FSS2021-0027ADDITIONAL SITES
CHRONOLOGY
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
NOTE JOSE DELGADO 9/27/2021 9/27/2021
CONTRACTOR REQUEST FINAL INSPECTION. PERMITED
EXPIRED AS OF 8/28/21. (6 MOS FROM DATE OF LAST
APPROVED INSPECTION. ADDED EXTENSION FEE OF $40.25
AND EXTEDED PERMIT TO 9/30/21 SO CONTRACTOR CAN PAY
FEE VIA ETRAKIT. WILL ALSO REQUIRE AN EXTENSION
REQUEST LETTER FROM CONTARACTOR. OK TO EXTEND PER
KOHL.
EXTENSION REQUEST LETTER RECEIVED. EXTENSION FEE
PAID. EXTENDED PERMIT BY 6 MONTHS.
CONDITIONS
Description: O'KEEFE RESIDENCE / BRES2020-0115
Type: FIRE SPRINKLER (WEB)Subtype: RESIDENTIAL - CUSTOM
HOMES
Status: FINALED Applied: 1/26/2021 ECON
Parcel No: 767690033 Site Address: 52805 MERIWETHER WY LA QUINTA,CA 92253 Approved: 2/17/2021 KHET
Subdivision: TR 33076-2 Block: Lot: 41 Issued: 2/25/2021 ONLINE
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 9/30/2021 KHET
Valuation: $12,000.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
Printed: Monday, February 27, 2023 1:25:18 PM 1 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2021-0027
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT DESERT FIRE EXTINGUISHER CO INC PO BOX 1607 PALM SPRINGS CA 92263 (760)322-0995 MARK@DESERT-
FIRE.COM
CONTRACTOR DESERT FIRE EXTINGUISHER CO INC PO BOX 1607 PALM SPRINGS CA 92263 (760)322-0995 MARK@DESERT-
FIRE.COM
OWNER TIMOTHY M O'KEEFE 1100 BELLEVUE WY BELLEVUE CA 98004 (760)322-0995
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD HYRO KHET 3/1/2021 3/1/2021 APPROVED
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $161.00 $161.00 2/25/21 WEB7486 095925 CREDIT DESERT FIRE
EXTINGUISHER CO INC ECON
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED PC
101-0000-42420 0 $242.00 $242.00 2/25/21 WEB7486 095925 CREDIT DESERT FIRE
EXTINGUISHER CO INC ECON
FIRE STAFF - PER HOUR 101-0000-42420 1 $40.25 $40.25 9/27/21 WEB9411 632673533
00 CREDIT 563921 ECON
Total Paid for FIRE FEES: $443.25 $443.25
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 2/25/21 WEB7486 095925 CREDIT DESERT FIRE
EXTINGUISHER CO INC ECON
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 2/25/21 WEB7486 095925 CREDIT DESERT FIRE
EXTINGUISHER CO INC ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$458.25 $458.25
Printed: Monday, February 27, 2023 1:25:18 PM 2 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2021-0027
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 1/26/2021 EtrakitContractor 1ST SUBMITTAL PLANS OKEEFE HOUSE
PLAN.pdf 1
DOC 1/26/2021 EtrakitContractor 1ST SUBMITTAL CALCS OKEEFE HYD CALC.pdf 1
DOC 1/26/2021 EtrakitContractor 1ST SUBMITTAL HYDOR
CALCS OKEEFE HYD GRAPH.pdf 1
DOC 1/26/2021 EtrakitContractor 1ST SUBMITTAL CUT
SHEETS
Residential Cut
sheets.pdf 1
