FSS2020-0030ADDITIONAL SITES
CHRONOLOGY
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
Description: NEUFIELD / FIRE SPRINKLERS / BRES2019-0187
Type: FIRE SPRINKLER Subtype: RESIDENTIAL - CUSTOM
HOMES
Status: FINALED Applied: 2/12/2020 AHI
Parcel No: 770370005 Site Address: 53630 DEL GATO DR LA QUINTA,CA 92253 Approved: 3/10/2020 KHET
Subdivision: TR 28867 Block: Lot: 104 Issued: 3/11/2020 JLIM
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 11/3/2020 KHET
Valuation: $0.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
Printed: Wednesday, February 08, 2023 12:45:40 PM 1 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0030
E-MAIL KOHL HETRICK 10/20/2020 10/20/2020
Now that I am back in the office, I wanted to touch back with
you and discuss the options.
Option 1: (As originally conditioned at Rough Inspection)
Submit Revisions with Calculations showing the ¾” WM and
125’ of 1” UG supply is sufficient.
Option 2: Bucket Test of the 2 most – remote/demanding
design heads to confirm adequate flow. *Test procedure
attached.
Option 3: Upgrade the water meter to 1” as per original
approved Calcs. *Consider upgrading the UG piping size from
the Meter to BOR.
Please let me know what you would like to do.
NOTE KAYLI ALFORD 10/15/2020 10/15/2020
CONTRACTOR REQUESTED INSPECTION. INFORMED THEM
THE PERMIT IS EXPIRED AND EXTENSION LETTER & FEE WILL
BE DUE PRIOR TO EXTENDING. OK TO EXTEND PER KOHL.
NOTE KAYLI ALFORD 10/19/2020 10/19/2020
PERMIT EXTENDED TO 10/20/20 SO CONTRACTOR CAN PAY
EXTENSION FEE ON ETRAKIT. PER KOHL, REQUIREMENT FOR
REVISION SUBMITTAL WITH REVISED CALCS WILL BE WAIVED.
RECEIVED PERMIT EXTENSION REQUEST LETTER & EXTENSION
FEE PAYMENT. EXTENDED PERMIT BY 6 MOS TO 4/19/21.
PLAN CHECK PICKED UP JACK LIMA 3/3/2020 3/3/2020 1ST PLAN CORRECTIONS PICKED UP BY MARK TRELAK.
PUBLIC COUNTER VISIT JACK LIMA 3/11/2020 3/11/2020 PERMIT ISSUED TO MARK TRELAK.
RESUBMITTAL JACK LIMA 3/6/2020 3/6/2020 2ND PLAN RESUBMITTAL MADE BY MARK TRELAK.
CONDITIONS
Printed: Wednesday, February 08, 2023 12:45:40 PM 2 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0030
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT DESERT FIRE EXTINGUISHER CO INC PO BOX 1607 PALM SPRINGS CA 92263 (306)221-9634 MARK@DESERT-
FIRE.COM
CONTRACTOR DESERT FIRE EXTINGUISHER CO INC PO BOX 1607 PALM SPRINGS CA 92263 (306)221-9634 MARK@DESERT-
FIRE.COM
OWNER DONALD J & JANET C NEUFELD 53630 DEL GATO LA QUINTA CA 92253 (306)221-9634 DON@JHBUILDERS.CO
M
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE FAILED OR
ADDITIONAL RE-
INSPECTION
101-0000-42421 0 $161.00 $161.00 11/2/20 WEB6649 036239 CREDIT DESERT FIRE
EXTINGUISHER CO INC ECON
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $242.00 $242.00 2/12/20 R59542 445 CHECK DESERT FIRE
EXTINGUISHER CO IN AHI
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED PC
101-0000-42420 0 $241.00 $241.00 2/12/20 R59542 445 CHECK DESERT FIRE
EXTINGUISHER CO IN AHI
FIRE STAFF - PER HOUR 101-0000-42420 0.25 $40.25 $40.25 10/19/20 WEB6538 077425 CREDIT DESERT FIRE
EXTINGUISHER CO INC ECON
Total Paid for FIRE FEES: $684.25 $684.25
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 2/12/20 R59542 445 CHECK DESERT FIRE
EXTINGUISHER CO IN AHI
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 2/12/20 R59542 445 CHECK DESERT FIRE
EXTINGUISHER CO IN AHI
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$699.25 $699.25
Printed: Wednesday, February 08, 2023 12:45:40 PM 3 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0030
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD ROUGH
PIPING KHET 3/16/2020 3/16/2020 APPROVED See Notes
(DISREGARD: Revisions and calcs required
prior to final. )
Confirm at final:
1) Add 1 head in kitchen ceiling pocket.
