FSS2021-0194ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT RESIDENTIAL FIRE SYSTEMS INC 8085 E CRYSTAL DRIVE ANAHEIM CA 92807 (714)666-8450 engineering@resfire.co
m
CONTRACTOR RESIDENTIAL FIRE SYSTEMS INC 8085 E. Crystal Drive Anaheim CA 92807 (714)666-8450 engineering@resfire.co
m
OWNER STEVEN ELLIOTT 221 CALDWELL AVE LOS GATOS CA 92253 (714)666-8450
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
NOTE JOSE DELGADO 9/22/2021 Contractor cancelled Rough/Hydro inspection on 9/22/21 @
10:45 pm
CONDITIONS
Description: LOGGIA AND COVERED PATIO CONVERTED INTO NEW OFFICE AND BAR
Type: FIRE SPRINKLER (WEB)Subtype: TENANT IMPROVEMENT Status: FINALED Applied: 8/23/2021 ECON
Parcel No: 777160039 Site Address: 80559 VIA PESSARO LA QUINTA,CA 92253 Approved: 9/8/2021 AMA
Subdivision: TR 29894-2 Block: Lot: 305 Issued: 9/20/2021 JOD
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 1/6/2022 KHET
Valuation: $4,785.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
FINANCIAL INFORMATION
Printed: Thursday, March 02, 2023 1:17:26 PM 1 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2021-0194
BOND INFORMATION
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD HYRO KHET 9/30/2021 9/30/2021 APPROVED
OVERHEAD ROUGH
PIPING
KHET 9/30/2021 9/30/2021 APPROVED As Builts Required
FIRE FINAL**KHET 1/6/2022 1/6/2022 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST FIRE (2 WK)KOHL
HETRICK 8/23/2021 9/7/2021 9/8/2021 APPROVED SEE ATTACHMENTS FEES ADJUSTED FOR MODIFICATION TO EXISTING
SYSTEM
1ST PERMIT TECH (1
DAY)
PERMIT TECH
BUCKET
8/23/2021 8/24/2021 8/24/2021 COMPLETE
PARENT PROJECTS
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE STAFF - PER HOUR 101-0000-42420 1.5 $241.50 $241.50 9/20/21 WEB9346 632576938
65 CREDIT 786965 ECON
Total Paid for FIRE FEES: $241.50 $241.50
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 9/20/21 WEB9346 632576938
65 CREDIT 786965 ECON
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 9/20/21 WEB9346 632576938
65 CREDIT 786965 ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$256.50 $256.50
Printed: Thursday, March 02, 2023 1:17:26 PM 2 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2021-0194
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 8/23/2021 EtrakitContractor FIRE SPRINKLER T.I.
PLANS
14252 The Elliott
Addition FSP-RG.pdf 1
DOC 10/4/2021 Etrakit Contractor
14252 The Elliott
Addition FSP-RG Delta
2.pdf
1
DOC 9/8/2021 KOHL HETRICK FSS2021-0194 - COA
AND JOB CARD.pdf
FSS2021-0194 - COA
AND JOB CARD.pdf 1
DOC 9/8/2021 KOHL HETRICK FSS2021-0194 -
APPROVED PLANS.pdf
FSS2021-0194 -
APPROVED PLANS.pdf 1
DOC 9/30/2021 KOHL HETRICK FSS2021-0194 9-30-
2021 - insp notes.pdf
FSS2021-0194 9-30-
2021 - insp notes.pdf 1
DOC 10/4/2021 KOHL HETRICK
FSS2021-0194 -
APPROVED AS-
BUILTS.pdf
FSS2021-0194 -
APPROVED AS-
BUILTS.pdf
1
Printed: Thursday, March 02, 2023 1:17:26 PM 3 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2021-0194
FSS2021-0194 - AS-BUILT
INSP. TEST
1" C
O
P
P
E
R
K
(
E
X
I
S
T
.
