FSS2020-0059ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT FIRE SPRINKLER SYSTEMS INC 705 E HARRISON ST STE
200
CORONA CA 92879 (949)789-1600 jamieb@fireinc.net
BILL TO FIRE SPRINKLER SYSTEMS INC 705 E HARRISON ST STE
200
CORONA CA 92879 (949)789-1600 jamieb@fireinc.net
CONTRACTOR FIRE SPRINKLER SYSTEMS INC 705 E HARRISON ST STE
200
CORONA CA 92879 (949)789-1600 jamieb@fireinc.net
OWNER LENNAR HOMES OF CALIFORNIA INC 15131 ALTON PKWY
#345
IRVINE CA 92618 (949)789-1600 carey.adams@lennar.c
om
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
NOTE KAYLI ALFORD 7/17/2020 7/17/2020 MSATER PLAN FCMP2020-0001 -PLAN TYPE 5
CONDITIONS
Description: GRIFFIN RANCH / BRES2019-0481 / FIRE SPRINKLER / PLAN 5B
Type: FIRE SPRINKLER Subtype: RESIDENTIAL - TRACT
HOMES
Status: FINALED Applied: 4/27/2020 AMA
Parcel No: 767770046 Site Address: 81272 MERV GRIFFIN WY LA QUINTA,CA 92253 Approved: 4/27/2020 AMA
Subdivision: TR 32879 Block: Lot: 39 Issued: 4/27/2020 Online
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 7/22/2020 KHET
Valuation: $0.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
Printed: Wednesday, February 08, 2023 3:11:47 PM 1 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0059
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD ROUGH
PIPING KHET 4/29/2020 4/29/2020 APPROVED SEE NOTES
REMOTE VIDEO INSPECTION
WM TO BOR EXCEEDS 70' (APPROX 120')
BUCKET TEST REQUIRED AS PART OF FINAL
INSPECTION (FIELD).
OVERHEAD HYRO KHET 4/29/2020 4/29/2020 APPROVED SEE NOTES
REMOTE VIDEO INSPECTION
WM TO BOR EXCEEDS 70' (APPROX 120')
BUCKET TEST REQUIRED AS PART OF FINAL
INSPECTION (FIELD).
FIRE FINAL**KHET 7/22/2020 7/22/2020 APPROVED BUCKET TEST
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
PARENT PROJECTS
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $161.00 $161.00 4/27/20 WEB4976 CREDIT FIRE SPRINKLER
SYSTEMS INC ECON
Total Paid for FIRE FEES: $161.00 $161.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 4/27/20 WEB4976 CREDIT FIRE SPRINKLER
SYSTEMS INC ECON
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 4/27/20 WEB4976 CREDIT FIRE SPRINKLER
SYSTEMS INC ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$176.00 $176.00
Printed: Wednesday, February 08, 2023 3:11:47 PM 2 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0059
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 5/4/2020 ARMANDO MAGALLON APPLICATION 3005_001.pdf 0
DOC 4/28/2020 KAYLI ALFORD 31630-DE Master Plan
4154 (AsBuilt3).pdf
31630-DE Master Plan
4154 (AsBuilt3).pdf 0
DOC 7/22/2020 KOHL HETRICK FSS2020-0059 Bucket
Test Results.pdf
FSS2020-0059 Bucket
Test Results.pdf 1
BOND INFORMATION
1ST FIRE (2 WK)FIRE BUCKET
1ST PERMIT TECH (1
DAY)
ARMANDO
MAGALLON 4/27/2020 4/28/2020 4/28/2020 COMPLETE
PERMITS WERE PREVIOUSLY APPROVED BY
MASTER PLAN
PLAN CHECK FEE HAS BEEN REMOVED
Printed: Wednesday, February 08, 2023 3:11:47 PM 3 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0059
Bucket Test Procedure – by FSS Kohl Hetrick
Contractor to provide (2) 30G+ bins pre-marked at preferably 1gal intervals, though every 5gal marks are acceptable.
Bins are placed at each of the design area fire sprinklers. These head locations are provided with an adapter extending
down from the ceiling level and provided with a 1/4 turn .5-inch ball valve. The piping for this adapter shall not be
greater than the pipe serving that particular head (i.e. 3/4”).
An additional 5gal bucket is provided for measuring domestic demand at spigot nearest fire riser.
Inspector will be at riser and domestic spigot with contractor, stopwatch ready. Helper(s) will be at the 2 design
heads. Through communication on phone or radio, signal “All Start.” Everyone turns on their valves and stopwatch
is started.
Once the 5gal bucket at Dom spigot is at reasonable max fill, signal “All Stop”. Everyone closes valves and stopwatch
is stopped.
Inspect the volumes acquired in the 2 bins at the sprinkler heads. Starting with the one with the least volume, take
the amount in gallons and divide by the number of seconds observed on the stopwatch. This will give you the gallons
per second. Now multiply that number by 60 to establish the gallons per minute for that single head.
Q = (V/T)60
Where:
Q is the flow in gallons per minute (gpm) at a single head discharge point.
V is the volume in gallons (approximate) observed discharged from the single head discharge point
T is the time in seconds (including fraction) it took to fill the 5-gallon container at the domestic spigot valve. *This
may be less than or greater than 60 seconds.
Example:
6 gallons observed at one of the design head discharges in 25 seconds
6/25= .24 gallons per second
.24x60= 14.4 gallons per minute
For the common K4.9 factor head doing a maximum 16x16 spacing, a minimum 13gpm needs to be provided to the
most remote/demanding head(s). This bucket test flow was satisfactory.
Both heads flowed the minimum gpm and you confirmed the minimum 5gpm domestic demand.
PERMIT: _____________________ Address: ________________________________________________
Static Pressure: _____________ *after blead-off **For documentation only.
Residual Pressure: _____________ *while flowing design heads and domestic simultaneously **For
documentation only.
Time (T): ___________ seconds
Volume 1(V1): ____________ gallons
Volume 2(V2): ____________ gallons
Head 1 = (Q) __________ = ((V1) _______ / (T) ________) x 60 Pass ☐ Fail ☐ [Required flow: _______ gpm]
Head 2 = (Q) __________ = ((V2) _______ / (T) ________) x 60 Pass ☐ Fail ☐ [Required flow: _______ gpm]
*Head 3 = (Q) __________ = ((V3) _______ / (T) ________) x 60 Pass ☐ Fail ☐ [Required flow: _______ gpm]
*Optional – for 3-head calculation situations. Will require a 3rd 30-Gallon bucket.
FSS2020-0059 81272 Merv Griffin
25
20
5.5
5.5
16.5
16.5
5.5 20
5.5 20
13
13
85
x
x