DOC 1/26/2021 EtrakitContractor 1ST SUBMITTAL STATIC
PRESSURE Static Pressure.pdf 1
DOC 2/10/2021 EtrakitContractor Revised Plans Rev. OKEEFE HOUSE
PLAN.pdf 1
DOC 2/10/2021 EtrakitContractor Revised Calcs Rev. OKEEFE HYD
CALC.pdf 1
BOND INFORMATION
OVERHEAD ROUGH
PIPING KHET 3/1/2021 3/1/2021 APPROVED
FIRE FINAL**KHET 9/30/2021 9/30/2021 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST FIRE (2 WK)KOHL
HETRICK
1/26/2021 2/9/2021 2/9/2021 REVISIONS REQUIRED SEE ATTACHMENTS
1ST PERMIT TECH (1
DAY)
PERMIT TECH
BUCKET
1/26/2021 1/27/2021 1/28/2021 COMPLETE
2ND FIRE (1 WK)KOHL
HETRICK
2/10/2021 2/19/2021 2/17/2021 APPROVED SEE ATTACHMENTS
PARENT PROJECTS
Printed: Monday, February 27, 2023 1:25:18 PM 3 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2021-0027
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 2/10/2021 EtrakitContractor Revised Hydro Graph Rev. OKEEFE HYD
GRAPH.pdf 1
DOC 9/27/2021 Etrakit Contractor Extension on Fire Permit
52805 Meriwther Wy
Residence Permit Letter
Extension .pdf
1
DOC 2/9/2021 KOHL HETRICK FSS2021-0027 - 1ST PC -
CORRECTIONS.pdf
FSS2021-0027 - 1ST PC -
CORRECTIONS.pdf 1
DOC 2/9/2021 KOHL HETRICK
FSS2021-0027 - PLAN
AND CALCS -
CORRECTIONS.pdf
FSS2021-0027 - PLAN
AND CALCS -
CORRECTIONS.pdf
1
DOC 2/17/2021 KOHL HETRICK
FSS2021-0027 -
APPROVED PLANS AND
CALCS.pdf
FSS2021-0027 -
APPROVED PLANS AND
CALCS.pdf
1
DOC 2/17/2021 KOHL HETRICK FSS2021-0027 - COA
AND JOB CARD.pdf
FSS2021-0027 - COA
AND JOB CARD.pdf 1
DOC 3/1/2021 KOHL HETRICK FSS2021-0027 - 3-1-21 -
REDLINES.pdf
FSS2021-0027 - 3-1-21 -
REDLINES.pdf 1
Printed: Monday, February 27, 2023 1:25:18 PM 4 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2021-0027
NO CLOSETS UNDER 24 SQ FT SHALL BE SPRINKLEREDNO BATHROOMS UNDER 55 SQ FT SHALL BE SPRINKLERED1" CITY WATER METERCONNECTION TO CITY1" PVC PIPE 50'-0"C-16# 563921“CPVC (ASTM F 442) pipe shall comply with theportions of the ASTM standards specified in NFPA 13D Table 5.2.2.2 that apply to thefire protection service. Not all pipe or tube made to ASTM F 442 or D 3309 are listed forfire sprinkler service. A copy of the listing shall be available at the job site.”“A list of CPVC compatible products, such as firecaulking, shall be provided at the job site for the inspectors review. ” All products thattouch CPVC piping shall be approved by the manufacturer. Please review productcompatibility guides. CRC 105.4.LOT 41B MADISON CLUBFSS2021-0027
Flow (gpm)
I
S
P
20
40
60
80
100
120
140
100 150 200 250 300 350 400 450 500
Job
OKEEFE RESIDENCE
LOT 41 B MADISON CLUB
LA QUINTA
Remote Area: 1
Water
Static Pres:
Resid. Pres:
Flow:
Date:
Loc:
75.0
60.0
500
psi
psi
gpm
Required
Pressure:
Sys Flow:
Sys+Hose:
Safety Pres:
Hd Elv Pres:
52.0
31
31
22.9
-1.7
psi
gpm
gpm
psi
psi
Hose Allowance
In:
Out:
