FSS2020-0050ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT J C FIRE PROTECTION 81705 DE ORO AVENUE INDIO CA 92201 (760)625-5908 JCFIREPROTECTION@V
ERIZON.NET
BILL TO JC FIRE PROTECTION 81705 DE ORO AVE INDIO CA 92201 (760)625-5908 jcfireprotection@veriz
on.net
CONTRACTOR J C FIRE PROTECTION 81705 DE ORO AVENUE INDIO CA 92201 (760)625-5908 JCFIREPROTECTION@V
ERIZON.NET
OWNER Benzinger Jay A / Benzinger Alicia A ,
CA
CA 95070 (760)625-5908
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
E-MAIL KOHL HETRICK 4/5/2020 4/5/2020 REQUESTED REVISED 1 HEAD CALCS FOR CORRECT FLOW AND
PRESSURE REQUIREMENTS
CONDITIONS
Description: BENZINGER / BRES2019-0317 / FIRE SPRINKLERS
Type: FIRE SPRINKLER (WEB)Subtype: RESIDENTIAL - CUSTOM
HOMES
Status: FINALED Applied: 3/23/2020 ECON
Parcel No: 762250006 Site Address: 57745 SOUTH VALLEY LN LA QUINTA,CA 92253 Approved: 4/7/2020 KHET
Subdivision: TR 28034 Block: Lot: 6 Issued: 4/7/2020 KHET
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 6/1/2020 KHET
Valuation: $10,000.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
Printed: Thursday, February 16, 2023 4:36:26 PM 1 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0050
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD ROUGH
PIPING KHET 4/9/2020 4/9/2020 APPROVED REMOTE VIDEO
INSPECTION
DOCUMENTED AS-BUILT CONDITIONS AND
UPLOADED TO ATTACHMENTS
OVERHEAD HYRO KHET 4/9/2020 4/9/2020 APPROVED REMOTE VIDEO
INSPECTION
FIRE FINAL**KHET 6/1/2020 6/1/2020 APPROVED REMOTE VIDEO
INSPECTION
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED STATUS REMARKS NOTES
PARENT PROJECTS
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $242.00 $242.00 3/23/20 WEB4733 039839 CREDIT J C FIRE PROTECTION ECON
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED PC
101-0000-42420 0 $242.00 $242.00 3/23/20 WEB4733 039839 CREDIT J C FIRE PROTECTION ECON
Total Paid for FIRE FEES: $484.00 $484.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 3/23/20 WEB4733 039839 CREDIT J C FIRE PROTECTION ECON
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 3/23/20 WEB4733 039839 CREDIT J C FIRE PROTECTION ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$499.00 $499.00
Printed: Thursday, February 16, 2023 4:36:26 PM 2 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0050
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 3/23/2020 EtrakitContractor 1ST SUBMITTAL AREA 2
ANALYSIS AREA 2 2 HEAD.pdf 1
DOC 3/23/2020 EtrakitContractor 1ST SUBMITTAL VIKING
2.8
vk 329 Recessed 2.8 k
QR.pdf 1
DOC 3/23/2020 EtrakitContractor 1ST SUBMITTAL VIKING
3.0
vk 470 Recessed 3.0
k.pdf 1
DOC 3/23/2020 EtrakitContractor 1ST SUBMITTAL TYCO blazemaster.pdf 1
DOC 3/24/2020 EtrakitContractor CVWD INVOICE AND
FIRE FLOW LETTER
CVWD Residential
Connection Estimate -
57745 S Valley Ln,
LQ.pdf
1
DOC 4/7/2020 KOHL HETRICK VK496 SPEC.pdf VK496 SPEC.pdf 1
DOC 4/7/2020 KOHL HETRICK 1ST SUBMITTAL - AREA
1 CALCULATION b AREA 1 1 HEAD.PDF 1
DOC 4/7/2020 KOHL HETRICK 1ST SUBMITTAL - PLANS
- APPROVED.pdf
1ST SUBMITTAL - PLANS
- APPROVED.pdf 1
DOC 4/7/2020 KOHL HETRICK
FSS2020-0050 -
BENZINGER RES - COA
AND JOB CARD.pdf
FSS2020-0050 -
BENZINGER RES - COA
AND JOB CARD.pdf
1
DOC 4/9/2020 KOHL HETRICK FSS2020-0050 - AS-
BUILTS.pdf
FSS2020-0050 - AS-
BUILTS.pdf 1
BOND INFORMATION
DATE
1ST PERMIT TECH (1
DAY)
AARON
HICKSON 3/23/2020 3/24/2020 3/23/2020 COMPLETE
1ST FIRE (2 WK)KOHL
HETRICK 3/23/2020 4/6/2020 4/7/2020 APPROVED SEE ATTACHMENTS
Printed: Thursday, February 16, 2023 4:36:26 PM 3 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0050
APPROVED
By:
FIRE SAFETY SPECIALIST
04/07/2020 2:55:09 PM
The approval of plans and specifications does not
permit the violation, deletion, omission or faulty
installation of any requirements of Title 24 or any
Local Ordinances. Construction shall remain
accessible and exposed for inspection purposes
until approved by the Fire Department.
PERMIT # -FSS2020-0050
43.220.038.915.0FSS2020-00508'8'
VK496AS-BUILTS 4-9-2020
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1DATE: 4/7/2020ZINGER RESIDENCE - LA QUINTA - CA - JCP\B AREA 1 1 HEAD.SDFJOB TITLE: AREA 1 1HD (16x16) (15 GPM) WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ’D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) M (N/A) 60.2 (N/A) 60.2 20.0 43.2
AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 20.0 GPMTOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPMOTHER HOSE STREAM ALLOWANCES 5.0 GPMTOTAL DISCHARGE FROM ACTIVE SPRINKLERS 15.0 GPM
NODE ANALYSIS DATANODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM)
P1 10.0 K= 3.00 25.0 15.0P2 12.0 - - - - 26.1 - - -P3 12.0 - - - - 26.1 - - -1 10.5 - - - - 24.9 - - -2 12.5 - - - - 25.9 - - -3 12.5 - - - - 25.9 - - -A 12.5 - - - - 25.9 - - -B 12.5 - - - - 25.9 - - -C 14.5 - - - - 25.5 - - -D 10.5 - - - - 28.1 - - -B1 10.5 - - - - 26.5 - - -C1 12.5 - - - - 26.4 - - -D1 10.5 - - - - 28.6 - - -TOR 10.5 - - - - 30.1 - - -FS1 4.0 - - - - 33.2 - - -FS2 4.0 - - - - 36.2 - - -BOR 0.5 - - - - 38.9 - - -DOM 0.5 HOSE STREAM 39.7 5.0UG -3.0 - - - - 42.5 - - -M -3.0 SOURCE 43.2 20.0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2DATE: 4/7/2020ZINGER RESIDENCE - LA QUINTA - CA - JCP\B AREA 1 1 HEAD.SDFJOB TITLE: AREA 1 1HD (16x16) (15 GPM) PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 -15.0 1.101 PL 0.50 PF 0.1P1 10.0 3.0 25.0 15.0 5.1 150 FTG E PE -0.21 10.5 0.0 24.9 0.0 0.040 TL 3.00 PV
Pipe: 2 0.0 1.101 PL 0.50 PF 0.0P2 12.0 0.0 26.1 0.0 0.0 150 FTG T PE -0.22 12.5 0.0 25.9 0.0 0.000 TL 6.50 PV
Pipe: 3 0.0 1.101 PL 0.50 PF 0.0P3 12.0 0.0 26.1 0.0 0.0 150 FTG E PE -0.23 12.5 0.0 25.9 0.0 0.000 TL 3.00 PV
Pipe: 4 -15.0 1.101 PL 25.75 PF 1.61 10.5 0.0 24.9 0.0 5.1 150 FTG 2T2R PE 0.0B1 10.5 0.0 26.5 0.0 0.040 TL 41.15 PV
Pipe: 5 0.0 1.101 PL 7.75 PF 0.02 12.5 0.0 25.9 0.0 0.0 150 FTG T PE 0.0A 12.5 0.0 25.9 0.0 0.000 TL 13.75 PV
Pipe: 6 0.0 1.101 PL 3.75 PF 0.03 12.5 0.0 25.9 0.0 0.0 150 FTG T PE 0.0A 12.5 0.0 25.9 0.0 0.000 TL 9.75 PV
Pipe: 7 0.0 1.101 PL 24.75 PF 0.0A 12.5 0.0 25.9 0.0 0.0 150 FTG T2R PE 0.0B 12.5 0.0 25.9 0.0 0.000 TL 34.15 PV
Pipe: 8 6.8 1.101 PL 10.50 PF 0.2B 12.5 0.0 25.9 0.0 2.3 150 FTG 2ETR PE 0.9B1 10.5 0.0 26.5 0.0 0.009 TL 23.20 PV
Pipe: 9 -8.2 1.101 PL 35.50 PF 0.7B1 10.5 0.0 26.5 0.0 2.8 150 FTG 2E2T3R PE -0.9C1 12.5 0.0 26.4 0.0 0.013 TL 57.60 PV
