FSS2019-0161ADDITIONAL SITES
CHRONOLOGY
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
Description: DEWEY / FIRE SPRINKLERS / BRES2019-0122
Type: FIRE SPRINKLER Subtype: RESIDENTIAL - CUSTOM
HOMES
Status: FINALED Applied: 12/23/2019 JLIM
Parcel No: 777200018 Site Address: 53488 VIA STRADA LA QUINTA,CA 92253 Approved: 2/4/2020 KHET
Subdivision: TR 29894-2 Block: Lot: 266 Issued: 2/5/2020 AMA
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 5/5/2020 crw
Valuation: $0.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
Printed: Tuesday, February 07, 2023 3:07:07 PM 1 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2019-0161
E-MAIL KOHL HETRICK 4/27/2020 4/27/2020
Good morning Chuck,
I attempted a Final Inspection with Jason on the above
permit. In part due to the poor cell signal in LQ, we were
unable to complete the inspection.
I wanted to share some concerns that I had. I accessed the
"As-Built" plans that you provided (dated 2/17/2020) and
were uploaded to the permit on 4/15/2020. These plans did
not appropriately capture the now 125-feet of piping
distance between the .75" water meter and base of riser. This
particular change was what identified as requiring a
submittal of revisions being required at time of the Overhead
Rough inspection on 2/7/2020. Please provide revised
hydraulic calculations for this original concern.
Also, at time of inspection, the riser gauge was showing a
static pressure of 40 psi and main drain residual of 35 psi. The
7/26/2019 water supply information shows a static pressure
of 63.20 psi. The 40 psi is far below the minimum pressure
allowed by the 90% safety factor. *Jason advised that there
was other contractor services (irrigation, plumbing) that may
be running water.
If you are able to supply the revised hydraulic calcs today (I
don't need plans again, I can use the as-builts) - then we can
see as early as tomorrow reinspecting (without additional
fees) for this project. *The revised calcs were also supposed
to account for the additional 90's added as noted on the as-
builts.
Please let me know what will work for you.
CONDITIONS
Printed: Tuesday, February 07, 2023 3:07:07 PM 2 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2019-0161
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT CHARLES F BROWN FIRE
PROTECTION DESIGN
21386 LILIUM COURT MORENO
VALLEY
CA 92557 (760)340-9800 CHUCK92234@AOL.CO
M
CONTRACTOR CHARLES F BROWN FIRE
PROTECTION DESIGN
21386 LILIUM COURT MORENO
VALLEY
CA 92557 (760)340-9800 CHUCK92234@AOL.CO
M
OWNER PAUL DEWEY LA QUINTA CA 92247 (760)340-9800
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE PLAN REVISION
SUBMITTALS 101-0000-42420 0 $161.00 $161.00 4/29/20 WEB5013 CREDIT CHARLES F BROWN
FIRE PROTECTIO ECON
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $161.00 $161.00 12/23/19 R57385 5282 CHECK CHARLES F BROWN
FIRE PROTECTIO JLIM
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED PC
101-0000-42420 0 $242.00 $242.00 12/23/19 R57385 5282 CHECK CHARLES F BROWN
FIRE PROTECTIO JLIM
Total Paid for FIRE FEES: $564.00 $564.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 12/23/19 R57385 5282 CHECK CHARLES F BROWN
FIRE PROTECTIO JLIM
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 12/23/19 R57385 5282 CHECK CHARLES F BROWN
FIRE PROTECTIO JLIM
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$579.00 $579.00
Printed: Tuesday, February 07, 2023 3:07:07 PM 3 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2019-0161
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 4/15/2020 KAYLI ALFORD
DEWEY AS BUILTS LOT
266 53488 VIA
STRADA WORKING
PLAN1-23-20-FP-1.1.pdf
DEWEY AS BUILTS LOT
266 53488 VIA
STRADA WORKING
PLAN1-23-20-FP-1.1.pdf
0
DOC 1/27/2020 KOHL HETRICK FSS2019-0161 - DEWEY
RES - CORRECTIONS.pdf
FSS2019-0161 - DEWEY
RES - CORRECTIONS.pdf 0
BOND INFORMATION
OVERHEAD ROUGH
PIPING KHET 2/7/2020 2/7/2020 APPROVED See Notes
Prior to final inspection, revisions are
required to show 125-ft 1.25" supply and
additional red-line changes and
observations.
OVERHEAD HYRO KHET 2/7/2020 2/7/2020 APPROVED
FIRE FINAL**KHET 5/5/2020 5/5/2020 APPROVED WITH BUCKET TEST
Static at riser = 64psi. Bucket test performed
on second floor only. Observed a minimum
16gpm from each head while flowing 5gpm
domestic.
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
JACK LIMA 12/23/2019 12/26/2019 12/26/2019 COMPLETE
1ST FIRE (2 WK)KOHL
HETRICK 12/23/2019 1/13/2020 1/16/2020 REVISIONS REQUIRED ADDED ADDITIONAL TIME TO ACCOUNT FOR THE
HOLIDAYS.
2ND FIRE (1 WK)KOHL
HETRICK
1/23/2020 1/30/2020 2/4/2020 APPROVED
1ST FIRE (2 WK)KOHL
HETRICK 4/28/2020 5/12/2020 4/29/2020 APPROVED-
CONDITIONS
REV 1 - BUCKET TEST
REQUIRED
PARENT PROJECTS
Printed: Tuesday, February 07, 2023 3:07:07 PM 4 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2019-0161
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 2/5/2020 KOHL HETRICK
FSS2019-0161 - DEWEY
RES - 2ND REVIEW -
APPR.pdf
FSS2019-0161 - DEWEY
RES - 2ND REVIEW -
APPR.pdf
0
DOC 2/7/2020 KOHL HETRICK OH Rough Red Lines.pdf OH Rough Red Lines.pdf 0
DOC 4/29/2020 KOHL HETRICK
FSS2019-0161 -
REVISION 1 PLANS and
CALCS - APPR
CONDITIONALLY.pdf
FSS2019-0161 -
REVISION 1 PLANS and
CALCS - APPR
CONDITIONALLY.pdf
1
Printed: Tuesday, February 07, 2023 3:07:07 PM 5 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2019-0161
APPROVALS AND CONDITIONSNO A.S. REQUIRED 2/17/2020 lot 266 53488 via strada< LESS THAN 55 SQ. FT.NO A. S.< LESS THAN 55 SQ. FT.NO A. S.< LESS THAN 55 SQ. FT.NO A. S.OPEN TO 2ND. FLR.OPEN TO 2ND. FLR.OPEN TO 2ND. FLR.SEE A.S. AT 2ND. FLR.1" UP TO 2ND. FLR.< LESS THAN 55 SQ. FT.NO A. S.FROM 2ND. FLR.First Floor Sprinkler PlanNORTHNO A.S. REQUIREDFROM 2ND. FLR.UP TO NODE 2Ax2 EXTRA 90'Sx3 EXTRA 90'Sx6 EXTRA 90'SUPRIGHT IN ATTIC ABOVE FAU.DN.22RSecond Floor Sprinkler Planlot 266 53488 via stradaOPEN TO 1ST. FLR.< LESS THAN 55 SQ. FT.NO A. S.< LESS THAN 55 SQ. FT.NO A. S.1" TO FIRST FLR GREAT ROOM FP-1.1SHEET TITLE: PIPING & DETAILSPROJECT:No. DATE DESCRIPTIONREVISIONS:VIKINGMODELSYMMAKEAUTOMATIC SPRINKLERSTYCOCONTRACTOR:FSS2019-0161 REV 1