FSS2021-0249ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT J C FIRE PROTECTION 81705 DE ORO AVENUE INDIO CA 92201 (760)625-5908 JCFIREPROTECTION@V
ERIZON.NET
CONTRACTOR J C FIRE PROTECTION 81705 DE ORO AVENUE INDIO CA 92201 (760)625-5908 JCFIREPROTECTION@V
ERIZON.NET
OWNER KIMBERLY LEE P O BOX 119 LA QUINTA CA 00000 (760)625-5908
CONDITIONS
Description: LEE RESIDENCE / HIDEAWAY LOT 124
Type: FIRE SPRINKLER (WEB)Subtype: Status: ISSUED Applied: 10/28/2021 ECON
Parcel No: 777140008 Site Address: 80900 VIA PORTOFINO LA QUINTA,CA 92253 Approved: 12/6/2021 KHET
Subdivision: TR 29894-2 Block: Lot: 124 Issued: 12/6/2021 AHI
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled:
Valuation: $8,000.00 Occupancy Type: Construction Type: Expired: 6/4/2022 AHI
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
FINANCIAL INFORMATION
Printed: Friday, March 03, 2023 9:31:13 AM 1 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2021-0249
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD ROUGH
PIPING LIN 2/2/2022 2/2/2022 APPROVED Requested as builts for
changes made
OVERHEAD HYRO LIN 2/2/2022 2/2/2022 APPROVED Requested as builts for
changes made
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
1ST FIRE - ETRAKIT
(2 WK)
KOHL
HETRICK 10/28/2021 11/12/2021 11/16/2021 REVISIONS REQUIRED SEE ATTACHMENTS REVISED PLANS AND CALCS AS AFFECTED BY
CHANGES REQUIRED
PARENT PROJECTS
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $250.00 $250.00 12/6/21 WEB10068 634056459
38 CREDIT 996335 ECON
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED PC
101-0000-42420 0 $250.00 $250.00 12/6/21 WEB10068 634056459
38 CREDIT 996335 ECON
Total Paid for FIRE FEES: $500.00 $500.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $11.00 $11.00 12/6/21 WEB10068 634056459
38 CREDIT 996335 ECON
Total Paid for RECORDS MANAGEMENT FEE: $11.00 $11.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 12/6/21 WEB10068 634056459
38 CREDIT 996335 ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$516.00 $516.00
Printed: Friday, March 03, 2023 9:31:13 AM 2 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2021-0249
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 10/28/2021 Etrakit Contractor 1ST SUBMITTAL PLAN Lee Residence Fire
Sprinklers.pdf 1
DOC 10/28/2021 Etrakit Contractor 1ST SUBMITTAL RCCE A.pdf 1
DOC 10/28/2021 Etrakit Contractor 1ST SUBMITTAL
HYDRAULIC CALCS. 1 AREA 1 1HD.PDF 1
DOC 10/28/2021 Etrakit Contractor 1ST SUBMITTAL
HYDRAULIC CALCS. 2 AREA 2 2HD.PDF 1
DOC 10/28/2021 Etrakit Contractor 1ST SUBMITTAL CPVC
PIPE AND FITTINGS blazemaster.pdf 1
DOC 10/28/2021 Etrakit Contractor 1ST SUBMITTAL VK 468 VK 468 Recessed 4.9
K.pdf 1
DOC 10/28/2021 Etrakit Contractor 1ST SUBMITTAL VK 494 VK 494 Flat Concealed
4.9 K.pdf 1
DOC 10/28/2021 Etrakit Contractor 1ST SUBMITTAL
APPLICATION
FIRE APPLICATION
SEPTEMBER 2019 FEE
UPDATE REVISED 3 .pdf
1
DOC 11/17/2021 Etrakit Contractor Revised Plan b Lee Residence Fire
Sprinklers.pdf 1
DOC 11/17/2021 Etrakit Contractor Revised Calcs b AREA 1 1HD.PDF 1
DOC 11/17/2021 Etrakit Contractor Revised Calcs b AREA 2 2HD.PDF 1
DOC 11/16/2021 KOHL HETRICK
FSS2021-0249 - 1ST
REVIEW - PLAN
CORRECTIONS.pdf
FSS2021-0249 - 1ST
REVIEW - PLAN
CORRECTIONS.pdf
1
BOND INFORMATION
1ST PERMIT TECH –
ETRAKIT (1 DAY)
PERMIT TECH
BUCKET 10/28/2021 10/29/2021 10/28/2021 COMPLETE
2ND FIRE (1 WK)KOHL
HETRICK 11/17/2021 11/24/2021 12/6/2021 APPROVED SEE ATTACHMENTS
Printed: Friday, March 03, 2023 9:31:13 AM 3 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2021-0249
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 12/6/2021 KOHL HETRICK
FSS2021-0249 -
APPROVED PLANS AND
CALCS.pdf
FSS2021-0249 -
APPROVED PLANS AND
CALCS.pdf
1
DOC 12/6/2021 KOHL HETRICK FSS2021-0249 - COA
AND JOB CARD.pdf
FSS2021-0249 - COA
AND JOB CARD.pdf 1
Printed: Friday, March 03, 2023 9:31:13 AM 4 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2021-0249
FSS2021-0249
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1DATE: 11/17/2021367 LEE RESIDENCE - LA QUINTA - CA - JCP\B AREA 2 2HD.SDFJOB TITLE: b AREA 2 2HD (16x16)(13 GPM) WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ’D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) M (N/A) 61.8 (N/A) 61.8 31.0 50.4 Available pressure is 11.4 psi (19%) greater than required pressure.
AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 31.0 GPMTOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPMOTHER HOSE STREAM ALLOWANCES 5.0 GPMTOTAL DISCHARGE FROM ACTIVE SPRINKLERS 26.0 GPM
NODE ANALYSIS DATANODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM)
P1 15.8 - - - - 5.1 - - -P2 10.0 K= 4.90 7.0 13.0P3 10.0 K= 4.90 7.0 13.01 16.3 - - - - 4.9 - - -2 10.5 - - - - 7.1 - - -3 10.5 - - - - 7.1 - - -A 10.5 - - - - 8.9 - - -A1 10.5 - - - - 7.4 - - -B 13.3 - - - - 20.5 - - -B1 18.0 - - - - 20.7 - - -C 10.5 - - - - 25.3 - - -C1 11.5 - - - - 26.3 - - -D 10.5 - - - - 28.4 - - -TOR 10.5 - - - - 29.5 - - -FS1 4.0 - - - - 33.2 - - -FS2 4.0 - - - - 36.2 - - -BOR 0.5 - - - - 39.7 - - -DOM 0.5 HOSE STREAM 41.9 5.0UG -3.0 - - - - 44.0 - - -M -3.0 SOURCE 50.4 31.0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2DATE: 11/17/2021367 LEE RESIDENCE - LA QUINTA - CA - JCP\B AREA 2 2HD.SDFJOB TITLE: b AREA 2 2HD (16x16)(13 GPM) PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 0.0 1.101 PL 0.50 PF 0.0P1 15.8 0.0 5.1 0.0 0.0 150 FTG T PE -0.21 16.3 0.0 4.9 0.0 0.000 TL 6.50 PV