Pipe: 10 -8.2 1.101 PL 73.75 PF 1.3C1 12.5 0.0 26.4 0.0 2.8 150 FTG 3ET7R PE 0.9D1 10.5 0.0 28.6 0.0 0.013 TL 99.15 PV
Pipe: 11 -6.8 1.101 PL 30.25 PF 0.4B 12.5 0.0 25.9 0.0 2.3 150 FTG 3ET2R PE -0.9C 14.5 0.0 25.5 0.0 0.009 TL 47.15 PV
Pipe: 12 -6.8 1.101 PL 67.00 PF 0.9C 14.5 0.0 25.5 0.0 2.3 150 FTG 4ET8R PE 1.7D 10.5 0.0 28.1 0.0 0.009 TL 96.60 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3DATE: 4/7/2020ZINGER RESIDENCE - LA QUINTA - CA - JCP\B AREA 1 1 HEAD.SDFJOB TITLE: AREA 1 1HD (16x16) (15 GPM) PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 13 -6.8 1.101 PL 36.00 PF 0.5D 10.5 0.0 28.1 0.0 2.3 150 FTG T5R PE 0.0D1 10.5 0.0 28.6 0.0 0.009 TL 50.50 PV
Pipe: 14 -15.0 1.101 PL 24.50 PF 1.5D1 10.5 0.0 28.6 0.0 5.1 150 FTG 2ETR PE 0.0TOR 10.5 0.0 30.1 0.0 0.040 TL 37.20 PV
Pipe: 15 -15.0 1.101 PL 6.50 PF 0.3TOR 10.5 0.0 30.1 0.0 5.1 150 FTG R PE 2.8FS1 4.0 0.0 33.2 0.0 0.040 TL 8.20 PV
Pipe: 16 FIXED PRESSURE LOSS DEVICEFS2 4.0 0.0 36.2 0.0 3.0 psi, 15.0 gpmFS1 4.0 0.0 33.2 0.0
Pipe: 17 -15.0 1.101 PL 3.50 PF 1.2FS2 4.0 0.0 36.2 0.0 5.1 150 FTG 27.0 PE 1.5BOR 0.5 0.0 38.9 0.0 0.040 TL 30.50 PV
Pipe: 18 -15.0 1.055 PL 2.00 PF 0.8BOR 0.5 0.0 38.9 0.0 5.5 150 FTG 2ET PE 0.0DOM 0.5 H.S. 39.7 5.0 0.049 TL 16.00 PV
Pipe: 19 -20.0 1.055 PL 3.50 PF 1.2DOM 0.5 H.S. 39.7 5.0 7.3 150 FTG EC PE 1.5UG -3.0 0.0 42.5 0.0 0.084 TL 14.50 PV
Pipe: 20 -20.0 1.394 PL 25.00 PF 0.8UG -3.0 0.0 42.5 0.0 4.2 150 FTG 3E PE 0.0M -3.0 SRCE 43.2 (N/A) 0.022 TL 36.40 PV
NOTES (HASS):
(1) Calculations were performed by the HASS 8.8 D computer program in accordance with NFPA13 (2016) under license no. 50081438 granted by HRS Systems, Inc. 208 Southside Square Petersburg, TN 37144 (931) 659-9760
(2) The system has been calculated to provide an average imbalance at each node of 0.007 gpm and a maximum imbalance at any node of 0.142 gpm.
(3) Total pressure at each node is used in balancing the system. Maximum water velocity is 7.3 ft/sec at pipe 19.
(4) Items listed in bold print on the cover sheet
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4DATE: 4/7/2020ZINGER RESIDENCE - LA QUINTA - CA - JCP\B AREA 1 1 HEAD.SDFJOB TITLE: AREA 1 1HD (16x16) (15 GPM) are automatically transferred from the calculation report.
(5) Available pressure at source node M under full flow conditions is 60.21 psi with a flow of 23.43 gpm.
(6) PIPE FITTINGS TABLE
HASS Pipe Table Name: standard.pip
PAGE: F MATERIAL: CPVC HWC: 150Diameter Equivalent Fitting Lengths in Feet (in) F E T R K C G F45 Ell Tee RunT Kplg ChkVlv Gate 1.101 1.40 2.50 6.00 1.70 1.00 8.00 0.40 1.394 1.80 3.80 7.30 2.30 1.00 11.00 0.80
PAGE: M MATERIAL: CT-M HWC: 150Diameter Equivalent Fitting Lengths in Feet (in) E T F R K C G N Ell Tee 45-Ell TeeRun Kouplg ChkVlv GatVlv NPTee 1.055 3.00 8.00 2.00 3.00 0.00 8.00 0.00 8.00
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5DATE: 4/7/2020ZINGER RESIDENCE - LA QUINTA - CA - JCP\B AREA 1 1 HEAD.SDFJOB TITLE: AREA 1 1HD (16x16) (15 GPM) WATER SUPPLY ANALYSISFixed Source Pressure: 60.21 psi-14.70.010.020.030.040.050.060.070.080.06009001200150018002100240027003000FLOW (GPM)Note: (1) Dashed Lines indicate extrapolated values from Test Results (2) On Site pressures are based on hose stream deduction at the sourceGAUGE PRESSURE (psi)A12BLEGEND1Available pressure60.21 psi @ 20.0 gpm2Required pressure 43.24 psi @ 20.0 gpmA. Source Supply CurveB. System Demand Curve
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6DATE: 4/7/2020ZINGER RESIDENCE - LA QUINTA - CA - JCP\B AREA 1 1 HEAD.SDFJOB TITLE: AREA 1 1HD (16x16) (15 GPM) WATER SUPPLY CURVE 72+ | | | 66+ | | | 600\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\ | | | 54+ | | | P 48+ R | E | S X S 42+ U | R | E | 36+ ( | P | S | I 30+ ) | | | 24+ | | | 18+ | | |============================== 12+ LEGEND " | " | X = Required Water Supply " | 43.24 psi @ 20.0 gpm " 6+ " | 0 = Available Water Supply " | 60.21 psi @ 20.0 gpm " | " 0++-+---+----+-----+------+--------+--------+---------+-----------+ 8001200 1600 2000 2400 2800 3200 3600 4000 FLOW (GPM)
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
DATE: 3/23/2020NZINGER RESIDENCE - LA QUINTA - CA - JCP\AREA 2 2 HEAD.SDF
JOB TITLE: AREA 2 2HD (12x12) (8 GPM)
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
M (N/A) 60.2 (N/A) 60.2 21.0 27.3
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 21.0 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 16.0 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
P1 10.0 - - - - 10.1 - - -
P2 12.0 K= 3.00 7.1 8.0
P3 12.0 K= 3.00 7.2 8.0
1 10.5 - - - - 9.9 - - -
2 12.5 - - - - 7.0 - - -
3 12.5 - - - - 7.0 - - -
A 12.5 - - - - 7.1 - - -
B 12.5 - - - - 8.7 - - -
C 14.5 - - - - 8.4 - - -
D 10.5 - - - - 11.3 - - -
B1 10.5 - - - - 9.9 - - -
C1 12.5 - - - - 9.7 - - -
D1 10.5 - - - - 11.9 - - -
TOR 10.5 - - - - 13.6 - - -
FS1 4.0 - - - - 16.8 - - -
FS2 4.0 - - - - 19.8 - - -
BOR 0.5 - - - - 22.7 - - -
DOM 0.5 HOSE STREAM 23.6 5.0
UG -3.0 - - - - 26.4 - - -
M -3.0 SOURCE 27.3 21.0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 3/23/2020NZINGER RESIDENCE - LA QUINTA - CA - JCP\AREA 2 2 HEAD.SDF
JOB TITLE: AREA 2 2HD (12x12) (8 GPM)
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 0.0 1.101 PL 0.50 PF 0.0
P1 10.0 0.0 10.1 0.0 0.0 150 FTG E PE -0.2
1 10.5 0.0 9.9 0.0 0.000 TL 3.00 PV
Pipe: 2 -8.0 1.101 PL 0.50 PF 0.1
P2 12.0 3.0 7.1 8.0 2.7 150 FTG T PE -0.2
2 12.5 0.0 7.0 0.0 0.012 TL 6.50 PV
Pipe: 3 -8.0 1.101 PL 0.50 PF 0.0
P3 12.0 3.0 7.2 8.0 2.7 150 FTG E PE -0.2
3 12.5 0.0 7.0 0.0 0.013 TL 3.00 PV
Pipe: 4 0.0 1.101 PL 25.75 PF 0.0
1 10.5 0.0 9.9 0.0 0.0 150 FTG 2T2R PE 0.0
B1 10.5 0.0 9.9 0.0 0.000 TL 41.15 PV
Pipe: 5 -8.0 1.101 PL 7.75 PF 0.2
2 12.5 0.0 7.0 0.0 2.7 150 FTG T PE 0.0
A 12.5 0.0 7.1 0.0 0.012 TL 13.75 PV
Pipe: 6 -8.0 1.101 PL 3.75 PF 0.1
3 12.5 0.0 7.0 0.0 2.7 150 FTG T PE 0.0
A 12.5 0.0 7.1 0.0 0.013 TL 9.75 PV
Pipe: 7 -16.0 1.101 PL 24.75 PF 1.5
A 12.5 0.0 7.1 0.0 5.4 150 FTG T2R PE 0.0
B 12.5 0.0 8.7 0.0 0.045 TL 34.15 PV
Pipe: 8 -8.2 1.101 PL 10.75 PF 0.3
B 12.5 0.0 8.7 0.0 2.8 150 FTG 2ETR PE 0.9
B1 10.5 0.0 9.9 0.0 0.013 TL 23.45 PV
Pipe: 9 -8.2 1.101 PL 35.50 PF 0.8
B1 10.5 0.0 9.9 0.0 2.8 150 FTG 2E2T3R PE -0.9
C1 12.5 0.0 9.7 0.0 0.013 TL 57.60 PV
