FSS2020-0157ADDITIONAL SITES
CHRONOLOGY
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
NOTE JOSE DELGADO 12/2/2021 12/13/2021
CONTRACTOR REQUESTED FINAL INSPECTION. PERMIT
EXPIRED AS OF 6/7/21 (6 MOS FROM DATE OF LAST
APPROVED INSPECTION). ADDED EXTENSION FEE OF $83 AND
EXTENDED PERMIT TO 12/3/21 SO CONTRACTOR CAN PAY
FEE VIA ETRAKIT. WILL ALSO REQUIRE AN EXTENSION
REQUEST LETTER FROM CONTRACTOR. OK TO EXTEND PER
KOHL. ALSO NOTIFIED CONTRACTOR THAT THEIR BUSINESS
LICENSE HAS BEEN EXPIRED AS OF 11/30/21 AND WOULD
NEED TO RENEW IT.
CONTRACTOR SUBMITTED EXTENSION LETTER AND FEE'S
HAVE BEEN PAID. PERMIT EXTENDED 6 MONTHS FROM DATE
EXTENSION LETTER WAS SUBMITTED.
CONDITIONS
Description: SIEGALL / BRES2020-0121 /TENANT IMPROVEMENT/ HOME ADDITION
Type: FIRE SPRINKLER (WEB)Subtype: RESIDENTIAL - CUSTOM
HOMES
Status: FINALED Applied: 11/23/2020 EPRS
Parcel No: 767670010 Site Address: 81175 ELSWORTH PL LA QUINTA,CA 92253 Approved: 12/8/2020 KHET
Subdivision: TR 33076-1 Block: Lot: 14 Issued: 12/9/2020 AMA
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 12/16/2021 KHET
Valuation: $4,300.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
Printed: Friday, February 24, 2023 10:35:30 AM 1 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0157
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT simon chavero 82417 priscilla ct indio CA 92201 (760)574-6512 simon@silveradofire.c
om
BILL TO simon chavero 82417 priscilla ct indio CA 92201 (760)574-6512 info@silveradofire.com
CONTRACTOR SILVERADO FIRE PROTECTION 82417 PRISCILLA
STREET
INDIO CA 92201 (760)574-6512 SIMON@SILVERADOFI
RE.COM
OWNER CLAY SIEGALL 82417 priscilla ct indio CA 92201 (760)574-6512 info@silveradofire.com
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $161.00 $161.00 12/9/20 R63237 INVOICE 65 CREDIT SIMON CHAVERO AMA
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED PC
101-0000-42420 0 $242.00 $242.00 12/9/20 R63237 INVOICE 65 CREDIT SIMON CHAVERO AMA
FIRE STAFF - PER HOUR 101-0000-42420 1 $83.00 $83.00 12/6/21 WEB10075 634063289
65 CREDIT simon chavero EPRS
Total Paid for FIRE FEES: $486.00 $486.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 12/9/20 R63237 INVOICE 65 CREDIT SIMON CHAVERO AMA
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 12/9/20 R63237 INVOICE 65 CREDIT SIMON CHAVERO AMA
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$501.00 $501.00
Printed: Friday, February 24, 2023 10:35:30 AM 2 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0157
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 11/23/2020 EtrakitPublicReg 1ST SUBMITTAL CVWD
CONNECTION
CVWD Connection
Letter.pdf 1
DOC 11/23/2020 EtrakitPublicReg 1ST SUBMITTAL FLOW
ANALYSIS
CVWD - Fire Flow
Letter.pdf 1
DOC 11/23/2020 EtrakitPublicReg 1ST SUBMITTAL
PENDANT
Globe Recessed
Pendent GL4110 (5).pdf 1
DOC 11/23/2020 EtrakitPublicReg 1ST SUBMITTAL GL4906 Globe GL4906 4.9K
(2).pdf 1
DOC 11/23/2020 EtrakitPublicReg 1ST SUBMITTAL
SPRINKLER PLAN
Siegall
Residence.pdf2nd
Floor.pdf
1
BOND INFORMATION
SCHEDULED
DATE
COMPLETED
DATE
OVERHEAD HYRO KHET 12/14/2020 12/14/2020 APPROVED REMOTE VIDEO
INSPECTION
OVERHEAD ROUGH
PIPING KHET 12/14/2020 12/14/2020 APPROVED REMOTE VIDEO
INSPECTION
CONTRACTOR TO TAKE PHOTOS OF
CONNECTION OF NEW PIPING TO EXISTING
SYSTEM IN 1ST FLOOR HALLWAY OFF OF
GARAGE.