2) Add 1 head in bedroom 2 closet.
3) Add 1 head in bedroom 3 bath.
4) Add 1 head under bedroom 4 entry soffit.
OVERHEAD HYRO KHET 3/16/2020 3/16/2020 APPROVED
FIRE FINAL**KHET 10/20/2020 10/20/2020 DISAPPROVE
D
Observed 3/4" WM and approximately 125'
of UG to new Riser Location. This is the
reason for the original requirement to
submit Revised Plans with Updated
Hydraulic Calcs. Contractor did not have
approved plans on site. PDF plans and calcs
were resourced via email and updated with
redline field notes based on observed
conditions. (3) options: 1) Provide Revisions
with Calcs that show the current WM and
UG supply is sufficient. 2) Bucket Test of 2
remote/demanding heads. 3) Upgrade the
underground and water meter.
FIRE FINAL**KHET 11/3/2020 11/3/2020 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
PERMIT TECH
BUCKET 2/12/2020 2/13/2020 2/12/2020 COMPLETE
PARENT PROJECTS
Printed: Wednesday, February 08, 2023 12:45:40 PM 4 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0030
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 11/5/2021 JOSE DELGADO Fire Review Application
Revision.pdf
Fire Review Application
Revision.pdf 0
DOC 11/5/2021 JOSE DELGADO Fire Review
Application.pdf
Fire Review
Application.pdf 0
DOC 11/5/2021 JOSE DELGADO
Approved Hydraulic
Design Information
Sheet.pdf
Approved Hydraulic
Design Information
Sheet.pdf
0
DOC 11/5/2021 JOSE DELGADO Approved FSS2020-
00030.pdf
Approved FSS2020-
00030.pdf 0
DOC 10/19/2020 KAYLI ALFORD Extension Request
Letter.pdf
Extension Request
Letter.pdf 0
DOC 3/3/2020 KOHL HETRICK
FSS2020-0030 -
NEUFIELD RESIDENCE -
1ST PC CORR.docx
FSS2020-0030 -
NEUFIELD RESIDENCE -
1ST PC CORR.docx
0
DOC 3/10/2020 KOHL HETRICK
FSS2020-0030 -
NEUFIELD HOUSE -
RESUBM 1 - APPR.pdf
FSS2020-0030 -
NEUFIELD HOUSE -
RESUBM 1 - APPR.pdf
0
DOC 10/20/2020 KOHL HETRICK NEUFIELD HOUSE HYD
CALC.pdf
NEUFIELD HOUSE HYD
CALC.pdf 1
DOC 10/20/2020 KOHL HETRICK NEUFIELD HOUSE HYD
GRPAH.pdf
NEUFIELD HOUSE HYD
GRPAH.pdf 1
DOC 10/20/2020 KOHL HETRICK NEUFIELD HOUSE.pdf NEUFIELD HOUSE.pdf 1
BOND INFORMATION
1ST FIRE (2 WK)KOHL
HETRICK 2/12/2020 2/26/2020 3/3/2020 REVISIONS REQUIRED SEE ATTACHMENTS
2ND FIRE (1 WK)KOHL
HETRICK 3/6/2020 3/13/2020 3/10/2020 APPROVED
1ST FIRE (1 DAY)KOHL
HETRICK 10/28/2020 10/28/2020 10/28/2020 APPROVED REVISED PLANS/CALCS