Pipe: 2 -13.0 1.101 PL 0.50 PF 0.2P2 10.0 4.9 7.0 13.0 4.4 150 FTG E PE -0.22 10.5 0.0 7.1 0.0 0.031 TL 7.50 PV
Pipe: 3 -13.0 1.101 PL 0.50 PF 0.2P3 10.0 4.9 7.0 13.0 4.4 150 FTG E PE -0.23 10.5 0.0 7.1 0.0 0.031 TL 7.50 PV
Pipe: 4 0.0 1.101 PL 29.75 PF 0.01 16.3 0.0 4.9 0.0 0.0 150 FTG 2ET2R PE 2.5A1 10.5 0.0 7.4 0.0 0.000 TL 53.15 PV
Pipe: 5 -13.0 1.101 PL 4.75 PF 0.32 10.5 0.0 7.1 0.0 4.4 150 FTG T PE 0.0A1 10.5 0.0 7.4 0.0 0.031 TL 10.75 PV
Pipe: 6 -13.0 1.101 PL 4.75 PF 0.33 10.5 0.0 7.1 0.0 4.4 150 FTG T PE 0.0A1 10.5 0.0 7.4 0.0 0.031 TL 10.75 PV
Pipe: 7 -26.0 1.101 PL 12.00 PF 1.5A1 10.5 0.0 7.4 0.0 8.8 150 FTG R PE 0.0A 10.5 0.0 8.9 0.0 0.111 TL 13.70 PV
Pipe: 8 -26.0 1.101 PL 59.50 PF 12.8A 10.5 0.0 8.9 0.0 8.8 150 FTG 6ET5R PE -1.2B 13.3 0.0 20.5 0.0 0.111 TL 116.00 PV
Pipe: 9 -12.7 1.101 PL 59.75 PF 3.6B 13.3 0.0 20.5 0.0 4.3 150 FTG 6ET8R PE 1.2C 10.5 0.0 25.3 0.0 0.029 TL 121.35 PV
Pipe: 10 -12.7 1.101 PL 73.00 PF 3.1C 10.5 0.0 25.3 0.0 4.3 150 FTG 3T8R PE 0.0D 10.5 0.0 28.4 0.0 0.029 TL 104.60 PV
Pipe: 11 -13.3 1.101 PL 33.00 PF 2.2B 13.3 0.0 20.5 0.0 4.5 150 FTG 3ET5R PE -2.1B1 18.0 0.0 20.7 0.0 0.032 TL 68.50 PV
Pipe: 12 -13.3 1.101 PL 52.75 PF 2.8B1 18.0 0.0 20.7 0.0 4.5 150 FTG 2ET9R PE 2.8C1 11.5 0.0 26.3 0.0 0.032 TL 88.05 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3DATE: 11/17/2021367 LEE RESIDENCE - LA QUINTA - CA - JCP\B AREA 2 2HD.SDFJOB TITLE: b AREA 2 2HD (16x16)(13 GPM) PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 13 -13.3 1.101 PL 23.00 PF 1.6C1 11.5 0.0 26.3 0.0 4.5 150 FTG 2E2TR PE 0.4D 10.5 0.0 28.4 0.0 0.032 TL 50.70 PV
Pipe: 50 -26.0 1.101 PL 3.00 PF 1.1D 10.5 0.0 28.4 0.0 8.8 150 FTG E PE 0.0TOR 10.5 0.0 29.5 0.0 0.111 TL 10.00 PV
Pipe: 51 -26.0 1.101 PL 6.50 PF 0.9TOR 10.5 0.0 29.5 0.0 8.8 150 FTG R PE 2.8FS1 4.0 0.0 33.2 0.0 0.111 TL 8.20 PV
Pipe: 52 FIXED PRESSURE LOSS DEVICEFS2 4.0 0.0 36.2 0.0 3.0 psi, 26.0 gpmFS1 4.0 0.0 33.2 0.0
Pipe: 53 -26.0 1.101 PL 3.50 PF 2.0FS2 4.0 0.0 36.2 0.0 8.8 150 FTG EC PE 1.5BOR 0.5 0.0 39.7 0.0 0.111 TL 18.50 PV
Pipe: 54 -26.0 1.055 PL 2.00 PF 2.2BOR 0.5 0.0 39.7 0.0 9.5 150 FTG 2ET PE 0.0DOM 0.5 H.S. 41.9 5.0 0.136 TL 16.00 PV
Pipe: 55 -31.0 1.291 PL 3.50 PF 0.5DOM 0.5 H.S. 41.9 5.0 7.6 150 FTG EG PE 1.5UG -3.0 0.0 44.0 0.0 0.070 TL 7.50 PV
Pipe: 56 -31.0 1.278 PL 80.00 PF 6.4UG -3.0 0.0 44.0 0.0 7.8 150 FTG 2E PE 0.0M -3.0 SRCE 50.4 (N/A) 0.074 TL 86.24 PV
NOTES (HASS):
(1) Calculations were performed by the HASS 2020 D computer program in accordance with NFPA13 (2016) under license no. 64622225 granted by HRS Systems, Inc. 208 Southside Square Petersburg, TN 37144 (931) 659-9760
(2) The system has been calculated to provide an average imbalance at each node of 0.003 gpm and a maximum imbalance at any node of 0.054 gpm.
(3) Total pressure at each node is used in balancing the system. Maximum water velocity is 9.5 ft/sec at pipe 54.
(4) Items listed in bold print on the cover sheet
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4DATE: 11/17/2021367 LEE RESIDENCE - LA QUINTA - CA - JCP\B AREA 2 2HD.SDFJOB TITLE: b AREA 2 2HD (16x16)(13 GPM) are automatically transferred from the calculation report.
(5) PIPE FITTINGS TABLE
HASS Pipe Table Name: standard.pip
PAGE: F MATERIAL: CPVC HWC: 150Diameter Equivalent Fitting Lengths in Feet (in) F E T R K C G F45 Ell Tee RunT Kplg ChkVlv Gate 1.101 1.40 7.00 6.00 1.70 1.00 8.00 0.40
PAGE: M MATERIAL: CT-M HWC: 150Diameter Equivalent Fitting Lengths in Feet (in) E T F R K C G N Ell Tee 45-Ell TeeRun Kouplg ChkVlv GatVlv NPTee 1.055 3.00 8.00 2.00 3.00 0.00 8.00 0.00 8.00 1.291 3.00 7.00 1.00 2.00 0.50 8.00 0.00 7.00
PAGE: * MATERIAL: S40 HWC: 120Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NPTee -------------------------------------------------------- F F45Ell 1.278 2.06 4.13 1.38 4.82 4.13 0.69 6.88 6.88 4.13 1.03
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5DATE: 11/17/2021367 LEE RESIDENCE - LA QUINTA - CA - JCP\B AREA 2 2HD.SDFJOB TITLE: b AREA 2 2HD (16x16)(13 GPM) WATER SUPPLY ANALYSIS
Fixed Source Pressure: 61.80 psi
-14.7
0.0
10.0
20.0
30.0
40.0
50.0
60.0
70.0
80.0
600 900 1200 1500 1800 2100 2400 2700 3000
FLOW (GPM)
Note: (1) Dashed Lines indicate extrapolated values from Test Results
G
A
U
G
E
P
R
E
S
S
U
R
E
(
p
s
i
)
A1
2
B
LEGEND
1 Available pressure
61.80 psi @ 31.0 gpm
2 Required pressure
50.36 psi @ 31.0 gpm
A. Source Supply Curve
B. System Demand Curve
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6DATE: 11/17/2021367 LEE RESIDENCE - LA QUINTA - CA - JCP\B AREA 2 2HD.SDFJOB TITLE: b AREA 2 2HD (16x16)(13 GPM) WATER SUPPLY CURVE 72+ | | | 66+ | | 0\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\ 60+ | | | 54+ | X | P 48+ R | E | S | S 42+ U | R | E | 36+ ( | P | S | I 30+ ) | | | 24+ | | | 18+ | | |============================== 12+ LEGEND " | " | X = Required Water Supply " | 50.36 psi @ 31.0 gpm " 6+ " | 0 = Available Water Supply " | 61.80 psi @ 31.0 gpm " | " 0++-+---+----+-----+------+--------+--------+---------+-----------+ 8001200 1600 2000 2400 2800 3200 3600 4000 FLOW (GPM)
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1DATE: 11/17/2021367 LEE RESIDENCE - LA QUINTA - CA - JCP\B AREA 1 1HD.SDFJOB TITLE: b AREA 1 1HD (20x20)(20 GPM) WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ’D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) M (N/A) 61.8 (N/A) 61.8 25.0 53.2 Available pressure is 8.6 psi (14%) greater than required pressure.
AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 25.0 GPMTOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPMOTHER HOSE STREAM ALLOWANCES 5.0 GPMTOTAL DISCHARGE FROM ACTIVE SPRINKLERS 20.0 GPM
NODE ANALYSIS DATANODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM)
P1 15.8 K= 4.90 16.7 20.0P2 10.0 - - - - 23.2 - - -P3 10.0 - - - - 23.2 - - -1 16.3 - - - - 16.9 - - -2 10.5 - - - - 23.0 - - -3 10.5 - - - - 23.0 - - -A 10.5 - - - - 23.9 - - -A1 10.5 - - - - 23.0 - - -B 13.3 - - - - 30.6 - - -B1 18.0 - - - - 29.9 - - -C 10.5 - - - - 34.0 - - -C1 11.5 - - - - 34.5 - - -D 10.5 - - - - 35.9 - - -TOR 10.5 - - - - 36.6 - - -FS1 4.0 - - - - 39.9 - - -FS2 4.0 - - - - 42.9 - - -BOR 0.5 - - - - 45.7 - - -DOM 0.5 HOSE STREAM 47.1 5.0UG -3.0 - - - - 48.9 - - -M -3.0 SOURCE 53.2 25.0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2DATE: 11/17/2021367 LEE RESIDENCE - LA QUINTA - CA - JCP\B AREA 1 1HD.SDFJOB TITLE: b AREA 1 1HD (20x20)(20 GPM) PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 -20.0 1.101 PL 0.50 PF 0.4P1 15.8 4.9 16.7 20.0 6.7 150 FTG T PE -0.21 16.3 0.0 16.9 0.0 0.068 TL 6.50 PV
Pipe: 2 0.0 1.101 PL 0.50 PF 0.0P2 10.0 0.0 23.2 0.0 0.0 150 FTG E PE -0.22 10.5 0.0 23.0 0.0 0.000 TL 7.50 PV
Pipe: 3 0.0 1.101 PL 0.50 PF 0.0P3 10.0 0.0 23.2 0.0 0.0 150 FTG E PE -0.23 10.5 0.0 23.0 0.0 0.000 TL 7.50 PV
Pipe: 4 -20.0 1.101 PL 29.75 PF 3.61 16.3 0.0 16.9 0.0 6.7 150 FTG 2ET2R PE 2.5A1 10.5 0.0 23.0 0.0 0.068 TL 53.15 PV
Pipe: 5 0.0 1.101 PL 4.75 PF 0.02 10.5 0.0 23.0 0.0 0.0 150 FTG T PE 0.0A1 10.5 0.0 23.0 0.0 0.000 TL 10.75 PV
Pipe: 6 0.0 1.101 PL 4.75 PF 0.03 10.5 0.0 23.0 0.0 0.0 150 FTG T PE 0.0A1 10.5 0.0 23.0 0.0 0.000 TL 10.75 PV
Pipe: 7 -20.0 1.101 PL 12.00 PF 0.9A1 10.5 0.0 23.0 0.0 6.7 150 FTG R PE 0.0A 10.5 0.0 23.9 0.0 0.068 TL 13.70 PV
Pipe: 8 -20.0 1.101 PL 59.50 PF 7.9A 10.5 0.0 23.9 0.0 6.7 150 FTG 6ET5R PE -1.2B 13.3 0.0 30.6 0.0 0.068 TL 116.00 PV
Pipe: 9 -9.8 1.101 PL 59.75 PF 2.2B 13.3 0.0 30.6 0.0 3.3 150 FTG 6ET8R PE 1.2C 10.5 0.0 34.0 0.0 0.018 TL 121.35 PV
Pipe: 10 -9.8 1.101 PL 73.00 PF 1.9C 10.5 0.0 34.0 0.0 3.3 150 FTG 3T8R PE 0.0D 10.5 0.0 35.9 0.0 0.018 TL 104.60 PV
Pipe: 11 -10.2 1.101 PL 33.00 PF 1.3B 13.3 0.0 30.6 0.0 3.4 150 FTG 3ET5R PE -2.1B1 18.0 0.0 29.9 0.0 0.020 TL 68.50 PV
Pipe: 12 -10.2 1.101 PL 52.75 PF 1.7B1 18.0 0.0 29.9 0.0 3.4 150 FTG 2ET9R PE 2.8C1 11.5 0.0 34.5 0.0 0.020 TL 88.05 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3DATE: 11/17/2021367 LEE RESIDENCE - LA QUINTA - CA - JCP\B AREA 1 1HD.SDFJOB TITLE: b AREA 1 1HD (20x20)(20 GPM) PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 13 -10.2 1.101 PL 23.00 PF 1.0C1 11.5 0.0 34.5 0.0 3.4 150 FTG 2E2TR PE 0.4D 10.5 0.0 35.9 0.0 0.020 TL 50.70 PV
Pipe: 50 -20.0 1.101 PL 3.00 PF 0.7D 10.5 0.0 35.9 0.0 6.7 150 FTG E PE 0.0TOR 10.5 0.0 36.6 0.0 0.068 TL 10.00 PV
Pipe: 51 -20.0 1.101 PL 6.50 PF 0.6TOR 10.5 0.0 36.6 0.0 6.7 150 FTG R PE 2.8FS1 4.0 0.0 39.9 0.0 0.068 TL 8.20 PV
Pipe: 52 FIXED PRESSURE LOSS DEVICEFS2 4.0 0.0 42.9 0.0 3.0 psi, 20.0 gpmFS1 4.0 0.0 39.9 0.0
Pipe: 53 -20.0 1.101 PL 3.50 PF 1.3FS2 4.0 0.0 42.9 0.0 6.7 150 FTG EC PE 1.5BOR 0.5 0.0 45.7 0.0 0.068 TL 18.50 PV
Pipe: 54 -20.0 1.055 PL 2.00 PF 1.3BOR 0.5 0.0 45.7 0.0 7.3 150 FTG 2ET PE 0.0DOM 0.5 H.S. 47.1 5.0 0.084 TL 16.00 PV
Pipe: 55 -25.0 1.291 PL 3.50 PF 0.4DOM 0.5 H.S. 47.1 5.0 6.1 150 FTG EG PE 1.5UG -3.0 0.0 48.9 0.0 0.047 TL 7.50 PV
Pipe: 56 -25.0 1.278 PL 80.00 PF 4.3UG -3.0 0.0 48.9 0.0 6.3 150 FTG 2E PE 0.0M -3.0 SRCE 53.2 (N/A) 0.050 TL 86.24 PV
NOTES (HASS):
(1) Calculations were performed by the HASS 2020 D computer program in accordance with NFPA13 (2016) under license no. 64622225 granted by HRS Systems, Inc. 208 Southside Square Petersburg, TN 37144 (931) 659-9760
(2) The system has been calculated to provide an average imbalance at each node of 0.007 gpm and a maximum imbalance at any node of 0.128 gpm.
(3) Total pressure at each node is used in balancing the system. Maximum water velocity is 7.3 ft/sec at pipe 54.
(4) Items listed in bold print on the cover sheet
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4DATE: 11/17/2021367 LEE RESIDENCE - LA QUINTA - CA - JCP\B AREA 1 1HD.SDFJOB TITLE: b AREA 1 1HD (20x20)(20 GPM) are automatically transferred from the calculation report.
