FSS2020-0054ADDITIONAL SITES
CHRONOLOGY
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
E-MAIL AARON HICKSON 4/1/2020 4/1/2020 EMAILED APPLICANT TO OBTAIN A CITY BL AND AND
CREATED A CONTRACTOR ACCOUNT FOR ETRAKIT.
E-MAIL AARON HICKSON 4/15/2020 4/15/2020 RCEIVED BL APPLICATION
NOTE AARON HICKSON 4/20/2020 4/20/2020 CONTRACTOR PAID FEE FOR CITY BL TRANSFERED FEE TO BL
NOTE KAYLI ALFORD 12/2/2020 12/2/2020
CONTRACTOR REQUESTED INSPECTION BUT PERMIT IS
EXPIRED AS OF 11/1/20. CONTRACTOR WAS INFORMED OF
EXTENSION FEE AND THAT AN EXTENSION REQUEST LETTER
WAS REQUIRED. PERMIT WILL BE EXTENDED TO 12/3/20 TO
ALLOW CONTRACTOR TO PAY FEE VIA ETRAKIT. OK TO
EXTEND PER KOHL
EXTENSION REQUEST LETTER & EXTENSION FEE PAYMENT
RECEIVED. PERMIT EXTENDED BY 6 MOS TO 6/3/21
Description: ABSOLUTE PARTNERS / BRES2018-0188 / FIRE SPRINKLERS
Type: FIRE SPRINKLER (WEB)Subtype: RESIDENTIAL - CUSTOM
HOMES
Status: FINALED Applied: 3/31/2020 EPRS
Parcel No: 766060027 Site Address: 58585 QUARRY RANCH RD LA QUINTA,CA 92253 Approved: 4/15/2020 KHET
Subdivision: TR 30651 Block: Lot: 6 Issued: 4/20/2020 Online
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 12/3/2020 KHET
Valuation: $11,500.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details: Design and Install of a NFPA 13D Automatic Fire Sprinkler System
Printed: Friday, February 17, 2023 9:48:58 AM 1 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0054
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT Blake Chapman 179 Torremolinos Dr Rancho Mirage CA 92270 (760)835-7453 bchapman@worldfirep
rotection.com
BILL TO World Fire Protection, Inc 41-905 Boardwalk Suite
B
Palm Desert CA 92211 (760)835-7453 bchapman@worldfirep
rotection.com
CONTRACTOR WORLD FIRE PROTECTION INC PO BOX 2596 RANCHO
MIRAGE
CA 92270 (760)835-7453 bchapman@worldfirep
rotection.com
OWNER ABSOLUTE PARTNERS, LLC.58585 QUARRY RANCH
RD
Palm Desert CA 92211 (760)835-7453 robert@absolute-
partners.com
CONDITION
TYPE CONTACT DATE
ADDED
DATE
REQUIRED
DATE
SATISFIED STATUS REMARKS NOTES
READY TO ISSUE
CHECKLIST
AARON
HICKSON 4/1/2020 4/21/2020 4/21/2020 COMPLETE
CITY BUSINESS LICENSE REQUIRED
BL FEE PAID ON THIS PERMIT AND TRANSFERRED
TO FSS2020-0054
NOTE KOHL HETRICK 4/27/2020 4/27/2020
Remote Video Inspection attempted on 4/27/2020 was
unsuccessful due to poor cellular signal in The Quarry
development area. Rescheduled for 4/28/2020 at 1300.