Printed: Wednesday, February 08, 2023 12:45:40 PM 5 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0030
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 10/28/2020 KOHL HETRICK
FSS2020-0030 - REVISED
PLANS AND CALCS -
APPROVED.pdf
FSS2020-0030 - REVISED
PLANS AND CALCS -
APPROVED.pdf
1
Printed: Wednesday, February 08, 2023 12:45:40 PM 6 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0030
3/4" CITY WATER METERCONNECTION TO CITYNO CLOSETS UNDER 24 SQ FT SHALL BE SPRINKLEREDNO BATHROOMS UNDER 55 SQ FT SHALL BE SPRINKLERED5 GPM LOSS FORDOMESTIC USEDEL GATTOI
s
land 10'-0" Soffit10'-0" Soffit10'-0" Soffit10'-0" Soffit10'-0" Soffit8'-6" Soffit11'-8" Soffit9'-8" Soffit9'-8" Soffit9'-8" Soffit8'-0" Soffit9'-0" Soffit10'-0" Soffit10'-0" Soffit8'-6" Soffit10'-0" Ceiling Ht.10'-0" Ceiling Ht.12'-0" Ceiling Ht.9'-0" Ceiling Ht.10'-0" Ceiling Ht.10'-0" Ceiling Ht.10'-0" Ceiling Ht.10'-0" Ceiling Ht.10'-0" Ceiling Ht.10'-0" Ceiling Ht.10'-0" Ceiling Ht.11'-0" Ceiling Ht.10'-0" Ceiling Ht.11'-0" Ceiling Ht.12'-0" Ceiling Ht.13'-0" Ceiling Ht.12'-0" Ceiling Ht.12'-0" Ceiling Ht.14'-6" Ceiling Ht.12'-0" Soffit13'-0" Ceiling Ht.11'-6" Soffit9'-7" Soffit8'-6" Soffit8'-6" Soffit10'-0" Ceiling Ht.11'-0" Ceiling Ht.13'-0" Ceiling Ht.13'-10" Ceiling Ht.10'-0" Ceiling Ht.10'-0" Ceiling Ht.10'-0" Ceiling Ht.9'-0" Ceiling Ht.13'-6" Soffit14'-6" Ceiling Ht.9'-7" Soffit10'-0" Soffit10'-0" Soffit10'-0" Soffit10'-0" Soffit10'-0" Ceiling Ht.10'-0" Ceiling Ht.9'-0" Ceiling Ht.12X812X812X812X812X810X610X610X610X610'-0" Ceiling Ht.10'-0" Ceiling Ht.13'-0" Ceiling Ht.NEW HOUSE PIPING PLAN.SCALE 1/8" = 1'-0"NOTE:EACH POCKET DOES NOT EXCED 100 CU FTTHE ENTIRE FLOOR AREA IS COVERED BY THE LOWER CEILING SPRINKLERSNOTE:EACH POCKET DOES NOT EXCED 100 SQ FTTHE ENTIRE FLOOR AREA IS COVERED BY THE LOWER CEILING SPRINKLERSNOTE:EACH POCKET DOES NOT EXCED 100 CU FTTHE ENTIRE FLOOR AREA IS COVERED BY THE LOWER CEILING SPRINKLERS1
0
'
-
0
"
C
E
I
L
ING
H
E
IGH
T
1
0
'
-
0
"
C
E
I
L
ING
H
E
IGH
T1" PVC PIPE 125'-0"JOB NUMBER:
APPROVAL: LQ FD
SCALE:AS NOTED
SHEET:1 OF 1
WATER
SOURCE: CVWD
CALCULATED WETSYSTEM TYPE
HAZARD
TOTAL DEMAND
TOTAL SYSTEM
AREA OF
SYSTEM DESIGN DATA
HYDRAULIC
TOTAL AMOUNT OF HEADS ON THIS SHEET
QUANTITYFINISHKTEMP.NPTTYPE ESC.SYMBOL MAKE, MODEL & S.I.N.
