FSS2021-0084ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT WORLD FIRE PROTECTION INC 41-905 Boardwalk Suite
B
Palm Desert ca 92211 (760)565-6030 bchapman@worldfirep
rotection.com
BILL TO World Fire Protecion 41905 Boardwalk Suite
B
Palm Desert CA 92211 (760)565-6030 info@worldfireprotecti
on.com
CONTRACTOR WORLD FIRE PROTECTION INC 41-905 Boardwalk Suite
B
Palm Desert ca 92211 (760)565-6030 bchapman@worldfirep
rotection.com
OWNER INLAND AMERICAN LAQUINTA PAV P O BOX 9271 OAK BROOK IL 92253 (760)565-6030
CONDITIONS
Description: YOGASIX TI / FIRE SPRINKLER / BCOM2020-0043 / STE 101
Type: FIRE SPRINKLER (WEB)Subtype: TENANT IMPROVEMENT Status: FINALED Applied: 4/12/2021 ECON
Parcel No: 600390029 Site Address: 79070 HIGHWAY 111 STE 101 LA QUINTA,CA 92253 Approved: 4/26/2021 KHET
Subdivision: PM 29351 Block: Lot: 11 Issued: 4/28/2021 ONLINE
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 5/17/2021 KHET
Valuation: $4,500.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
FINANCIAL INFORMATION
Printed: Tuesday, February 28, 2023 11:21:23 AM 1 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2021-0084
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD HYRO KHET 5/3/2021 5/3/2021 APPROVED
OVERHEAD ROUGH
PIPING KHET 5/3/2021 5/3/2021 APPROVED
HYDRAULIC CALC PLATE SHOWS 435 GPM @
105 PSI RESIDUAL - GAUGES SHOWING
STATIC OF 88 PSI. WORLD FIRE WILL
INVESTIGATE AND CONFIRM ORIGINAL
DESIGN REQUIRMENTS FROM SHASTA FIRE
PROTECTION.
FIRE FINAL**KHET 5/11/2021 5/11/2021 PARTIALLY
APPROVED SEE NOTES
Yesterday's inspection revealed that a duct
sock was installed in modest proximity to a
row of heads. The impact of the duct sock
and it's intended use presents concern of
obstruction to sprinkler coverage and
increased ambient heat above 100F.
Requested contractor to change 8-heads in
the affected room to intermediate and to
adjust 3 heads 1-tile over to improve
coverage.
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE STAFF - PER HOUR 101-0000-42420 1 $161.00 $161.00 4/28/21 WEB8079 002796 CREDIT WORLD FIRE
PROTECTION INC ECON
Total Paid for FIRE FEES: $161.00 $161.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 4/28/21 WEB8079 002796 CREDIT WORLD FIRE
PROTECTION INC ECON
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 4/28/21 WEB8079 002796 CREDIT WORLD FIRE
PROTECTION INC ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$176.00 $176.00
Printed: Tuesday, February 28, 2023 11:21:23 AM 2 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2021-0084
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 4/12/2021 EtrakitContractor Ti Sprink Plans LA QUINTA YOGA
PLANS.pdf 1
DOC 4/12/2021 EtrakitContractor Sprink Cut Sheet VK302 Pend.pdf 1
DOC 4/26/2021 KOHL HETRICK FSS2021-0084 -
APPROVED PLANS.pdf
FSS2021-0084 -
APPROVED PLANS.pdf 1
DOC 4/26/2021 KOHL HETRICK FSS2021-0084 - COA
AND JOB CARD.pdf
FSS2021-0084 - COA
AND JOB CARD.pdf 1
DOC 5/12/2021 KOHL HETRICK FSS2021-0084 - INSP
NOTES.pdf
FSS2021-0084 - INSP
NOTES.pdf 1
BOND INFORMATION
FIRE FINAL**KHET 5/17/2021 5/17/2021 APPROVED Confirm head adjustments
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST FIRE (2 WK)KOHL
HETRICK
4/12/2021 4/26/2021 4/26/2021 APPROVED SEE ATTACHMENTS
1ST PERMIT TECH (1
DAY)
PERMIT TECH
BUCKET
4/12/2021 4/13/2021 4/13/2021 COMPLETE
PARENT PROJECTS
Printed: Tuesday, February 28, 2023 11:21:23 AM 3 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2021-0084
OPEN TOABOVENEW FIRE SPRINKLER DROP LOCATION
OPEN TOABOVENEW FIRE SPRINKLER DROP LOCATION
MICROFAST® QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6)
TECHNICAL DATA
Form No. F_033314 19.10.14 Rev 19.2
Page 1 of 6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
1. DESCRIPTION
The Viking Microfast® Quick Response Pendent Sprinkler VK302 is a small ther-
mosensitive glass bulb spray sprinkler available with various finishes and tempera-
ture ratings to meet design requirements. The special Polyester and Electroless
Nickel PTFE (ENT) coatings can be used in decorative applications where colors
are desired. In addition, these coatings have been investigated for installation in
corrosive environments and are Listed and Approved as indicated in the Approval
Charts.
