Description: LIVIN ON THE EIGHTH, LLC / FIRE SPRINKLER / BRES2019-0147
Type: FIRE SPRINKLER Subtype: RESIDENTIAL - CUSTOM
HOMES
Status: FINALED Applied: 1/29/2020 AHI
Parcel No: 767680052 Site Address: 53494 ROSS AVE LA QUINTA,CA 92253 Approved: 2/11/2020 KHET
Subdivision: TR 33076-1 Block: Lot: 47 Issued: 2/12/2020 JLIM
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 8/19/2020 KHET
Valuation: $0.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
Printed: Thursday, January 12, 2023 2:33:34 PM 1 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0022
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD ROUGH
PIPING KHET 3/5/2020 3/5/2020 PARTIALLY
APPROVED Partial -South side only
OVERHEAD HYRO KHET 3/5/2020 3/5/2020 PARTIALLY
APPROVED Partial -South side only
OVERHEAD ROUGH
PIPING KHET 4/13/2020 4/13/2020 APPROVED PARTIAL
REMOTE VIDEO INSPECTION.
THIS COVERED THE MASTER SUITE & GUEST
SUITE SIDE OF THE HOUSE.
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE FAILED OR
ADDITIONAL RE-
INSPECTION
101-0000-42421 0 $161.00 $161.00 8/26/20 WEB6088 517719 CREDIT J D MECHANICAL FIRE
INC ECON
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $241.00 $241.00 1/29/20 R58799 1782 CHECK J D MECHANICAL FIRE
INC AHI
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED PC
101-0000-42420 0 $242.00 $242.00 1/29/20 R58799 1782 CHECK J D MECHANICAL FIRE
INC AHI
Total Paid for FIRE FEES: $644.00 $644.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 1/29/20 R58799 1782 CHECK J D MECHANICAL FIRE
INC AHI
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 1/29/20 R58799 1782 CHECK J D MECHANICAL FIRE
INC AHI
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$659.00 $659.00
Printed: Thursday, January 12, 2023 2:33:34 PM 2 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0022
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 4/10/2020 ARMANDO MAGALLON PLAN SET - APPROVED FSS2020-0022 PLAN
SET.pdf 0
DOC 8/17/2020 EtrakitContractor Lot 47 pdfSprinkler As
Builds.pdf 1
DOC 12/9/2021 JOSE DELGADO Fire Review
Application.pdf
Fire Review
Application.pdf 0
DOC 12/9/2021 JOSE DELGADO FSS2020-0022 -
CALCULATIONS.pdf
FSS2020-0022 -
CALCULATIONS.pdf 0
DOC 12/9/2021 JOSE DELGADO
FSS2020-0022 - CVWD
RESIDENTIAL
CONNECTION CHARGE
ESTIMATE.pdf
FSS2020-0022 - CVWD
RESIDENTIAL
CONNECTION CHARGE
ESTIMATE.pdf
0
BOND INFORMATION
OVERHEAD ROUGH
PIPING KHET 4/13/2020 4/13/2020 APPROVED PARTIAL AS-BUILTS REQUIRED PRIOR TO FINAL
INSPECTION.
OVERHEAD HYRO KHET 4/13/2020 4/13/2020 APPROVED FINAL PARTIAL
REMOTE VIDEO INSPECTION.
THIS COVERED THE MASTER SUITE & GUEST
SUITE SIDE OF THE HOUSE.