FIRE FINAL**KHET 12/16/2021 12/16/2021 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST FIRE (2 WK)KOHL
HETRICK
11/23/2020 12/9/2020 12/8/2020 APPROVED SEE ATTACHMENTS
1ST PERMIT TECH (1
DAY)
PERMIT TECH
BUCKET
11/23/2020 11/24/2020 11/24/2020 COMPLETE
PARENT PROJECTS
Printed: Friday, February 24, 2023 10:35:30 AM 3 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0157
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 11/23/2020 EtrakitPublicReg 1ST SUBMITTAL PLAN
1ST FLOOR SPRINKLER
Siegall Residence.pdf1st
Floor.pdf 1
DOC 11/23/2020 EtrakitPublicReg 1ST SUBMITTAL 2ND
FLOOR 09-S2.PDF 1
DOC 11/23/2020 EtrakitPublicReg 1ST SUBMITTAL PLAN
1ST FLOOR 08-S1 (1).PDF 1
DOC 12/13/2021 JOSE DELGADO Extension letter request
Elsworth pl.pdf Elsworth pl.pdf 0
DOC 12/8/2020 KOHL HETRICK FSS2020-0157 -
APPROVED PLANS.pdf
FSS2020-0157 -
APPROVED PLANS.pdf 1
DOC 12/8/2020 KOHL HETRICK FSS2020-0157 - COA
AND JOB CARD.pdf
FSS2020-0157 - COA
AND JOB CARD.pdf 1
DOC 12/14/2020 KOHL HETRICK FSS2020-0157 - 12-14-20
INSP AS-BULTS.pdf
FSS2020-0157 - 12-14-20
INSP AS-BULTS.pdf 1
Printed: Friday, February 24, 2023 10:35:30 AM 4 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2020-0157
(N) BEDROOM
(N) BATH
HALL
1 3/8"
1 1/2"
DRYERVENTS
100
GAL.
75
GAL.
600 AMP
26802680POCKET3080FR. FR.13420 FIXEDPR. 2680FR. DRS.2030CSMT.
1280FIXED 1280FIXED
2080FIXEDFR. DR.
2080FIXEDFR. DR.2680NEWGATE
SEAT CLOSETMASTER
BEDROOM
PATIOHIS
CLOSET
HIS
MASTER
BATH
STEAM
ENTRY
GREAT
ROOM
DINING
ROOM
WINE
ENTRY
COURT
(E) HER
CLOSET
(E) HER
MASTER
BATH
CASITA
LIVING
ROOM
(E) BEDROOM 5
(E) BATH 5
BATH 4
BEDROOM 4
ENTRY
LN.
KIT.
LOGGIA
BEDROOM 2
BATH 2
POWDERSERVICE
GARAGE
GOLF
ROOM
GOLF
CART
BACK KITCHEN
KITCHEN
PATIO
BBQ
BAR
BAR
OUTDOOR
SHOWER
OUTDOOR
SHOWER
TREE
WELL
CL.
(E) CL
MECH
PRIVATE
SANCTUARY
PRIVATE
SPA
PRIVATE
VANITY
DOG
WASH
SWIM
UP
BAR
SPA
A/V
PRIVATE
PATIO
(E) PATIOPATIO
POOL
BATH
PORTO COCHERE COURTYARD
D
D
W
W
D
W
W/D
LINEN
PANTRY
UPUPPROVIDE OUTSIDECOMBUSTION AIR -VENT TO ROOF
PROVIDE OUTSIDECOMBUSTION AIR
775 SQ.FT.
NFPA 13D REFERANCE NOTES
1. NFPA 13D, Section 8.3.2
Sprinklers shall not be required in bathrooms of 55 sq. ft. and less.
2. NFPA 13D, Section 8.3.3
Sprinklers shall not be required in clothes closets, linen closets, and pantries
that meet all of the following conditions.
(1) The area of the space does not exceed 24 sq. ft.
(2) The walls and ceilings are surfaced with noncombustible or limited-combustible
material as defined in NFPA 220.
3. NFPA 13D Section 8.3.4
Sprinklers shall not be required in garages, open attached porches, carports, and
similar structures.
Note that CFC 2016 Chapter 80 Referance Standards requires attached garages,
attached porches, carports, and similar structures shall be sprinklered if there is
occupied living space above.
4. NFPA 13D Section 8.2.5.6 Shadow Areas
Shadow areas shall be permitted in the protection area of a sprinkler as long as
the cumulative dry areas do not exceed 15 sq. ft. (1.4 sq. m.) per sprinkler.