CONDITIONS
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE FAILED OR
ADDITIONAL RE-
INSPECTION
101-0000-42421 0 $161.00 $161.00 4/29/20 WEB5012 CREDIT WORLD FIRE
PROTECTION INC ECON
FIRE PLAN REVISION
SUBMITTALS 101-0000-42420 0 $161.00 $161.00 4/29/20 WEB5012 CREDIT WORLD FIRE
PROTECTION INC ECON
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $161.00 $161.00 3/31/20 WEB4791 032556 CREDIT Blake Chapman EPRS
Printed: Friday, February 17, 2023 9:48:58 AM 2 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0054
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD ROUGH
PIPING KHET 4/28/2020 4/28/2020 DISAPPROVE
D
SEE ATTACHMENTS
OVERHEAD HYRO KHET 4/28/2020 4/28/2020 DISAPPROVE
D
SEE ATTACHMENTS
OVERHEAD ROUGH
PIPING
KHET 5/5/2020 5/5/2020 APPROVED
OVERHEAD HYRO KHET 5/5/2020 5/5/2020 APPROVED
FIRE FINAL**KHET 12/3/2020 12/3/2020 APPROVED REMOTE VIDEO
INSPECTION
REVIEWS
PARENT PROJECTS
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED PC
101-0000-42420 0 $242.00 $242.00 3/31/20 WEB4791 032556 CREDIT Blake Chapman EPRS
FIRE STAFF - PER HOUR 101-0000-42420 0.25 $40.25 $40.25 12/2/20 WEB6892 036452 CREDIT WORLD FIRE
PROTECTION INC ECON
Total Paid for FIRE FEES: $765.25 $765.25
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 3/31/20 WEB4791 032556 CREDIT Blake Chapman EPRS
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 3/31/20 WEB4791 032556 CREDIT Blake Chapman EPRS
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$780.25 $780.25
Printed: Friday, February 17, 2023 9:48:58 AM 3 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0054
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 4/29/2020 EtrakitContractor Revised Calcs Document.pdfCalc-1
Quarry.pdf 1
DOC 4/29/2020 EtrakitContractor Water Flow Doc - Mar 25 2020 - 2-47
PM_1.pdf 1
DOC 4/29/2020 EtrakitContractor Revised Plans Quarry
Ranch.pdfDetail.pdf 1
DOC 4/29/2020 EtrakitContractor Revised Plans Quarry
Ranch.pdfRevision 3.pdf 1
DOC 3/31/2020 EtrakitPublicReg 1ST SUBMITTAL FIRE
FLOW ANALYSIS
Doc - Mar 25 2020 - 2-47
PM.pdf 1
DOC 3/31/2020 EtrakitPublicReg 1ST SUBMITTAL GLOBE
CONCEALED Globe GL4906 4.9K.pdf 1
DOC 3/31/2020 EtrakitPublicReg 1ST SUBMITTAL GLOBE
RECESSED
Globe Recessed
Pendent GL4110.pdf 1
DOC 3/31/2020 EtrakitPublicReg 1ST SUBMITTAL
HYDRAULIC CALCS Quarry Ranch Calcs.pdf 1
DOC 12/2/2020 KAYLI ALFORD extension request.pdf extension request.pdf 0
BOND INFORMATION
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
AARON
HICKSON 3/31/2020 4/1/2020 4/20/2020 COMPLETE
1ST FIRE (2 WK)KOHL
HETRICK 3/31/2020 4/14/2020 4/15/2020 APPROVED SEE ATTACHMENTS
1ST FIRE (2 WK)KOHL
HETRICK 4/27/2020 5/11/2020 4/29/2020 REVISIONS REQUIRED REVISION 1 - WM
CHANGE SEE ATTACHMENTS.
