams. NFPA 13D
Section 10.2.4.
CONDITIONS
Description: BR GROUP / BRES2018-0376 / 29 HEADS
Type: FIRE SPRINKLER Subtype: RESIDENTIAL - CUSTOM
HOMES
Status: FINALED Applied: 10/16/2019 AMA
Parcel No: 774265031 Site Address: 54765 AVENIDA JUAREZ LA QUINTA,CA 92253 Approved: 11/4/2019 KAL
Subdivision: SANTA CARMELITA VALE LA QUINTA
UNIT 25
Block: 275 Lot: 2 Issued: 11/5/2019 KAL
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 2/25/2020 crw
Valuation: $0.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
Printed: Tuesday, February 07, 2023 2:54:37 PM 1 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2019-0144
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT J C FIRE PROTECTION 81705 DE ORO AVENUE INDIO CA 92201 JCFIREPROTECTION@V
ERIZON.NET
BILL TO J C FIRE PROTECTION 81705 DE ORO AVENUE INDIO CA 92201 JCFIREPROTECTION@V
ERIZON.NET
CONTRACTOR J C FIRE PROTECTION 81705 DE ORO AVENUE INDIO CA 92201 JCFIREPROTECTION@V
ERIZON.NET
OWNER BR GROUP 54765 AVENIDA
JUAREZ
LA QUINTA CA 92253
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE FAILED OR
ADDITIONAL RE-
INSPECTION
101-0000-42421 0 $161.00 $161.00 11/13/19 R55984 1777 CHECK J C FIRE PROTECTION JLIM
FIRE PLAN REVISION
SUBMITTALS 101-0000-42420 0 $161.00 $161.00 12/6/19 R56932 1790 CHECK J C FIRE PROTECTION AHI
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $161.00 $161.00 10/16/19 R54944 1747 CHECK J C FIRE PROTECTION AMA
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED PC
101-0000-42420 0 $242.00 $242.00 10/16/19 R54944 1747 CHECK J C FIRE PROTECTION AMA
Total Paid for FIRE FEES: $725.00 $725.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 10/16/19 R54944 1747 CHECK J C FIRE PROTECTION AMA
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 10/16/19 R54944 1747 CHECK J C FIRE PROTECTION AMA
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
Printed: Tuesday, February 07, 2023 2:54:37 PM 2 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2019-0144
BOND INFORMATION
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD ROUGH
PIPING KHET 11/7/2019 11/7/2019 DISAPPROVE
D
NFPA 13D section 10.2 identifies the
parameters for number of design sprinklers
and them being located in/under beams. OH
Rough inspection identified heads in all
pockets and an increase in the number of
heads in the compartment. Heads shall be
installed as shown on approved plans in the
beams, or a redesign with a minimum 3-
head calculation will be required prior to
Reinspection.
OVERHEAD HYRO KHET 11/7/2019 11/7/2019 APPROVED
OVERHEAD ROUGH
PIPING
KHET 12/6/2019 12/6/2019 APPROVED
FIRE FINAL**KHET 2/25/2020 2/25/2020 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
ARMANDO
MAGALLON
10/16/2019 10/17/2019 10/16/2019 COMPLETE
1ST FIRE (2 WK)KOHL
HETRICK
10/16/2019 10/30/2019 11/4/2019 APPROVED
1ST FIRE (2 WK)FIRE BUCKET 11/13/2019 11/27/2019 12/5/2019 APPROVED REVISION 1 PLANS WERE SWITCHED FOR 12X12 3-HEAD CALC
DUE TO BEAMS AND HEADS IN POCKETS
PARENT PROJECTS
TOTALS:$740.00 $740.00
Printed: Tuesday, February 07, 2023 2:54:37 PM 3 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2019-0144
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 11/5/2019 KAYLI ALFORD FIRE JOB CARD FIRE JOB CARD.doc
DOC 11/7/2019 KOHL HETRICK FSS2019-0144 OH Rough
Corr.pdf
FSS2019-0144 OH Rough
Corr.pdf 0
Printed: Tuesday, February 07, 2023 2:54:37 PM 4 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2019-0144
78-495 Calle Tampico, La Quinta CA 92253
Main: 760-777-7000 Direct: 760-777-7074
PAGE _____ OF _____
PERMIT/CASE#: NOTICE NO:
FACILITY NAME: DATE:
FACILITY ADDRESS: CONTACT:
The items below are in violation of or shall meet additional requirements of one or more of the following:
CALIFORNIA FIRE CODE __________________ NFPA STD. ______________
CALIFORNIA BUILDING CODE _____________ CCR TITLE ______________
LA QUINTA MUNICIPAL CODE _____________ OTHER ________________
The listed violations/requirements shall be corrected immediately.
A re-inspection will be conducted on or after ______________________________ 20____.
FAILURE TO COMPLY MAY RESULT IN LEGAL ACTION AND/OR SIGNIFICANT DELAYS FOR APPROVAL.
Received By: __________________________________ Signature: _______________________________________
Fire Inspector: _________________________________ Radio I.D.: _______________________________________
IF YOU HAVE ANY QUESTIONS OR NEED ADDITIONAL INFORMATION, PLEASE CALL 760-777-7074.
79485 Calle Tampico La Quinta, CA 92253 Main Number (760) 777-7158 Inspection Number (760)777-7131
CITY OF LA QUINTA FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 54765 AVENIDA JUAREZ PERMIT# : FSS2019-0144 DATE
ISSUED: 11/5/2019
DESCRIPTION: BR GROUP / BRES2019-0376 / 29 HEADS CONTRACTOR: J C FIRE PROTECTION
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
79485 Calle Tampico La Quinta, CA 92253 Main Number (760) 777-7158 Inspection Number (760)777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration.
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may
cause the affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number
available when scheduling inspections. The inspection hotline for the City of La Quinta is (760)777-7131
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT
commence without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be
required to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the
responsible party not on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be
entered into the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire
Clearance has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building
Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS
MUST BE AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED
WITHIN 180 DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE
RESTRICTIVE REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.