SPRINKLER PIPEINSULATION
BOTTOM CORD OF ROOF TRUSS
OR CEILING JOIST
PIPE INSULATION DETAIL CPVC HANGERS
NO SCALE
TOLCO FIG. 24
DOUBLE-FASTENER
SIDE-MOUNT HANGER
(OR EQUAL)
SELF-DRILLING
HEX HEAD SCREW
TOLCO FIG. 23
DOUBLE-FASTENER
STRAP TYPE HANGER
(OR EQUAL)
TOLCO FIG. 28M
OFFSET HANGER
(OR EQUAL)
TOLCO FIG. 22
SINGLE-FASTENER
STRAP-TYPE HANGER
(OR EQUAL)
TOLCO FIG. 28
DOUBLE-FASTENER
STAND-OFF HANGER
(OR EQUAL)
TOLCO FIG. 29
DOUBLE-FASTENER
DOUBLE OFFSET HANGER
(OR EQUAL)
CPVC HANGER SPACING
PIPE SIZE
11/4"
1"
MAXIMUM SUPPORT SPACING
6'-6"
6'-0"
2"8'-0"
11/2"7'-0"
Existing 1-1/4" Riser
E
E
E
E
N
N N
N
N
NN
NN
N N
N
These 6 heads will be lowered
14" in the clouded area only as
the ceiling will lowered to accomadate
the new 2nd floor bedrooms
1" COMING DOWN
FROM 2nd FLOOR
Fire Department Notes
A. The installation of new fire sprinkler systems or modifications to existing systems shall
comply with the following:
NFPA 13D 2016
CBC 2019
CFC 2019
Local Municipal Codes
Requirements of the AHJ
All Manufacture Installation Guidelines
Note: When conflict arrises between existing codes and standards,
the most stringent shall apply.
B. The Fire Department Shall require the following inspections and tests.
1. Overhead installation and hydrostatic test, ( prior to cover ).
a. Normal opperating pressure when no FDC is installed.
b. 200psi when FDC is required.
c. Two hour minimum.
2. Final sprinkler and underground, ( prior to building final ).
a. All inspections shall be scheduled by the contractor of record.
b. Inspections shall be scheduled 24 hours in advance.
GENERAL NOTES
1.General: All materials and devices shall conform to 2016 NFPA 13D standards. Installation
shall conform to all applcable State and Local Codes.
2.Scope of Work: Install a new T.I. Residential Fire Protection System.
3.Piping: All overhead pipe and fittings shall be CPVC unless otherwise noted.
4.Design: NFPA 13D 2016 Edition and CFC Chapter 80 Standards.
5.System Demand @ Source. Two Sprinklers Flowing (16X16 Spacing):
31 gpm @ ______psi ( 512 sf Max )
6.Water Supply Data: Water is supplied from public water main in street.
Static Pressure:
Information Source:
7.Sprinkler Head Spacing and Installation Requirements:Sprinklers shall not be located
Closer than 8'-0" apart where there is no intervening obstruction.
Sprinklers near potential obstruction shall be located per manufactures instructions.
8.Piping Supports: Piping shall be supported and restrained in conformance with local
plumbing codes and CPVC manufactures instructions . Eachpipe section that supplies
a drop to a sprinkler shall be secured no more than 12" from the drop to prevent laterial
and vertical movement.
9.Pipe lenghts are approximate for hydraulic calculation and plan review purposes only.
10.The owner shall furnish sufficant heat in all areas to prevent freezingof pipe.
11.Waterflow Switch and Alarm: By Others
a. A dedicated electrical circuit with a circuit breaker lock shall be provided for waterflow
horn/strobes.
b. An approved audible sprinkler waterflow alarm shall be visible from the street.
The device shall be listed for outdoor use.
An approved sign shall be placed at or near the device stating,
SPRINKLER FIRE ALARM - WHEN ALARM SOUNDS CALL 911
c. An approved audible sprinkler waterflow alarm module shall be conected to the
smoke detectors to alert occupants shall be provided.
simon@silverado
Scale
Project number
Date
Drawn by
Checked by Silverado Fire ProtectionP.O. Box 11474Palm Desert Ca 92255760-574-6512C-16 # 1068664
As indicated
11/23/2020 10:42:33 AMFP-1
Sprinkler T.I. Plan 1st
Floor
Project Number
11-24-20
JA
JC
No. Description Date
1 Revision 1 Date 1
LOT 14ASIEGALL RESIDENCET.I.Madison ClubLa Quinta, Ca3/32" = 1'-0"1 1st Floor SPK
Sprinkler Schedule
No. of
Sprklrs Description
SIN
(Hydratec)K-Factor
Orifice
Size Temp
13 GL4906 Concealed Pendent Light Hazard Quick Response1/2 Orifice 3mm GB 4.9 1/2" 155 °F
6 GL4910 Recessed Pendent Light Hazard Quick Response1/2 Orifice 3mm GB 4.9 1/2" 200 °F
: 19
Total No. of Sprinklers: 19
(E) OFFICE/
(E) BATH 3
(E) HALL
(E) POWDER
(E) CLO
(E) DECK
BEDROOM 3
BAR
BAR
COVERED
DECK
LIVING/
LOUNGE
2680
26802680
205ocsmt205ocsmt205ocsmt405ofixed
205ocsmt205ocsmt405ofixed
2680fr. dr.