(5) PIPE FITTINGS TABLE
HASS Pipe Table Name: standard.pip
PAGE: F MATERIAL: CPVC HWC: 150Diameter Equivalent Fitting Lengths in Feet (in) F E T R K C G F45 Ell Tee RunT Kplg ChkVlv Gate 1.101 1.40 7.00 6.00 1.70 1.00 8.00 0.40
PAGE: M MATERIAL: CT-M HWC: 150Diameter Equivalent Fitting Lengths in Feet (in) E T F R K C G N Ell Tee 45-Ell TeeRun Kouplg ChkVlv GatVlv NPTee 1.055 3.00 8.00 2.00 3.00 0.00 8.00 0.00 8.00 1.291 3.00 7.00 1.00 2.00 0.50 8.00 0.00 7.00
PAGE: * MATERIAL: S40 HWC: 120Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NPTee -------------------------------------------------------- F F45Ell 1.278 2.06 4.13 1.38 4.82 4.13 0.69 6.88 6.88 4.13 1.03
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5DATE: 11/17/2021367 LEE RESIDENCE - LA QUINTA - CA - JCP\B AREA 1 1HD.SDFJOB TITLE: b AREA 1 1HD (20x20)(20 GPM) WATER SUPPLY ANALYSIS
Fixed Source Pressure: 61.80 psi
-14.7
0.0
10.0
20.0
30.0
40.0
50.0
60.0
70.0
80.0
600 900 1200 1500 1800 2100 2400 2700 3000
FLOW (GPM)
Note: (1) Dashed Lines indicate extrapolated values from Test Results
G
A
U
G
E
P
R
E
S
S
U
R
E
(
p
s
i
)
A1
2
B
LEGEND
1 Available pressure
61.80 psi @ 25.0 gpm
2 Required pressure
53.23 psi @ 25.0 gpm
A. Source Supply Curve
B. System Demand Curve
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6DATE: 11/17/2021367 LEE RESIDENCE - LA QUINTA - CA - JCP\B AREA 1 1HD.SDFJOB TITLE: b AREA 1 1HD (20x20)(20 GPM) WATER SUPPLY CURVE 72+ | | | 66+ | | 0\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\ 60+ | | | 54+ X | | P 48+ R | E | S | S 42+ U | R | E | 36+ ( | P | S | I 30+ ) | | | 24+ | | | 18+ | | |============================== 12+ LEGEND " | " | X = Required Water Supply " | 53.23 psi @ 25.0 gpm " 6+ " | 0 = Available Water Supply " | 61.80 psi @ 25.0 gpm " | " 0++-+---+----+-----+------+--------+--------+---------+-----------+ 8001200 1600 2000 2400 2800 3200 3600 4000 FLOW (GPM)
General
Description
Tyco Fire & Building Products (TFBP)
BlazeMaster CPVC Pipe and Fittings
are designed exclusively for use in wet
pipe automatic fire sprinkler systems.
They are made from a specially devel-
oped thermoplastic compound com-
posed of post chlorinated polyvinyl
chloride (CPVC) resin and state of the
art additives. TFBP BlazeMaster
CPVC products are easier to install
than traditional steel pipe systems,
and at the same time, provide superior
heat resistance and strength as com-
pared to traditional CPVC and PVC
piping materials used in the plumbing
trade. Various adapters are available
to connect CPVC pipe to metallic pip-
ing. All female pipe thread adapters
have brass inserts for durability.
Grooved adapters connect directly to
grooved end valves and metallic pipe,
with flexible grooved end couplings.
WARNING
Tyco Fire & Building Products (TFBP)
BlazeMaster CPVC Pipe and Fittings
described herein mustbe installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction.Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Technical
Data
Sizes
3/4" to 3"
Maximum Working Pressure
175 psi
Approvals
UL, FM, CUL, NSF, Dade County,
LPCB, MEA, and the City of Los Ange-
les. (Refer to IH-1900, Rev. 0, Janu-
ary 2005 “Installation Instruction &
Technical Handbook” for exact list-
ing/approval information.)
Manufacture Source
U.S.A.
Material
•Pipe: ASTM F442, SDR 13.5
•Fittings: ASTM F438 (Sch. 40) and
ASTM F439 (Sch. 80), ASTM F1970
Color
Orange
BlazeMaster ®
CPVC Fire Sprinkler Pipe & Fittings
Submittal Sheet
Page 1 of 6 TFP1915JANUARY, 2006
Technical Services:Tel: (800) 381-9312 / Fax: (800) 791-5500
BlazeMaster®is a registered trademark
of Noveon IP Holding Corp.
Installation
Tyco Fire and Building Products
(TFBP) BlazeMaster CPVC Pipe and
Fittings are to be installed in accord-
ance with IH-1900, Rev. 0, January
2005“Installation Instruction &Techni-
cal Handbook”.
Care and
Maintenance
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any
authority having jurisdiction. The in-
stallingcontractor orproductmanufac-
turer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
NOTES
Before closing a fire protection system
control valve for inspection or mainte-
nance work on the fire protection sys-
tem that it controls, permission to shut
down the affected fire protection sys-
tem must first be obtained from the
proper authorities and all personnel
who may be affected by this action
must be notified.
After placing a fire protection system
in service, notify the proper authorities
and advise thoseresponsibleformoni-
toring proprietary and/or central sta-
tion alarms.
Page2of6 TFP1915
FIGURE 1 — PIPE DIMENSIONS
2"
1"
1-1/4"
1-1/2"
3/4"
2.375" 2.003"
1.315"
1.660"
1.900"
1.050"
1.101'
1.394"
1.598"
0.874"
SIZE
NOMINAL
2.200.84
0.67
0.44
1.08
1.41
0.26
0.42
0.54
0.18
3"
2-1/2"
3.500" 2.952"
2.875" 2.423"
4.831.87
3.261.26
10841260
1320
1339
1191
1213
5040
2835
2205
7875
1344720
15311215
O.D.
AVERAGE
lbs./ft.
WEIGHTAVERAGE
I.D.FILLED WEIGHT
WATER
lbs./ft.
FT. OF PIPE
PER LIFT
WEIGHT PER LIFT
lbs.
TFP1915 Page3of6
FIGURE 2 — FITTING DIMENSIONS (Part 1 of 4)
NOMINAL TAKE-OUTFITTINGNOMINAL SIZETYPE
PART
NUMBER (T/O)
T/O T/O
80004
80003
80002
TEE
T/O 80001
80000
2"
1-1/4"
1-1/2"
3/4"
1"
1-3/8"
1-1/16"
7/8"
0.90
0.51
0.26
5/8"
11/16"0.19
0.11
REDUCING TEE
1-1/2" x 1-1/2" x 1-1/4"
80266
80267
80274
80264
80275
80261
80262
80263
80260
2" x 2" x 3/4"
2" x 2" x 1"
2" x 2" x 1-1/2"
1-1/2" x 1-1/2" x 1"
7/8"
1-1/8"
1-1/16"
7/8"
9/16"
1-1/2" x 1-1/2" x 3/4"
1-1/4" x 1-1/4" x 3/4"
1-1/4" x 1-1/4" x 1"
1" x 1" x 3/4"
5/8"
9/16"
3/4"
5/8"
1-3/8"
1-3/8"
1-3/8"
7/8"
9/16"
1"
1-1/16"
0.66
0.78
0.74
0.45
0.38
7/8"5/8"
9/16"
3/4"
1"
7/8"
5/8" 13/16"
0.23
0.36
0.26
0.16
YXx YxZ XZ
80132 3/4" x 3/4" x 1" 3/4" 3/4" 5/8"
0.14
80133 9/16"1" x 3/4" x 3/4" 9/16"
0.143/4"
80134 1" x 3/4" x 1" 3/4" 11/16" 3/4"
0.17
80135 1-1/4" x 1" x 3/4" 5/8"5/8"0.2115/16"
80136 1-1/4" x 1" x 1" 3/4" 3/4" 15/16"
0.22
15/16"1-1/4" x 1" x 1-1/4"80137 15/16"
0.267/8"
80138 1-1/4" x 1-1/4" x 1-1/2"
1" 1" 1" 0.43
80140 1-1/2" x 1-1/4" x 3/4" 9/16" 9/16"
1" 0.36
1-1/2" x 1-1/4" x 1"80141 9/16" 9/16"
0.381-1/16"
80265 3/4" 1-3/8"
0.61
T/O
T/O T/O
X Y
Z
7/8"
1-1/8"
1-1/16"
3/4"
WEIGHT
(lb.)
T/O
T/O
T/O T/O
CROSS & REDUCING CROSS
1-1/16"
80009
80010
80011
80013
80012
0.139/16"
1-5/16"
11/16"
15/16"
1.00
0.23
0.34
0.67
80006
80005
3"
2-1/2"
1-13/16"
1-9/16"
2.41
1.59
2-1/2" x 2-1/2" x 1-1/2"
80270
80269
80268
80272
80273
80271
3" x 3" x 1-1/2"
3" x 3" x 2"
3" x 3" x 2-1/2"
2-1/2" x 2-1/2" x 1-1/4"
1-13/16"
1-13/16"
1-13/16"
1-9/16"
1-9/16"
2-1/2" x 2-1/2" x 1" 1-9/16"
1-13/16"
1-13/16"
1-3/4"
1-9/16"
1-9/16"
1-9/16"
1-9/16"
2.28
2.44
2.25
1.48
1.46
1-9/16" 1-9/16"
1.43
80276 2-1/2" x 2-1/2" x 2" 1-9/16" 1-9/16"
1.50
1-13/16"
1-13/16"
1-13/16"
1-9/16"
2" x 2" x 1-1/4"
1-9/16"
80008
80014
1-13/16" 2.89
1.91
2"
1-1/4"
1-1/2"
3/4"
1"
3"
2-1/2"
80015 0.281" x 1" x 3/4" x 3/4" 7/8"
SCHD.