Pipe: 10 -8.2 1.101 PL 73.75 PF 1.3
C1 12.5 0.0 9.7 0.0 2.8 150 FTG 3ET7R PE 0.9
D1 10.5 0.0 11.9 0.0 0.013 TL 99.15 PV
Pipe: 11 -7.9 1.101 PL 30.25 PF 0.6
B 12.5 0.0 8.7 0.0 2.6 150 FTG 3ET2R PE -0.9
C 14.5 0.0 8.4 0.0 0.012 TL 47.15 PV
Pipe: 12 -7.9 1.101 PL 67.00 PF 1.2
C 14.5 0.0 8.4 0.0 2.6 150 FTG 4ET8R PE 1.7
D 10.5 0.0 11.3 0.0 0.012 TL 96.60 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 3/23/2020NZINGER RESIDENCE - LA QUINTA - CA - JCP\AREA 2 2 HEAD.SDF
JOB TITLE: AREA 2 2HD (12x12) (8 GPM)
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 13 -7.9 1.101 PL 36.00 PF 0.6
D 10.5 0.0 11.3 0.0 2.6 150 FTG T5R PE 0.0
D1 10.5 0.0 11.9 0.0 0.012 TL 50.50 PV
Pipe: 14 -16.0 1.101 PL 24.50 PF 1.7
D1 10.5 0.0 11.9 0.0 5.4 150 FTG 2ETR PE 0.0
TOR 10.5 0.0 13.6 0.0 0.045 TL 37.20 PV
Pipe: 15 -16.0 1.101 PL 6.50 PF 0.4
TOR 10.5 0.0 13.6 0.0 5.4 150 FTG R PE 2.8
FS1 4.0 0.0 16.8 0.0 0.045 TL 8.20 PV
Pipe: 16 FIXED PRESSURE LOSS DEVICE
FS2 4.0 0.0 19.8 0.0 3.0 psi, 16.0 gpm
FS1 4.0 0.0 16.8 0.0
Pipe: 17 -16.0 1.101 PL 3.50 PF 1.4
FS2 4.0 0.0 19.8 0.0 5.4 150 FTG 27.0 PE 1.5
BOR 0.5 0.0 22.7 0.0 0.045 TL 30.50 PV
Pipe: 18 -16.0 1.055 PL 2.00 PF 0.9
BOR 0.5 0.0 22.7 0.0 5.9 150 FTG 2ET PE 0.0
DOM 0.5 H.S. 23.6 5.0 0.056 TL 16.00 PV
Pipe: 19 -21.0 1.055 PL 3.50 PF 1.3
DOM 0.5 H.S. 23.6 5.0 7.7 150 FTG EC PE 1.5
UG -3.0 0.0 26.4 0.0 0.092 TL 14.50 PV
Pipe: 20 -21.0 1.394 PL 25.00 PF 0.9
UG -3.0 0.0 26.4 0.0 4.4 150 FTG 3E PE 0.0
M -3.0 SRCE 27.3 (N/A) 0.024 TL 36.40 PV
NOTES (HASS):
(1) Calculations were performed by the HASS 8.8 D computer program
in accordance with NFPA13 (2016)
under license no. 50081438 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
(2) The system has been calculated to provide an average
imbalance at each node of 0.005 gpm and a maximum
imbalance at any node of 0.098 gpm.
(3) Total pressure at each node is used in balancing the system.
Maximum water velocity is 7.7 ft/sec at pipe 19.
(4) Items listed in bold print on the cover sheet
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 3/23/2020NZINGER RESIDENCE - LA QUINTA - CA - JCP\AREA 2 2 HEAD.SDF
JOB TITLE: AREA 2 2HD (12x12) (8 GPM)
are automatically transferred from the calculation report.
(5) Available pressure at source node M under full flow conditions is
60.21 psi with a flow of 33.08 gpm.
(6) PIPE FITTINGS TABLE
HASS Pipe Table Name: standard.pip
PAGE: F MATERIAL: CPVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) F E T R K C G
F45 Ell Tee RunT Kplg ChkVlv Gate
1.101 1.40 2.50 6.00 1.70 1.00 8.00 0.40
1.394 1.80 3.80 7.30 2.30 1.00 11.00 0.80
PAGE: M MATERIAL: CT-M HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T F R K C G N
Ell Tee 45-Ell TeeRun Kouplg ChkVlv GatVlv NPTee
1.055 3.00 8.00 2.00 3.00 0.00 8.00 0.00 8.00
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 3/23/2020NZINGER RESIDENCE - LA QUINTA - CA - JCP\AREA 2 2 HEAD.SDF
JOB TITLE: AREA 2 2HD (12x12) (8 GPM)
WATER SUPPLY ANALYSIS
Fixed Source Pressure: 60.21 psi
-14.7
0.0
10.0
20.0
30.0
40.0
50.0
60.0
70.0
80.0
600 900 1200 1500 1800 2100 2400 2700 3000
FLOW (GPM)
Note: (1) Dashed Lines indicate extrapolated values from Test Results
G
A
U
G
E
P
R
E
S
S
U
R
E
(
p
s
i
)
A1
2
B
LEGEND
1 Available pressure
60.21 psi @ 21.0 gpm
2 Required pressure
27.27 psi @ 21.0 gpm
A. Source Supply Curve
B. System Demand Curve
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
DATE: 3/23/2020NZINGER RESIDENCE - LA QUINTA - CA - JCP\AREA 2 2 HEAD.SDF
JOB TITLE: AREA 2 2HD (12x12) (8 GPM)
WATER SUPPLY CURVE
72+
|
|
|
66+
|
|
|
600\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\
|
|
|
54+
|
|
|
P 48+
R |
E |
S |
S 42+
U |
R |
E |
36+
( |
P |
S |
I 30+
) |
X
|
24+
|
|
|
18+
|
|
|==============================
12+ LEGEND "
| "
| X = Required Water Supply "
| 27.27 psi @ 21.0 gpm "
6+ "
| 0 = Available Water Supply "
| 60.21 psi @ 21.0 gpm "
| "
0++-+---+----+-----+------+--------+--------+---------+-----------+
8001200 1600 2000 2400 2800 3200 3600 4000
FLOW (GPM)
FREEDOM® RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK496 (K3.0)TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 1 of 5
Form No. F_032218 19.03.21 Rev 19.1
1. DESCRIPTION
Viking Freedom® Residential Concealed Pendent Sprinkler VK496 is a small thermosensitive, glass-bulb residential sprinkler designed for installation on concealed pipe systems where the appearance of a smooth ceiling is desired. The orifice design, with a K-Factor of 3.0 (43.2 metric*), allows the sprinkler’s efficient use of available water supplies for the hydraulically designed fire-protection system. The fast response glass bulb operating element and special deflector characteristics meet the challenges of residential sprinkler standards.
The sprinkler is pre-assembled with a threaded adapter for installation with a low-profile small-diameter cover assembly installed flush to the ceiling. The two-piece design allows installation and testing of the sprinkler prior to installation of the cover plate. The “push-on”, “thread-off” design of the concealed cover plate assembly allows easy installation of the cover plate after the system has been tested and the ceiling finish has been applied, while also providing up to 1/2” (13 mm) of vertical adjustment. The cover assembly can be removed and reinstalled, allowing temporary removal of ceiling panels without taking the sprinkler system out of service or removing the sprinkler. The Electroless Nickel PTFE (ENT) coating has been investigated for installation in corrosive atmospheres and is C-UL-US-EU Listed as corrosion resistant as indicated in the Approval Charts. The ENT finish is only available for the sprinkler assembly, the cover plate is not plated.
2. LISTINGS AND APPROVALS
UL Listed (C-UL-US-EU): Category VKKW
Refer to the Approval Charts and Design Criteria on for C-UL-US-EU Listing
requirements that must be followed.
3. TECHNICAL DATASpecifications:Minimum Operating Pressure: Refer to the Approval Chart.Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi (34.5 bar).Thread size: 1/2” (15 mm) NPT Nominal K-Factor: 3.0 U.S. (43.2 metric*)Glass-bulb fluid temperature rated to -65 °F (-55 °C)
* Metric K-factor measurement shown is in Bar. When pressure is measured in kPa, divide the metric
K-factor shown by 10.0.