1ST FIRE (1 DAY)KOHL
HETRICK 4/30/2020 5/4/2020 5/4/2020 APPROVED Rev 2 - WM Change SEE IN ATTACHMENTS
Printed: Friday, February 17, 2023 9:48:58 AM 4 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0054
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 4/15/2020 KOHL HETRICK
FSS2020-0054 - 1ST
SUBMITTAL PLANS -
APPROVED.pdf
FSS2020-0054 - 1ST
SUBMITTAL PLANS -
APPROVED.pdf
1
DOC 4/15/2020 KOHL HETRICK FSS2020-0054 - COA
AND JOB CARD.pdf
FSS2020-0054 - COA
AND JOB CARD.pdf 1
DOC 4/29/2020 KOHL HETRICK
FSS2020-0054 -
REVISION 1 PLANS and
CALCS -
CORRECTIONS.pdf
FSS2020-0054 -
REVISION 1 PLANS and
CALCS -
CORRECTIONS.pdf
1
DOC 4/29/2020 KOHL HETRICK
4-28-2020 - OH Rough
Inspection - Corrections
Notice.pdf
4-28-2020 - OH Rough
Inspection - Corrections
Notice.pdf
1
DOC 5/4/2020 KOHL HETRICK
FSS2020-0054 -
REVISION 2 PLANS and
CALCS - APPROVED.pdf
FSS2020-0054 -
REVISION 2 PLANS and
CALCS - APPROVED.pdf
1
Printed: Friday, February 17, 2023 9:48:58 AM 5 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0054
FSS2020-0054 - REVISION 2
3'-61_2"14' - 6 1/2"1" Fire Riser
Master
Bedroom
Master
Bath
Office
Covered Patio
Kitchen
Great
Room
Dining
Bed 2
Bed 3
Bed 4
Laundry
Ba 2
Powr
Portico
Entry Courtyard
Car Garage 1
Car Garage 2
WIC
WIC
WIC
1 1/2"53' -0"1 1/2"
26' -0"1"10' -1"1"13' -5"1"16' -1 1/2"1"13' -5"1"16' -1 1/2"1"10' -1 1/2"1"12' -0 1/2"1"2' -4 1/2"1"
14' -6"
1"
3' -7"1"14' -7 1/2"1"
3' -11"
1"
2' -1"1"8' -0"1"1' -9"1"0' -5"1"
9' -2"1"3' -6"1"3' -6"1"9' -6 1/2"1"9' -6 1/2"1"
11' -6"
1"
4' -10 1/2"1"
3' -4"1"10' -1 1/2"1"13' -3 1/2"1"9' -5 1/2"1"4' -10 1/2"1"6' -0 1/2"1"2' -6"1"
8' -6"
1"
9' -8 1/2"1"0' -10"1"
4' -0 1/2"1"4' -1 1/2"1"1' -4 1/2"1"
1' -8"1"4' -1 1/2"1"4' -1 1/2"1"6' -4 1/2"1"9' -2"1"6' -6 1/2"1"
7' -10"
1"
0' -4 1/2"
1"
2' -4 1/2"1"6' -6"1"
3' -11 1/2"
1"
0' -6 1/2"
1"
0' -4"
1"
3' -3"
1"
6' -10"
1"
6' -10"
1"
10' -0"1"8' -10"1"
0' -11 1/2"
1"
0' -10"
1"
7' -9"
1"
2' -8"
1"
3' -9"
1"
0' -6 1/2"1"10' -9"1"10' -9"1"5' -8"1"
4' -0"
1"
0' -9"
1"
5' -6"
1"
2' -0 1/2"
1"
1' -10 1/2"
1"
1' -3 1/2"
1"
11' -10 1/2"
1"
1' -1 1/2"1"3' -6 1/2"1"3' -6 1/2"1"
4' -2 1/2"1"10' -1"1"3' -3 1/2"1"
11' -4"
Calc Area -1
3/4" Water Meter
1-1/2" PVC UG By OthersSupply Point
Water Supply Information
Static Pressure:
Residual Pressure:
Residual Flow:
Additional Hose Flow:
75.47 psi
67.23 psi
1750 GPM
0 GPM
Remote area number:
Occupancy classification:
Density:
Area of application:
Total water required
(including hose streams):
@ a required
system pressure
of:
Fire Protection System Demand:
No. of sprinklers calculated:
Inside Hose Streams:
Outside Hose
Streams:
Calc-1
R-3
2
Gpm/SqFt
512 Max SqFt
31.1103 GPM
43.714 Psi
5 GPM
0 GPM
6 1
5
BOR
TOR
7
2
WM
DOM
4
WATER NOTE:
3/4" Water Meter
will Create an additional 15 psi max loss
at the meter leaving 8.516 psi safety margin
which is = to a 19% safety margin
CEILING HIGHT
10
CEILING HIGHT
15'
CEILING HIGHT
12'
12' - 6"1" x 2' -6"1" x 2' -6"1" x 2' -6"1" x 2' -6"3
1) System needs to be charged to static pressure for hydro
2) Fuel -fired utiliy in garage ( Head Added)
3) Bath 3 ( Head Added)
4) Office ( Head Added)
5) CPVC Pipe protection ( Pipe insulation added to avoid insulation contact)
NOTE: Calulations reflect a 15 psi loss due to 3/4" water meter
Correction Notes
info@worldfireprotection.com
Scale
Project number
Date
Drawn by
Checked by World Fire Protection41905 Boardwalk Suite BPalm Desert, Ca. 92211760-565-6030C-16 # 10497203/16" = 1'-0"4/29/2020 2:19:59 PMFP-1
Sprinkler Plan
Project Number
03-26-2020