FIRE SPRINKLERINSTALLATIONSDESIGN
DRAWN BY: AARON J
DATE: 10/28/2020
DESERT
558 INDUSTRIAL PLACE PALM SPRINGS, CA 92264 760 322-0995
FIRE EXTINGUISHER
FIRE SPRINKLER LEGEND
SSP 1/2 4.9 200°TYCO TYFRB PENDENT TY2234
TYCO LF II CONCEALED PENDANTS TY 3596 SSP 1/2 4.9 155°WHITE WHITE
WHITEWHITE CLASSIFICATION:RESIDENTAIL 13D
DESIGN DATA:16X16
APPLICATION:
REQUIREMENTS:
AT SOURCE:
26.0 GPM @ 25.0 PSI AT BASE OF RISER
SQFT DOMESTIC .05 GPM
256 SQ FT/HD
92 STATIC PRESS.RESIDUAL PRESS. 85 PSI@ 1500 GPMSUPPLY:
CONTRACT WITHAPPROVALSPHONEJOB:NEUFIELD HOUSE
LA QUINTA, CA
55
64
9
C-16# 563921
53630 DEL GATTO DR 1-1/2" OFFSET EDGE FOR ABRASION ELIMINATION REQUIRED FASTENER FURNISHED WITH THE HANGER,NEEDS NO PREDRILLINGSPACE HANGERS PER CHART BELOWAND SUPERIOR STRENGTHFEATURES:OFFSET PIPE/CPVC HANGERAFCON NO. 514 MATERIAL: CARBON STEELFINISH: MIL. GALVANIZEDSIZE: 3/4" THRU 2" PIPELISTING: UL IN US AND CANADAINSTALLATION: INSTALL ON THE SIDEOF WOOD BEAMS AS DESCRIBED:INSTALLED PER NFPA 13, 13R, AND 13DFUNCTION: HANGER FOR USE OF CPVC PIPINGFURNISHED WITH PRODUCT. INSTALL FASTENERS, AS FOLLOWS:IN WOOD - USE LISTED HEX HEAD SCREW AROUND PIPE ALLOWING PIP TO SLIDE FREELYSNAP OVER PIPE THEN SQUEEZE STRAP BACK "A""B"RISER DETAIL1"TO SPRINKLER SYSTEMFROM UGBORNO SCALERISER TO BE ACCESSIBLEIF ACCESS DOOR IS INSTALLEDLABEL DOOR "FIRE SPRINKLER RISER"ACCESS DOOR BY OTHERS.1" CPVC 90 ELLW
1" CITY WATER METERCONNECTION TO CITYNO CLOSETS UNDER 24 SQ FT SHALL BE SPRINKLEREDNO BATHROOMS UNDER 55 SQ FT SHALL BE SPRINKLERED5 GPM LOSS FORDOMESTIC USEDEL GATTOI
s
land 10'-0" Soffit10'-0" Soffit10'-0" Soffit10'-0" Soffit10'-0" Soffit8'-6" Soffit11'-8" Soffit9'-8" Soffit9'-8" Soffit9'-8" Soffit8'-0" Soffit9'-0" Soffit10'-0" Soffit10'-0" Soffit8'-6" Soffit10'-0" Ceiling Ht.10'-0" Ceiling Ht.12'-0" Ceiling Ht.9'-0" Ceiling Ht.10'-0" Ceiling Ht.10'-0" Ceiling Ht.10'-0" Ceiling Ht.10'-0" Ceiling Ht.10'-0" Ceiling Ht.10'-0" Ceiling Ht.10'-0" Ceiling Ht.11'-0" Ceiling Ht.10'-0" Ceiling Ht.11'-0" Ceiling Ht.12'-0" Ceiling Ht.13'-0" Ceiling Ht.12'-0" Ceiling Ht.12'-0" Ceiling Ht.14'-6" Ceiling Ht.12'-0" Soffit13'-0" Ceiling Ht.11'-6" Soffit9'-7" Soffit8'-6" Soffit8'-6" Soffit10'-0" Ceiling Ht.11'-0" Ceiling Ht.13'-0" Ceiling Ht.13'-10" Ceiling Ht.10'-0" Ceiling Ht.10'-0" Ceiling Ht.10'-0" Ceiling Ht.9'-0" Ceiling