Material Standards:Sprinkler Body: Brass UNS-C84400 or QM BrassDeflector: Phosphor Bronze UNS-C51000Deflector Pins: Stainless Steel UNS-S30200Button: Brass UNS-C31600Pip Cap and Insert Assembly: Copper UNS-C11000 and SS UNS-S30400Compression Screw: 18-8 Stainless SteelYoke: UNS-S43000 Stainless Steel or Phosphor Bronze UNS-C51000Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE TapeCover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc PlatingShipping Cap: PolyethyleneCover Plate Materials:Cover Plate Assembly: Copper UNS-C11000 and Brass UNS-C26800Spring: Beryllium NickelSolder: Eutectic
Available Finishes and Temperature Ratings:
Finish Brass ENT
Suffix A JN
Temperature 155 °F (68 °C)200°F (93 °C)
Suffix B E
Ordering Information: Refer to Tables 1 and 2.
New page.
FREEDOM® RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK496 (K3.0)TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 2 of 5
Form No. F_032218 19.03.21 Rev 19.1
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches, releasing the deflector. Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand, causing the glass to shatter, releasing the yoke and pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the deflector, forming a uniform spray pattern over a specific area of coverage determined by the water supply pressure at the sprinkler to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCERefer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
Viking Sprinkler Model VK496 is available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEEFor details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
TABLE 1: ORDERING INFORMATION
Instructions: Using the sprinkler base part number,
(1) add the suffix for the desired Finish
(2) add the suffix for the desired Temperature Rating.
(3) Order a cover plate (refer to Table 2)
Sprinkler
Base Part
No.
Size 1: Finishes 2: Temperature Ratings
NPT
Inch
BSPT
mm Description Suffix1 Nominal Rating Bulb Color Max. Ambient Ceiling
Temperature2 Suffix
22773 1/2 --Brass A 155 °F (68 °C)Red 100 °F (38 °C)B
ENT 3,4 JN 200 °F (93 °C)Green 150 °F (65 °C)E
Example: 22773AE =
200 °F (93 °C) Temperature Rated Sprinkler
with a standard Brass finish.
Accessories
Sprinkler Wrenches (see Figure 1):
A. Heavy Duty Part Number: 14047WB5
B. Head Cabinet Wrench Part Number: 140316
Sprinkler Cabinet:
Part number 01731A.
Footnotes
1. Where a dash (-) is shown in the Finish suffix designation, insert the desired Temperature Rating suffix. See example above.
2. Based on NFPA 13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
Jurisdiction. Refer to specific installation standards.
3. UL Listed as corrosion resistant.
4. The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart. These tests cannot and
do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed
environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway.
5. Requires a 1/2” ratchet which is not available from us.
6. Optional for removal of the protective cap. Ideal for sprinkler cabinets.
FREEDOM® RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK496 (K3.0)TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 3 of 5
Form No. F_032218 19.03.21 Rev 19.1
TABLE 2: COVER PLATE ORDERING INFORMATION
Instructions: Using the cover plate base part number,
(1) add the suffix for the desired Finish
(2) add the suffix for the required Cover Plate Nominal Rating.
Cover Plate
Base Part
Number4
Size
Inch (mm)Style
1: Finishes Temperature Rating Matrix1,2
Description Suffix6
Cover Plate
Nominal Rating
(Required)
Sprinkler
Nominal Rating
Sprinkler Max.
Ambient Ceiling
Temperature2
Suffix
13504 2-3/4 (70)Round Polished Chrome F 135 °F (57 °C)155 °F (68 °C)100 °F (38 °C)A
13642 3-5/16 (84)Round Brushed Chrome F-/B 165 °F (73 °C)3 200 °F (93 °C)150 °F (65 °C)C
15394 3-5/16 (84)Square Bright Brass B
Corrosion Resistant Sprinkler Coating: ENT5
Example: 13504MA/W =
135 °F (57 °C) Temperature Rated 2-3/4” (70 mm) Diameter
Round Cover Plate with a Painted White finish.
Antique Brass B-/A
Brushed Brass B-/B
Brushed Copper E-/B
Painted White M-/W
Painted Ivory M-/I
Painted Black M-/B
Footnotes
1. The sprinkler temperature rating is stamped on the deflector.
2. Based on NFPA-13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
Jurisdiction. Refer to specific installation standards.
3. Maximum ambient temperature for cover assembly is 100 °F (38 °C).
4. Part number shown is the base part number. For complete part number, refer to current our price list schedule.
5. The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These tests cannot and
do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed
environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway. For ENT coated sprinklers, the Belleville
spring is exposed.
6. Where a dash (-) is shown in the Finish suffix designation, insert the desired Temperature Rating suffix. See example above.
FREEDOM® RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK496 (K3.0)TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 4 of 5
Form No. F_032218 19.03.21 Rev 19.1
APPROVAL CHART VK496, 3.0 K-Factor Residential Concealed Pendent Sprinkler
For systems designed to NFPA 13D or NFPA 13R. For systems designed to NFPA 13, refer to the design criteria. For Ceiling types refer to current editions of NFPA 13, 13R or 13D
S p r i n k l e r B a s e
Part Number 1 SIN Thread Size Nominal K-Factor Maximum Water Working PressureInchesmmU.S.metric 2
22773 VK496 1/2 15 3.0 43.2 175 psi (12 bar)
Maximum
Coverage Area 5
W X L
Ft. X Ft.
(m X m)
All Temperatures Deflector
to Ceiling Installation Type
Listings and
Approvals3 Minimum Spacing
Ft.
(m)Flow
gpm (Lpm)
Pressure
PSI (bar)
4
12 X 12
(3.7 X 3.7)
8
(30.3)
7.1
(0.49)
Refer to
Figure 2
Concealed with Cover
Plate Assembly. See
Footnotes 6 & 7.
See Footnotes 3, 4, and 8 8
(2.4)
14 X 14
(4.3 X 4.3)
12
(45.4)
16
(1.1)
16 X 16
(4.9 X 4.9)
15
(56.8)
25
(1.72)
Footnotes
1. Part number shown is the base part number. For complete part number, refer to current our price schedule.
2. Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3. This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approv-
als. Refer also to Design Criteria.
4. Listed by Underwriter’s Laboratories, Inc. for use in the U.S., Canada, and European Union.
5. For areas of coverage smaller than shown, use the “Flow” and “Pressure” for the next larger area listed. Flows and pressures listed are per sprinkler. The distance from
sprinklers to walls shall not exceed one-half the sprinkler spacing indicated for the minimum “Flow” and “Pressure” used.
6. Other paint colors are available on request with the same listings as the standard finish colors. Listings and approvals apply for any paint manufacturer. Contact Viking
for additional information. Custom colors are indicated on a label inside the cover assembly. Refer to Figure 3.
7. Accepted Cover Plate Finishes are: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or
Painted Black 6.
8. C-UL-US-EU Listed as corrosion resistant - Electroless Nickel PTFE (ENT)
FREEDOM® RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK496 (K3.0)TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 5 of 5
Form No. F_032218 19.03.21 Rev 19.1
DESIGN CRITERIA
(Also refer to the Approval Chart on page 3.)
UL Listing Requirements (C-UL-US-EU):
When using Viking Residential Concealed Pendent Sprinkler VK496 for systems designed to NFPA 13D or NFPA 13R, apply the listed areas of cover-age and minimum water supply requirements shown in the Approval Chart.
For systems designed to NFPA 13: The number of design sprinklers is to be the four contiguous most hydraulically demanding sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the following:
• The flow rates given in the Approval Chart for NFPA 13D and NFPA 13R applications for each listed area of coverage, or
• Calculated based on a minimum discharge of 0.1 gpm/sq. ft. over the “design area” in accordance with sections 8.5.2.1 or 8.6.2.1.2 of NFPA 13.
• Minimum distance between residential sprinklers: 8 ft. (2.4 m).
NOTE: Concealed sprinklers must be installed in neutral or negative pressure plenums only.
IMPORTANT: Always refer to Bulletin Form No. F_080415 - Best Practices for Residential Sprinkler Handling and Installation. Also refer to Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be in-stalled in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA and any other similar Authorities Having Jurisdiction, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Final approval and acceptance of all residential sprinkler installations must be obtained from the Authorities Having Jurisdiction.
Sprinkler and Adapter Assembly
• Protective cap removed
• Use wrench 14047W/B**
Step 1:
Carefully slide the wrench sideways around
the deflector and pins
Sprinkler Wrench
Part No. 14047W/B**
** A 1/2” ratchet is required (Not available from Viking)
2-1/4” (57 mm)
diameter opening
required in the
ceiling.
Step 2:
Carefully press the wrench upward and turn slightly to ensure engagement with
the sprinkler wrench flats.
Figure 1: Sprinkler Installation and Proper Wrench Usage
NEVER install the sprinkler by applying the installation
wrench across the frame arms. DO NOT overtighten.
Use only the designated sprinkler wrenches, Viking
Part Numbers 14047W/B** or 14031**. A leak tight seal
should be achieved by turning the sprinkler clockwise 1 to 1-1/2 turns beyond finger tight.