80
40
80
40
40
80
80
80
80
80
80
40
40
40
40
40
40
40
40
40
80
80
80
80
80
80
80
80
80
80
80
80
80
80
40
80
40
40
80
80
40
T/O
T/O
90° ELBOW &
1-1/16"
80029
80026
80025
80027
80028
2"
3/4"
1"
1-1/4"
1-1/2"
0.791-5/16"
5/8"
3/4"
7/8"0.21
0.14
0.40
0.09
Y
X
1-9/16"
80031
80030
3"
2-1/2"
1.821-13/16"
1.14
XxY
80032 1" x 3/4"
0.16
X
11/16"
Y
13/16"
REDUCING ELBOW
80
40
80
40
40
80
80
40
Page4of6 TFP1915
FIGURE 2 — FITTING DIMENSIONS (Part 2 of 4)
0.2580078
T/O
80079 0.38
T/O
COUPLING &
T/O
45° ELBOW
80053
80054
80075
80076
80077
80050
80051
80052
0.311/2"
1/8"
3/4"
0.11
0.07
0.12
0.56
3/8"
3/8"
3/4"
0.08
0.11
0.20
1/8"
3/16"
3/16"
3/16"
80203
80206
80205
80204
80200
80201
80202
80207
80208
80209
T/O
REDUCER BUSHING
2" x 1-1/4"
2" x 1-1/2"
2" x 1"
1-1/2" x 3/4"
1-1/2" x 1-1/4"
1-1/4" x 3/4"
1-1/2" x 1"
2" x 3/4"
1-1/4" x 1"
1" x 3/4"
11/16"
9/16"
7/16"
5/8"
1/2"
13/16"
3/8"
5/16"
1/2"
7/16"
0.26
0.24
0.19
0.16
0.27
0.17
0.14
0.04
0.12
0.11
NOMINAL TAKE-OUTFITTINGNOMINAL SIZETYPE
PART
NUMBER (T/O)
2"
3/4"
1"
1-1/4"
1-1/2"
13/16"
80056
80055
3"
2-1/2"
1.191"
0.89
80
40
80
40
40
80
80
REDUCING COUPLING
2"
3/4"
1"
1-1/4"
1-1/2"
1/4"
80081
80080
3"
2-1/2"
0.913/16"
0.67
80
40
80
40
40
80
80
80220 0.081" x 3/4"
1/8"40
80
40
80
40
40
80
80
80
80
80
80
80
80
80
80
80
80215 2-1/2" x 1" 15/16"
0.42
80214 2-1/2" x 1-1/4" 13/16"
0.45
80213 2-1/2" x 1-1/2" 11/16"
0.46
80211 2-1/2" x 2"
5/8"0.29
80210 3" x 2"
3/4"0.72
80212 3" x 2-1/2"
1/2"0.47
WEIGHT
(lb.)SCHD.
T/O
80104
80103
80102
CAP
80101
80100
2"
1-1/4"
1-1/2"
3/4"
1"
5/8"
11/16"
7/16"
0.31
0.20
0.10
5/16"
3/8"0.06
0.04
80106
80105
3"
2-1/2"
1"
7/8"
0.88
0.58
80
40
80
40
40
80
80
1-1/4" x 1-1/4" Groove 2-5/16"
80161
80162
T/O
1-1/2" x 1-1/2" Groove
2" x 2" Groove 2-5/16"
2-5/16"
80160
COUPLING ADAPTER
0.95
1.42
0.78
GROOVED
80163 2-1/2" x 2-1/2" Groove 2-5/16"
2.28
80164 3" x 3" Groove 2-1/4"
3.00
80169 2-1/2" x 76,1 mm Groove 2-5/16"
2.28
40
80
80
80
80
80
PIPE
O.D.
T/O PIPE O.D.
1-1/4" (1.660")
2" (2.375")
1-1/2" (1.900")
2-1/2" (2.875")
3" (3.500")
76,1 mm (3.000")
TFP1915 Page5of6
3/4" x 3/4" NPT 13/16"
80145
80146
T/O
1' x 1" NPT
1-1/4" x 1-1/4" NPT 1-1/8"
7/8"
80142
0.63
1.03
0.41
80147 1-1/2" x 1-1/2" NPT 1-3/8"
1.42
80148 2" x 2" NPT 1-11/16" 2.66
40
40
80
40
80
3/4" x 3/4" NPT 1-5/16"
80158 1' x 1" NPT 1-3/8"
80157
0.56
0.3340
40
T/O
80177L 3/4" x 1/2" NPT
0.16401/2"
80178 1" x 1/2" NPT
0.20409/16"
T/O
80258
80253
80256
2" x 1-1/2" x 1/2" NPT
2" x 2" x 1/2" NPT
1-1/4" x 1" x 1/2" NPT
1/2"
1/2"
7/16"
1-11/16"5/8"
1/2" 1-11/16"
9/16" 1-5/16"
0.56
0.62
0.30
80250 3/4" x 3/4" x 1/2" NPT 9/16" 9/16"
1" 0.22
80251 11/16"1" x 1" x 1/2" NPT 11/16"
0.291-3/16"
80249 1" x 1" x 1" NPT 15/16" 15/16" 1-9/16"
0.73
80252 1-1/4" x 1-1/4" x 1/2" NPT 7/16"7/16"0.311-5/16"
80257 1-1/2" x 1-1/4" x 1/2" NPT 1/2" 11/16" 1-7/16"
0.43
1/2"1-1/2" x 1-1/2" x 1/2" NPT80254 1/2"
0.461-7/16"
80
80
40
40
40
40
40
80
80
T/OT/O
Z
XY
T/O
80175E 3/4" x 1/2" NPT
0.20
80176E 1" x 1/2" NPT
0.22
80
80
7/16"
7/16"
80175WL 3/4" x 1/2" NPT
0.16407/16"
80179 1" x 3/4" NPT
0.434013/16"
NOMINAL TAKE-OUTFITTINGNOMINAL SIZETYPE
PART
NUMBER (T/O)
FEMALE ADAPTER
MALE ADAPTER
WEIGHT
(lb.)SCHD.
ADAPTER (SPIGOT)
SPRINKLER HEAD
YXx YxZ XZ
ADAPTER TEE
SPRINKLER HEAD
ADAPTER
SPRINKLER HEAD
ADAPTER
SPRINKLER HEAD
80175W 3/4" x 1/2" NPT
0.19401/2"
80176W 1" x 1/2" NPT
0.18401/2"
T/O
T/O
80180 1" x 3/4" NPT
0.40407/8"
FIGURE 2 — FITTING DIMENSIONS (Part 3 of 4)
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
havebeensubjecttomisuse,improper
installation,corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP’s sole
option. TFBP neither assumes, nor
authorizes any person to assume forit,
any other obligation in connection with
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer’s repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect,specialorconsequentialdam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP’s liability exceed an amount
equal to the sales price.
Theforegoingwarrantyismadeinlieu
of any and all other warranties, ex-
press or implied, including warranties
ofmerchantabilityandfitnessforapar-
ticular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
Page6of6 TFP1915
TYCO FIRE & BUILDING PRODUCTS,451 North Cannon Avenue, Lansdale, Pennsylvania 19446
FIGURE 2 — FITTING DIMENSIONS (Part 4 of 4)
5/8"
5/8"
X Y, Z
1-5/16"
1-3/16"
Xx YxZ
80459 1" x 1/2" NPT x 1/2" NPT
0.48
80460 1" x 1/2" NPT x 1/2" NPT
0.46
40
40
BACK-TO-BACK TEE
T/O
T/OT/O
T/O
T/OT/O
T/O
Z
X
X
Z
W
Y
Y
5/8"
5/8"
X, Y Z, W
1-3/16"
1-5/16"
X x Y x Z x W
80462 1" x 1" x 1/2" NPT x 1/2" NPT
0.46
80463 1" x 1" x 1/2" NPT x 1/2" NPT
0.47
40
40
BACK-TO-BACK CROSS
NOMINAL TAKE-OUTFITTINGNOMINAL SIZETYPE
PART
NUMBER (T/O)
WEIGHT
(lb.)SCHD.