0
0
gpm
gpm
Supply
OKEEFE RESIDENCE Drawing Date:2/9/21 2/10/21 8:27
HYDRAULIC DESIGN INFORMATION SHEET
Job Name: OKEEFE RESIDENCE
Location: LOT 41 B MADISON CLUB
LA QUINTA, CA, 92253, US
Drawing Date: 2/9/21 Remote Area Number: 1
Contractor: DESERT FIRE EXTINGUISHER Telephone: 760 322-0995
558 INDUSTRIAL PLACE
PALM SPRINGS, CA 92264
Designer: AARON J
Calculated By:SprinkCAD
www.sprinkcad.com
1400 Pennbrook Pkwy.
Lansdale, PA 19446
Construction: WOOD Occupancy:RESIDENTIAL
Reviewing Authorities:LQ FD
__________________________________________________________________________
SYSTEM DESIGN
__________________________________________________________________________
Code:NFPA 13D Hazard:LIGHT System Type:WET
__________________________________________________________________________
Area of Sprinkler Oper. 512 sq ft| Sprinkler or Nozzle
Density (gpm/sq ft) RES | Make: TYCO
Area per Sprinkler 256.0 sq ft| Model: TY3596
Hose Allowance Inside 0 gpm | K-Factor: 4.90
Hose Allowance Outside 0 gpm | Temperature Rating: 155
__________________________________________________________________________
CALCULATION SUMMARY 2 Flowing Outlets
gpm Required: 31.2 psi Required: 52.0 @ City Supply
__________________________________________________________________________
WATER SUPPLY
__________________________________________________________________________
Water Flow Test | Pump Data |
Date of Test | Rated Capacity 0 gpm |
Static Pressure 75.0 psi | Rated Pressure 0.0 psi |
Residual Pres 60.0 psi | Elevation 0 |
At a Flow of 500 gpm | Make: |
Elevation 0" | Model: |
__________________________________________________________________________
Location:
Source of Information: WATER AGENCY
__________________________________________________________________________
SYSTEM VOLUME 35 Gallons
__________________________________________________________________________
Notes:
OKEEFE RESIDENCE Drawing Date:2/9/21 2/10/21 8:27
HYDRAULIC CALCULATION DETAILS
HYDRAULIC FLOW LOSS
QTY DESCRIPTION LENGTH C ID gpm psi TOTALS
Hydr Ref W Required at Hyd Area 1 26 28.0 psi
1 Pipe 1" 40x21 Allied Domestic 12' 120 1.049 26 2.6
1 1" Thrd 90 Ell DI 2' 120 1.049 26 0.5
1 1" Thrd Check Valve CSC "F18" 5' 120 1.049 26 1.1
Fixed Flow Flow Loss 5 gpm
3 1" CPVC 90 Ell 15' 120 1.049 31 5.6
1 Pipe 1" PVx15 BlazeMa Plastic 50' 150 1.101 31 7.7
1 1" Thrd Other Valve CITY "METER" CHART LOSS 31 5.0
1 1" Thrd Check Valve CSC "F18" 5' 120 1.049 31 1.5
______
Total Loss for Underground 24.0 psi
______
Hydr Ref SRC Required at City Supply 31 52.0 psi
Water Source 75.0 psi static, 60.0 psi residual @ 500 gpm 31 gpm 74.9 psi
=======
SAFETY PRESSURE 22.9 psi
Available Pressure of 74.9 psi Exceeds Required Pressure of 52.0 psi
This is a safety margin of 22.9 psi or 31 % of Supply
Maximum Water Velocity is 8.9 fps
OKEEFE RESIDENCE Drawing Date:2/9/21 2/10/21 8:27
Page 3
FITTING NAME TABLE
ABBREV. NAME
C Coupling
E 90' Standard Elbow
F 45' Elbow
S Straight Flow Thru Tee
T 90' Flow Thru Tee
V Valve
LEGEND
HYD REF Hydraulic reference. Refer to accompanying flow diagram. __
K FACTOR Flow factor for open head or path where Flow (gpm) = K x -\/P
Qa Flow added or subtracted
Qt Total flow
DIA Actual internal diameter of pipe
C Hazen Williams pipe roughness factor
Pf/ft Friction loss per foot of pipe
PIPE Length of pipe
FTNG'S Number of fittings. See table above.
TOTAL Total length (PIPE + FTNG'S)
Pt Total pressure (psi) at fitting
Pe Pressure due to change in elevation
where Pe = 0.433 x change in elevation
Pf Friction loss (psi) to fitting
where Pf = l x 4.52 x (Q/C)^1.85 / ID^4.87
Pv Velocity pressure (psi)
where Pv = 0.001123 x Q^2/ID^4
Pn Normal pressure (psi), where Pn = Pt - Pv
NOTES:
- Pressures are balanced to 0.01 psi. Pressures are listed to
0.1 psi. Addition may vary by 0.1 psi due to accumulation of
round off.
- Calculations conform to NFPA 13.