Ht.13'-6" Soffit14'-6" Ceiling Ht.9'-7" Soffit10'-0" Soffit10'-0" Soffit10'-0" Soffit10'-0" Soffit10'-0" Ceiling Ht.10'-0" Ceiling Ht.9'-0" Ceiling Ht.12X812X812X812X812X810X610X610X610X610'-0" Ceiling Ht.10'-0" Ceiling Ht.13'-0" Ceiling Ht.NEW HOUSE PIPING PLAN.SCALE 1/8" = 1'-0"NOTE:EACH POCKET DOES NOT EXCED 100 CU FTTHE ENTIRE FLOOR AREA IS COVERED BY THE LOWER CEILING SPRINKLERSNOTE:EACH POCKET DOES NOT EXCED 100 SQ FTTHE ENTIRE FLOOR AREA IS COVERED BY THE LOWER CEILING SPRINKLERSNOTE:EACH POCKET DOES NOT EXCED 100 CU FTTHE ENTIRE FLOOR AREA IS COVERED BY THE LOWER CEILING SPRINKLERS1
0
'
-
0
"
C
E
I
L
ING
H
E
IGH
T
1
0
'
-
0
"
C
E
I
L
ING
H
E
IGH
T1" PVC PIPE 50'-0"JOB NUMBER:
APPROVAL: LQ FD
SCALE:AS NOTED
SHEET:1 OF 1
WATER
SOURCE: CVWD
CALCULATED WETSYSTEM TYPE
HAZARD
TOTAL DEMAND
TOTAL SYSTEM
AREA OF
SYSTEM DESIGN DATA
HYDRAULIC
TOTAL AMOUNT OF HEADS ON THIS SHEET
QUANTITYFINISHKTEMP.NPTTYPE ESC.SYMBOL MAKE, MODEL & S.I.N.
FIRE SPRINKLERINSTALLATIONSDESIGN
DRAWN BY: AARON J
DATE: 2/10/2019
DESERT
558 INDUSTRIAL PLACE PALM SPRINGS, CA 92264 760 322-0995
FIRE EXTINGUISHER
FIRE SPRINKLER LEGEND
SSP 1/2 4.9 200°TYCO TYFRB PENDENT TY2234
TYCO LF II CONCEALED PENDANTS TY 3596 SSP 1/2 4.9 155°WHITE WHITE
WHITEWHITE CLASSIFICATION:RESIDENTAIL 13D
DESIGN DATA:16X16
APPLICATION:
REQUIREMENTS:
AT SOURCE:
26.0 GPM @ 25.0 PSI AT BASE OF RISER
SQFT DOMESTIC .05 GPM
256 SQ FT/HD
92 STATIC PRESS.RESIDUAL PRESS. 85 PSI@ 1500 GPMSUPPLY:
CONTRACT WITHAPPROVALSPHONEJOB:NEUFIELD HOUSE
LA QUINTA, CA
55
64
9
C-16# 563921
53630 DELGATO DRIVE 1-1/2" OFFSET EDGE FOR ABRASION ELIMINATION REQUIRED FASTENER FURNISHED WITH THE HANGER,NEEDS NO PREDRILLINGSPACE HANGERS PER CHART BELOWAND SUPERIOR STRENGTHFEATURES:OFFSET PIPE/CPVC HANGERAFCON NO. 514 MATERIAL: CARBON STEELFINISH: MIL. GALVANIZEDSIZE: 3/4" THRU 2" PIPELISTING: UL IN US AND CANADAINSTALLATION: INSTALL ON THE SIDEOF WOOD BEAMS AS DESCRIBED:INSTALLED PER NFPA 13, 13R, AND 13DFUNCTION: HANGER FOR USE OF CPVC PIPINGFURNISHED WITH PRODUCT. INSTALL FASTENERS, AS FOLLOWS:IN WOOD - USE LISTED HEX HEAD SCREW AROUND PIPE ALLOWING PIP TO SLIDE FREELYSNAP OVER PIPE THEN SQUEEZE STRAP BACK "A""B"RISER DETAIL1"TO SPRINKLER SYSTEMFROM UGBORNO SCALERISER TO BE ACCESSIBLEIF ACCESS DOOR IS INSTALLEDLABEL DOOR "FIRE SPRINKLER RISER"ACCESS DOOR BY OTHERS.1" CPVC 90 ELLW