T/O
T/O
X
Y
ADAPTER 90° ELBOW
SPRINKLER HEAD
9/16"
3/4"
XY
1"
1-1/4"
XxY
80199 3/4" x 1/2" NPT
0.20
80198 1" x 1/2" NPT
0.26
40
40
1-1/16" 1-7/16"80196 1" x 3/4" NPT
0.2640
FREEDOM® RESIDENTIAL
PENDENT SPRINKLER
VK468 (K4.9)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Form No. F_012706 Rev 14.2 Page 1 of 5
1. DESCRIPTION
Viking Freedom® Residential Pendent Sprinkler VK468 is a small, thermosensitive, glass-
bulb residential sprinkler available in several different finishes and temperature ratings to
meet varying design requirements. The Electroless Nickel PTFE (ENT) coating has been
investigated for installation in corrosive atmospheres and is C-UL-US-EU Listed as corro-
sion resistant as indicated in the Approval Chart. The orifice design, with a K-Factor of 4.9
(70.6 metric†), allows efficient use of available water supplies for the hydraulically designed
fire-protection system. The glass bulb operating element and special deflector characteris-
tics meet the challenges of residential sprinkler standards.
2. LISTINGS AND APPROVALS
UL Listed (C-UL-US-EU): Category VKKW
VdS Approved
NYC Approved: MEA 89-92-E, Volume 35
UL Classified to: NSF/ANSI Standard 61, Drinking Water System Components (MH48034). Refer to the Approval Chart
and Design Criteria for C-UL-US-EU Listing requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Available since 2006.Minimum Operating Pressure: Refer to the Approval Chart.
Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi (34.5 bar).
Thread size: 1/2” (15 mm) NPT
Nominal K-Factor: 4.9 U.S. (70.6 metric†)
†Metric K-factor measurement shown is in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: 2-1/4” (58 mm)
Material Standards:Frame Casting: Brass UNS-C84400 or QM Brass
Deflector: Brass UNS-C23000, Phosphor Bronze UNS-C51000, or Brass
UNS-C26000
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Polytetrafluoroethylene (PTFE) Tape
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel
UNS-S30400
Compression Screw: Brass UNS-C36000
For ENT coated sprinklers: Belleville spring - Exposed, Screw and Pipcap
- ENT plated.
Ordering Information: (Also refer to the current Viking price list.)Sprinkler: Base Part No. 13637Order Sprinkler VK468 by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the tempera-
ture rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, and ENT = JN
Temperature Suffix: 155 °F (68 °C) = B, 175 °F (79 °C) = D
For example, sprinkler VK468 with a Brass finish and a 155 °F (68 °C) temperature rating = Part No. 13637AB.
Available Finishes And Temperature Ratings:
Refer to Table 1.
Accessories: (Also refer to the “Sprinkler Accessories” section of the Viking data book.)
Sprinkler Wrenches:
A. Standard Wrench: Part No. 10896W/B (available since 2000)
B. Wrench for recessed sprinklers: Part No. 13577W/B* (available since 2006)
C. Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool** Part No. 15915 (available since 2010.)
*A ½” ratchet is required (not available from Viking).
**Allows use from the floor by attaching a length of 1” diameter CPVC tubing to the tool. Ideal for sprinkler cabinets. Refer to Bulletin F_051808.
Sprinkler Cabinets:
Viking Technical Data may be found on
The Viking Corporation’s Web site at
http://www.vikinggroupinc.com.
The Web site may include a more recent
edition of this Technical Data Page.
(Added VdS Approval)
FREEDOM® RESIDENTIAL
PENDENT SPRINKLER
VK468 (K4.9)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Form No. F_012706 Rev 14.2 Page 2 of 5
A. Six-head capacity: Part No. 01724A (available since 1971)
B. Twelve-head capacity: Part No. 01725A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
The Viking Model VK468 Sprinkler is available through a network of domestic and international distributors. See The Viking
Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Temperature
Classification
Sprinkler Nominal
Temperature Rating1
Maximum Ambient
Ceiling Temperature2 Bulb Color
Ordinary 155 °F (68 °C)100 °F (38 °C)Red
Intermediate 175 °F (79 °C)150 °F (65 °C)Yellow
Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, and ENT
Corrosion Resistant Coatings3: ENT
Footnotes
1 The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards.
3 The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compat-ible with or suitable for the proposed environment. For ENT coated sprinklers, the waterway is coated. Note that the spring is exposed on sprinklers with ENT coating.
Figure 1: Standard Sprinkler Wrench 10896W/B
FREEDOM® RESIDENTIAL
PENDENT SPRINKLER
VK468 (K4.9)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Form No. F_012706 Rev 14.2 Page 3 of 5
Approval ChartViking VK468, 4.9 K-Factor Residential Pendent Sprinkler
For systems designed to NFPA 13D or NFPA 13R. For systems designed to NFPA 13, refer to the design criteria. For Ceiling types refer to
NFPA 13, 13R or 13D 2013 Editions
Sprinkler Base
Part Number1 SIN NPT Thread Size Nominal K-Factor Maximum Water
Working Pressure
Overall Length
Inches mm U.S.metric2 Inches mm
13637 VK468 1/2 15 4.9 70.6 175 psi (12 bar)2-1/4 58
Max. Coverage
Area4
Ft.X Ft.
(m X m)
Ordinary Temp
Rating (155 °F/68 °C)
Intermediate Temp
Rating (175 °F/79 °C)Deflector
to
Ceiling
Installation
Type
Listings and Approvals3 Minimum
Spacing
Ft.
(m)
Flow4
GPM
(L/min)
Pressure4
PSI
(bar)
Flow4
GPM
(L/min)
Pressure4
PSI
(bar)
C-UL-
US-
EU5
VdS NYC6 NSF8
12 X 12
(3.7 X 3.7)
13
(49.2)
7.0
(0.48)
13
(49.2)
7.0
(0.48)
1-1/8 to
2 inch
Standard sur-
face-mounted
escutcheons, the
Microfast® Model
F-1 Adjustable
Escutcheon, or
recessed with
the Micromatic®
Model E-1,
E-2, or
E-3 Recessed
Escutcheon
See
Foot-
notes
7 and
10.
See
Foot-
notes
7 and
10.
See
Foot-
note
7.
See
Foot-
note
7.
8
(2.4)
14 X 14
(4.3 X 4.3)
13
(49.2)
7.0
(0.48)
13
(49.2)
7.0
(0.48)
16 X 16
(4.9 X 4.9)
13
(49.2)
7.0
(0.48)
13
(49.2)
7.0
(0.48)
18 X 18
(5.5 X 5.5)
17
(64.4)
12.0
(0.83)
17
(64.4)
12.0
(0.83)
20 X 20
(6.1 X 6.1)
20
(75.7)
16.7
(1.15)
20
(75.7)
16.7
(1.15)
Footnotes
1 Part number shown is the base part number. For complete part number, refer to Viking’s current price schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by
10.0.
3 This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any
additional approvals. Refer also to Design Criteria.
4 For areas of coverage smaller than shown, use the “Flow” and “Pressure” for the next larger area listed. Flows and pressures listed are per sprinkler.
The distance from sprinklers to walls shall not exceed one-half the sprinkler spacing indicated for the minimum “Flow” and “Pressure” used.
5 Listed by Underwriter’s Laboratories, Inc. for use in the U.S., Canada, and European Union.
6 Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. 35.
7 Approved Finishes are: Brass, Chrome, White Polyester, and Black Polyester9
8 UL Classified to: NSF/ANSI Standard 61, Drinking Water System Components (MH48034).
9 Other paint colors are available on request with the same C-UL-US-EU listings as the standard finish colors.
10 Approved finish is Electroless Nickel PTFE (ENT). ENT is C-UL-US-EU Listed as corrosion resistant. ENT is available with standard surface-mounted
escutcheons or the Micromatic Model E-1 Recessed Escutcheon.