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV
FM Approved: Class Series 2000
VdS Approved: Certificates G414009, G414010, G4040095, and 4880045
LPCB Approved: Certificate 096e/06
CE Certified: Standard EN 12259-1, certificate of constancy of performance 0832-CPR-S0021
CCCF Approved: Approved by the China Certification Center for Fire Products (CCCF)
MED Certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003
Refer to Approval Chart 1 and Design Criteria cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria for
FM Approval requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Minimum Operating Pressure: 7 psi (0.5 bar)
Rated to 175 psi (12 bar) water working pressure
Factory tested hydrostatically to 500 psi (34.5 bar)
Thread size: 1/2” NPT, 15 mm BSP
Nominal K-Factor: 5.6 U.S. (80.6 metric**)
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: 2-1/4” (58 mm)
*cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE
Approvals ONLY is 5 psi (0.35 bar).
Material Standards:
Frame Casting: Brass UNS-C84400 or QM Brass
Deflector: Phosphor Bronze UNS-C51000 or Copper UNS-C19500
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Screw: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400
For Polyester Coated Sprinklers: Belleville Spring-Exposed
For ENT Coated Sprinklers: Belleville Spring-Exposed, Screw and Pipcap - ENT plated.
Ordering Information: (Also refer to the current Viking price list.)
Order Quick Response Pendent Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the appropriate
suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, and ENT = JN
Temperature Suffix: 135 °F (57 °C) = A, 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E, 286 °F (141 °C) = G
Replaces Form No. F_033314 Rev 19.1
(Added ENT; updated FM language.)
MICROFAST® QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6)
TECHNICAL DATA
Form No. F_033314 19.10.14 Rev 19.2
Page 2 of 6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
For example, sprinkler VK302 with a Brass finish and a 155 °F (68 °C) temperature rating = Part No. 12979AB
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the current Viking price list.)
Sprinkler Wrenches:
A. Standard Wrench: Part No. 21475M/B.
B. Wrench for Recessed Pendent Sprinklers: Part No. 13655W/B** (available since 2006)
C. Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool*** Part No. 15915 (available since 2010)
**A ½” ratchet is required (not available from Viking).
***Allows use from the floor by attaching a length of 1” diameter CPVC tubing to the tool. Ideal for sprinkler cabinets. Refer to Bulletin F_051808.
Sprinkler Cabinets:
A. Six-head capacity: Part No. 01724A (available since 1971)
B. Twelve-head capacity: Part No. 01725A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
The Viking Microfast® Quick Response Pendent Sprinkler VK302 is available through a network of domestic and international dis-
tributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
Figure 1:
Standard Sprinkler Wrench 21475M/B
Protective Sprinkler Cap
Wrench Flat
MICROFAST® QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6)
TECHNICAL DATA
Form No. F_033314 19.10.14 Rev 19.2
Page 3 of 6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Temperature
Classification
Sprinkler Nominal
Temperature Rating1
Maximum Ambient
Ceiling Temperature2 Bulb Color
Ordinary 135 °F (57 °C)100 °F (38 °C)Orange
Ordinary 155 °F (68 °C)100 °F (38 °C)Red
Intermediate 175 °F (79 °C)150 °F (65 °C)Yellow
Intermediate 200 °F (93 °C)150 °F (65 °C)Green
High 286 °F (141 °C)225 °F (107 °C)Blue
Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, and ENT
Corrosion-Resistant Coatings3: White Polyester, and Black Polyester. ENT in all temperature ratings except 135 °F (57 °C)
Footnotes
1 The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These
tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are com-
patible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces
only. Note that the spring is exposed on sprinklers with Polyester and ENT coatings. For ENT coated automatic sprinklers, the waterway is coated.