2680pocket
2680
PR. 2650CSMT
EXISTING DR.UNIT TO BERELOCATED PR. 268026802030CSMT.2030CSMT2030CSMT.2030CSMTLess Than
24 sf
N N
N N
N N
1" PIPE UP FROM 1st FLOOR
Less Than
55 sf
Less Than
55 sf
Less Than
55 sf
Less Than
55 sf
(N) BEDROOM 7
(N) BEDROOM 7
(N) BEDROOM 6
simon@silverado
Scale
Project number
Date
Drawn by
Checked by Silverado Fire ProtectionP.O. Box 11474Palm Desert Ca 92255760-574-6512C-16 # 1068664
As indicated
11/23/2020 10:43:00 AMFP-2
Sprinkler Plan T.I.
second Floor
Project Number
11-24-20
JA
JC
No. Description Date
1/8" = 1'-0"1 2nd Floor SPK
LOT 14ASIEGALL RESIDENCEMadison ClubLa Quinta, Ca.
APRIL 2019 REV.A GFS-302 PAGE 1 of 4
SERIES GL-RES
RESIDENTIAL PENDENT AND RECESSED PENDENT
K-FACTOR: 3.0, 4.1, 4.9, 5.6
4077 Airpark Dr. Standish, MI 48658 • 989-846-4583 • www.globesprinkler.com
Technical Support • 989-414-2600 • techservice@globesprinkler.com
NOTE:
Users should refer to Globe’s web site (www.globesprinkler.com)
to assure that the most recent technical literature is being utilized.
GENERAL DESCRIPTION
The series GL-RES pendent sprinklers are decorative fast
response glass bulb sprinklers specifically tested and List-
ed for use in residential applications such as homes, apart-
ments, hotels, and dormitories to provide control of these
residential type fires and to improve the chance for occu-
pants to escape. They utilize a 3mm frangible glass bulb as
its heat sensing operating element. The recessed version
of each of these Residential Sprinklers is intended for use
in areas with finished ceilings. It employs a two-piece Re-
cessed Escutcheon. The Recessed Escutcheon provides a
total adjustment of 1/2 inch (12.7mm) from the flush ceiling
position or ±1/4 inch (6.4mm) of recessed adjustment. The
adjustment provided by the Recessed Escutcheon reduces
the accuracy to which the pipe drops to the sprinklers must
be cut.
This sprinkler may be installed within dwelling occupancies
as allowed by NFPA 13, 13D, 13R and any other related
documents as appropriate.
The GL3010 is typically utilized when maximum coverag-
es are not needed, thereby reducing flow demands. The
GL5610 is typically the sprinkler of choice when utilizing
Residential Sprinklers within an NFPA 13 Occupancy. The
larger K-factor can be advantageous when needed to con-
form to the NFPA 13 hydraulic Special Design Approach for
Residential Sprinklers.
OPERATION
Upon exposure to heat such as from a fire, the fluid in the
bulb expands, compressing the air bubble within the bulb.
When the air bubble can no longer compress, the fluid ex-
pansion causes breakage of the glass bulb, resulting in re-
lease of the water seat assembly, and discharge of water
from the sprinkler.
TECHNICAL DATA
Approvals
• See TABLE A
Maximum Working Pressure
• 175 psi (12 bar)
Temperature Rating
• See TABLE A
K-Factor
• GL3010 K3.0 gpm/psi½ (43.2 lpm/bar½)
• GL4110 K4.1 gpm/psi½ (59.0 lpm/bar½)
• GL4910 K4.9 gpm/psi½ (70.6 lpm/bar½)
• GL5610 K5.6 gpm/psi½ (80.6 lpm/bar½)
Thread Size
• 1/2” NPT (15 mm)
Length
• 2-1/2” (6.3 cm)
Materials of Construction
• Frame - bronze • Deflector - brass • Screw - brass
• Lodgement Wire (GL5610 only) - stainless steel • Bulb
seat - copper
• Spring - nickel alloy • Seal - teflon
• Bulb - glass with alcohol based solution, 3mm
• Escutcheon Assembly - carbon steel
FINISHES AND ACCESSORIES
Finishes
• Factory Bronze • Chrome • White Polyester
• Black Polyester - special order
Escutcheons
• Brass • Chrome • White Polyester • Black Polyester
Wrenches
• Standard • Recess • 1/2” NPT
SERIES GL-RES
GL3010, GL4110, GL4910, GL5610
SERIES GL-RES RESIDENTIAL PENDENT AND RECESSED PENDENT K-FACTOR: 3.0, 4.1, 4.9, 5.6 SERIES GL-RES RESIDENTIAL PENDENT AND RECESSED PENDENT K-FACTOR: 3.0, 4.1, 4.9, 5.6GFS-302 GFS-302
APRIL 2019 REV.A GFS-302 PAGE 2 of 4
DESIGN CRITERIA
The Globe Residential Pendent Sprinkler Series GL-RES is
cULus Listed for installation in accordance with this data
sheet as well as the applicable installation Standard being
utilized.
Globe Residential Sprinkler Installation Guide
When conditions exist that are outside the scope of the pro-
vided criteria, refer to the Globe Residential Sprinkler Instal-
lation Guide (Document GFS-380) for recommendations
that may be acceptable to the authority having jurisdiction.