FREEDOM® RESIDENTIAL
PENDENT SPRINKLER
VK468 (K4.9)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Form No. F_012706 Rev 14.2 Page 4 of 5
Figure 3: Sprinkler VK468 Dimensions with a Standard Escutcheon and the Model F-1 Adjustable Escutcheon
Figure 2: Wrench 13577W/B for Recessed Sprinkler
FREEDOM® RESIDENTIAL
PENDENT SPRINKLER
VK468 (K4.9)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Form No. F_012706 Rev 14.2 Page 5 of 5
Figure 4: Sprinkler VK468 Dimensions with the Model E-1 and E-2 Recessed Escutcheons
DESIGN CRITERIA
(Also refer to the Approval Chart.)
UL Listing Requirements (C-UL-US-EU):
When using Viking Residential Pendent Sprinkler VK468 for systems designed to NFPA 13D or NFPA 13R, apply the listed areas of coverage and
minimum water supply requirements shown in the Approval Chart.
For systems designed to NFPA 13: The number of design sprinklers is to be the four contiguous most hydraulically demanding sprinklers. The mini-
mum required discharge from each of the four sprinklers is to be the greater of the following:
• The flow rates given in the Approval Chart for NFPA 13D and NFPA13R applications for each listed area of coverage, or
• Calculated based on a minimum discharge of 0.1 gpm/sq. ft. over the “design area” in accordance with sections 8.5.2.1 or 8.6.2.1.2 of NFPA 13.
• Minimum distance between residential sprinklers: 8 ft. (2.4 m).
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to pages
RES1-17 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, VdS, and any other
similar Authorities Having Jurisdiction, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable. Final approval and acceptance of all residential sprinkler installations must be
obtained from the Authorities Having Jurisdiction.
(Added VdS Approval)
freedom® residential
concealed pendent
sprinkler vk494 (k4.9)
tecHnical data
the viking corporation, 210 n industrial park drive, Hastings mi 49058
telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com
visit the viking website for the latest edition of this technical data page.
Page 1 of 5
Form No. F_012116 16.06.27 Rev 16.1
1. description
Viking Freedom® Residential Concealed Pendent Sprinkler VK494 is a small thermosensitive, glass-bulb residential sprinkler designed for installation on concealed pipe systems where the appearance of a smooth ceiling is desired. The orifice design, with a K-Factor of 4.9 (70.6 metric*), allows the sprinkler’s efficient use of available water supplies for the hydraulically designed fire-protection system. The fast response glass bulb operating element and special deflector characteristics meet the challenges of residential sprinkler standards.
The sprinkler is pre-assembled with a threaded adapter for installation with a low-profile small-diameter cover assembly installed flush to the ceiling. The two-piece design allows installation and testing of the sprinkler prior to installation of the cover plate. The “push-on”, “thread-off” design of the concealed cover plate assembly allows easy installation of the cover plate after the system has been tested and the ceiling finish has been applied, while also providing up to ½” (13 mm) of vertical adjustment. The cover assembly can be removed and reinstalled, allowing temporary removal of ceiling panels without taking the sprinkler system out of service or removing the sprinkler. The Electroless Nickel PTFE (ENT) coating has been investigated for installation in corrosive atmospheres and is C-UL-US-EU Listed as corrosion resistant as indicated in the Approval Charts. The ENT finish is only available for the sprinkler assembly, the cover plate is not plated.
2. listinGs and approvals
Ul listed (c-Ul-Us-eU): Category VKKW
Refer to the Approval Charts and Design Criteria on for C-UL-US-EU Listing
requirements that must be followed.
3. tecHnical dataSpecifications:Minimum Operating Pressure: Refer to the Approval Chart.Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi (34.5 bar).Thread size: 1/2” (15 mm) NPT Nominal K-Factor: 4.9 U.S. (70.6 metric*)Glass-bulb fluid temperature rated to -65 °F (-55 °C)
* Metric K-factor measurement shown is in Bar. When pressure is measured in kPa, divide the metric
K-factor shown by 10.0.
material standards:Sprinkler Body: Brass UNS-C84400 or QM BrassDeflector: Phosphor Bronze UNS-C51000Deflector Pins: Stainless Steel UNS-S30200Button: Brass UNS-C36000Pip Cap and Insert Assembly: Copper UNS-C11000 and SS UNS-S30400Compression Screw: 18-8 Stainless SteelYoke: UNS-S43000 Stainless SteelBelleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE TapeCover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc PlatingShipping Cap: Polyethylenecover plate materials:Cover Plate Assembly: Copper UNS-C11000 and Brass UNS-C26800Spring: Beryllium NickelSolder: Eutecticordering information: (Also refer to the current Viking price list.)Viking Freedom® Residential Concealed Pendent Sprinkler VK494 and Cover Plate Assembly must be ordered separately:sprinkler: Order Sprinkler VK494 by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass = A and ENT = JNTemperature Suffix: 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = EFor example, sprinkler VK494 with a Brass finish and a 200 °F (93 °C) temperature rating = Part No. 20759AE.cover plate assembly: Base Part No. 13504 (2-3/4” diameter), Base Part No. 13642 (3-5/16” diameter), or Base Part No. 15394 (square cover plate, 3-5/16” diameter)
(New product, new page)
freedom® residential
concealed pendent
sprinkler vk494 (k4.9)
tecHnical data
the viking corporation, 210 n industrial park drive, Hastings mi 49058
telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com
visit the viking website for the latest edition of this technical data page.
Page 2 of 5
Form No. F_012116 16.06.27 Rev 16.1
Specify finish and temperature rating of the cover plate assembly by adding the appropriate suffixes for the finish and the cover temperature rating to the base part number:Finish Suffix: Polished Chrome = F, Brushed Chrome = F-/B, Bright Brass = B, Antique Brass = B-/A, Brushed Brass = B-/B, Brushed Copper = E-/B, Painted White = M-/W, Painted Ivory = M-/I, Painted Black = M-/BTemperature Suffix: 135 °F/57 °C = A For example, cover 13504 with a Polished Chrome finish and a 135 °F/57 °C temperature rating = 13504FA.
available finishes and temperature ratings: Refer to Table 1.
accessories: (Also refer to the “Sprinkler Accessories” section of the Viking data book.)sprinkler Wrenches**:A. Heavy Duty Part No. 14047W/B** (available since 2006), orB. Head Cabinet Wrench Part No. 14031*** (available since 2006) C. Optional Concealed Cover Plate Installer Tool Part No. 14412 (available since 2007)D. Optional Large Concealed Cover Plate Installer Tool Part No. 14867 (available since 2007)
**Requires a ½” ratchet (not available from Viking). ***Also optional for removal of the protective cap. Ideal for sprinkler cabinets.
sprinkler cabinet: Part No. 01731A (available since 1971)
4. installation
Refer to appropriate NFPA Installation Standards.
5. operation
During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches, releasing the deflector. Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand, causing the glass to shatter, releasing the yoke and pip cap and sealing spring assembly. . Water flowing through the sprinkler orifice strikes the deflector, forming a uniform spray pattern over a specific area of coverage determined by the water supply pres-sure at the sprinkler to extinguish or control the fire.
6. inspections, tests and maintenance
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. availability
Viking Sprinkler Model VK494 is available through a network of domestic and international distributors. See The Viking Corporation
web site for the closest distributor or contact The Viking Corporation.
8. GUarantee
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
table 1: available sprinkler temperatUre ratinGs and finisHes
sprinkler
temperature
classification
sprinkler
nominal
temperature
rating1
maximum
ambient
ceiling
temperature2
temperature rating
of the cover
assembly
(required)3
cover
plate
base part
number4
large
cover plate
base part
number4
square
cover plate
base part
number4
bulb color
Ordinary 155 °F (68 °C)100 °F (38 °C)135 °F (57 °C)13504 13642 15394 Red
Intermediate 175 °F (79 °C)150 °F (65 °C)135 °F (57 °C)13504 13642 15394 Yellow
Intermediate 200 °F (93 °C)150 °F (65 °C)135 °F (57 °C)13504 13642 15394 Green
sprinkler finishes: Brass and ENT
cover plate finishes: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or Painted Black
corrosion resistant coatings5: ENT
footnotes
1 The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
Jurisdiction. Refer to specific installation standards.