FIRE FINAL**KHET 8/19/2020 8/19/2020 APPROVED PROCESSED AFTER FEES
PAID
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
PERMIT TECH
BUCKET
1/29/2020 1/30/2020 1/30/2020 COMPLETE
1ST FIRE (2 WK)KOHL
HETRICK
1/29/2020 2/12/2020 2/11/2020 APPROVED
PARENT PROJECTS
Printed: Thursday, January 12, 2023 2:33:34 PM 3 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0022
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 12/9/2021 JOSE DELGADO FSS2020-0022 -COA.pdf FSS2020-0022 -COA.pdf 0
Printed: Thursday, January 12, 2023 2:33:34 PM 4 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0022
x;GARAGE
x;MASTER
SUITE
x;OFFICE
x;ENTRY COURTYARD
x;KITCHEN
x;BAR
x;ENTRY
x;CLOSET
x;LAUNDRYx;MECH.x;BATH
x;HALL
x;TUB
x;BATH
x;DINNING
x;DEN
x;KID #2x;KID #1
x;GUEST
x;CLOSET
x;CLOSET
x;CLOSET
x;OUTDOOR
LIVING
x;SITTING
x;HIS
x;SITTING
x;COVERED
CAR PORT
x;HER
CLOSET
x;GUEST
SUITE
x;A/V
x;PANTRY
x;POWDER x;POWDER
x;KID
x;CLOSET
x;CLOSET
x;BATH
x;ELECT
x;MASTER BATH
x;SHOWER
x;HALL
x;VESTIBULE
x;GUEST
BATH
12'-0"12'-1"
10'-1"
10'-1"
10'-1"
12'-1"13'-1"
12'-1"
12'-1"
12'-1"
10'-1"
12'-1"
14'-1"
13'-1"
16'-1"
11'-1"11'-1"
16'-1"
12'-1"12'-1"
12'-1"
12'-1"
12'-1"
11'-1"
14'-1"
14'-1"
11'-1"
11'-1"
12'-1"
12'-1"12'-1"
11'-1"
11'-1"
12'-1"16'-1"
11'-1"
14'-1"
14'-1"
12'-4"
12'-1"
12'-1"
11'-1"
x;W
x;D
SC
SC SC
SC
SC
SC
SC
SC
SC
N
x;SINKx;SINK
x;SINK x;FPx;FPx;FP x;FP
x;FP
x;FP
x;FPx;FPFire Sprinkler Riser Detail
1" CPVC to supply fire sprinkler system
TOR
BOR
Domestic
Supply
Check
Flow Control
1" CPVC
Flow Switch Note Wiring by Others
300psi Gage
Sprinkler Box with Wrench & two
Sprinkler Heads Each Type
1/2" Drain to
Outside1"1"1"
Potter Horn Strobe
Wired by Others
not to scale
Module Must Connect to the Multi
Station Smoke Alarm System and
the Fire Sprinkler Flow Switch
( all wiring by others )
CPVC HANGERS
NO SCALE
TOLCO FIG. 24
DOUBLE-FASTENER
SIDE-MOUNT HANGER
(OR EQUAL)
SELF-DRILLING
HEX HEAD SCREW
TOLCO FIG. 23
DOUBLE-FASTENER
STRAP TYPE HANGER
(OR EQUAL)
TOLCO FIG. 28M
OFFSET HANGER
(OR EQUAL)
TOLCO FIG. 22
SINGLE-FASTENER
STRAP-TYPE HANGER
(OR EQUAL)
TOLCO FIG. 28
DOUBLE-FASTENER
STAND-OFF HANGER
(OR EQUAL)
TOLCO FIG. 29
DOUBLE-FASTENER
DOUBLE OFFSET HANGER
(OR EQUAL)
CPVC HANGER SPACING
PIPE SIZE
11/4"
1"
MAXIMUM SUPPORT SPACING
6'-6"
6'-0"
2"8'-0"
11/2"7'-0"
INSPECTOR TEST DETAIL
5'
1" Ball Valve Access Panel
(By Others)
Exterior Wall of Building
Inspector Test to Terminate
in a Smooth Bore Corrosion
Resistant Orfice With a Flow
Equivalent to One Sprinkler
NOTE: Access Panel Shall have sign
Indicating Inspector Test
RING HANGER
(TOLCO FIG. 200)
3/8" ALL-THREAD
ROD
PIPE
WOOD BEAM
OR RAFTER
WOOD SAMMY
SUPERSCREW
(Model GST20)
2x_ BLOCKING (TO BE SAME SIZE AS
RAFTER) NAILED TO RAFTERS w/ (2)
10d NAILS EACH SIDE OF BLOCK.
WOOD BEAM
OR RAFTER
WOOD BEAM
OR RAFTER
RING HANGER
(TOLCO FIG. 200)
3/8" ALL-THREAD
ROD
PIPE
WOOD SAMMY
SIDEWINDER
(Model SWG20)
RING HANGER
(TOLCO FIG. 200)
3/8" ALL-THREAD
ROD
PIPE
WOOD BEAM
OR RAFTER
WOOD SAMMY
SIDEWINDER
(Model SWG20)
2x_ BLOCKING (TO BE SAME SIZE AS
RAFTER) NAILED TO RAFTERS w/ (2)
10d NAILS EACH SIDE OF BLOCK.