Hydraulic Design (NFPA 13D and 13R)
For systems designed to NFPA 13D or NFPA 13R, the min-
imum required sprinkler flow rate is given in Table A for the
coverage areas shown. The sprinkler flow rate is the min-
imum required discharge from each of the total number of
“design sprinklers” as specified in NFPA 13D or NFPA 13R.
Hydraulic Design (NFPA 13)
The minimum required discharge from each design area
sprinkler shall be the greater of the following:
(1) In accordance with minimum flow rates indicated in
TABLE A.
(2) In rooms or compartments greater than 800 ft2
(74.3 m2), calculated based on delivering a minimum
of 0.1 gpm/ft2 (4.1 mm/min) over the coverage area of
each sprinkler, calculated in accordance with the
S x L Rules for density area sprinklers.
(3) In rooms or compartments 800 ft2 (74.3 m2) or less
(Defined as “Small Rooms”) calculated based on de-
livering a minimum of 0.1 gpm/ft2 (4.1 mm/min) over
the room or compartment using the area of the room
divided by the number of sprinklers in the room. (7psi
minimum)
SIN
K
FACTOR
GPM/PSI½
(lpm/bar½)
TEMPERATURE MAX.AREA OF
COVERAGE
FEET (m)
MINIMUM
PRESSURE
PSI (bar)
MINIMUM
FLOW
GPM (L/min.)
DEFLECTOR TO
CEILING/
MOUNTING
SURFACE
DISTANCE
INCHES (mm)
MINIMUM
DISTANCE
BETWEEN
SPRINKLERS
FEET (m)155°F (68°C)175°F (79°C)200°F (93°C)
GL3010 3.0
(43.2)
cULus
EU(1)cULus cULus 12 (3.6) x 12 (3.6)7.1 (.49)8.0 (30.3)
Smooth Ceilings
Recessed
1-1/8 (29)
to 1-5/8 (41)
Smooth Ceilings
Exposed
Max. 4 (101.6)
Beamed Ceilings
Adjacent
per NFPA 13, 13D,
or 13R
as appropriate
Beamed Ceilings
In Beam
14” Max. Beam Depth
1-1/8 (29)
to 1-5/8 (41)
8 (2.4)
cULus
EU(1)cULus cULus 14 (4.3) x 14 (4.3)11.1 (.765)10.0 (37.8)
GL4110 4.1
(59)
cULus
EU(1)cULus
EU(1)NA 12 (3.6) x 12 (3.6)7.2 (.5)11.0 (42)
cULus
EU(1)NA NA 14 (4.3) x 14 (4.3)8.6 (.59)12.0 (45)
cULus
EU(1)cULus NA 16 (4.9) x 16 (4.9)11.7 (.81)14.0 (53)
GL4910 4.9
(70.6)
cULus
EU(1)cULus
EU(1)NA 12 (3.6) x 12 (3.6)7.0 (.48)13.0 (49)
cULus
EU(1)cULus
EU(1)NA 14 (4.3) x 14 (4.3)8.2 (.57)14.0 (53)
cULus
EU(1)cULus
EU(1)NA 16 (4.9) x 16 (4.9)8.2 (.57)14.0 (53)
cULus
EU(1)cULus
EU(1)NA 18 (5.5) x 18 (5.5)12.0 (.83)17.0 (64)
cULus
EU(1)cULus
EU(1)NA 20 (6.1) x 20 (6.1)16.7 (1.15)20.0 (76)
GL5610 5.6
(80.6)
cULus NA NA 12 (3.6) x 12 (3.6)7.2 (.5)15.0 (57)
cULus NA NA 16 (4.9) x 16 (4.9)11.5 (.79)19.0 (72)
cULus NA NA 18 (5.5) x 18 (5.5)14.1 (.97)21.0 (79)
cULus NA NA 20 (6.1) x 20 (6.1)18.4 (1.27)24.0 (91)
TABLE A: NFPA 13, 13R, AND 13D
HYDRAULIC AND INSTALLATION DESIGN CRITERIA
(1)LISTED BY UNDERWRITERS LABORATORIES, INC. FOR USE IN THE U.S., CANADA, AND EUROPEAN UNION.
NOTE: Deflector-to-Ceiling Distance Criteria reflects 2019 Edition of NFPA 13D and 13R.
APRIL 2019 REV.A GFS-302 PAGE 3 of 4
4077 Airpark Dr. Standish, MI 48658 • 989-846-4583 • www.globesprinkler.com
Technical Support • 989-414-2600 • techservice@globesprinkler.com
NOTICE
Do not install any bulb-type sprinkler if the bulb is cracked or there is loss of liquid from the bulb. Sprinklers should be tightened enough to obtain a leak-tight joint when water pressure is applied and/or hydrostatic test is performed. Sprinklers should not be overtightened as this can result in distortion and subsequent leak-age. It is recommended not to exceed 14 ft.-lb. (19.0 Nm) torque for 1/2 inch NPT sprinkler threads.