3 Maximum ambient temperature for cover assembly is 100 °F (38 °C).
4 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
5 The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These tests cannot and
do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed
environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway. For ENT coated sprinklers, the Belleville spring
is exposed.
freedom® residential
concealed pendent
sprinkler vk494 (k4.9)
tecHnical data
the viking corporation, 210 n industrial park drive, Hastings mi 49058
telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com
visit the viking website for the latest edition of this technical data page.
Page 3 of 5
Form No. F_012116 16.06.27 Rev 16.1
approval chartviking vk494, 4.9 k-factor residential concealed pendent sprinkler
for systems designed to nfpa 13d or nfpa 13r. for systems designed to nfpa 13, refer to the design criteria. for ceiling types refer to
current editions of nfpa 13, 13r or 13d
sprinkler base
part number 1 sin npt thread size nominal k-factor maximum Water Wor-
king pressureinchesmmU.s.metric 2
20759 VK494 1/2 15 4.9 70.6 175 psi (12 bar)
max. coverage
area 6
W X l
ft. X ft.
(m X m)
flow
Gpm
(lpm)
pressure
psi (bar)Deflector to
ceiling
installation
type
listings and
approvals3,5
minimum
spacing
ft.
(m)155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C)
Temperature Rated Sprinklers
4
12 X 12
(3.7 X 3.7)
13
(49.2)
7.0
(0.48)
Refer to Figure 2
Concealed with
Cover Plate
Assembly.
See Footnote 9.
See Footnotes 7,10, & 11 8
(2.4)
14 X 14
(4.3 X 4.3)
13
(49.2)
7.0
(0.48)
16 X 16
(4.9 X 4.9)
13
(49.2)
7.0
(0.48)
18 X 18
(5.5 X 5.5)
17
(64.4)
12.0
(0.83)
20 X 20
(6.1 X 6.1)
20
(75.7)
16.7
(1.15)
footnotes
1 Part number shown is the base part number. For complete part number, refer to current Viking price schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3 This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals.
Refer also to Design Criteria.
4 Listed by Underwriter’s Laboratories, Inc. for use in the U.S., Canada, and European Union.
5 Meets New York City requirements, effective July 1, 2008.
6 For areas of coverage smaller than shown, use the “Flow” and “Pressure” for the next larger area listed. Flows and pressures listed are per sprinkler. The distance from
sprinklers to walls shall not exceed one-half the sprinkler spacing indicated for the minimum “Flow” and “Pressure” used.
7 Cover Temperature Rating is 135 °F (57 °C). Cover Part No. 135041, 136421 (large diameter), or 153941 (square cover plate).
9 Other paint colors are available on request with the same listings as the standard finish colors. Listings and approvals apply for any paint manufacturer. Contact Viking
for additional information. Custom colors are indicated on a label inside the cover assembly. Refer to Figure 3.
10 Accepted Cover Plate Finishes are: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or
Painted Black 9.
11 C-UL-US-EU Listed as corrosion resistant - Electroless Nickel PTFE (ENT)
freedom® residential
concealed pendent
sprinkler vk494 (k4.9)
tecHnical data
the viking corporation, 210 n industrial park drive, Hastings mi 49058
telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com
visit the viking website for the latest edition of this technical data page.
Page 4 of 5
Form No. F_012116 16.06.27 Rev 16.1
desiGn criteria
(Also refer to the Approval Chart on page 3.)
Ul listing requirements (c-Ul-Us-eU):
When using Viking Residential Concealed Pendent Sprinkler VK494 for systems designed to NFPA 13D or NFPA 13R, apply the listed areas of cover-age and minimum water supply requirements shown in the Approval Chart.
For systems designed to NFPA 13: The number of design sprinklers is to be the four contiguous most hydraulically demanding sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the following:
• The flow rates given in the Approval Chart for NFPA 13D and NFPA 13R applications for each listed area of coverage, or
• Calculated based on a minimum discharge of 0.1 gpm/sq. ft. over the “design area” in accordance with sections 8.5.2.1 or 8.6.2.1.2 of NFPA 13.
• Minimum distance between residential sprinklers: 8 ft. (2.4 m).
note: concealed sprinklers must be installed in neutral or negative pressure plenums only.
important: always refer to bulletin form no. f_080415 - best practices for residential sprinkler Handling and installation. also refer to form no. f_080614 for general care, installation, and maintenance information. viking sprinklers are to be in-stalled in accordance with the latest edition of viking technical data, the appropriate standards of nfpa and any other similar authorities Having Jurisdiction, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. final approval and acceptance of all residential sprinkler installations must be obtained from the authorities Having Jurisdiction.
sprinkler and adapter assembly
• protective cap removed
• Use wrench 14047W/b**
step 1:
carefully slide the
wrench sideways around
the deflector and pins
sprinkler Wrench
part no. 14047W/b**
** a 1/2” ratchet is required (not available from viking)
2-1/4” (57 mm)
diameter opening
required in the
ceiling.
step 2:
carefully press the wrench upward and
turn slightly to ensure engagement with
the sprinkler wrench flats.
figure 1: sprinkler installation and proper Wrench Usage
never install the sprinkler by applying the installation
wrench across the frame arms. do not overtighten.
Use only the designated sprinkler wrenches, viking
part numbers 14047W/b** or 14031**. a leak tight seal
should be achieved by turning the sprinkler clockwise
1 to 1-1/2 turns beyond finger tight.
sprinkler
wrench flat
sprinkler
frame arms
freedom® residential
concealed pendent
sprinkler vk494 (k4.9)
tecHnical data
the viking corporation, 210 n industrial park drive, Hastings mi 49058
telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com
visit the viking website for the latest edition of this technical data page.
Page 5 of 5
Form No. F_012116 16.06.27 Rev 16.1
figure 2: sprinkler dimensions and cover installation
(New product, new page)
1/2” (15 mm) npt
2-1/8”(54mm)2-9/16” (65 mm)maximum 2-1/16” (52 mm)minimum
2-3/4” (70 mm) or
3-5/16” (84 mm)note: Upon sprinkler activation, the deflector descends
to approximately 13/16” (21 mm) below the sprinkler body.
figure 3: identification of custom paint for concealed covers
All custom color painted cover plates will have an
identifying label affixed to the inside of the cover that
indicates the custom color and will have a representative
sample (a paint dot) of the paint on the label.FACTORY APPLIE D C USTO
M
P
AI
NT COLORfigure 4: square cover assembly 15394
3-5/16” (84 mm)
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
December 6, 2021
J C Fire Protection
81705 De Oro Avenue
Indio, CA 92201
Re: Residential Fire Sprinkler Plan Review – HIDEAWAY LOT 124
FSS2021-0249 / 80900 VIA PORTOFINO, LA QUINTA, CA 92253
The sprinkler plans you submitted for the above referenced project have been reviewed by Riverside County
Fire Department - Office of the Fire Marshal personnel and are approved with the following conditions.
Permanently marked identification signs shall be attached to all control valves.
The following inspections/tests are required to be witnessed by Office of the Fire Marshal Staff:
(a) Overhead Rough and Hydro static test: All piping shall be visible and pumped at normal
operating pressure. *No jacketed electrical and data wiring shall be in contact with, nor have the
potential to contact CPVC piping once insulation is installed.
(b) Final inspection
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Kohl Hetrick - Fire Safety Specialist
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
RIVERSIDE COUNTY FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 80900 VIA PORTOFINO PERMIT#: FSS2021-0249 DATE
ISSUED: 12/6/2021
DESCRIPTION: HIDEAWAY LOT 124 CONTRACTOR: JC FIRE PROTECTION
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F Access & Address verification
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
**WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE**
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler
Systems)
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the
affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when
scheduling inspections. For City of La Quinta inspections call: (760) 777-7131.
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence
without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required
to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not
on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into
the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance
has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE
AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180
DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE
REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.