WOOD BEAM
OR RAFTER
WOOD BEAM
OR RAFTER
RING HANGER
(TOLCO FIG. 200)
3/8" ALL-THREAD
ROD
PIPE
WOOD SAMMY
SUPERSCREW
(Model GST20)
TOLCO
TOLCO 15' - 2"Supply Point
Water Supply Information
Static Pressure:
Residual Pressure:
Residual Flow:
Additional Hose Flow:
76.70 psi
58.85 psi
5000 GPM
0 GPM
Remote area number:
Occupancy classification:
Density:
Area of application:
Total water required
(including hose streams):
@ a required
system pressure
of:
Fire Protection System Demand:
No. of sprinklers calculated:
Inside Hose Streams:
Outside Hose
Streams:
Calc-1
R-3
2
Gpm/SqFt
512 SF Max SqFt
31.1914 GPM
38.8217 Psi
5 GPM
0 GPM
BOR
8
TOR
7
6
9
4
5
WM
DOM
1"
15' -6"1"5' -2 1/2"3/4"9' -4"1"
10' -10 1/2"3/4"1' -11"1"
4' -3 1/2"3/4"10' -1"3/4"5' -6"3/4"
6' -4 1/2"3/4"1' -1"3/4"
7' -1"3/4"1' -11"3/4"7' -5 1/2"3/4"
5' -7 1/2"3/4"1' -6"3/4"8' -6"3/4"
4' -3"3/4"1' -0"3/4"9' -0"1"
8' -11"
1"
10' -6 1/2"3/4"10' -1"3/4"5' -6"3/4"
6' -9"3/4"0' -10"3/4"2' -2"3/4"7' -7"3/4"
4' -5"
3/4"
1' -4 1/2"3/4"8' -6"3/4"
5' -2 1/2"
3/4"
1' -4 1/2"3/4"8' -6"3/4"
7' -0"
1"
0' -5 1/2"
1"
2' -2 1/2"
1"
2' -0"
1"
4' -2"3/4"12' -7"3/4"
6' -5 1/2"
3/4"
1' -0"3/4"8' -7 1/2"3/4"
3' -9"3/4"
1' -6"3/4"9' -9"3/4"
5' -11"3/4"
1' -6"3/4"9' -9"1"
5' -4"3/4"9' -5 1/2"3/4"13' -5 1/2"1"
0' -8"
1"
12' -8 1/2"3/4"7' -3 1/2"3/4"13' -7"3/4"11' -8 1/2"3/4"1' -10 1/2"3/4"
16' -5"1"6' -3 1/2"1"13' -7"1"
0' -7"
1"
12' -4"
1"
12' -8"
3/4"
1' -7 1/2"
1"
12' -8"
3/4"
1' -7 1/2"1"3' -7"1"
13' -1 1/2"
1"
7' -3"
1"
11' -3"
1"
1' -9"
3/4"
7' -3 1/2"
1"
10' -7 1/2"3/4"5' -7"3/4"5' -4 1/2"1"
12' -4 1/2"3/4"5' -4 1/2"3/4"5' -7"1"
12' -4 1/2"
1"
14' -9 1/2"
1"
1' -1 1/2"1"7' -5"1"
11' -1"1"4' -6"1"
3' -11 1/2"
1"
8' -0"3/4"6' -3 1/2"1"
1' -0"
3/4"
2' -8 1/2"1"8' -0"1"
11' -6 1/2"3/4"4' -5"3/4"8' -4"1"
13' -3"3/4"4' -5"1"8' -4"1"
0' -10"
1"
0' -10"1"
15' -10 1/2"
1"
2' -8 1/2"1"8' -0"3/4"
5' -7"
3/4"
3' -4 1/2"
3/4"
4' -4"3/4"6' -4 1/2"3/4"4' -4 1/2"1"
2' -0"3/4"6' -4 1/2"3/4"
4' -4 1/2"
1"
8' -5"3/4"
2' -11 1/2"
1"
14' -7"3/4"5' -3"3/4"3' -7"3/4"
5' -3"
3/4"
1' -7 1/2"1"15' -10"1"13' -5 1/2"1"9' -5 1/2"3/4"
1' -7 1/2"3/4"7' -3 1/2"3/4"13' -7"3/4"13' -7"3/4"6' -3 1/2"3/4"13' -7"3/4"3' -5"3/4"3' -4"3/4"1' -11"1"1' -11"1"1' -11"1"10' -9"3/4"5' -2 1/2"3/4"12' -2"3/4"5' -2 1/2"3/4"12' -2"1"
1' -6 1/2"
2"
6' -10"2"33' -0"3/4"
4' -1"
1"
8' -10"
1"
5' -4"
3/4"
5' -3"2" Underground Copper By Others1" Fire Riser 3/4"12' -2"16' - 0"3/4"13' -7"11' - 8"11' - 9"
Inspectors Test Valve
GENERAL NOTES
1.General: All materials and devices shall conform to 2019 NFPA 13D standards. Installation
shall conform to all applcable State and Local Codes.