Step1. Sprinklers must be properly oriented.
Step2. With pipe thread sealant applied to the pipe
threads, hand tighten the sprinkler into the sprin-
kler fitting. Note: Do not grasp the sprinkler by
the deflector.
Step3. Wrench-tighten the sprinkler using only the
appropriate wrench. Wrenches are only to be
applied to the sprinkler wrench flats or wrench
hex as applicable. Note: Do not apply wrench to
frame arms.
INSTALLATION
CARE AND MAINTENANCE
Prior to installation, it is important to read and follow the
“Sprinkler Caution” sheet (GFS-840) included within each
box of sprinklers. This sheet is available on Globe’s web
site (www.globesprinkler.com).
Always obtain permission from the proper authorities to
shut down the affected fire protection system and notify all
personnel who may be affected by this action before closing
a fire protection system main control valve for maintenance
work on the system that it controls.
Sprinklers should only be cleaned by means of gently dust-
ing with a feather duster; otherwise, non-operation in the
event of a fire or inadvertent operation may result.
Store sprinklers in a cool, dry place. Exposure to extreme
heat will damage the thermal sensing element, possibly re-
sulting in premature activation. Avoid direct sunlight.
Replace any sprinkler that shows any corrosion, damage,
or loss of liquid from the glass bulb.
Do not attempt to paint or alter the sprinkler’s coating in any
manner after leaving the manufacturing plant.
Do not attach wiring, ropes, decorations or fixtures to a
sprinkler.
Absence of an escutcheon, used to cover a ceiling hole,
may delay sprinkler operation in a fire situation.
It is the owner’s responsibility for inspection, testing and
maintenance of the fire sprinkler system with all components
and devices in accordance with the National Fire Protection
Association Pamphlet 25 as well as any other requirements
as set forth by the local Authority Having Jurisdiction (AHJ).
FIGURE 1: STANDARD WRENCH
P/N 325390
FIGURE 2: RECESSED WRENCH
P/N 325391
FIGURE 3: 1/2” ADJUSTMENT RECESSED PENDENT
APRIL 2019 REV.A GFS-302 PAGE 4 of 4
GLOBE® PRODUCT WARRANTY
Globe agrees to repair or replace any of its manufactured
products found to be defective in material or workmanship
for a period of one year from date of shipment.
For specific details of our warranty please refer to Price List
Terms and Conditions of Sale (Our Price List).
ORDERING INFORMATION
SPECIFY:
• WRENCH
• Quantity • Part Number
1/2” NPT Standard . . . . . . . . . . . 325390
1/2” NPT Recess . . . . . . . . . . . . 325391
• Quantity • Part Number
Cap . . . . . . . . . . . . . . . . . . . 327109-Cap
• PROTECTIVE CAPS
• SPRINKLER
• ESCUTCHEON
• Quantity • Finish • Part Number (See TABLE C)
• Quantity • SIN • Temperature Rating • Finish
• Part Number (See TABLE B)
TABLE B: PART NUMBER SELECTION
PART NUMBER
SIN + TEMPERATURE + FINISH
XXXX XXX XX
SIN TEMPERATURE FINISH
GL3010 3010 155 155°F (68°C)01 BRONZE
GL4110 4110 175 175°F (79°C)02 CHROME
GL4910 4910 200 200°F (93°C)03 WHITE POLYESTER
GL5610 5610 04 BLACK POLYESTER
Note: All combinations may not be available.
Refer to TABLE A for available listed combinations
1/2" (13mm) ADJUSTABLE RECESSED ESCUTCHEON
FINISH FRICTION FIT 1/2” NPT THREADED 1/2” NPT
Chrome 332071 329301
White Polyester 332073-W 329303-W
Brass 332072 NA
Black Polyester 332073-B NA
TABLE C: ESCUTCHEONS
APRIL 2019 GFS-360 PAGE 1 of 4
SERIES GL-RES/INCH
RESIDENTIAL ADJUSTABLE FLAT PLATE
THE INCH® CONCEALED PENDENT
K-FACTOR 4.9
TECHNICAL DATA
Approvals
•cULus - EU
K-Factor
•K4.9 gpm/psi½ (70.6 lpm/bar½)
Temperature Rating
•Sprinkler: 155°F (68°C)
•Cover Plate: 135°F (57°C)
Cover Plate Finishes
•Chrome/White Painted
(For painted plates other than white, contact Customer
Service)
Thread Size
•1/2” NPT (15mm)
Vertical Adjustment
•1” (25mm) Nominal
Maximum Working Pressure
•175 psi (12 bar)
Materials of Construction
•Frame - bronze •• Screw - brass
•Lodgement Wire - stainless steel • Bulb seat - copper
•Spring - nickel alloy •
•Bulb (3mm) - glass
•Cover Plate - brass • Concealed Cup - carbon steel
4077 Airpark Dr.Standish, MI 48658 • 989-846-4583 • www.globesprinkler.com
Technical Support • 989-414-2600 •techservice@globesprinkler.com
NOTE:
GENERAL DESCRIPTION
The GL4906 Adjustable Flat Plate Concealed pendent
sprinkler is a decorative fast response glass bulb sprinkler
-
tions such as homes, apartments, hotels, and dormitories to
the chance for occupants to escape. The GL4906 utilizes a
3mm frangible glass bulb as its heat sensing operating ele-
ment. While providing the optimal aesthetic appeal with the
the largest vertical adjustment in the industry of a nominal
1”. This nominal 1” adjustment allows for previously unrec-
dwelling occupancies as allowed by NFPA 13, 13D, 13R
and any other related documents as appropriate.