Sprinkler
wrench flat
Sprinkler frame arms
FREEDOM® RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK496 (K3.0)TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 6 of 5
Form No. F_032218 19.03.21 Rev 19.1
Figure 2: Sprinkler Dimensions and Cover Installation
1/2” (15 mm) NPT
2-1/4”(58 mm)2-9/16” (65 mm)Maximum 2-1/16” (52 mm)Minimum
2-3/4” (70 mm) or
3-5/16” (84 mm)NOTE: Upon sprinkler activation, the deflector descends
to approximately 13/16” (21 mm) below the sprinkler body.
Figure 3: Identification of Custom Paint for Concealed Covers
All custom color painted cover plates will have an
identifying label affixed to the inside of the cover that
indicates the custom color and will have a representative
sample (a paint dot) of the paint on the label.FACTORY APPLIE D C USTO
M
P
AI
NT COLORFigure 4: Square Cover Assembly 15394
3-5/16” (84 mm)
New page.
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
FREEDOM® RESIDENTIAL
PENDENT SPRINKLER
VK470 (K3.0)
Form No. F_061011 Rev 14.1
Page 1 of 5
1. DESCRIPTION
Viking Freedom® Residential Pendent Sprinkler VK470 is a thermosensitive, glass-bulb residen-
tial sprinkler available in several different finishes and temperature ratings to meet varying de-
sign requirements. The Electroless Nickel PTFE (ENT) coating has been investigated for instal-
lation in corrosive atmospheres and is C-UL-US-EU Listed as corrosion resistant as indicated
in the Approval Chart. The sprinkler orifice design, with a K-Factor of 3.0 (43.2 metric*), allows
efficient use of available water supplies for the hydraulically designed fire-protection system.
The glass bulb operating element and special deflector characteristics meet the challenges of
residential sprinkler standards.
2. LISTINGS AND APPROVALS
UL Listed (C-UL-US-EU): Category VKKW
Refer to the Approval Chart and Design Criteria for C-UL-US-EU Listing requirements
that must be followed.
3. TECHNICAL DATA
6SHFL¿FDWLRQV
Avaiilable since 2012.
Minimum Operating Pressure: Refer to the Approval Chart.
Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically
to 500 psi (34.5 bar).
Thread size: 1/2” (15 mm) NPT
Nominal K-Factor: 3.0 U.S. (43.2 metric*)
* Metric K-factor measurement shown is in Bar. When pressure is measured in kPa,
divide the metric K-factor shown by 10.0.
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: 2-1/4” (58 mm)
Material Standards:
Frame Casting: QM Brass
Deflector: Phosphor Bronze UNS-C51000 or Brass UNS-C23000
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Compression Screw: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400
For ENT coated sprinklers: Belleville spring - Exposed, Screw and Pipcap - ENT plated.
Ordering Information: (Also refer to the current Viking price list.)
Sprinkler: Base Part No. 17147
Order Sprinkler VK470 by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the tempera-
ture rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, and ENT = JN
Temperature Suffix: 155 °F (68 °C) = B, 175 °F (79 °C) = D
For example, sprinkler VK470 with a Brass finish and a 155 °F (68 °C) temperature rating = Part No. 17147AB.
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the “Sprinkler Accessories” section of the Viking data book.)
Sprinkler Wrenches:
A. Standard Wrench: Part No. 10896W/B (available since 2000)
B. Wrench for Recessed Sprinklers: Part No. 16036W/B** (available since 2011)
C. Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool*** Part No. 15915 (available since 2010.)
**A ½” ratchet is required (not available from Viking).
***Allows use from the floor by attaching a length of 1” diameter CPVC tubing to the tool. Ideal for sprinkler cabinets. Refer to Bulletin F_051808.
Sprinkler Cabinets:
A. Six-head capacity: Part No. 01724A (available since 1971)
B. Twelve-head capacity: Part No. 01725A (available since 1971)
(Added EU Listing)
Viking Technical Data may be found on
The Viking Corporation’s Web site at
http://www.vikinggroupinc.com.
The Web site may include a more recent
edition of this Technical Data Page.
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
FREEDOM® RESIDENTIAL
PENDENT SPRINKLER
VK470 (K3.0)
Form No. F_061011 Rev 14.1
Page 2 of 5
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
The Viking Model VK470 Sprinkler is available through a network of domestic and international distributors. See The Viking
Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Temperature
Classification
Sprinkler Nominal
Temperature Rating1
Maximum Ambient
Ceiling Temperature2 Bulb Color
Ordinary 155 °F (68 °C) 100 °F (38 °C) Red
Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow
Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, and ENT
Corrosion Resistant Coatings3: ENT
Footnotes
1 The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
3 The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart. These
tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compat-
ible with or suitable for the proposed environment. For ENT coated sprinklers, the waterway is coated. Note that the spring is exposed on sprinklers
with ENT coating.
Figure 1: Standard Sprinkler Wrench 10896W/B
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
FREEDOM® RESIDENTIAL
PENDENT SPRINKLER
VK470 (K3.0)
Form No. F_061011 Rev 14.1
Page 3 of 5
Approval Chart
Viking VK470, 3.0 K-Factor Residential Pendent Sprinkler
For systems designed to NFPA 13D or NFPA 13R. For systems designed to NFPA 13, refer to the design criteria. For Ceiling types refer to
NFPA 13, 13R or 13D 2013 Editions
Sprinkler Base
Part Number 1 SIN NPT Thread Size Nominal K-Factor Maximum Water
Working Pressure
Overall Length
Inches mm U.S. metric
2 Inches mm
17147 VK470 1/2 15 3.0 43.2 175 psi (12 bar) 2-1/4 58
Max. Coverage
Area 4
Ft.X Ft.
(m X m)
Ordinary Temp Rating
(155 °F/68 °C)
Intermediate Temp
Rating (175 °F/79 °C)Deflector
to
Ceiling
Installation
Type
Listings and Approvals 3
Minimum
Spacing
Ft.
(m)
Flow 4
GPM
(L/min)
Pressure 4
PSI
(bar)
Flow 4
GPM
(L/min)
Pressure 4
PSI
(bar)
5
NYC NSF
12 X 12
(3.7 X 3.7)
8
(30.3)
7.11
(0.49)
8
(30.3)
7.11
(0.49)
1-1/8 to 2
inch
Standard
surface-
mounted
escutch-
eons, the
Microfast®
Model F-1
Adjustable
Escutcheon,
or recessed
with the
Micromatic®
Model
E-1, E-
2, or E-3
Recessed
Escutcheon
See
Footnotes
6 and 9
See
Foot-
note 7
--8
(2.4)
14 X 14
(4.3 X 4.3)
10
(37.9)
11.11
(0.77)
10
(37.9)
11.11
(0.77)
16 X 16
(4.9 X 4.9)
13
(49.2)
18.8
(1.29)
13
(49.2)
18.8
(1.29)
Footnotes
1 Part number shown is the base part number. For complete part number, refer to Viking’s current price schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-
factor shown by 10.0.
3 This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the
manufacturer for any additional approvals. Refer also to Design Criteria.
4 For areas of coverage smaller than shown, use the “Flow” and “Pressure” for the next larger area listed. Flows and pressures listed
are per sprinkler.
5 Listed by Underwriter’s Laboratories, Inc. for use in the U.S., Canada, and European Union.
6 Approved Finishes are: Brass, Chrome, White Polyester, and Black Polyester 8.
7 Meets New York City requirements, effective July 1, 2008.
8 Other paint colors are available on request with the same C-UL-US-EU listings as the standard finish colors.
9 Approved finish is Electroless Nickel PTFE (ENT). ENT is C-UL-US-EU Listed as corrosion resistant. ENT is available with standard
surface-mounted escutcheons or the Micromatic Model E-1 Recessed Escutcheon.
5
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
FREEDOM® RESIDENTIAL
PENDENT SPRINKLER
VK470 (K3.0)
Form No. F_061011 Rev 14.1
Page 4 of 5
DESIGN CRITERIA
(Also refer to the Approval Chart.)
UL Listing Requirements (C-UL-US-EU):
When using Viking Residential Pendent Sprinkler VK470 for systems designed to NFPA 13D or NFPA 13R, apply the listed areas of coverage and
minimum water supply requirements shown in the Approval Chart.
For systems designed to NFPA 13: The number of design sprinklers is to be the four contiguous most hydraulically demanding sprinklers. The mini-
mum required discharge from each of the four sprinklers is to be the greater of the following:
The flow rates given in the Approval Chart for NFPA 13D and NFPA13R applications for each listed area of coverage, or
Calculated based on a minimum discharge of 0.1 gpm/sq. ft. over the “design area” in accordance with sections 8.5.2.1 or 8.6.2.1.2 of NFPA 13.
Minimum distance between residential sprinklers: 8 ft. (2.4 m).
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to pages RES1-17 for
general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest
edition of Viking technical data, the appropriate standards of NFPA and any other similar Authorities Having Jurisdiction,
and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Final approval and
acceptance of all residential sprinkler installations must be obtained from the Authorities Having Jurisdiction.