2.Scope of Work: Install a new Residential Fire Protection System.
3.Piping: All overhead pipe and fittings shall be CPVC unless otherwise noted.
4.Design: NFPA 13D 2019 Edition and CFC Chapter 80 Standards.
5.System Demand @ Source. Two Sprinklers Flowing (16X16 Spacing):
31.19 gpm @ _38.82__psi ( AREA )
6.Water Supply Data: Water is supplied from public water main in street.
Static Pressure: 76.7
Information Source: CVWD
7.Sprinkler Head Spacing and Installation Requirements:Sprinklers shall not be located
Closer than 8'-0" apart where there is no intervening obstruction.
Sprinklers near potential obstruction shall be located per manufactures instructions.
8.Piping Supports: Piping shall be supported and restrained in conformance with local
plumbing codes and CPVC manufactures instructions . Eachpipe section that supplies
a drop to a sprinkler shall be secured no more than 12" from the drop to prevent laterial
and vertical movement.
9.Pipe lenghts are approximate for hydraulic calculation and plan review purposes only.
10.The owner shall furnish sufficant heat in all areas to prevent freezingof pipe.
11.Waterflow Switch and Alarm: By Others
a. A dedicated electrical circuit with a circuit breaker lock shall be provided for waterflow
horn/strobes.
b. An approved audible sprinkler waterflow alarm shall be visible from the street.
The device shall be listed for outdoor use.
An approved sign shall be placed at or near the device stating,
SPRINKLER FIRE ALARM - WHEN ALARM SOUNDS CALL 911
c. An approved audible sprinkler waterflow alarm module shall be conected to the
smoke detectors to alert occupants shall be provided.
Fire Department Notes NFPA 13D 2019
A. The installation of new fire sprinkler systems or modifications to existing systems shall
comply with the following:
NFPA 13D 2019
CBC 2019
CFC 2019
Local Municipal Codes
Requirements of the AHJ
All Manufacture Installation Guidelines
Note: When conflict arrises between existing codes and standards,
the most stringent shall apply.
B. The Fire Department Shall require the following inspections and tests.
1. Overhead installation and hydrostatic test, ( prior to cover ).
a. Normal opperating pressure when no FDC is installed.
b. 200psi when FDC is required.
c. Two hour minimum.
2. Final sprinkler and underground, ( prior to building final ).
a. All inspections shall be scheduled by the contractor of record.
b. Inspections shall be scheduled 24 hours in advance.
jd@jdmechanical.co
Scale
Project number
Date
Drawn by
Checked by JD Mechanical Fire Inc.82579 Fleming Way Suite DIndio Ca. 92201(760) 775-6220JD Mechanical
Fire Inc.
C-16 # 1020141
As indicated
8/14/2020 4:35:08 PMFP-2
Sprinkler Plan
Project Number
Issue Date
Author
Checker
No. Description Date
MADISON LOT 4753494 Ross AveLa Quinta, Ca. 900631/8" = 1'-0"1 Sprinkler Plan
Sprinkler Schedule
K-Factor Manufacturer Description Temperature Rating Count
4.9 SENJU Senju SS8464 Conceled Pendent Light Hazard Quick Response1/2 Orifice 3mm GB 162 °F 91
4.2 Tyco Tyco TY2231 Recessed Pendent Light Hazard Quick Response1/2 Orifice 3mm GB 175 °F 9