OPERATION
The soldered cover plate drops off the retainer assembly
which is connected to two guide pins, drops down below
the ceiling into its intended position. As heat encompasses
release of the water seat assembly, and discharge of water
from the sprinkler.
SERIES GL-RES/INCH
GL4906
APRIL 2019 GFS-360 PAGE 2 of 4
1 1/4"MAX.
1/4"MIN.CEILING
DESIGN CRITERIA
The Globe Concealed Pendent Sprinkler (GL4906) is cULus
Listed for installation in accordance with this data sheet as
well as the applicable installation Standard being utilized.
Globe Residential Sprinkler Installation Guide
-
vided criteria, refer to the Globe Residential Sprinkler Instal-
lation Guide (Document GFS-380) for recommendations
that may be acceptable to the authority having jurisdiction.
Hydraulic Design (NFPA 13D and 13R)
For systems designed to NFPA 13D or NFPA 13R, the mini-
-
imum required discharge from each of the total number of
Hydraulic Design (NFPA 13)
The minimum required discharge from each design area
sprinkler shall be the greater of the following:
(1)
TABLE A.
(2)In rooms or compartments greater than 800 ft2
(74.3 m2), calculated based on delivering a minimum
of 0.1 gpm/ft2 (4.1 mm/min) over the coverage area of
each sprinkler, calculated in accordance with the
(3)In rooms or compartments 800 ft2 (74.3 m2) or less
de-
livering a minimum of 0.1 gpm/ft2 (4.1 mm/min) over
the room or compartment using the area of the room
divided by the number of sprinklers in the room.(7 psi
minimum)
FIGURE 1: GL4906
INSTALLED POSITION
FIGURE 2: GL4906
ACTIVATED POSITION
3 5/16" DIA.
2 3/4" MAX.
1 7/8" MIN.
1/8"CEILING COVER PLATE
SUPPORT SHELL
CUP
DEFLECTOR
DROP PIN
1" x 1/2"
REDUCER
2 3/8" DIA.
CEILING
2 3/4" DIA. MIN.
HOLE IN CEILING
SIN STYLE
MAX.AREA OF
COVERAGE
MINIMUM
PRESSURE
MINIMUM
FLOW
DEFLECTOR TO CEILING
DISTANCE
MINIMUM
DISTANCE
BETWEEN
SPRINKLERS
GL4906
THE INCH®
ADJUSTABLE
CONCEALED
PENDENT
7.0 (.48)13 (49)Smooth Ceilings
(When sprinkler is in activated position)
Beamed Ceilings - Adjacent
Allowed in ceiling.
Beamed Ceilings - In Beam
(When sprinkler is in activated position)
9 (2.7)
7.0 (.48)13 (49)
7.0 (.48)13 (49)
12.0 (.83)17 (64)
16.7 (1.15)20 (76)
TABLE A: NFPA 13, 13R, AND 13D
HYDRAULIC AND INSTALLATION DESIGN CRITERIA
FOR GL4906 CONCEALED SPRINKLER
NOTE:
APRIL 2019 GFS-360 PAGE 3 of 4
CARE AND MAINTENANCE
Step 1.Install pendent sprinklers in the pendent
position, with the centerline of the sprinkler
perpendicular to the mounting surface.
Step 2.Remove the Protective Cap.
Step 3.With pipe-thread sealant applied to the pipe
threads, and using the Concealed Sprinkler
Wrench P/N 332765 (FIGURE 6), install and
tighten the Sprinkler/Concealed Cup Assembly
Step 4.Replace the Protective Cap by pushing it
upwards until it bottoms out against the Sup-
port Cup. The Protective Cap helps prevent
ceiling installation and/or during application of
NOTICE:
The system is considered Out of Service when
Step 5.After the ceiling has been completed with the
2-3/4” (70mm) diameter hole, remove and
discard the Protective Cap and verify that the
does not move up and down freely, replace
the entire sprinkler assembly. Do not attempt
to modify or repair.