Figure 3: Sprinkler VK470 Dimensions with a Standard Escutcheon and the Model F-1 Adjustable Escutcheon
Figure 2: Wrench 16036W/B for Installing Recessed Sprinkler VK470
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
FREEDOM® RESIDENTIAL
PENDENT SPRINKLER
VK470 (K3.0)
Form No. F_061011 Rev 14.1
Page 5 of 5
Figure 4: Sprinkler VK470 Dimensions with the Model E-1 and E-2 Recessed Escutcheons
(Added EU Listing)
MICROFAST® QUICK
RESPONSE PENDENT
SPRINKLER VK329 (K2.8)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Page 1 of 6
Form No. F_061714 16.01.28 Rev 16.1
1. DESCRIPTION
The Viking Microfast® Quick Response Pendent Sprinkler VK329 is
a small thermosensitive glass bulb spray sprinkler available with various
finishes and temperature ratings to meet design requirements. The spe-
cial Polyester and Polytetrafluoroethelyne (PTFE) coatings can be used in
decorative applications where colors are desired. In addition, these coat-
ings have been investigated for installation in corrosive atmospheres and
are listed/approved as corrosion resistant as indicated in the Approval
Charts. (Note: FM Global has no approval classification for PTFE and Polyester
coatings as corrosion resistant.)
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV
FM Approved: Class Series 2000
Refer to Approval Chart 1 and Design Criteria cULus Listing requirements,
and refer to Approval Chart 2 and Design Criteria for FM Approval requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Minimum Operating Pressure: 7 psi (0.5 bar)
Rated to 175 psi (12 bar) water working pressure
Factory tested hydrostatically to 500 psi (34.5 bar)
Thread size: 1/2” NPT, 15 mm BSP
Nominal K-Factor: 2.8 U.S. (40.3 metric**)
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: 2-1/4” (58 mm)
*cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar).
The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi (0.35 bar).
Material Standards:
Frame Casting: Brass UNS-C84400 or QM Brass
Deflector: Brass UNS-C26000
Bushing: Brass UNS-C36000
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Screw: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400
For PTFE Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-PTFE Coated
For Polyester Coated Sprinklers: Belleville Spring-Exposed
Ordering Information: (Also refer to the current Viking price list.)
Order Quick Response Upright and Pendent Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the
appropriate suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, and Black PTFE = N
Temperature Suffix: 135 °F (57 °C) = A, 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E, 286 °F (141 °C) = G
For example, sprinkler VK329 with a Brass finish and a 155 °F (68 °C) temperature rating = Part No. 12981AB
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the “Sprinkler Accessories” section of the Viking data book.)
Sprinkler Wrenches:
A. Standard Wrench: Part No. 10896W/B (available since 2000).
B. Wrench for Recessed Pendent Sprinklers: Part No. 16036W/B** (available since 2011)
C. Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool*** Part No. 15915 (available since 2010)
**A ½” ratchet is required (not available from Viking).
***Allows use from the floor by attaching a length of 1” diameter CPVC tubing to the tool. Ideal for sprinkler cabinets. Refer to Bulletin F_051808.
Viking Technical Data may be found on
The Viking Corporation’s Web site at
http://www.vikinggroupinc.com.
The Web site may include a more recent
edition of this Technical Data Page.
Replaces form F_061714 Rev. 14.2 (Revised temperature suffix designation)
MICROFAST® QUICK
RESPONSE PENDENT
SPRINKLER VK329 (K2.8)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Page 2 of 6
Form No. F_061714 16.01.28 Rev 16.1
Sprinkler Cabinets:
A. Six-head capacity: Part No. 01724A (available since 1971)
B. Twelve-head capacity: Part No. 01725A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
The Viking Microfast® Quick Response Pendent Sprinkler VK329 is available through a network of domestic and international dis-
tributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
Figure 1: Standard Sprinkler Wrench 10896W/B
Protective Sprinkler
Cap
Wrench FlatProtective Sprinkler
Clip
MICROFAST® QUICK
RESPONSE PENDENT
SPRINKLER VK329 (K2.8)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Page 3 of 6
Form No. F_061714 16.01.28 Rev 16.1
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Temperature
Classification
Sprinkler Nominal
Temperature Rating1
Maximum Ambient
Ceiling Temperature2 Bulb Color
Ordinary 135 °F (57 °C)100 °F (38 °C)Orange
Ordinary 155 °F (68 °C)100 °F (38 °C)Red
Intermediate 175 °F (79 °C)150 °F (65 °C)Yellow
Intermediate 200 °F (93 °C)150 °F (65 °C)Green
High 286 °F (141 °C)225 °F (107 °C)Blue
Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, and Black PTFE
Corrosion-Resistant Coatings3: White Polyester, Black Polyester, and Black PTFE.
Footnotes
1 The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These
tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compat-
ible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only.
Note that the spring is exposed on sprinklers with Polyester and PTFE coatings.
Figure 2: Wrench 16036W/B for Recessed Pendent Sprinklers
Carefully slide the wrench sideways around
the protective cap, ensuring engagement with
the sprinkler wrench flats
Sprinkler wrench 16036W/B**
for recessed pendent
sprinklers
** A 1/2” ratchet is required
(not available from Viking)
MICROFAST® QUICK
RESPONSE PENDENT
SPRINKLER VK329 (K2.8)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Page 4 of 6
Form No. F_061714 16.01.28 Rev 16.1
Approval Chart 1 (UL)
The Viking Microfast® Quick Response
Pendent Sprinkler VK329
Maximum 175 PSI (12 Bar) WWP
Base
Part
Number1
SIN Sprinkler
Style
Thread Size Nominal K-Factor Overall Length Listings and Approvals3
(Refer also to Design Criteria.)
NPT BSP U.S.metric2 Inches mm cULus4 VdS LPCB
12981 VK329 Pendent 1/2”15 mm 2.8 40.3 2-1/4 58 A1Z, B1Y ------
NOTICE - Product Below - Limited Availability (Contact Local Viking Office)
06718B VK329 Pendent 1/2”15 mm 2.8 40.3 2-3/16 56 A1Z, B1Y ------
Approved Temperature Ratings
A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79
°C), 200 °F (93 °C), 286 °F (141 °C)
B - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79
°C), and 200 °F (93 °C)
Approved Finishes
1 - Brass, Chrome, White
Polyester5,6, Black Polyester5,6,
and Black PTFE
Approved Escutcheons
Y - Standard surface-mounted escutcheon or the
Viking Microfast® Model F-1 Adjustable Escutcheon, or
recessed with the Viking Micromatic® Model E-1, E-2, or
E3 Recessed Escutcheon
Z - Standard surface-mounted escutcheon or the
Viking Microfast® Model F-1 Adjustable Escutcheon
Footnotes
1 Base part number shown. For complete part number, refer to Viking’s current price schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by
10.0.
3 This table shows the listings and approvals available at the time of printing. Other approvals may be in process.
4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.
5 cULus Listed as corrosion-resistant.
6 Other colors are available on request with the same Listings and Approvals as the standard colors.
DESIGN CRITERIA - UL
(Also refer to Approval Chart 1 above.)
cULus Listing Requirements:
The Viking Microfast® Quick Response Pendent Sprinkler VK329 is cULus Listed as indicated in the Approval Chart for installation in
accordance with the latest edition of NFPA 13 for standard spray sprinklers.
• Small orifice sprinklers are limited to Light Hazard where allowed by the installation standards being applied, with hydraulically
calculated wet systems only.
• The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accor-
dance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS
or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards,
whenever applicable.
MICROFAST® QUICK
RESPONSE PENDENT
SPRINKLER VK329 (K2.8)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Page 5 of 6
Form No. F_061714 16.01.28 Rev 16.1
Approval Chart 2 (FM)
The Viking Microfast® Quick Response
Pendent Sprinkler VK329
Maximum 175 PSI (12 Bar) WWP
Base Part
Number1 SIN Sprinkler
Style
Thread Size Nominal K-Factor Overall Length FM Approvals3
(Refer also to Design Criteria.)NPT BSP U.S.metric2 Inches mm
12981 VK329 Pendent 1/2”15 mm 2.8 40.3 2-1/4 58 A1Z
NOTICE - Product Below - Limited Availability (Contact Local Viking Office)
16718B VK329 Pendent 1/2”15 mm 2.8 40.3 2-3/16 56 A1Z
Approved Temperature Ratings
A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F
(93 °C), 286 °F (141 °C)
Approved Finishes
1 - Brass and Chrome
Approved Escutcheons
Z - Standard surface-mounted escutcheon or the
Viking Microfast® Model F-1 Adjustable Escutcheon
Footnotes
1 Base part number shown. For complete part number, refer to Viking’s current price schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by
10.0.
3 This table shows the FM Approvals available at the time of printing. Other approvals may be in process.
4 Other colors are available on request with the same Approvals as the standard colors.
DESIGN CRITERIA - FM
(Also refer to Approval Chart 2 above.)
FM Approval Requirements:
The Viking Microfast® Quick Response Pendent Sprinkler VK329 is FM Approved as quick response Non-storage upright and pendent
sprinklers as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable
FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but
not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable
spacing, and deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable.
MICROFAST® QUICK
RESPONSE PENDENT
SPRINKLER VK329 (K2.8)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Page 6 of 6
Form No. F_061714 16.01.28 Rev 16.1
Figure 4: Sprinkler Dimensions with the Model E-1 and E-2 Recessed Escutcheons
Figure 3: Sprinkler Dimensions with a Standard Escutcheon and the Model F-1 Adjustable Escutcheon
1/2”
(15 mm)
NPT
2-1/4”
(57 mm)1-3/4”
(44.5 mm)
2”
(51 mm)
Max.