- Velocity Pressures are not considered in these Calculations
OKEEFE RESIDENCE Drawing Date:2/9/21 2/10/21 8:27
Page 4
NODE ELEVATION SPRINKLER PRESSURE ACTUAL MINIMUM ACTUAL
NUMBER K-FACTOR FLOW FLOW DENSITY
(FT) (GPM/(PSI^½)) (PSI) (GPM) (GPM) (GPM/SQ.FT)
1 14.00 4.8
1S 8.00 4.90 7.1 13.1 13.1 0.05
2 14.00 5.0
2S 8.00 4.90 7.1 13.1 13.1 0.05
A1 12.00 11.6
W 12.00 28.0
Max velocity of 8.90 occurs in the pipe from A1 TO W
Nodes with "S" indicate a node at the top of a sprig or bottom
of drop pendent. The node without an "S" is on the branch.
OKEEFE RESIDENCE Drawing Date:2/9/21 2/10/21 8:27
Tyco Fire Products Page 5
HYD. Qa DIA. FITTING PIPE Pt Pt
REF "C" TYPES FTNG'S Pe Pv ******* NOTES *******
POINT Qt Pf/ft TOTAL Pf Pn
PATH 1 FROM HYDRAULIC REFERENCE 1 TO W (PRIMARY PATH)
13.06 1.101 1E 6.00 7.1 7.1 K = 4.90
1S C=150 3.83 -2.6 0.0
13.06 0.031 9.83 0.3 7.1 Vel = 4.44
1.101 7.41 4.8 4.8 EqK = 5.96
1 C=150 0.00 0.0 0.0
13.06 0.031 7.41 0.2 4.8 Vel = 4.44
13.10 1.101 1E 37.77 5.0 5.0 EqK = 5.84
2 C=150 1T 13.39 0.9 0.0
26.16 0.112 51.16 5.7 5.0 Vel = 8.90
1.101 1E 142.63 11.6 11.6
A1 C=150 3.83 0.0 0.0
26.16 0.112 146.46 16.4 11.6 Vel = 8.90
W 26.16 28.0 K = 4.94
13.10 1.101 1T 6.00 7.1 7.1 K = 4.90
2S C=150 9.56 -2.6 0.0
13.10 0.031 15.56 0.5 7.1 Vel = 4.46
2 13.10 5.0 K = 5.84
UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI)
September 27, 2021
RE: Permit FSS2021-0027 / 52805 Meriwether Wy
Desert Fire is requesting an extension on fire permit due to construction hold up. On permit #
FSS2021-0027 / 52805 Meriwether Wy
Any questions can be directed to Brittany Smith at Desert Fire 760-322-0995.
Sincerely,
Brittany Smith
Executive Assistant Fire Sprinkler Manager, Desert Fire Extinguisher Co., Inc.
760-322-0995
P.O. Box 1607, Palm Springs, CA 92263 ▪ 760.322.0995 ▪ 760.325.7239 Fax
558 E. Industrial Place, Palm Springs, CA 92264 ▪ www.desert-fire.com ▪ info@desert-fire.com Email
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
February 17, 2021
Desert Fire Extinguisher
PO Box 1607
Palm Springs, CA 92263
Re: Residential Fire Sprinkler Plan Review – O’KEEFE RESIDENCE
FSS2021-0027 / 52805 MERIWETHER WAY, LA QUINTA, CA 92253
The sprinkler plans you submitted for the above referenced project have been reviewed by Riverside County
Fire Department - Office of the Fire Marshal personnel and are approved with the following conditions.
Permanently marked identification signs shall be attached to all control valves.
The following inspections/tests are required to be witnessed by Office of the Fire Marshal Staff:
(a) Overhead Rough and Hydro static test: All piping shall be visible and pumped at normal
operating pressure. *No jacketed electrical and data wiring shall be in contact with, nor have the
potential to contact CPVC piping once insulation is installed.
(b) Final inspection
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Kohl Hetrick - Fire Safety Specialist
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
RIVERSIDE COUNTY FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 52805 MERIWETHER WAY PERMIT#: FSS2021-0027 DATE
ISSUED: 2/17/2021
DESCRIPTION: O’KEEFE RESIDENCE CONTRACTOR: DESERT FIRE
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F Access & Address verification
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
**WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE**
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler
Systems)
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the
affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when
scheduling inspections. For City of La Quinta inspections call: (760) 777-7131.
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence
without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required
to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not
on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into
the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance
has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE
AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180
DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE
REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.