JA
LS
No. Description Date
1 Revision 1 Date 1
GIGI CRONIN RESIDENCE58585 Quarry Ranch RoadLa Quinta, Ca. 92253THE QUARRY LOT 63/16" = 1'-0"1 Sprinkler Plan
Sprinkler Schedule
K-Factor Manufacturer Description Temperature Rating Count
4.9 GLOBE Globe GL4906Pendent Light Hazard Quick Response1/2 Orifice 3mm GB 155 °F 39
4.9 GLOBE Globe GL4910 Recesed Pendent Light Hazard Quick Response1/2 Orifice 3mm GB 200 °F 10
World Fire Protection
41905 Boardwalk Suite B
Your Street Address 2
Palm Desert, Ca. 92211
760-565-6030
Job Name : Quarry Ranch
Drawing :
Location :
Remote Area :
Contract :
Data File : Quarry Ranch Area Calc-1.WXF
Computer Programs by Hydratec Inc. Revision: 50.54.2
World Fire ProtectionPage 1 Quarry RanchDate 10203040E50R60U70S80S90E100R110P120130140150200 400 600 800 1000 1200 1400 1600 1800FLOW ( N ^ 1.85 )City Water Supply:Demand:C1C2C1 - Static Pressure : 75.47 C2 - Residual Pressure: 67.23 C2 - Residual Flow : 1750 D1 - Elevation : 5.630 D2 - System Flow : 31.185 D2 - System Pressure : 60.255 Hose ( Demand ) : _______D3 - System Demand : 31.185 Safety Margin : 15.210 D1D2Water Supply Curve CComputer Programs by Hydratec Inc. Revision: 50.54.2
World Fire ProtectionPage 2 Quarry RanchDate Fitting Legend Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24 E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 N * CPVC 90'Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0 O * CPVC Tee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0 R * CPVC Coupling Tee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0 T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 6071 81 91 101 121 Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used SummaryComputer Programs by Hydratec Inc. Revision: 50.54.2
World Fire Protection Page 3
Quarry Ranch Date
Node Elevation K-Fact Pt Pn Flow Density Area Press
No.Actual Actual Req.
1 10.0 4.9 7.04 na 13.0 0.05 60 7.04
2 10.5 7.62 na
3 10.5 13.5 na
4 13.0 14.91 na
TOR 10.5 31.59 na
DOM 4.42 35.34 na
BOR 1.0 37.2 na 5.0
5 -3.0 41.41 na
8 -3.0 43.77 na
WM -3.0 43.85 na
9 -3.0 60.26 na
6 10.0 4.9 7.24 na 13.18 0.05 46 7.0
7 13.0 14.37 na
The maximum velocity is 10.51 and it occurs in the pipe between nodes BOR and 5
Pressure / Flow Summary - STANDARD
Computer Programs by Hydratec Inc. Revision: 50.54.2
World Fire Protection Page 4
Quarry Ranch Date
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe ******* Notes ******
Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf
1 10 4.90 13.00 1 2N 14.0 11.980 150 7.040
to 0.0 14.000 -0.217
2 10.5 13.0 1.101 0.0 25.980 0.0307 0.797 Vel = 4.38
2 10.5 13.18 1 2O 10.0 36.520 150 7.620
to 6R 6.0 16.000 0.0
3 10.5 26.18 1.101 0.0 52.520 0.1120 5.883 Vel = 8.82
3 10.5 -11.78 1 2N 14.0 42.120 150 13.503
to 2O 10.0 25.000 -1.083
4 13 14.4 1.101 R 1.0 67.120 0.0371 2.489 Vel = 4.85
4 13 11.78 1 5E 19.125 91.480 150 14.909
to 3T 28.688 47.814 1.083
TOR 10.5 26.18 1.101 0.0 139.294 0.1120 15.602 Vel = 8.82
TOR 10.5 0.0 1 E 3.825 6.080 150 31.594
to 0.0 3.825 2.633
DOM 4.42 26.18 1.101 0.0 9.905 0.1120 1.109 Vel = 8.82
DOM 4.42 0.0 1 0.0 3.420 150 35.336
to 0.0 0.0 1.481
BOR 1 26.18 1.101 0.0 3.420 0.1123 0.384 Vel = 8.82
BOR 1 + 5.00 5.00 1 3E 11.475 4.500 150 37.201
to 0.0 11.475 1.732
5 -3 31.18 1.101 0.0 15.975 0.1547 2.472 Vel = 10.51
5 -3 0.0 1.5 2E 11.656 82.030 150 41.405
to 0.0 11.656 0.0
8 -3 31.18 1.598 0.0 93.686 0.0252 2.363 Vel = 4.99
8 -3 0.0 1 0.0 0.500 150 43.768
to 0.0 0.0 0.0
WM -3 31.18 1.101 0.0 0.500 0.1560 0.078 Vel = 10.51