)EX. 1" WATER METEREXISTING INSPECTOR TEST15'-0"1-1/2" PVC (EXISTING)79'-7"EXISTING RISER LOCATION(PART OF SUBMITTAL)EXISTING COVERED PATIOCONVERSION INTO NEW INTERIORWET BAR(PART OF SUBMITTAL)EXISTING FIREPLACE WASRELOCATED(PART OF SUBMITTAL)EXISTING LOGGIA CONVERSIONINTO NEW OFFICE(NOT PART OF SUBMITTAL)(NOT PART OF SUBMITTAL)RESIDENTIALfire systems inc.09.09.1643251
GALLERYH=14'-0"H=13'-0"B.O.SOFFITH=18'-6"H=14'-0"H=17'-6"B.O.SOFFITH=13'-0"B.O.SOFFITWESTINSP. TEST
NEW BAR/LOUNGESOFFIT HT. 10'-8 3/4"FINISHED HDR. HT. 10'-0"
FINISHED HDR. HT. 10'-0"SHADE POCKET (+8")LIGHT POCKET (+8")12'-0" CEILINGFINISHED HDR. HT. 10'-0"11'-5 1/4" CEILINGNEW OFFICECABINETARCH 8'-0" SOFFIT12'-0" CEILING12'-0" CEILING12'-0" CEILINGSHADE POCKET (+8")LIGHT POCKET (+8")11'-0" CEILING68.5 ft³H=14'-0"H=13'-0"B.O.SOFFIT34 ft³17 ft³20 ft³15 ft³NICHE NICHEFIREPLACE
HEAT ZONE
68 ft³68 ft³42 ft³SHELVES
MATCHLINEMATCHLINE(NOT PART OF SUBMITTAL)112MATCHLINEMATCHLINERESIDENTIALfire systems inc.09.09.1643251OBSTRUCTIONDABOBSTRUCTIONCLG.BABCLG.WALLABA08.18.16FIRE SPRINKLER PLAN (NFPA 13D) NOTES:- ALL NEW + EXISTING COMPARTMENTS WITH 1 RESIDENTIAL HEAD TO BE SPACED @ MAX. ALL COMPARTMENTS WITH 2 OR MORE RESIDENTIAL HEADS TO BE SPACED @ MAX.- ALL NEW + EXISITNG PIPING TO BE CPVC PIPE U.N.O.- ALL NEW + EXISTING DROPS TO HEADS TO BE CPVC PIPE1"1"20'x20'16'x16'1
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
September 8, 2021
Residential Fire Systems INC
8085 E Crystal Drive
Anaheim, CA 92807
Re: Residential Fire Sprinkler Plan Review – ELLIOT ADDITION
FSS2021-0194 / 80559 VIA PESSARO, LA QUINTA, CA 92253
The sprinkler plans you submitted for the above referenced project have been reviewed by Riverside County
Fire Department - Office of the Fire Marshal personnel and are approved with the following conditions.
Permanently marked identification signs shall be attached to all control valves.
The following inspections/tests are required to be witnessed by Office of the Fire Marshal Staff:
(a) Overhead Rough and Hydro static test: All piping shall be visible and pumped at normal
operating pressure. *No jacketed electrical and data wiring shall be in contact with, nor have the
potential to contact CPVC piping once insulation is installed.
(b) Final inspection
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Kohl Hetrick - Fire Safety Specialist
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
RIVERSIDE COUNTY FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 80559 VIA PESSARO PERMIT#: FSS2021-0194 DATE
ISSUED: 9/8/2021
DESCRIPTION: ELLIOT ADDITION CONTRACTOR: RESIDENTIAL FIRE SYSTEMS INC
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F Access & Address verification
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
**WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE**
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler
Systems)
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Insp ector before any work is started that may cause the
affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when
scheduling inspections. For City of La Quinta inspections call: (760) 777-7131.
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence
without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required
to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible part y not
on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into
the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance
has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE
AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180
DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE
REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.