2-1/8”
(54 mm)
1-1/2”
(38 mm)
Min.
Installed with a standard
1/8” surface-mounted
escutcheon
Installed with a Microfast
Model F-1 Adjustable
Escutcheon
Ceiling Opening Size:
2-516/” (58.7 mm) minimum
2-1/2” (63.5 mm) maximum
Note: At maximum, adapter is
exposed 1/2” (12.7 mm) from
face of ceiling
1-3/4”
(44.5 mm)
Max.
2-1/8”
(54 mm)
1-1/8”
(28.6 mm)
Min.
2””
(51 mm)
Max.
1-1/8”
(28.6 mm)
Min.
2-1/8”
(54 mm)
Ceiling Opening Size:
2-516/” (58.7 mm) minimum
2-1/2” (63.5 mm) maximum
Installed with a
Model E-1 Recessed
Escutcheon
Installed with a Model
E-2 Thread-on Recessed
Escutcheon
Replaces form F_061714 Rev. 14.2 (Revised temperature suffix designation)
General
Description
Tyco Fire & Building Products (TFBP)
BlazeMaster CPVC Pipe and Fittings
are designed exclusively for use in wet
pipe automatic fire sprinkler systems.
They are made from a specially devel-
oped thermoplastic compound com-
posed of post chlorinated polyvinyl
chloride (CPVC) resin and state of the
art additives. TFBP BlazeMaster
CPVC products are easier to install
than traditional steel pipe systems,
and at the same time, provide superior
heat resistance and strength as com-
pared to traditional CPVC and PVC
piping materials used in the plumbing
trade. Various adapters are available
to connect CPVC pipe to metallic pip-
ing. All female pipe thread adapters
have brass inserts for durability.
Grooved adapters connect directly to
grooved end valves and metallic pipe,
with flexible grooved end couplings.
WARNING
Tyco Fire & Building Products (TFBP)
BlazeMaster CPVC Pipe and Fittings
described herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction.Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Technical
Data
Sizes
3/4" to 3"
Maximum Working Pressure
175 psi
Approvals
UL, FM, CUL, NSF, Dade County,
LPCB, MEA, and the City of Los Ange-
les. (Refer to IH-1900, Rev. 0, Janu-
ary 2005 “Installation Instruction &
Technical Handbook” for exact list-
ing/approval information.)
Manufacture Source
U.S.A.
Material
•Pipe: ASTM F442, SDR 13.5
•Fittings: ASTM F438 (Sch. 40) and
ASTM F439 (Sch. 80), ASTM F1970
Color
Orange
BlazeMaster ®
CPVC Fire Sprinkler Pipe & Fittings
Submittal Sheet
Page 1 of 6 TFP1915JANUARY, 2006
Technical Services:Tel: (800) 381-9312 / Fax: (800) 791-5500
BlazeMaster®is a registered trademark
of Noveon IP Holding Corp.
Installation
Tyco Fire and Building Products
(TFBP) BlazeMaster CPVC Pipe and
Fittings are to be installed in accord-
ance with IH-1900, Rev. 0, January
2005“Installation Instruction & Techni-
cal Handbook”.
Care and
Maintenance
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any
authority having jurisdiction. The in-
stallingcontractor orproductmanufac-
turer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
NOTES
Before closing a fire protection system
control valve for inspection or mainte-
nance work on the fire protection sys-
tem that it controls, permission to shut
down the affected fire protection sys-
tem must first be obtained from the
proper authorities and all personnel
who may be affected by this action
must be notified.
After placing a fire protection system
in service, notify the proper authorities
and advise thoseresponsiblefor moni-
toring proprietary and/or central sta-
tion alarms.
Page 2 of 6
TFP1915
FIGURE 1 — PIPE DIMENSIONS
2"
1"
1-1/4"
1-1/2"
3/4"
2.375" 2.003"
1.315"
1.660"
1.900"
1.050"
1.101'
1.394"
1.598"
0.874"
SIZE
NOMINAL
2.200.84
0.67
0.44
1.08
1.41
0.26
0.42
0.54
0.18
3"
2-1/2"
3.500" 2.952"
2.875" 2.423"
4.831.87
3.261.26
10841260
1320
1339
1191
1213
5040
2835
2205
7875
1344720
15311215
O.D.
AVERAGE
lbs./ft.
WEIGHTAVERAGE
I.D.FILLED WEIGHT
WATER
lbs./ft.
FT. OF PIPE
PER LIFT
WEIGHT PER LIFT
lbs.
TFP1915 Page 3 of 6
FIGURE 2 — FITTING DIMENSIONS (Part 1 of 4)
NOMINAL TAKE-OUTFITTINGNOMINAL SIZETYPE
PART
NUMBER (T/O)
T/O T/O
80004
80003
80002
TEE
T/O 80001
80000
2"
1-1/4"
1-1/2"
3/4"
1"
1-3/8"
1-1/16"
7/8"
0.90
0.51
0.26
5/8"
11/16"0.19
0.11
REDUCING TEE
1-1/2" x 1-1/2" x 1-1/4"
80266
80267
80274
80264
80275
80261
80262
80263
80260
2" x 2" x 3/4"
2" x 2" x 1"
2" x 2" x 1-1/2"
1-1/2" x 1-1/2" x 1"
7/8"
1-1/8"
1-1/16"
7/8"
9/16"
1-1/2" x 1-1/2" x 3/4"
1-1/4" x 1-1/4" x 3/4"
1-1/4" x 1-1/4" x 1"
1" x 1" x 3/4"
5/8"
9/16"
3/4"
5/8"
1-3/8"
1-3/8"
1-3/8"
7/8"
9/16"
1"
1-1/16"
0.66
0.78
0.74
0.45
0.38
7/8"5/8"
9/16"
3/4"
1"
7/8"
5/8" 13/16"
0.23
0.36
0.26
0.16
YX x Y x Z
XZ
80132 3/4" x 3/4" x 1" 3/4" 3/4" 5/8"
0.14
80133 9/16"1" x 3/4" x 3/4" 9/16"
0.143/4"
80134 1" x 3/4" x 1" 3/4" 11/16" 3/4"
0.17
80135 1-1/4" x 1" x 3/4" 5/8"5/8"0.2115/16"
80136 1-1/4" x 1" x 1" 3/4" 3/4" 15/16"
0.22
15/16"1-1/4" x 1" x 1-1/4"80137 15/16"
0.267/8"
80138 1-1/4" x 1-1/4" x 1-1/2"
1" 1" 1" 0.43
80140 1-1/2" x 1-1/4" x 3/4" 9/16" 9/16"
1" 0.36
1-1/2" x 1-1/4" x 1"80141 9/16" 9/16"
0.381-1/16"
80265 3/4" 1-3/8"
0.61
T/O
T/O T/O
X Y
Z
7/8"
1-1/8"
1-1/16"
3/4"
WEIGHT
(lb.)
T/O
T/O
T/O T/O
CROSS & REDUCING CROSS
1-1/16"
80009
80010
80011
80013
80012
0.139/16"
1-5/16"
11/16"
15/16"
1.00
0.23
0.34
0.67
80006
80005
3"
2-1/2"
1-13/16"
1-9/16"
2.41
1.59
2-1/2" x 2-1/2" x 1-1/2"
80270
80269
80268
80272
80273
80271
3" x 3" x 1-1/2"
3" x 3" x 2"
3" x 3" x 2-1/2"
2-1/2" x 2-1/2" x 1-1/4"
1-13/16"
1-13/16"
1-13/16"
1-9/16"
1-9/16"
2-1/2" x 2-1/2" x 1" 1-9/16"
1-13/16"
1-13/16"
1-3/4"
1-9/16"
1-9/16"
1-9/16"
1-9/16"
2.28
2.44
2.25
1.48
1.46
1-9/16" 1-9/16"
1.43
80276 2-1/2" x 2-1/2" x 2" 1-9/16" 1-9/16"
1.50
1-13/16"
1-13/16"
1-13/16"
1-9/16"
2" x 2" x 1-1/4"
1-9/16"
80008
80014
1-13/16" 2.89
1.91
2"
1-1/4"
1-1/2"
3/4"
1"
3"
2-1/2"
80015 0.281" x 1" x 3/4" x 3/4" 7/8"
SCHD.