Figure 2: Wrench 13655W/B for Recessed Pendent Sprinklers
Carefully slide the wrench sideways around
the protective cap, ensuring engagement with
the sprinkler wrench flats
Sprinkler wrench 13655W/B**
for recessed pendent
sprinklers
** A 1/2” ratchet is required
(not available from Viking)
MICROFAST® QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6)
TECHNICAL DATA
Form No. F_033314 19.10.14 Rev 19.2
Page 4 of 6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
Approval Chart 1 (UL)
The Viking Microfast® Quick Response
Pendent Sprinkler VK302
Maximum 175 PSI (12 Bar) WWP
Base
Part
Number1
SIN Sprinkler
Style
Thread Size Nominal
K-Factor
Overall
Length
Listings and Approvals3
(Refer also to Design Criteria.)
NPT BSP U.S.metric2 Inches mm cULus4 VdS LPCB 7 8
12979 VK302 Pendent 1/2”15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y, D2, C2X A1 A1Z, B1Y D1Z, C1Y D1 --
19780 VK302 Pendent 1/2” --5.6 80.6 2-1/4 58 ----------D3
21354 VK302 Pendent --15 mm 5.6 80.6 2-1/4 58 ----------D3
NOTICE - Product Below - Limited Availability (Contact Local Viking Office)
06662B VK302 Pendent 1/2”15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y, D2, C2X ----------
18021 VK302 Pendent 1/2”15 mm 5.6 80.6 2-1/4 58 A1X, B1Y A1 A1X, B1Y D1X, C1Y7 D1 --
Approved Temperature Ratings
A - 135 °F (57 °C), 155 °F (68 °C), 175 °F
(79 °C), 200 °F (93 °C), 286 °F (141 °C)
B - 135 °F (57 °C), 155 °F (68 °C), 175 °F
(79 °C), and 200 °F (93 °C)
C - 155 °F (68 °C), 175 °F (79 °C), and
200 °F (93 °C)
D - 155 °F (68 °C), 175 °F (79 °C), 200 °F
(93 °C), 286 °F (141 °C)
Approved Finishes
1 - Brass, Chrome, White
Polyester5,6, Black Polyes-
ter5,6
2 - ENT5
3 - Chrome
Approved Escutcheons
X - Standard surface-mounted escutcheon or the Viking Micromatic® Model E-1 Recessed Escutcheon
Y - Standard surface-mounted escutcheon or recessed with the Viking Micromatic® Model E-1, E-2, or E-3 Recessed Escutcheon
Z - Standard surface-mounted escutcheon
Footnotes
1 Base part number shown. For complete part number, refer to Viking’s current price schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3 This table shows the listings and approvals available at the time of printing. Other approvals may be in process.
4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.
5 cULus Listed as corrosion-resistant.
6 Other colors are available on request with the same Listings and Approvals as the standard colors.
7 CE Certified, Standard EN 12259-1, EC-certificate of constancy of performance 0832-CPR-S0021.
8 MED Certified, Standard EN 12259-1, EC-0832-MED-1003.
DESIGN CRITERIA - UL
(Also refer to Approval Chart 1 above.)
cULus Listing Requirements:
The Viking Microfast® Quick Response Pendent Sprinkler VK302 is cULus Listed as indicated in the Approval Chart for installation in
accordance with the latest edition of NFPA 13 for standard spray sprinklers.
• Designed for use in Light and Ordinary occupancies.
