FSS2020-0064ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT SOUTHWEST FIRE PROS 31-410 RESERVE DR STE
#2
THOUSAND
PALMS
CA 92276 (760)343-2233 maureen@swfirepros.c
om
BILL TO Maureen Co 31410 reserve Dr.Thousand Palms CA 92276 (760)343-2233 maureen@swfirepros.c
om
CONTRACTOR SOUTHWEST FIRE PROS 31-410 RESERVE DR STE
#2
THOUSAND
PALMS
CA 92276 (760)343-2233 maureen@swfirepros.c
om
OWNER PEPE BUILDS 77-137 CASA DEL SOL LA QUINTA CA 92253 (760)343-2233
CONDITIONS
Description: PEPE BUILDS / BRES2018-0086 / FIRE SPRINKLERS
Type: FIRE SPRINKLER (WEB)Subtype: RESIDENTIAL - CUSTOM
HOMES
Status: FINALED Applied: 5/15/2020 ECON
Parcel No: 773360013 Site Address: 77137 CASA DEL SOL LA QUINTA,CA 92253 Approved: 5/29/2020 KHET
Subdivision: TR 28409 Block: Lot: 13 Issued: 5/29/2020 KHET
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 9/28/2020 KHET
Valuation: $9,000.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
FINANCIAL INFORMATION
Printed: Tuesday, February 21, 2023 10:10:14 AM 1 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0064
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD ROUGH
PIPING KHET 6/11/2020 6/11/2020
APPROVED
W/EXCEPTIO
N
BUCKET TEST REQUIRED Bucket test option is being requested by the
contractor due to Water Meter size reduced.
OVERHEAD HYRO KHET 6/11/2020 6/11/2020 APPROVED
MAIN DRAIN -
INSPECTORS TEST KHET 6/17/2020 6/17/2020 APPROVED 2 HEAD BUCKET TEST Observed 14.1 gpm from each head while
flowing 5 gpm domestic.
FIRE FINAL**KHET 9/28/2020 9/28/2020 APPROVED REMOTE VIDEO
INSPECTION
REVIEWS
PARENT PROJECTS
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $161.00 $161.00 5/15/20 WEB5148 06521G CREDIT SOUTHWEST FIRE
PROS ECON
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED PC
101-0000-42420 0 $242.00 $242.00 5/15/20 WEB5148 06521G CREDIT SOUTHWEST FIRE
PROS ECON
Total Paid for FIRE FEES: $403.00 $403.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 5/15/20 WEB5148 06521G CREDIT SOUTHWEST FIRE
PROS ECON
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 5/15/20 WEB5148 06521G CREDIT SOUTHWEST FIRE
PROS ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$418.00 $418.00
Printed: Tuesday, February 21, 2023 10:10:14 AM 2 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0064
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 5/29/2020 KOHL HETRICK MATERIAL
SPECIFICATIONS.pdf
MATERIAL
SPECIFICATIONS.pdf 1
DOC 5/29/2020 KOHL HETRICK
FSS2020-0064 -
SPRINKLER PLANS and
CALCS - APPROVED.pdf
FSS2020-0064 -
SPRINKLER PLANS and
CALCS - APPROVED.pdf
1
DOC 5/29/2020 KOHL HETRICK FSS2020-0064 - COA and
JOB CARD.pdf
FSS2020-0064 - COA and
JOB CARD.pdf 1
DOC 6/11/2020 KOHL HETRICK
FSS2020-0064 -
APPROVED PLANS and
CALCS - OH ROUGH
NOTES.pdf
FSS2020-0064 -
APPROVED PLANS and
CALCS - OH ROUGH
NOTES.pdf
1
BOND INFORMATION
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST PERMIT TECH (1
DAY)
AARON
HICKSON 5/15/2020 5/18/2020 5/15/2020 COMPLETE
1ST FIRE (2 WK)KOHL
HETRICK 5/15/2020 5/29/2020 5/29/2020 APPROVED SEE ATTACHMENTS
Printed: Tuesday, February 21, 2023 10:10:14 AM 3 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0064
FSS2020-0064
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
May 29, 2020
SOUTHWEST FIRE PROS
31410 Reserve Drive #2
Thousand Palms, CA 92276
Re: Residential Fire Sprinkler Plan Review – PEPE BUILDS
FSS2020-0064 / 77137 CASA DEL SOL, LA QUINTA, CA 92253
The sprinkler plans you submitted for the above referenced project have been reviewed by Riverside County
Fire Department - Office of the Fire Marshal personnel and are approved with the following conditions.
Permanently marked identification signs shall be attached to all control valves.
The following inspections/tests are required to be witnessed by Office of the Fire Marshal Staff:
(a) Overhead Rough and Hydro static test: All piping shall be visible and pumped at normal
operating pressure. *No jacketed electrical and data wiring shall be in contact with, nor have the
potential to contact CPVC piping once insulation is installed.
(b) Final inspection
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Kohl Hetrick - Fire Safety Specialist
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
RIVERSIDE COUNTY FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 77137 CASA DEL SOL PERMIT#: FSS2020-0064 DATE
ISSUED: 5/29/2020
DESCRIPTION: PEPE BUILDS – RES. FIRE SPRK CONTRACTOR: SOUTHWEST FIRE PROS
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F Access & Address verification
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
**WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE**
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler
Systems)
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible dur ing the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the
affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when
scheduling inspections. For City of La Quinta inspections call: (760) 777-7131.
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence
without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required
to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not
on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into
the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance
has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE
AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180
DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE
REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.