80
40
80
40
40
80
80
80
80
80
80
40
40
40
40
40
40
40
40
40
80
80
80
80
80
80
80
80
80
80
80
80
80
80
40
80
40
40
80
80
40
T/O
T/O
90° ELBOW &
1-1/16"
80029
80026
80025
80027
80028
2"
3/4"
1"
1-1/4"
1-1/2"
0.791-5/16"
5/8"
3/4"
7/8"0.21
0.14
0.40
0.09
Y
X
1-9/16"
80031
80030
3"
2-1/2"
1.821-13/16"
1.14
XxY
80032 1" x 3/4"
0.16
X
11/16"
Y
13/16"
REDUCING ELBOW
80
40
80
40
40
80
80
40
Page 4 of 6
TFP1915
FIGURE 2 — FITTING DIMENSIONS (Part 2 of 4)
0.2580078
T/O
80079 0.38
T/O
COUPLING &
T/O
45° ELBOW
80053
80054
80075
80076
80077
80050
80051
80052
0.311/2"
1/8"
3/4"
0.11
0.07
0.12
0.56
3/8"
3/8"
3/4"
0.08
0.11
0.20
1/8"
3/16"
3/16"
3/16"
80203
80206
80205
80204
80200
80201
80202
80207
80208
80209
T/O
REDUCER BUSHING
2" x 1-1/4"
2" x 1-1/2"
2" x 1"
1-1/2" x 3/4"
1-1/2" x 1-1/4"
1-1/4" x 3/4"
1-1/2" x 1"
2" x 3/4"
1-1/4" x 1"
1" x 3/4"
11/16"
9/16"
7/16"
5/8"
1/2"
13/16"
3/8"
5/16"
1/2"
7/16"
0.26
0.24
0.19
0.16
0.27
0.17
0.14
0.04
0.12
0.11
NOMINAL TAKE-OUTFITTINGNOMINAL SIZETYPE
PART
NUMBER (T/O)
2"
3/4"
1"
1-1/4"
1-1/2"
13/16"
80056
80055
3"
2-1/2"
1.191"
0.89
80
40
80
40
40
80
80
REDUCING COUPLING
2"
3/4"
1"
1-1/4"
1-1/2"
1/4"
80081
80080
3"
2-1/2"
0.913/16"
0.67
80
40
80
40
40
80
80
80220 0.081" x 3/4"
1/8"40
80
40
80
40
40
80
80
80
80
80
80
80
80
80
80
80
80215 2-1/2" x 1" 15/16"
0.42
80214 2-1/2" x 1-1/4" 13/16"
0.45
80213 2-1/2" x 1-1/2" 11/16"
0.46
80211 2-1/2" x 2"
5/8"0.29
80210 3" x 2"
3/4"0.72
80212 3" x 2-1/2"
1/2"0.47
WEIGHT
(lb.)SCHD.
T/O
80104
80103
80102
CAP
80101
80100
2"
1-1/4"
1-1/2"
3/4"
1"
5/8"
11/16"
7/16"
0.31
0.20
0.10
5/16"
3/8"0.06
0.04
80106
80105
3"
2-1/2"
1"
7/8"
0.88
0.58
80
40
80
40
40
80
80
1-1/4" x 1-1/4" Groove 2-5/16"
80161
80162
T/O
1-1/2" x 1-1/2" Groove
2" x 2" Groove 2-5/16"
2-5/16"
80160
COUPLING ADAPTER
0.95
1.42
0.78
GROOVED
80163 2-1/2" x 2-1/2" Groove 2-5/16"
2.28
80164 3" x 3" Groove 2-1/4"
3.00
80169 2-1/2" x 76,1 mm Groove 2-5/16"
2.28
40
80
80
80
80
80
PIPE
O.D.
T/O PIPE O.D.
1-1/4" (1.660")
2" (2.375")
1-1/2" (1.900")
2-1/2" (2.875")
3" (3.500")
76,1 mm (3.000")
TFP1915 Page 5 of 6
3/4" x 3/4" NPT 13/16"
80145
80146
T/O
1' x 1" NPT
1-1/4" x 1-1/4" NPT 1-1/8"
7/8"
80142
0.63
1.03
0.41
80147 1-1/2" x 1-1/2" NPT 1-3/8"
1.42
80148 2" x 2" NPT 1-11/16" 2.66
40
40
80
40
80
3/4" x 3/4" NPT 1-5/16"
80158 1' x 1" NPT 1-3/8"
80157
0.56
0.3340
40
T/O
80177L 3/4" x 1/2" NPT
0.16401/2"
80178 1" x 1/2" NPT
0.20409/16"
T/O
80258
80253
80256
2" x 1-1/2" x 1/2" NPT
2" x 2" x 1/2" NPT
1-1/4" x 1" x 1/2" NPT
1/2"
1/2"
7/16"
1-11/16"5/8"
1/2" 1-11/16"
9/16" 1-5/16"
0.56
0.62
0.30
80250 3/4" x 3/4" x 1/2" NPT 9/16" 9/16"
1" 0.22
80251 11/16"1" x 1" x 1/2" NPT 11/16"
0.291-3/16"
80249 1" x 1" x 1" NPT 15/16" 15/16" 1-9/16"
0.73
80252 1-1/4" x 1-1/4" x 1/2" NPT 7/16"7/16"0.311-5/16"
80257 1-1/2" x 1-1/4" x 1/2" NPT 1/2" 11/16" 1-7/16"
0.43
1/2"1-1/2" x 1-1/2" x 1/2" NPT80254 1/2"
0.461-7/16"
80
80
40
40
40
40
40
80
80
T/OT/O
Z
XY
T/O
80175E 3/4" x 1/2" NPT
0.20
80176E 1" x 1/2" NPT
0.22
80
80
7/16"
7/16"
80175WL 3/4" x 1/2" NPT
0.16407/16"
80179 1" x 3/4" NPT
0.434013/16"
NOMINAL TAKE-OUTFITTINGNOMINAL SIZETYPE
PART
NUMBER (T/O)
FEMALE ADAPTER
MALE ADAPTER
WEIGHT
(lb.)SCHD.
ADAPTER (SPIGOT)
SPRINKLER HEAD
YX x Y x Z
XZ
ADAPTER TEE
SPRINKLER HEAD
ADAPTER
SPRINKLER HEAD
ADAPTER
SPRINKLER HEAD
80175W 3/4" x 1/2" NPT
0.19401/2"
80176W 1" x 1/2" NPT
0.18401/2"
T/O
T/O
80180 1" x 3/4" NPT
0.40407/8"
FIGURE 2 — FITTING DIMENSIONS (Part 3 of 4)
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
have beensubject tomisuse, improper
installation,corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP’s sole
option. TFBP neither assumes, nor
authorizes any person to assume for it,
any other obligation in connection with
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer’s repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect,specialorconsequentialdam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP’s liability exceed an amount
equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties, ex-
press or implied, including warranties
ofmerchantabilityandfitnessforapar-
ticular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
Page 6 of 6
TFP1915
TYCO FIRE & BUILDING PRODUCTS,451 North Cannon Avenue, Lansdale, Pennsylvania 19446
FIGURE 2 — FITTING DIMENSIONS (Part 4 of 4)
5/8"
5/8"
X Y, Z
1-5/16"
1-3/16"
X x Y x Z
80459 1" x 1/2" NPT x 1/2" NPT
0.48
80460 1" x 1/2" NPT x 1/2" NPT
0.46
40
40
BACK-TO-BACK TEE
T/O
T/OT/O
T/O
T/OT/O
T/O
Z
X
X
Z
W
Y
Y
5/8"
5/8"
X, Y Z, W
1-3/16"
1-5/16"
X x Y x Z x W
80462 1" x 1" x 1/2" NPT x 1/2" NPT
0.46
80463 1" x 1" x 1/2" NPT x 1/2" NPT
0.47
40
40
BACK-TO-BACK CROSS
NOMINAL TAKE-OUTFITTINGNOMINAL SIZETYPE
PART
NUMBER (T/O)
WEIGHT
(lb.)SCHD.
T/O
T/O
X
Y
ADAPTER 90° ELBOW
SPRINKLER HEAD
9/16"
3/4"
XY
1"
1-1/4"
XxY
80199 3/4" x 1/2" NPT
0.20
80198 1" x 1/2" NPT
0.26
40
40
1-1/16" 1-7/16"80196 1" x 3/4" NPT
0.2640
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
April 7, 2020
JC Fire Protection
81705 De Oro Ave.
Indio, CA 92201
Re: Residential Fire Sprinkler Plan Review – Benzinger Residence
FSS2020-0050 / 57745 SOUTH VALLEY LN, LA QUINTA, CA 92253
The sprinkler plans you submitted for the above referenced project have been reviewed by Riverside County
Fire Department - Office of the Fire Marshal personnel and are approved with the following conditions.
Permanently marked identification signs shall be attached to all control valves.
The following inspections/tests are required to be witnessed by Office of the Fire Marshal Staff:
(a) Overhead Rough and Hydro static test: All piping shall be visible and pumped at normal
operating pressure. *No jacketed electrical and data wiring shall be in contact with, nor have the
potential to contact CPVC piping once insulation is installed.
(b) Final inspection
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Kohl Hetrick - Fire Safety Specialist
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
RIVERSIDE COUNTY FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 57745 S. VALLEY LANE PERMIT#: FSS2020-0050 DATE
ISSUED: 4/7/2020
DESCRIPTION: RESIDENTIAL FIRE SPRINKLER SYSTEM CONTRACTOR: JC FIRE PROTECTION
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F Access & Address verification
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
**WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE**
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler
Systems)
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible dur ing the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the
affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when
scheduling inspections. For City of La Quinta inspections call: (760) 777-7131.
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence
without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required
to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not
on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into
the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance
has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE
AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180
DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE
REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.