• The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614
for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest
edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and
also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
MICROFAST® QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6)
TECHNICAL DATA
Form No. F_033314 19.10.14 Rev 19.2
Page 5 of 6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
Approval Chart 2 (FM)
The Viking Microfast® Quick Response
Pendent Sprinkler VK302
Maximum 175 PSI (12 Bar) WWP
Base Part
Number1 SIN Sprinkler
Style
Thread Size Nominal K-Factor Overall Length FM Approvals3
(Refer also to Design Criteria.)NPT BSP U.S.metric2 Inches mm
12979 VK302 Pendent 1/2”15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y, D2X, C2
NOTICE - Product Below - Limited Availability (Contact Local Viking Office)
06662B VK302 Pendent 1/2”15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y, D2X, C2
18021 VK302 Pendent 1/2”15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y
Approved Temperature Ratings
A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F
(93 °C), 286 °F (141 °C)
B - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and
200 °F (93 °C)
C - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286
°F (141 °C)
D - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C)
Approved Finishes
1 - Brass, Chrome, White Polyester4,
and Black Polyester4
2 - ENT5
Approved Escutcheons
X - Standard surface-mounted escutcheon or the
Viking Micromatic® Model E-1 Recessed Escutcheon
Y - Standard surface-mounted escutcheon or recessed
with the Viking Micromatic® Model E-1 or E-2
Recessed Escutcheon
Z - Standard surface-mounted escutcheon
Footnotes
1 Base part number shown. For complete part number, refer to Viking’s current price schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by
10.0.
3 This table shows the FM Approvals available at the time of printing. Other approvals may be in process.
4 Other colors are available on request with the same Approvals as the standard colors.
5 FM approved as corrosion resistant.
DESIGN CRITERIA - FM
(Also refer to Approval Chart 2 above.)
FM Approval Requirements:
The Viking Microfast® Quick Response Pendent Sprinkler VK302 is FM Approved as quick response Non-storage pendent sprinklers
as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss
Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not
limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable
spacing, and deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614
for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest
edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organiza-
tions, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
MICROFAST® QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6)
TECHNICAL DATA
Form No. F_033314 19.10.14 Rev 19.2
Page 6 of 6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
Figure 4: Sprinkler Dimensions with the Model E-1 and E-2 Recessed Escutcheons
Figure 3: Sprinkler Dimensions with a Standard Escutcheon
1/2”
(15 mm)
NPT
2-1/4”
(57 mm)1-3/4”
(45 mm)
Installed with a standard
1/8” surface-mounted
escutcheon
Ceiling Opening Size:
2-5/16” (59 mm) minimum
2-1/2” (64 mm) maximum
1-3/4” (45 mm)Max.
2-1/8” (54 mm)
1-1/8” (29 mm)Min.
2”” (51 mm)Max.
1-1/8” (29 mm)Min.
2-1/8” (54 mm)
Ceiling Opening Size:
2-5/16” (59 mm) minimum
2-1/2” (64 mm) maximum
Installed with a
Model E-1 Recessed
Escutcheon
Installed with a Model
E-2 Thread-on Recessed
Escutcheon
Replaces Form No. F_033314 Rev 19.1
(Added ENT; updated FM language.)
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
April 26, 2021
World Fire Protection Inc
41905 Boardwalk #B
Palm Desert, CA 92211
Re: TI Fire Sprinkler Plan Review – YOGASIX
FSS2021-0084
The sprinkler plans you submitted for the above referenced project have been reviewed by Riverside County
Fire Department - Office of the Fire Marshal personnel and are approved with the following conditions.
The following inspections/tests are required to be witnessed by the Office of the Fire Marshal staff:
1) Overhead Rough: All installed/relocated piping must be visible.
2) Final inspection: All trim is in place, 5-Year certification is current. New/added heads shall be
included in the spare head box compliment.
*Water-flow signal test may be performed during the Final Inspection.
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Kohl Hetrick - Fire Safety Specialist
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
RIVERSIDE COUNTY FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 79070 HIGHWAY 111 PERMIT#: FSS2021-0084 DATE
ISSUED: 4/26/2021
DESCRIPTION: YOGASIX TI CONTRACTOR: WORLD FIRE
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F Access & Address verification
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
**WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE**
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler
Systems)
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the
affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when
scheduling inspections. For City of La Quinta inspections call: (760) 777-7131.
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence
without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required
to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not
on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into
the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance
has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE
AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180
DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE
REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.