Step 6.Push on the Cover Plate Assembly until its
screw on the Cover Plate Assembly such that
it lifts a ceiling panel out of its normal posi-
tion. If the Cover Plate Assembly cannot be
engaged with the Mounting Cup or the Cover
-
ly to contact the ceiling, the Sprinkler Fitting
must be repositioned.
Always obtain permission from the proper authorities to
personnel who may be affected by this action before closing
work on the system that it controls. Sprinklers should only
be cleaned by means of gently dusting with a feather dust-
-
tent operation may result.
When properly installed, there is a nominal 1/8” (3mm) air
gap between the Cover Plate and the ceiling (FIGURE 1).
This air gap is necessary for proper operation of the sprin-
above the Cover Plate to help assure appropriate release of
be maintained and should never be sealed or caulked.
Factory painted Cover Plates must not be repainted.
In accordance with NFPA 25, Sprinklers which are found to
replaced.
Automatic sprinklers must never be painted, plated, coated,
or otherwise altered after leaving the factory.
before, during, and after installation. Sprinklers damaged
by dropping, striking, wrench slippage, or similar incidents,
must be replaced.
The owner is responsible for the inspection, testing, and
compliance with this document, as well as with the appli-
cable standards of the National Fire Protection Association
(e.g. NFPA 25), in addition to the standards of any other
authorities having jurisdiction.
Refer to Globe’s Residential Installation Guide for further
Care and Maintenance information.
INSTALLATION
FIGURE 3: HAND HELD
INSTALLATION TOOL
P/N 332875
FIGURE 4:
INSTALLATION TOOL
USED WITH EXTENSION
P/N 332876
FIGURE 5: PROTECTIVE CAP
P/N 332871
FIGURE 6: CONCEALED WRENCH
P/N 332765
APRIL 2019 GFS-360 PAGE 4 of 4
ORDERING INFORMATION
GLOBE® PRODUCT WARRANTY
Globe agrees to repair or replace any of its manufactured
products found to be defective in material or workmanship
for a period of one year from date of shipment.
List
Terms and Conditions of Sale (Our Price List).
4077 Airpark Dr.Standish, MI 48658 • 989-846-4583 • www.globesprinkler.com
Technical Support • 989-414-2600 •techservice@globesprinkler.com
Sprinkler/Cup Assembly
Specify:
Qty. •P/N . . . . . . . . . . . . . . . . . . . . .GL490615501
Cover Plate Assembly Finish
Specify:
Qty. • P/N
135°F (57°C) Chrome . . . . . . . . . . . . . . .332891
135°F (57°C) White . . . . . . . . . . . . . . . .332892
Custom Painted: Contact Customer Service
Sprinkler Wrench
Specify:
Qty. • P/N
Concealed Wrench .................332765
The Inch Installation Tool
Specify:
Qty. • P/N
Hand Held . . . . . . . . . . . . . . . . . . . . .332875
. . . . . . . . . . . . . . . .332876
Protective Caps
Specify:
Qty. •P/N . . . . . . . . . . . . . . . . . . . . .332871
82417 Priscilla Ct
INDIO CA, 92201
C-16 #1068664
12/6/2021
www.silveradofire.com
760-600-0765
Info@silveradofire.com
Re: FSS2020- 0157 81175 Elsworth Pl La Quinta, CA 92253
Good afternoon, our time to finish the project extended the time allowed by
the permit. The reason being, the owners of the house were not in. They have
returned and work has started back up. Please extend permit time, we are ready
to proceed.
Best regards,
Simon Chavero
Owner
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
December 8, 2020
Silverado Fire Protection
82417 Priscilla Ct
Indio, CA 92201
Re: Residential (TI) Fire Sprinkler Plan Review – SIEGALL RESIDENCE (ADDITION)
FSS2020-0157 / 81175 ELSWORTH PL, LA QUINTA, CA 92253
The sprinkler plans you submitted for the above referenced project have been reviewed by Riverside County
Fire Department - Office of the Fire Marshal personnel and are approved with the following conditions.
Permanently marked identification signs shall be attached to all control valves.
The following inspections/tests are required to be witnessed by Office of the Fire Marshal Staff:
(a) Overhead Rough and Hydro static test: All piping shall be visible and pumped at normal
operating pressure. *No jacketed electrical and data wiring shall be in contact with, nor have the
potential to contact CPVC piping once insulation is installed.
(b) Final inspection
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Kohl Hetrick - Fire Safety Specialist
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
RIVERSIDE COUNTY FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 81175 ELSWORTH PL PERMIT#: FSS2020-0157 DATE
ISSUED: 12/8/2020
DESCRIPTION: RESIDENTIAL TI – ADDITION CONTRACTOR: SILVERADO FIRE PROTECTION
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F Access & Address verification
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
**WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE**
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler
Systems)
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the
affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when
scheduling inspections. For City of La Quinta inspections call: (760) 777-7131.
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence
without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required
to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not
on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into
the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance
has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE
AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180
DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE
REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.