WM -3 0.0 1 0.0 9.110 150 43.846
to 0.0 0.0 15.000 * * Fixed Loss = 15
9 -3 31.18 1.101 0.0 9.110 0.1547 1.409 Vel = 10.51
0.0
9 31.18 60.255 K Factor = 4.02
6 10 4.90 13.18 1 2N 14.0 4.000 150 7.239
to R 1.0 15.000 -0.217
2 10.5 13.18 1.101 0.0 19.000 0.0315 0.598 Vel = 4.44
0.0
2 13.18 7.620 K Factor = 4.77
3 10.5 11.78 1 4R 4.0 53.470 150 13.503
to O 5.0 23.000 -1.083
7 13 11.78 1.101 2N 14.0 76.470 0.0256 1.954 Vel = 3.97
7 13 0.0 1 T 9.563 11.350 150 14.374
to 0.0 9.562 0.0
4 13 11.78 1.101 0.0 20.912 0.0256 0.535 Vel = 3.97
0.0
4 11.78 14.909 K Factor = 3.05
Final Calculations : Hazen-Williams
Computer Programs by Hydratec Inc. Revision: 50.54.2
Permit Extension Request Letter
To Whom it May Concer,
This letter is to request an extension for our fire sprinkler permit number: FSS2020-0054 58585. The
owner of the property has had some issues which caused the progress of his project to move along at a
less than desirable pace. Due to the delay of the over-all project is has caused us to be unable to finish
our trim work until just a couple days ago.
Please let me know if you require any other information.
Thank you
-Blake Chapman
President
World Fire Protection, Inc.
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
April 15, 2020
World Fire Protection
41905 Boardwalk #B
Palm Desert, CA 92211
Re: Residential Fire Sprinkler Plan Review – ABSOLUTE PARTNERS
FSS2020-0054 / 58585 QUARRY RANCH RD, LA QUINTA, CA 92253
The sprinkler plans you submitted for the above referenced project have been reviewed by Riverside County
Fire Department - Office of the Fire Marshal personnel and are approved with the following conditions.
Permanently marked identification signs shall be attached to all control valves.
The following inspections/tests are required to be witnessed by Office of the Fire Marshal Staff:
(a) Overhead Rough and Hydro static test: All piping shall be visible and pumped at normal
operating pressure. *No jacketed electrical and data wiring shall be in contact with, nor have the
potential to contact CPVC piping once insulation is installed.
(b) Final inspection
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Kohl Hetrick - Fire Safety Specialist
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
RIVERSIDE COUNTY FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 58585 QUARRY RANCH ROAD PERMIT#: FSS2020-0054 DATE
ISSUED: 4/15/2020
DESCRIPTION: RES. FIRE SPRINKLER SYSTEM CONTRACTOR: WORLD FIRE PROTECTION
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F Access & Address verification
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
**WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE**
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler
Systems)
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible dur ing the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the
affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when
scheduling inspections. For City of La Quinta inspections call: (760) 777-7131.
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence
without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required
to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not
on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into
the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance
has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE
AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180
DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE
REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.